| 1 | Electrical Items : Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required |
| 2 | CI/MS cover plate hinged to frame with locking arrangement-01 No.,Charcoal-96.00 KG, Salt-5.00 kG, Common burnt clay F.P.S.-50 Nos.) and Earthing pit depth- 12\"-15\" with all etc. as required. |
| 3 | Copper Strip in 40 mm dia G.I. Pipe |
| 4 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required |
| 5 | Copper Strip on wall surface |
| 6 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 7 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 8 | upto 35 sq. mm |
| 9 | Laying and fixing of one number PVC inslulated and PVC sheated/ XLPE power cable of 1.1KV grade of following size on wall surface as required. |
| 10 | upto 35 sq mm (clamped with 1mm thick saddle) |
| 11 | Above 35 sqmm and upto 95 sq mm(Clamped with 25 x 3 mm M.S.flat clamps) |
| 12 | Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required. |
| 13 | size 60 cm X 60 cm at the bottom and 50 cm X 50 cm |
| 14 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required |
| 15 | 4 X 16 sq. mm (28mm) |
| 16 | 3½ X 25 sq. mm (28mm) |
| 17 | 3½ X 35 sq. mm (32mm) |
| 18 | 3½ X 50 sq. mm (35mm) |
| 19 | 3½ X 120 sq. mm (45mm) |
| 20 | Providing 15mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels. |
| 21 | mix 1:4 (1 cement : 4 fine sand |
| 22 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required |
| 23 | 150 mm dia |
| 24 | Supplying and laying of following sizeDWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc.conforming toIS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 25 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 26 | 90 mm dia (OD-90 mm & ID-76 mm nominal) |
| 27 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 28 | PAINTING WITH ONE OR MORE COAT OF SYNTHETIC ENAMEL PAINT OF APPROVED BRAND AND MANUFACTURER OF REQUIRED COLOUR TO GIVE AN EVEN SHADE. |
| 29 | One or more coats on old work |
| 30 | Re-lettering with black Japan paint of approved brand and manufacture. |
| 31 | One or more coats on old work |
| 32 | Supplying and laying of following size ISI marked PVC insulated and PVC sheathed/XLPE /FRLS (Flame proof, water proof) aluminium conductor steel armoured cable of 1.1KV grade as required. |
| 33 | 4 X 16 sqmm |
| 34 | 3.5 x 25 sq mm |
| 35 | 3.5 x 35 sqmm |
| 36 | 3.5 x 50 sq mm |
| 37 | 3.5 x 120 sq mm |
| 38 | Supplying & febrication,installation,testing and commissioning of 4 poles,LT Outdoor panel with double wall housing with spacing about 6 inchs with each other (Duble wall cubical panel for environmental protection) made of 2 mmthick CRCA-MS sheet suitable housing of 500 mm deep with mounting arrangement Din ril for fixing of Incomer 250Amp.-01 N0. MCCB,1000 A 4 STRIP Aluminioum busbar duly sleeved making suitable hole for cable entries detachble gland plates at bottom painting with supierior quaility . bus bar with heat shirnk sleeves etc, dust and vermin proof IP 65 standred having the switch gears and metering facility compelete with connections & inter connections painting etc.as required. (Every seperate feeder name plate fabrication and installation work and about 2 feet height solid high quality angle iron stand is also included in this Item). The panel must be factory fabricated.The drawing of the panel will be factory fabricated.The drawing of the panel fabricated and after fabrication the same will be inspected and aproved by Engineer-in-charge before its dispatch from factory to site. |
| 39 | INCOMING:-A. 250 A,Four Pole MCCB adjustable thermal & adjustable magnetic setting, Breaking capacity 36 KA,-01 No. outgoing- 63 Amp. 4 pole isolator-08 Nos.Note:- Dismentaling the old panels, Cables & switchgears and fixing of new panels, all cable and Supplying & fixing of new switchgears Installaton, testing snd commissionning & other fixing works are included with the same. |