| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. |
| 2 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as reqd. |
| 3 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16Amodular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 4 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 6 way double door |
| 5 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single Pole & neutral |
| 6 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 Amps |
| 7 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. |
| 8 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 9 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 10 | S/I/T/C of LED Tube type Luminaire 20W rating complete with Polycarbonate housing Battenintegrated electronic driver prewired with high efficient LED with the following: (a) Total System wattage 20 watt +/- 5% (b) Luminous Efficacy Lumens/watt >=95 (c) power factor >= 0.95 |
| 11 | Supply of 12\" (300 mm) sweep 1400 RPM exhaust fan heavy duty complete with shutter, blade etc as required. |
| 12 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep |
| 13 | Supply,installation,testing and commissioning of single/three phasemonoblock pumpset complete with all accessories workable on 240/415 Volts 50 Hz AC supply (a)01 HP (.75 KW) single phase pumpset head from 12-30 mt suction and delivery 25X25 mm |
| 14 | SITC of 30 watt LED flood light luminiare fitted with lens made of pressure dia cast aluminium housing & toughened glass cover complete with the following specification as reqd WITH IP-66 (a)Total system wattage=30 watt+/-5%(b) Luminaire Efficency>=100 Lm/w (c) Power factor>=0.95 (d) Protection class IP-66 |
| 15 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40A |
| 16 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing masonry open duct as required. Upto 35 sqmm |
| 17 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required.Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 18 | Supply of XLPE insulated,PVC sheathed Al.conductor Armoured Cable Conforming to IS 7098/1988 of following Sizes (a) 3 X6 SQmm |
| 19 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 20 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. 2x4 sq mm+1x4 sqmm earth wire |
| 21 | Supplying and fixing brass baten/ angle holder including connection etc. as required |
| 22 | Supply of 14/15 Watt LED retrofit lamp suitable for B 22 Holder. |