Military Engineer Services-MES has published Repair To Internal Electrification Including Meters Ceiling Fan Geyser And External Electrification Including Fps Dbs Lt Panel Cable Street Light And Apfc At Akash Vihar And Repair To Internal Electrification Including Meters Ceiling Fan Geyser And Exter. Submission Date for this Tender is 12-11-2021. Electrification Work Tenders in GE (AF) MARATHAHALLI Karnataka. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 23-Oct-2021 | BOQ CORRIGENDUM_1 | BOQ | 05-11-2021 |
2 | 05-Nov-2021 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 12-11-2021 |
Sl. No. | Item Description |
1 | Taking down unserviceable wire carefully copper/ aluminum point wiring (light, fan, socket or power) complete including fittings such as switches, ceiling roses, regulators, sockets, light fittings, fans etc., and making good the disturbed surfaces of walls, ceiling etc., including painting with same colour of the background, complete all as specified and as directed. |
2 | Taking down carefully Unserviceable Sub main wiring of any size and type batten or conduit, surface or concelaed including removing material from site and making good the disturbed surfaces of walls, roofs etc to match the existing complete all as specified and as directed. Note: Taking down of Fittings and Fixtures shall be measured under respective Items Separately. |
3 | Wiring complete with 1.5 Sqmm single core FRLSPVC insulated unsheathed cable 1100 volts grade multi stranded with copper conductor conforming to IS 694 drawn through and incl non-metalic rigid PVC conduit incl accessories surface type run on walls/ ceiling incl MS terminal boxesmounted concealed on walls with hylon laminated sheet top cover 3 mm thick fixed with cadmium plated iron screws for housing the switches, switch socket andoutlets, fan regulators etc., incl provision of 1.5 Sqmm FRLS PVC insulated single core multi stranded copper conductor cable as earth continuity conductor and connecting to common earth dolly, all as specified and as directed. (a)One Light,Fan/Exhaust. fan point controlled by one switch |
4 | All as per item no 3 above, but, One light point controlled by 02 two way switches complete all as specified and as directed. |
5 | All as per item no 3 above, but,One 5A 2pin/3pin switch socket out let multipurpose on independent Board complete all as specified and as directed. |
6 | All as per item no 3 above, but,One 5 Amps socket point on same board with other switches complete all as specified and as directed. |
7 | All as per item no 3 above, but,One call bell point controlled by one bell push complete all as specified and as directed. |
8 | All as per item No -03 above but wiring complete with 2.5Sqmm for 5 pin 5/15A socket multipurpose on independent board complete all as specified and as directed. Note:- item No03to 04(i) The earth wire for the points should be in respective switch board only . (ii) Earth wire inthe conduit only. (iii)Cost of terminal box is deemed to be included in the item rate quoted for point wiring |
9 | S & F Modular Switch 1 way 6 A 1 module complete all as specified and as directed. |
10 | S & F Modular Switch 2 way 6 A 1 module complete all as specified and as directed. |
11 | S & F Modulur Switch socket out let combination ,3 pin, 5 Amps 230 volts complete all as specified and as directed. |
12 | S & FModularSwitch Socket Combination 2 in 1, 5pin 5 Amps and 15 Amps flush type , 230 volts complete all as specified and as directed. |
13 | S & Fin repair Socket outlet 2 in 1, 3 pin, 5A Flush type 230 volts complete all as specified and as directed. |
14 | S & F in repair Socket Outlet 2 in 1, 3 pin, 5 and 15 amp flush type 230 volts complete all as specified and as directed. |
15 | S & Fin repair Switch Piano Flush type, Single pole, One way 230 volts 15 / 16 Amps complete all as specified and as directed. |
16 | S & Fin repair step type electronic fanregulator, - 2 module complete all as specified and as directed. |
17 | S& Fin repairPVC ceiling rosetwo to threeterminals all as specified complete all as specified and as directed. |
18 | S & Fin repair ding dong bell AC, 230 volts, single pole complete all as specified and as directed. |
19 | S&F in repairAngle holder PVC/polycarbonate type complete all as specified and as directed. |
20 | Supply and fixingin repair 600x600mm surface/ recessed mounted LEDLight fitting 36 /35 W,glare freeuniform illuminationacrylic diffuser,connector block etc., complete with all accessoriesand including connecting up with 3 core 0.5sqmm copper wire between ceiling rose and fitting terminal complete all as specified and as directed. |
21 | Supply and Fixing in repairs LED Tube light fitting 1 x20 W,220VCRCAhousing withPC diffuserbox type with driver,holder including LED tube light connecting upwith 3 core 0.5sqmm copper wire between ceiling rose and fitting terminal all as specified and as directed. |
22 | Supply and fixing in repairround shape15 watts 220 volts AC recessed/ surface type with high efficiency PMMAdiffuser soft glared light completewithdrivers ,holders LED lampsincluding connecting up with 3 core 0. 5sqmm copper wire between ceiling rose and fitting terminal Complete all as specified and as directed. |
23 | Supply and fixing LED light fittings 1x10W bulkhead luminarieswithdrivers ,holders LED lampsincluding connecting up with 3 core 0. 5sqmm copper wire between ceiling rose and fitting terminal complete all as specified and as directed. |
24 | Supply and Fixing in repairs MCB DB SPN 8 way,Double door, 240 V, AC, 50 Hz, with 200Amp rated bus bar complete all as specified and as directed. |
25 | Supply and Fixing in repairs MCB SP 5 to 32 Amps rating, 10 KAB "curve240V, 50 Hz AC complete all as specified and as directed. |
26 | Supply and Fixing in repairs MCB SPN 32 Amps rating,10 KA "C"curve, 240V, 50 Hz AC complete all as specified and as directed. |
27 | Supply and Fixing in repairs MCB TP 25- 100 Amps rating, , 10 KA B" curve415V, 50 Hz AC complete all as specified and as directed. |
28 | Supply and Fixing in repairs MCB TPN /FP 40 to100 Amps rating,, 10 KA Çcurve , 415V, 50 Hz AC complete all as specified and as directed. |
29 | Material and Labour forsub main wiring1100 volts grade PVC insulatedFRLS multistranded copper conductors, two runs of single core4 Sqmm along with one run 4 Sqmm PVC insulated single core FRLS multistranded copper conductor cable as earth continuity conductor along with one run of PVC medium grade conduit all as specified and as directed. Note :-3 run ofmultistranded copperconductorand 1 run of PVC conduit shall be measured as one unit. |
30 | Material and Labour forsub main wiring1100 volts grade PVC insulatedFRLS multistranded copper conductors, two runs of single core 2.5 Sqmm along with one run 2.5 Sqmm PVC insulated single core FRLS multistranded copper conductor cable as earth continuity conductor along with one run of PVC medium grade conduit all as specified and as directedNote :-3 run ofmultistranded copperconductorand 1 run of PVC conduit shall be measured as one unit, |
31 | Taking out and dismantling all components from ceiling fan existing make 1200mm sweep, cutting and removing burnt out copper wining from the rotor assy and rewinding with super enamelled copper winding wire of suitable gauge and turns with necessary insulation materials , varnishing, reassembling , greasing to bearing , replacing bushes, replacement of capacitor,inculding fixing in existing position painting of fan with orginal manufactures colourcompletelytesting all as directed. Note:- (a) The spares like ball bearing, capacitor and GM bush required for repair the ceiling fan will be measured and paid separately under respective item. (b) Expendable stores like cotton waste /cleaning materials, grease, lubricants, machine screws, safety split pin, bolts, nuts and transportation to and fro from site to work place are deemed to be included in rate quoted. |
32 | Tanking downdismantling all components Exhaust fan 250mm to 300mmcomplete of any type and size , cleaning, servicing, greasing to bearings checking of nuts bolts , safety split pin, bushes , capacitor, painting of fan with orginal manufactures colour, complete testing including hanging to its orginal position all as directed Note :- Expendable stores like cotton waste/cleaning materials, grease, lubricants, machine screws, safety split pin, bots/nuts and transportation to and from site to work place are deemed to be included in rate quoted |
33 | Tanking downdismantling all components Exhaust fan 400 mm to 450mmcomplete of any type and size , cleaning, servicing, greasing to bearings checking of nuts bolts , safety split pin, bushes , capacitor, painting of fan with orginal manufactures colour and complete testingincluding hanging to its orginal position all as directed Note :- Expendable stores like cotton waste/cleaning materials, grease, lubricants, machine screws, safety split pin, bots/nuts and transportation to and from site to work place are deemed to be included in rate quoted. Note: item No - 31 to 33- Servicing offans and Spares will be measured and paid separately under relevant items of this schedule. |
34 | Supply Only Ball bearings suitable for Ceiling fans / Exhaust fans / Wall mounting fans of 1200 Sweep complete all as specified and as directed. |
35 | Supply Only 2.5 MFD Capacitors for the fan in position complete all as specified and as directed. |
36 | Supply Only 4 MFD Capacitors of the fan in position complete all as specified and as directed. |
37 | Supply and fix ceilin fans complete with blades, down rod electronic regulator and accessories 230V,1200 mm sweep. Min 6.00 BEE. Five star rated with brushhless directed current motor (BLDC) all as secified and directed |
38 | Supply and fix electric water heater,storage type steel body with copper inner tank and heating element upto 2 KW capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostate,NRV, connection piece etc. complete all as specified and as directed . |
39 | Taking out unserviceable geyser element including supply and fixingheating elementsuitable to existing model and make 1.5 / 2 KW dual clip type/tri angle type / round type with rubber gasketsuitable for geysers up to 25 Ltr capacity complete all as specified and as directed. |
40 | Taking out unserviceable thermostat including Supplyandfixingthermostat clip type (Range 30 C° to 80 C and acting at 70C°) forgeysers up to 50 Lts all as specified and as directed. |
41 | Takingout unserviceable PVC connection including supply and fixing15mm bore PVC connections with brass nuts650 mm in length suitable to connect GI pipe 15 mm dia to hot /Cold water outlet of geyser. Complete all as specified and directed . |
42 | Taking out unservice pressure release valveSupplyand fixing pressure release valves suitable for geyser up to 50 ltrs capacity type asper existing PR valve complete all as specified and directed . |
43 | Taking out unservice indication lamp including supply and fixingindicating lamps green / red suitable forgeysers up to 50 ltrs completeall specified and directed . |
44 | Taking out the unservieable 3 core wire including supply and fix FRLSPVCinsulated copper flexible cable 2.5 sqmm , 3 core PVC sheathed,1100 Volts grade complete allas specified and directed . |
45 | Excavation in trenches in Soft / Loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying of cables etc, getting out and forming bottom surface to required gradient Complete all as specified and as directed. |
46 | Returning filling including Spreading levelling watering and well ramming to excavated soil in layers not exc 25 cm thick Complete all as specified and as directed |
47 | Removing excavated material not exc 50m and depositing where directed at a level not exc 1.5m above the starting point in soils Complete all as specified and as directed. |
48 | Material and labour forriddledSandCushioning to cablesa layer of 8 cm thick beforelaying the cable and second layer of 15 cmthick after layingthe cable Complete all as specified and as directed. Note :- Sand shall be measured after punned down. |
49 | S & Fsub classburnt Bricks for cable protection Complete all as specified and as directed |
50 | S&F G.I. tubinglightgrade of size 50mm bore for protection of cables to be laid under roads, crossings / culverts complete all as specified and as directed. |
51 | Boring of holes under roads,pavement,hard standing by trenchless technology using ultra sounding technique andnecessary machine including HDPE pipe of 150mmdia suitable for 0.4 mpa working pressure complete all as specified and as directed. |
52 | Taking out old unserviceable UG cable including supply and laying 240 Sqmm, 3.5 Core LT UG cable grade PVC XLPE insulated, PVC sheathed armoured, heavy duty, in trenches / walls / poles / passing through pipes with multistranded aluminium conductor including lugs / thimbles / ferrules connection, testing and commissioning complete all as specified and as directed. |
53 | Taking out old unserviceable UG cable including supply and laying 70 Sqmm, 3.5 Core LT UG cable grade PVC XLPE insulated, PVC sheathed armoured, heavy duty, in trenches / walls / poles / passing through pipes with multistranded aluminium conductor including lugs / thimbles / ferrules connection, testing and commissioning Complete all as specified and as directed. |
54 | Taking out old unserviceable UG cable including supply and laying 50 Sqmm, 3.5 Core LT UG cable grade PVC XLPE insulated, PVC sheathed armoured, heavy duty, in trenches / walls / poles / passing through pipes with multistranded aluminium conductor including lugs / thimbles / ferrules connection, testing and commissioning Complete all as specified and as directed. |
55 | Taking out old unserviceable UG cable including supply and laying 35 Sqmm, 4 Core LT UG cable grade PVC XLPE insulated, PVC sheathed armoured, heavy duty, in trenches / walls / poles / passing through pipes with multistranded aluminium conductor including lugs / thimbles / ferrules connection, testing and commissioning complete all as specified and as directed. |
56 | Taking out old unserviceable UG cable including supply and laying 16 Sqmm, 4 Core LT UG cable grade PVC XLPE insulated, PVC sheathed armoured, heavy duty, in trenches / walls / poles / passing through pipes with multistranded aluminium conductor including lugs / thimbles / ferrules connection, testing and commissioning complete all as specified and as directed. |
57 | Taking out old unserviceable UG cable including supply and laying 10 Sqmm, 2 Core LT UG cable grade PVC XLPE insulated, PVC sheathed armoured, heavy duty, in trenches / walls / poles / passing through pipes with multistranded aluminium conductor including lugs / thimbles / ferrules connection, testing and commissioning complete all as specified and as directed. |
58 | Material and Labour for Straight through joints (Epoxy) heat shrinkable type for UG cable including jointing kit and all accessories complete for making joints suitable for LT UG Cable of Aluminium conductor of size 16 to 35, Sqmm 3.5 / 4 core complete all as specified and as directed. |
59 | Material and Labour for Straight through joints (Epoxy) heat shrinkable type for UG cable including jointing kit and all accessories complete for making joints suitable for LT UG Cable of Aluminium conductor of size 50 to 95, Sqmm 3.5 / 4 core Complete all as specified and as directed. Note for ser item No.58 & 59 (i) Earth work excavation, sand cushioning, bricks for protection, GI pipe etc shall be measured and paid for separately under relevant items of this schedule. |
60 | Supply and Fixing in repairs MCCB Triple pole 415 volts 50 HZ AC suitable for current carrying capacity 25 to 100 Amps rating, fixed typewith rupturing capacity 16 KA all as specified and directed. |
61 | Supply and Fixing in repairs MCCB 3 Pole, 415 volts 50 HZ AC suitable for current carrying capacity 160 Amps rating, fixed and thermal magnetic release with rupturing capacity 25 KA all as specified and directed. |
62 | Supply and Fixing in repairs MCCB 4 Pole, 415 volts 50 HZ AC suitable for current carrying capacity 200 Amps rating, fixed and thermal magnetic release with rupturing capacity 35 KA all as specified and directed. |
63 | Supply and Fixing in repairs MCCB4Pole, 415 volts 50 HZ AC suitable for current carrying capacity400 Amps rating, fixed and thermal magnetic release with rupturing capacity 36 KA all as specified and directed. |
64 | Supply and fixing moulded (FRP) junction boxwith IP 65 protection of size 300x200x80mm with 32 Amp 4 way heavy duty terminal block with 6Amp MCBSP and two number of cable entry gland of standard size with suitable stainless steel bracket to fix with pole complete all as directed |
65 | Supply and Fixing in repairs voltmeter digital type 0-500 Volts Complete all as specified and as directed. |
66 | Supply and Fixing in repairs Ammeter digital type 0-200 Amps Complete all as specified and as directed. |
67 | Disconnecting the electrical connections including taking down the unserviceable LED Street light fittings of 75/45/25 watts of any type and any make from pole for repair and replacement of unserviceable parts like driver, surg protectionetc., and fixing back to the original position after getting repairs including connecting testing and commissioning all as specified and directed . |
68 | Material and Labour for preperation of old painted steel surfaces of any description over 10 cm width or girth and applying one coat of synthetic enamel paint complete all as specified and as directed. |
69 | Supply andlaying synthetic rubber insulating Matssuitable for 11 KVelectrical insulation 2 Mtr x 1 Mtr x2.5 mm thick complete all as specified and as directed. |
70 | Taking out the unserviceable HPSV /CFL street light fitting any watts , Supply and fixing 1x 60 WLEDstreetlight fitting with pressure die-cast housing with toughened glass and individual LEDs with secondary optics and IP 66 protection complete all as specified and as directed. |
71 | Taking out the unserviceableflood light fittingsSupply and fixing 1x70 WLED flood light fitting230V out door type with thermal management in multiple optics and equipped with IP-66 protection with impact and corrosion resistants complete with driver and lamp complete all as specified and as directed. |
72 | Taking out the unserviceable post top latern fitting ,Supply and Fixingpost top lantern LED type 20 W 230 VoltsAC out door typewith decorativepost top for 360 degree indirect light IP65protection with impact and corrosionresistantCompletewith driver and lamp complete all as specified and as directed. |
73 | Earthing complete with galvanized iron or steel plate electrode 600 mm x 600 mm x 6.0 mm buried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to GI earth earth strip 25 x 4 mm by means of GI bolts, nuts, check nuts and washers, earth wire protected by galvanized steel pipe 15 mm bore (light grade) connected to machinery/ equipment all as shown in Electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of soil, 20 mm bore light grade GI pipe for watering funnel wire mesh, PCC (1:3:6), type C-1 chamber, RCC (1:2:4), type B-1, reinforced with 6 mm dia MS round bars @ 15cm c/c both way for cover and MS frame etc., Complete all as specified and as directed. |
74 | Repair/ servicing of out door typeAPFC panelat Akash Vihar :- (i) APFC panel (out door Type) 100 (8x12.5) KVAR - 02 No , (ii) APFC panel ( Out door Type) 125 (20x5,2X12.5) KVAR - 01 No capacitors, internal wiring,inresh current limiting coil ., auxillary contactor, indicating lamps, auto-manual selector switch, MCCB, axial flow fan and replace the unserviceable parts complete all as specified and as directed. The following checking will be carried outto ensure smooth and effective operation all the timeall as specified and directed. (a) Checking of the control panel, power supply, fuses, circuits etc and tighten to any loose contact.(b) Checking of the healthiness of capacitors, contactors and APFC relays. (c) Cleaningof the panel by using blower without any disturbance/ damages. Note:- spare parts materialwill be measured and paid separately under relevant items of this schedule. |
75 | Supply Only in repairs10/12. 5 KVAR Capacitor heavy duty existing make and type 440 volts with inrush current Limiting Coil Complete all as specified and as directed. |
76 | Supply Only in repairs 20KVAR Capacitor heavy duty existing make and type440 volts with inrush current Limiting Coil Complete all as specified and as directed. |
77 | Supply Only Automatic power factor relay ( APFCR )8 stage Complete all as specified and as directed. |
78 | Supply only duty contactor suitable for 20Kvar capacitor Complete all as specified and as directed. |
79 | Supply only duty contactor suitable for12.5 Kvar capacitor complete all as specified and as directed. |
80 | S & F switch piano flush type, single pole, one way5 Amps complete all as specified and as directed. |
81 | S & Fin repairSwitch socket combination 2 -in-1, 3 pin/5 pin, 5 Amps 230 volts complete all as specified and as directed. |
82 | S & F in repairSwitch Socket Combination 2 in 1, 3 pin 5 Amps and 15 Amps flush type , 230 volts complete all as specified and as directed. |
83 | S & Fin repair Modular Switch 1 way 6 Amps 1 Module complete all as specified and as directed. |
84 | S & F in repairModular Socket,6 Amps- 2/3 pin combined 2 Moduler complete all as specified and as directed. |
85 | S & F in repairModular Switch 1 way 16 Amps 1 Moduler complete all as specified and as directed. |
86 | S & F in repairModular Socket,6 A/16A,2 Moduler complete all as specified and as directed. |
87 | S & F in repair Modulartype Fan step regulator 120Wtype2 moduler complete all as specified and as directed. |
88 | Supply and fixingLEDlight fitting 40 W recessed & surface LED 1X4 Flat Panel ceiling light with high performance,with in built driver, complete with all accessoriesand including connecting up with 3 core 0.5sqmm copper wire between ceiling rose and fitting terminal complete all as specified and as directed. |
89 | Supply and Fixing in repairs Aesthetically designed linear mirror light with high output PMMA diffuser for glare free light LED light fitting 1 x 10 W with all accessories and including connecting up complete all as specified and as directed. |
90 | Supply and Fixing in repairs retro type LEDin built driver,linearT8 tubler lamp 20 W complete all as specified and as directed. |
91 | Supply and Fixing in repairs retro type LEDin built driver, linearT8 tubler lamp 9 W complete all as specified and as directed. |
92 | Supply and Fixing in repairs LED linear T5 tubler lamp 18 W complete all as specified and as directed. |
93 | Supply and Fixing in repairs MCB DB TPN4 way, double door,415 V, AC, 50 Hz, complete all as specified and as directed. |
94 | Supply and Fixing in repairs MCB TP 25- 63 Amps rating, , 10 KA Ç" crve415V, 50 Hz AC complete all as specified. |
95 | Supply and Fixing in repairs MCB TPN 63 Amps rating,, 10 KA Çcurve , 415V, 50 Hz AC complete all as specified and as directed. |
96 | Taking out and dismantling all components from ceiling fan existing any make 1200mm sweep, cutting and removing burnt out copper wining from the rotor assy and rewinding with super enamelled copper winding wire of suitable gauge and turns with necessary insulation materials , varnishing, reassembling , greasing to bearing , replacing bushes, replacement of capacitor,inculding fixing in existention of rod for false ceiling addition position painting of fan with orginal manufactures colour, extesion of rodcompletelytesting all as directed. Note:- (a) The spares like ball bearing, capacitor and GM bush required for repair the ceiling fan will be measured and paid separately under respective item. (b) Expendable stores like cotton waste /cleaning materials, grease, lubricants, machine screws, safety split pin, bolts, nuts and transportation to and fro from site to work place are deemed to be included in rate quoted. |
97 | Taking downdismantling all components Exhaust fan 250mm to 300mmcomplete of any type and size , cleaning, servicing, greasing to bearings checking of nuts bolts , safety split pin, bushes , capacitor, painting of fan with orginal manufactures colour, complete testing including , fixing in its existing position with all new fitting & fixtures, complete all as specified and as directed.NOTE:- Expendable stores like cotton waste/cleaning materials, grease, lubricants, machine screws, safety split pin, bolts/nuts and transportation to and from site to work place are deemed to be included in rate quoted |
98 | Disconnecting the power supply and taking down the exhaust fandismantling the defective fans motor up 400 to 450 mm sweeptaking to work shop and by taking out burnt copper winding and rewinding with super enamelled copper wire of existing gauge and weight including replacement of all insulation material, andother petty items required for making motor functional, fixing in its existing position with all new fitting & fixtures, complete all as specified and as directed. |
99 | Supply and fix wall mounting fans completewith all its orginal acessories in put 90 to245V,400 mm sweep RPM 1350 energy efficent.directed current motor (BLDC) all as secified and directed |
100 | Disconnecting the power supply and taking down the wall mounting fan300 to 450 mm ,taking to work shop and by taking out burnt copper winding and rewinding with super enamelled copper wire of existing gauge and weight including replacement of all insulation material, andother petty items required for making motor functional , fixing in its existing position with all new fitting & fixtures, complete all as specified and as directed. Note: Item No -99 to 100- Servicing of Exhaustfans and Spares will be measured and paid separately under relevant items of this schedule. |
101 | Supply Only GM bush suitable for Ceiling fan 1200 Sweep complete all as specified and as directed. |
102 | Supply only ball bearings suitable for Ceiling fans / Exhaust fans / Wall mounting fans of 1200 Sweep complete all as specified and as directed. |
103 | Supply Only 2.5 MFD Capacitors for the fan in position Complete all as specified and as directed. |
104 | Supply Only 4 MFD Capacitors of the fan in position complete all as specified and as directed. |
105 | Taking out old unserviceable UG cable including supply and laying 95 Sqmm, 3.5 Core LT UG cable grade PVC XLPE insulated, PVC sheathed armoured, heavy duty, in trenches / walls / poles / passing through pipes with multistranded aluminium conductor including lugs / thimbles / ferrules connection, testing and commissioning complete all as specified and as directed. |
106 | Material and Labour for Straight through joints (Epoxy) heat shrinkable type for UG cable including jointing kit and all accessories complete for making joints suitable for LT UG Cable of Aluminium conductor of size Upto 35, Sqmm 3.5 / 4 core complete all as specified and as directed. |
107 | Material and Labour for Straight through joints (Epoxy) heat shrinkable type for UG cable including jointing kit and all accessories complete for making joints suitable for LT UG Cable of Aluminium conductor of size 50 to 95, Sqmm 3.5 / 4 core Complete all as specified and as directed. Note for ser item No.106 & 107 (i) Earth work excavation, sand cushioning, bricks for protection, GI pipe etc shall be measured and paid for separately under relevant items of this schedule. |
108 | Supply and Fixing in repairs MCCB4Pole, 415 volts 50 HZ AC suitable for current carrying capacity 250 Amps rating, fixed and thermal magnetic release with rupturing capacity 35 KA complete all as specified and directed. |
109 | Supply Only in repairs of 25 KVAR Capacitor heavy duty existing make and type440 volts with inrush current Limiting Coil complete all as specified and as directed. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy