Special Repair To Lt Oh Line And Ug Cable And Provn Of 01 X Refrigerator With Volatage Stabilizer Under Aor Of Age E / M Under Ge ( South ) Akhnoor Special Repair To Lt Oh Line And Ug Cable And Provn Of 01 X Refrigerator With Volatage Stabilizer Under, GE SOUTH AKHNOOR-Jammu And Kashmir

Military Engineer Services-MES has published Special Repair To Lt Oh Line And Ug Cable And Provn Of 01 X Refrigerator With Volatage Stabilizer Under Aor Of Age E / M Under Ge ( South ) Akhnoor Special Repair To Lt Oh Line And Ug Cable And Provn Of 01 X Refrigerator With Volatage Stabilizer Under. Submission Date for this Tender is 08-11-2021. Overhead Line Tenders in GE SOUTH AKHNOOR Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

29570597
Special Repair To Lt Oh Line And Ug Cable And Provn Of 01 X Refrigerator With Volatage Stabilizer Under Aor Of Age E / M Under Ge ( South ) Akhnoor Special Repair To Lt Oh Line And Ug Cable And Provn Of 01 X Refrigerator With Volatage Stabilizer Under
Open Tender
Indian
Jammu And Kashmir
GE SOUTH AKHNOOR
08-11-2021

Tender Details

Special Repair To Lt Oh Line And Ug Cable And Provn Of 01 X Refrigerator With Volatage Stabilizer Under Aor Of Age E / M Under Ge ( South ) Akhnoor Special Repair To Lt Oh Line And Ug Cable And Provn Of 01 X Refrigerator With Volatage Stabilizer Under Aor Of Age E / M Under Ge ( South ) Akhnoor

Key Value

Document Fees
INR 500 /-
EMD
INR 58000.0 /-
Tender Value
INR 29 Lakhs /-

BOQ Items

Name of Work: SPECIAL REPAIR TO LT OH LINE AND UG CABLE AND PROVN OF 01 X REFRIGERATOR WITH VOLATAGE STABILIZERUNDER AOR OF AGE E/M UNDER GE (SOUTH) AKHNOOR.
Sl. No. Item Description
1Excavation in trenches, not exceeding 1.50 mtr wide and not exceeding 1.50mtr in depth; not exceeding 10 Sqm on plan and not exceeding 1.50 mtr in depth and getting out, in any type of soil, for laying electric cables or foundation of poles/ stays etc, complete all as specified and as directed by Engineer-In-Charge.
2Excavation in trenches, not exceeding 1.50 mtr wide andexceeding 1.50mtr but not exceeding 3.0mtrs in depth, not exceeding 10 Sqm on plan and getting out, in any type of soil, for foundation of poles/ stays etc, complete all as specified and as directed by Engineer-In-Charge.
3Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25Cm, complete all as specified and directed by Engineer-In-Charge.
4Removing excavated materials/ soils, not exceeding 50mtrs and depositing where directed at a level not exceeding 1.50mtrs, complete all as specified and directed by Engineer-In-Charge.
5Sand cushioning to protection of underground cables, laid 8 Cm before laying and 15 Cm after laying of cable, and punned to form an overall layer of 18 Cm thick, complete all as specified and directed by Engineer-In-Charge. Note: Punned thickness shall be measured.
6Sub class ‘B’ bricks, modular size, brick covering laid dry, flat, transversally along the length of cable on sand cushioning for mechanical protection of cable, with width equal to the length of the brick, complete all as specified.
7Supply, erecting and fixing in replacement of old pole in true vertical position, steel tubular swaged pole (410 SP – 31), 09 meter long, complete with cast iron base plate, pole cap / finial taper plug, bolts, nuts and washers, welded reduced section and longitudinal weld throughout entire length of pole including 2 coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole shall be provided with one coat of red oxide primer and two coats of aluminium paint including taking down old damaged poles complete all as specified and directed.
8Plain cement concrete M-7.50 (1:4:8), type D-2 (using 40mm graded crushed stone aggregate), as in or as mass concrete in foundation of poles/ stays etc , complete all as specified and as directed by Engineer-In-Charge.
9M&L for PCCtype C-2 (1:3:6)with 40 mm gradded stone aggregate for coping ofpolesincluding necessary formwork complete all as specified and directed.
10S&F in replacement of Earthing complete with galvanised steel earth plate electrode 60 cm x 60cmx6mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 meters below normal ground level. connecting to the GI wire 4 mm dia by means of bolls, nuts, check nuts and washers of galvanised iron and earth wire protected by provision of GI light grade pipe 15 mm bore including provision of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone aggregates with 40mm thick cover of RCC (1:2:4) reinforced with XPM weight not less than 4 Kg/Sqm) and frame of angle iron 25x25x6mm with lugs 02 Nos and handle of 6mm dia MS bar made to shape, GI medium grade 20mm bore pipe for watering , perforated at bottom. 1.75 metre long placed on top edge of earth plate. charcoal and common salt fillingwith fixing arrangement, funnel wire mesh and earth work in soft soil returning filling in and removal of surplus soil to a distance not exceeding 50 meters all as per electrical plate 3 of SSR-2009 Part-I and connecting to earth test point all as specified or indicated including testing on completion. NOTE :- (i) Item of earthing includes cost of 7.5 m long GI wire of size 4 mm dia with protection pipe of 15mm dia GI medium grade, any variation in length shall be adjusted through deviation order based on SSR rates enhanced by (-40)%. (ii) On testing after completion of earthing if the desired earth resistance is not obtained earthing will be re-done by the contractor at his own risk and cost.
11Material & labour for earthing complete with galvanised cast iron earth plate electrode of size 600x600x6.3mm thick buried directly in ground less than 3.0m deep below normal ground level as earth electrode with top edge of the earth plate not less than 2.25mtr below ground level using GI strip 32x6 mm dia as earth continuity conductor connected to earth plate by means of welding, GI thimbles, nuts, bolts & washers all as directed including providing earth wire protection pipe GI light grade15mm dia from earth plate to main switch board/panel, watering pipe 20mm dia with wire mesh and funnel at top, earth pit and RCC pit coverwith handle of angle iron frame of size 40 x 40 x 6mm in PCC 1:3:6 adequate quantity of charcoal dust and salt and kalmi shore all around the earth plate, earth work in any type of soil remaining surplus excavated material all as required at site and specified in EP No 3 of SSR part I 2009 or directed by Engineer-in-charge and incl testing on completion. NOTE :- (i) Item of earthing includes cost of 7.5 m long GI strip of size 32x6mm with protection pipe of 40mm dia GI medium grade, any variation in length shall be adjusted through deviation order based on SSR rates enhanced by (-40)%. (ii) On testing after completion of earthing if the desired earth resistance is not obtained earthing will be re-done by the contractor at his own risk and cost.
12Replacement of old unserviceable/ damaged stay assembly with new stay assembly, galvanised iron, complete with accessories as shown in electrical plate No-1, diameter of stay rod 20mm dia, including galvanised iron stay plate 300x300x6mm, galvanised iron thimble, 14mm dia 400mm long stay bow and galvanised iron nuts bolts, washers including loop type insulator, vitreous porcelain, white, brown or green, large size, with overall dimensions 65x90mm, clearance of hole 16.0mm, including stay wire, galvanised iron, stay wire 7/4mm stranded, complete all as specified and as directed by Engineer-In-Charge. Note: Excavation, earth work and PCC shall be measured and paid separately under relevant item of Schedule ‘A’/ BOQ.
13S&F in replacement ofFactory made LT electrical panel board, AC, 3 phase, 4 wire, 415 / 500 V, 50 Hz, cubical outdoortype, fabricated with 3.40 mm thick made mild steel sheet /CRCA (1200mmx1500mmx450mm), powder coated , CPRI Approved , bottom with detachable plates, front and rear with hinged type double door and locking arrangements, chamber for cable entry and exit, chamber for aluminium bus bars including aluminium bus bars 4 Nos, 800 amps capacity insulated with colored PVC sleeves mounted on frame of mild steel angle iron 25x25x5mm, 30Cm above from the ground level duly supported with mild steel angle iron 40x40x5mm, embedded in Plain Cement Concrete M-10 (1:3:6), type C-1 (using 20mm graded crushed stone aggregates) 300mm below the ground level and required masonry in brick work in cement mortar 1:6 incl suitable insulators and separators, holes drilled for connections, complete suitable for mounting following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated, complete all as specified and comprising of the followings:- OUTGOING :- (a)MCCB 4 Pole, 415 V, Thermal Magnetic type, 200 Amps with breaking capacity 25 KA - 02 No (a)MCCB 4 Pole, 415 V, Thermal Magnetic type, 100 Amps with breaking capacity 25 KA - 04 No. (b) MCB 2 Pole, 415 V, 63 Amp rating with sensitivity of 30 MA - 02 No. (c) Change over switch onload 415 volts TPN in sheet metal enclosureof capacity 200 Amps -02 No INCOMING :- (d)MCCB 4 Pole, 415 V, Thermal Magnetic type, 630 Amps with breaking capacity 36 KA - 01 No (e) AC Three phase static energy meter of accuracy class 1.0 ,3 X 240 V ,50 Hz withBacklit LCD display of rating 10 - 60 A (measures and displays KWH ,V, Current I, KW, pf last month history of KWH, MD in KW) with special features like TOD, temper logging, optical communication port display in absence of power with transparent hinge type box-01 Nos (f)Capacitor metalized poly propylene heavy duty (MPP-H) for 3 phase ,440 V, 50 Hz System for permissible non- linear load 15% of 20 KVAR capacity -01 No (g) Phase indication lamps - 3 Nos. (H)Digital type Ammeter along with 4 step selector switch and CTs of suitable size - 01 Set (J) Digital type Voltmeter along with 7 step selector switch- 01 No
14S& F in replacement of Factory madeLT Feeder Pillar Box, outdoor, cubical type, floor mounted, factory made, CPRI approved, size 750x500x150mmpowder coated , CPRI Approved , bottom with detachable plates, front and rear with hinged type double door and locking arrangements, chamber for cable entry and exit, chamber for aluminium bus bars including aluminium bus bars 4 Nos, 400 amps capacity insulated with colored PVC sleeves mounted on frame of mild steel angle iron 25x25x5mm, 30Cm above from the ground level duly supported with mild steel angle iron 40x40x5mm, embedded in Plain Cement Concrete M-10 (1:3:6), type C-1 (using 20mm graded crushed stone aggregates) 300mm below the ground level and required masonry in brick work in cement mortar 1:6 incl suitable insulators and separators, holes drilled for connections, complete suitable for mounting following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated, complete all as specified and comprising of the followings:- OUTGOING :- (a)MCCB 4 Pole, 415 V, Thermal Magnetic type, 100 Amps with breaking capacity 25KA - 02 Nos. (b)MCCB 4 Pole, 415 V, Thermal Magnetic type, 63 Amps with breaking capacity 16KA - 04 Nos. INCOMING:- (c) MCCB 4 Pole, 415 V, Thermal Magnetic type, 250 Amps with breaking capacity 36KA - 01 No. (d) Change over switch onload 415 volts TPN in sheet metal enclosureof capacity 100 Amps -02 No INCOMING :- (e) Phase indication lamps - 3 Nos. (f)Digital type Ammeter along with 4 step selector switch and CTs of suitable size - 01 Set (g) Digital type Voltmeter along with 7 step selector switch- 01 No
15S& F in replacement of Factory madeLT Feeder Pillar Box, outdoor, cubical type, floor mounted, factory made, CPRI approved, size 750x500x150mmpowder coated , CPRI Approved , bottom with detachable plates, front and rear with hinged type double door and locking arrangements, chamber for cable entry and exit, chamber for aluminium bus bars including aluminium bus bars 4 Nos, 400 amps capacity insulated with colored PVC sleeves mounted on frame of mild steel angle iron 25x25x5mm, 30Cm above from the ground level duly supported with mild steel angle iron 40x40x5mm, embedded in Plain Cement Concrete M-10 (1:3:6), type C-1 (using 20mm graded crushed stone aggregates) 300mm below the ground level and required masonry in brick work in cement mortar 1:6 incl suitable insulators and separators, holes drilled for connections, complete suitable for mounting following switch gear items internally connected with suitable capacity aluminium strip/ rods insulated, complete all as specified and comprising of the followings:- OUTGOING :- (a)MCCB 4 Pole, 415 V, Thermal Magnetic type, 100 Amps with breaking capacity 16KA - 02 Nos. (b) MCB 2 Pole, 415 V, 40-63 Amp rating with sensitivity of 30 MA -10 No. (c) Change over switch onload 415 volts TPN in sheet metal enclosureof capacity 100 Amps -02 No INCOMING :- (d)MCCB 4 Pole, 415 V, Thermal Magnetic type, 200 Amps with breaking capacity 36KA - 01 No. (e) Phase indication lamps - 3 Nos. (f)Digital type Ammeter along with 4 step selector switch and CTs of suitable size - 01 Set (g) Digital type Voltmeter along with 7 step selector switch- 01 No
16S&F in replacement ofSMC FRP junction Box, sliding door fixed to base by means of ssliding, pole monunting arrangeemnt, maint free, fire retardent, pilferage proof for entry the cable from side and bottom of size 340x160x90mm with aluminium bus bar for street lighting of 3 phasse/ 4 core complete all as specified and directed. Make: sintex GS-JB-3416 or equivelent in Havells/L&T.
17S&F in replacement of 1100VGradeLTAerialBunchedCable of size 3x16 + 1x16 + 1x16 sq.mm (Phase Wire + Neutral Wire + Insulated MessengerWire)havingthreePowerCore&Oneinsulated MessengerCoreofstrandedcompactedcircularAluminiumBlack coloured XLPE insulated & Core identification by ridges,one,twoandthree&fourrespectively.Neutral Wire should be of stranded compacted Circular Aluminium Alloy Conductor conforming to IS 8130/1984, IS-398(Part-IV)/1979 and IS-14255/1995 with upto date amendments,if any, composition of phase wire, neutral wire and messeanger wire all shall conform to manufacturer instructions subject to compliance with Electricty manual /Indian Electricity Act -2003, andthere by changes in the size of messeanger and neutral wire, nothing shall be admissible on this ground, including necessary connecting accessories like Anchor Clamps (3 Bolt and 2 Bolt Type), Eye hook with Suspension Clamp Assembly, PCC Pole Clamp, Insulation Piercing Connectors with cover or P.G.Connectors with insulation cover,Water Proof pre-insulated Hexagonal Compression Connectors & Lugs etc , complete all as specified and as directed by Engr-in-Charge. Make: Havells/ Poycab/ Finolex/ Gloster Cables Ltd/KEI.
181100VGradeL.T.AerialBunchedCable of size 3x120 + 1x35 + 1x120 sq.mm (Phase Wire + Neutral Wire + Insulated MessengerWire)havingthreePowerCore&Oneinsulated MessengerCoreofstrandedcompactedcircularAluminiumBlack coloured XLPE insulated & Core identification by ridges,one,twoandthree&fourrespectively.Neutral Wire should be of stranded compacted Circular Aluminium Alloy Conductor conforming to IS 8130/1984, IS-398(Part-IV)/1979 and IS-14255/1995 with upto date amendments,if any, composition of phase wire, neutral wire and messeanger wire all shall conform to manufacturer instructions subject to compliance with Electricty manual /Indian Electricity Act -2003, andthere by changes in the size of messeanger and neutral wire, nothing shall be admissible on this ground, including necessary connecting accessories like Anchor Clamps (3 Bolt and 2 Bolt Type), Eye hook with Suspension Clamp Assembly, PCC Pole Clamp, Insulation Piercing Connectors with cover or P.G.Connectors with insulation cover,Water Proof pre-insulated Hexagonal Compression Connectors & Lugs etc , complete all as specified and as directed by Engr-in-Charge. Make: Havells/ Poycab/ Finolex/ Gloster Cables Ltd/KEI.
19S&F in replacement of New generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high efficient LED as lighting source with toughened glass having IP66 protection and impact resistance of IK07, including LED lamps of 70 Watt and connecting up with twin core twisted flexible copper conductor cable with suitable size,, including House service bracket for mounting light fittings House service bracket any type complete with 1.50mtr long galvanised iron pipe 40mm dia medium grade, bent to required shape including mild steel clamps of flat iron 40x6mm, hook, stay, nut, bolt and washer including painting with two coats of synthetic enamel paint over one coat of red oxide primer , complete all as specified. Make: Havells cat part No- Endura cityliner Neo ENDURACITYLINERNEOSL70WLED757PASYBOTG OR Equivalent makes and specifications in Philips/Wipro
20Dismantling of insulators of any type and any description, complete all as specified and as directed by Engineer-In-Charge.
21Replacement of old unserviceable/ damaged Mild steel in cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one coat of red oxide primer, one under coat and one finishing coat of aluminium paint, complete all as specified and as directed by Engineer-In-Charge.
22Replacement of old unserviceable rubber mat with new synthetic rubber insulating mat for preventing HT shock, thickness not less than 25mm, size 2.00x1.00 mtrs, complete all as specified and as directed by Engineer-In-Charge.
23Replacement of old unserviceable/ damaged LT XLPE cable with new XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross-sectional area 150.0 Sqmm,3.50-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends, complete all as specified and as directed by Engineer-In-Charge.
24Replacement of old unserviceable/ damaged LT XLPE cable with new XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross-sectional area 95.0 Sqmm,3.50-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends, complete all as specified and as directed by Engineer-In-Charge.
25Replacement of old unserviceable/ damaged LT XLPE cable with new XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross-sectional area 70.0 Sqmm,3.50-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends, complete all as specified and as directed by Engineer-In-Charge.
26Replacement of old unserviceable/ damaged LT XLPE cable with new XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross-sectional area 50.0 Sqmm,3.50-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends, complete all as specified and as directed by Engineer-In-Charge.
27Replacement of old unserviceable/ damaged LT XLPE cable with new XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross-sectional area 35.0 Sqmm,3.50-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends, complete all as specified and as directed by Engineer-In-Charge.
28Replacement of old unserviceable/ damaged LT XLPE cable with new XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross-sectional area 25.0 Sqmm,4.0-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends, complete all as specified and as directed by Engineer-In-Charge.
29Dismantling of ACSR or AAC conductors From poles at any height and location, complete all as specified and as directed by Engineer-In-Charge.
30Supply and fixing, 1100 Volts grade, heavy duty, multi-stranded cable, PVC insulated aluminium conductor, multi-stranded, cross sectional area 10.0 Sqmm, 2-core, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 50 Centimetre apart Including 4.0mm suspension wire, complete all as specified and as directed.
31Refrigerator, 220 to 240 Ltrs capacity, ssingle door, single phase 240 Volts, 50 Hz, five star rating in power savings, powder coated painted body for glossy finish, door lock system for restricted accessibility, frost free switch for faster cooling when needed, complete all as specified and as directed by Engineer-In-Charge. Make: LG cat part No- LG B245BPZNor Samsung/ Voltas/ Godrej.
32Voltage stabilizer for automatic operations, copper wounded, single phase, naturally air cooled, indoor type with copper wound, , working voltage range (input), 90 Volts to 270 Volts, with output voltage stabilizer at 230V current capacity upto 12 Amps, 4.0 KVA capacity, with accuracy of ±2.50%, complete all as specified and as directed by Engineer-In-Charge. Make: AE/ ElectricField/ Andrew Yule / Godrej.
33Plug top with new plug top, 20 Amps, 3-pin, 240 volts, metal clad alongwith earthing arranagements with 20 Amp MCB SP, complete all as specified and as directed by Engineer-In-Charge.
34Amount of Schedule of credit of for Rs 1,62,500.00 shall be deducted from quoted amount.