| 1 | Supply,Installation & Commissioning of SCADA software (Make-Schiender/Simens/Fox) with Graphical processor visualisation Advanced alaram management,historical and Real time trending,Built-in-reporting,Stastical process control,Multithreaded citect VBA and Cicode programming language with 500 Tag SCADA Software (Make- Schneider, Siemens),1KVa online Ups with 30Min batery backup- 1Nos,CPU Having Preloaded win-10 Proffessional, I3-10gen 2.4 Ghz Prrocessor, DDR4 8gb Ram, 500 gb 7200 Rpm HDD-1 Nos ( Make- HP,DELL,LENOVO),USB based keyboard - 1Nos,USB based Optical Mouse- 1Nos,43\"\" LED monitor - 1Nos,A4 size laserPrinter - 1Nos,Wooden Computer table - 1 Nos ,Preparation of P&I diagram, Creation of Multi visualization screen for Process control,alarm managenent, Historical and realtime process trend, Daily reporting etc complete as per requirement & direction of Engineer - in - Charge. |
| 2 | Supply of PLC Panel with following technical specification i,e. Enclosure:800x400x800mm-01No,PLC-Schneider M200/221-01No,AI CARD:SCHNEIDER 8CH-01No,HMI;Schneider HMIGMU 7\"-01,SMPS:10A-01Nos,MCB DP 10A-10Nos,Panel cooling fan-01 Nos,Panel Light-01 No,TB-100 terminal,Wiring with PVC duct & C-Channel-=01No,Gland plate with 10 Nos fibre Glands-01 Set,Installation of panel -01 No,Programming of PLC-01 No,Programming of HMI-01 No |
| 3 | Supplying all materials,labour,T&P, for fitting of PLC panel with following data/ power cables including jointing socketing testing & commissioning etc. complete as per specification basing on requirement and direction of Engineer in charge.as per electrical specificationControl Cable |
| 4 | 2.5 sqmm x 10 CoreCu. Armoured over all shielded Cable |
| 5 | 1.5 sqmm x 2CoreOverall Shielded Cu. Armoured Cable |
| 6 | 16 mm SC Gland |
| 7 | 19 mm SC Gland |
| 8 | PowerCable 6 sqmm x 4 CoreCu. Armoured Cable |
| 9 | 1.5 sqmm x 3 core Cu.Armoured Cable |
| 10 | 50 sqmm x 3.5 Core AL.Armourded cable |
| 11 | 150 sqmm x 3.5 CoreAL. Armoured Cable |
| 12 | 45MM SC Gland |
| 13 | 57MM SC Gland |
| 14 | 19 mm SC Gland |
| 15 | 25 mm SC Gland |
| 16 | 6 mm COPPER RING socket |
| 17 | 1.5 mm COPPER Pin socket |
| 18 | 150 mm alluminium socket |
| 19 | 50 mm alluminium socket |
| 20 | Supplying all labour, T&P and earth work in excavation in all kinds of soil in pipe trenchs etc including dressing and levelling the bed and depositing the soil within 50M initial lead and 1.5M initial lift & filling the trenches with excavated earth as per the direction of the Engineer-in-charge. |
| 21 | Laying in trenches unplasticised PVC pipes conforming to IS:4985-2000 and specials of the following outside diameter for all classes including jointing with supply of approved solvent cement by non-heat application method including testing as per specification complete. (Earth work in trenches to be measured and paid for separately) |
| 22 | 90mm dia rigid UPVC pipe Class-3 (0.60 mpa) For laying of data/power supply cable |
| 23 | 50 mm dia HDPE Pipe -PE - 63 (6Kg/cm2) For laying of data/power supply cable |
| 24 | Laying of one number of PVC insulated and PVC seathed / XLPE power cable of 1.1 KV grade of size not exceeding 25 sq.mm direct in ground including excavationand refilling the trench etc. as required |
| 25 | 1.5 sqmm x 2 CoreOverall Shielded Cu. Armoured Cable |
| 26 | 50 sqmm x 3.5 Core AL.Armourded cable |
| 27 | 150 sqmm x 3.5 CoreAL. Armoured Cable |
| 28 | Supply, Installation, Testing& CommissioningofChemical Earthingincluding supply of all materialsT&P and Labour Etc. All completed asper electrical specification and as per direction of EIC. |
| 29 | Supplying, installation, Testing & commissioning of electric powered electromagnetic full bore type IP 68 fully welded Flanged type water flow meter of Pulse DC type of Flow tube SS304, coil housing & electrodes SS316, SS ring type grounding etc with IP 67 signal converter remote mounting,input power supply 220VAC & out put 24V DC 4 - 20 mA,programable LCD display to show Actual flow rate, totalised flow, flow direction, flow velocity,conductivity with + or - 0.5 % accuracy etc & provision to diagnostics empty pipe detection, coil temperature, coil resistance etc & compatable to data communication modules & communication the data to remote SCADA station for live monitoring where ever required including providing data cable & power cablerequired as per site condition .The standard calibration certificate & guarantee certificate for flow meter & electromagnetic signal converter to be given for minimum one year from the date of installation. |
| 30 | Electro magnetic flow meter 150mm dia Flow meter for Delivery line from ESR at Police Colony |
| 31 | 200mm dia Flow meter for Delivery line from ESR |
| 32 | 250mm dia Flow meter for Delivery line from ESR |
| 33 | 400mm dia Flow meter for loading of UGR |
| 34 | Supplying, installation, Testing & commissioning of Battery powered electromagnetic full bore type IP 68 fully welded Flanged type water flow meter of Pulse DC type of Flow tube/ Housing Metallic Alloy,electrodes HC22 grounding etc with IP 68 signal converter remote mounting, power supply24V DC,programable LCD display to show Instantaneous Flow, batteey life with + or - 0.2 % accuracy etc & compatable to data communication modules & communication the data to remote SCADA station for live monitoring where ever required including providing data cable & power cablerequired as per site condition .The battery life should be minimum 10 years.The standard calibration certificate & guarantee certificate for flow meter & electromagnetic signal converter to be given for minimum one year from the date of installation. |
| 35 | Battery Operated flow meter 300mm dia Flow meter Delivery line infront of VSS Nagar Pump House |
| 36 | 100mm dia Flow meter Near Senior Citezen Club at VSS Nagar |
| 37 | 150mm dia Flow meter Near Trinath Slum |
| 38 | 200mm dia Flow meter Near By pass arrangement |
| 39 | Manufacturing, supply and delivery installation & testing & commissioning of DI D/F non-rising spindle soft seated glandless Gate Valves with electrically Operated Actuator with body and bonnet of Ductile cast iron of grade GGG-40, wedge with fully encapsulated EPDM rubber W-270 (approved for drinking water) and seals of NBR. The valves should be with replaceable stem nut and replaceable sliding shoes. Valve stems shall be of single piece thread rolled. Valve shall have 3 “O” rings of NBR for stem sealing. Gate valve shall be compatible forburried applications without valve chamber. Face-to-face dimensions as per BS 5163-89/IS 14846-PD/EN 558F4 and flange connections as per IS 1538, Maximum Valve operating torque should be at least 40% less than the torque as stated in the standard EN 1074. Electrostatic epoxy powder/liquid coating (EP-P) inside and outside color blue RAL 5005 with minimum coating thickness of 250 microns. The EPDM rubber & Epoxy Powder should be approved by W 270. (EP-P ? it is a resi-coat powder approved for drinking water application, applied through fusion bonding technology process by dipping the shot-blasted casted components heated up to 200 deg C). Material of Construction:The acuator should be compatible for fixing on similar type of any other make valves & cost includes 20 mtr datacommunication & power supply cable required for operation of valve through acuator with SCADA Control including testing & commissioning at site etc complete. |
| 40 | 400mm diaelectrically operated compacted Actuator valve with Glandless Sluice Valveunitwith 415 volt grade integrated panel circuitinch type 4 to 20Amp Out put along with fuse /moisture protection IP-68all complete valve with actuator slim linein loading line of UGR. Near Taping Point Control valve |
| 41 | 250mm diaelectrically operated compacted Actuator valve with Glandless Sluice Valveunitwith 415 volt grade integrated panel circuitinch type 4 to 20Amp Out put along with fuse /moisture protection IP-68all complete valve with actuator slim line. in loadingline of ESR 1 & 2 |
| 42 | 150mm diaelectrically operated compacted Actuator valve with Glandless Sluice Valveunitwith 415 volt grade integrated panel circuitinch type 4 to 20Amp Out put along with fuse /moisture protection IP-68all complete valve with actuator slim line. Police Colony Pump House ESR Delivery Line |
| 43 | Supplying, Fitting,Commissioning,Fixing double chamber control valve,hydraulic operated with battery powered, selonoid valve,electronic timer controller,Timer,integral oriface plate assembly,differential control,reverse flow control,restriction orifice Fitting,Commissionings,valve position indicator,USB Port withj cable ,liscensed software,IP68,with builtin power supply for 2 years operations for operating pressure 1.0-2.0 Kg/cm2 Body A216 WCBintegrated with PLC pannel for operation (local/remort and web enabled with command and control) at ESR of make CLA/DOROT/SINGERto control water supplyincluding the cost of valve cutting the pipeline & making good to the damagesincludingcost ofall labours, T&P etc. all completeas per the direction of Engineer-in-charge. |
| 44 | 200mm dia electric operated Selonid valve pilot Actuated |
| 45 | Dismantling of cement concrete pavement by mechanical means using pneumatic tools, breaking to pieces not exceeding 0.02 cum in volume and stock piling at designated locations and disposal of dismantled materials up to a lead of 1000 metres, stacking serviceable and unserviceable materials separately |
| 46 | For installation of 250mm dia Flanged Water Flow Meter |
| 47 | Cutting in disintegrated rock not requiring blasting to be removed by pick axes and crow bars and depositing materials within 50m initial lead and 1.5m initial lift including rough dressing as per direction and specification of the department including stacking the useful materials separately as ordered etc as per direction of Engineer - in - Charge. |
| 48 | Supplying all materials, labour, and T&P for providing mechanical joints to flange socket as per relevant IS with suitable flanged joints and fitting & fixing of following in pipeas per specifications including testing with cost of all jointing materials, transportation to site etc. all completeas per the specifications and directions of Engineer-in-charge.For Valve, Flow meter & By pass arrangement |
| 49 | 100mm dia MJ Socketed Tail Piece - |
| 50 | 150mm dia MJ Socketed Tail Piece - |
| 51 | 200mm dia MJ Socketed Tail Piece - |
| 52 | 250mm dia MJ Socketed Tail Piece - |
| 53 | 300mm dia MJ Socketed Tail Piece - |
| 54 | 400mm dia MJ Socketed Tail Piece - |
| 55 | Supplying all labour and T&P for providing and laying MS pipe and specials confirming to IS 3589/99 of quality grade FE 410/ GI Pipe (Medium ) confirming to specificationof following nominal dia and including transportation of pipes and fitting to site etc all complete as per the direction of E.I.C. |
| 56 | 250mm dia M.S.Pipe (6.30mm thick) For Installation of Flow meter |
| 57 | 250mm dia M.S. Flange.(12mm thick) For Installation of Flow meter |
| 58 | 300mm dia M.S.Pipe (7.10mm thick)For Installation of Flow meter |
| 59 | 300mm dia M.S. Flange.(12mm thick) For Installation of Flow meter |
| 60 | 150mm dia M.S.Pipe (4.50mm thick) For Inter Connection with Existing line |
| 61 | 150mm dia M.S. Flange.(12mm thick) For Inter Connection with Existing line |
| 62 | 150mm dia x 45\" M.S. Bend(0.75 mtr ) 4.5mm thick For Inter Connection with Existing line |
| 63 | 400mm dia M.S.Pipe (8.80mm thick) For Inter Connection with Existing line |
| 64 | 400mm dia M.S. Flange.(16mm thick) For Inter Connection with Existing line |
| 65 | 200mm dia M.S.Pipe (6.30mm thick) For By pass arrangement |
| 66 | 200mm dia M.S. Flange.(12mm thick) For By pass arrangement |
| 67 | 200mm dia x 45\" M.S. BendFor By pass arrangement |
| 68 | Cutting of C.I /DI pipe by mechanical means at site including cost of materials,labour,T & P etc all complete. |
| 69 | Supplying all labour and T&P for cutting of following dia MS pipe of following thick in treanches by gas cutter set of pocket etc all complete |
| 70 | For Installation of Flow meter & Inter connection & By Pass Arrangement |
| 71 | Supplying all labour and T&P for jointing following dia MS pipe up to8.0mm thick in treanches by electric arc welding & genetator set of pocket etc all complete |
| 72 | Supplying all materials,labour and T&P for filling foundation and plinth with excavated materials as per direction of Engineer-in-charge. |
| 73 | Supplying all materials, labour and T&P for making flanged joints for C.I. pipes and specials of the following diameter including testing of joints as per specification and direction of E.I.C. |
| 74 | 250mm dia - For Installation of Flow meter |
| 75 | 300mm dia -For Installation of Flow meter |
| 76 | Protection unit for Electromagnetic flow meterThe display unit along with circuite breaker, Surge protection device, DC power supply unit with minimum 30 minutes power back up will be provided with a wall monting / floor mounting SS panel to accomodate the required instrument complete as per the site condition.One chemical earthing to be installed for each flow meter including jointing, conecting with flow meter unit for grounding of curent etc complete in all respect as per approved specification & direction of Engineer - in charge. |
| 77 | 200 / 300 mm dia electric power operated flow meter |
| 78 | Supplying all materials, labour & T & P for fitting and fixing of water meter as per specification and direction of Engineer-in-charge. |
| 79 | 100mm dia Bulk water meter conforming to IS:2373-1981 |
| 80 | Supplying all materials Labour& T & Pfor Fixing DuctileIron Sluice Valve / NR Valve with double flanged ends for water works purposes conforming to IS specification for the followingnominal diameters as per specificationcomplete including cost of Sluice valve. |
| 81 | 200mm dia D/F Gate valve (PN1.6) Vag make |
| 82 | 250mm dia D/F Gate Valve (PN1.6) Vag make |
| 83 | 300mm dia D/F Gate Valve (PN1.6) Vag make |
| 84 | 400mm dia D/F Sluice / Gate Valve (PN1.6) Vag make |
| 85 | Data Communication systemProvision for data communication with industrial GPRS/ GSM modem for mounting on EN DIN rails. GSM & GPRS. 850 + 900 + 1800 + 1900 Mhz etc complete in all respect as per approved specification & direction of Engineer - in charge. |
| 86 | Supplying all labour, T&P materials for laying of twelve core optical fiber cable with pole mounted from VSS Nagar Pumping Staion to H.L Tank through connection the inter midiated pumping station such as Saheed Nagar, Satyanagar & Kharaval Nagar etc. all completeas per the approved drawing if any and the direction of Engineer-in-charge. |
| 87 | Data transmission from VSS Nagar Pumping Staion to H.L Tank throughetc. all completeas per the approved drawing if any and the direction of Engineer-in-charge.(Per Annuan) |
| 88 | Supplying all labour, T&P materials etc. and the construction of brick masonry sluice valve chamber of over all of following internal; earth work in excavation in all kinds of soil; laying of 150mm thick CC (1:3:6) with crusher broken hard granite metal up to 4 cm size metal; 250mm thick brick masonry workin C.M (1:4) with fly ash bricks having crushing strength betgween 75 Kg/cmsq. 12mm thick cement plastering with CM(1:3) forinside surfaces & out side cement pointingetc. all completeas per the approved drawing if any and the direction of Engineer-in-charge.(Excluding cost of Cover slab which will be provided separately) |
| 89 | 0.90 m x 0.90 m x 1.20 m ( deep) Fordifferent dia Flow Meter |
| 90 | 1.20 m x 1.20 m x 1.20 m ( deep) Fordifferent dia Flow Meter |
| 91 | Supplying, fabricating, fitting and fixing of stainless steel of 304 gradeframe with coverstructure madeout of different size of ss angles, Square bar, Flat & sheet duly welded including all cost, taxes, transportation as per approved design and specification, buffing, polishing etc with cost, conveyance, taxes of all materials, labour, T&P etc. required for the work complete in all respect. (As per analysis attached) |
| 92 | 0.90 x 0.90 |
| 93 | 1.20 x 1.20 |
| 94 | Supply of Level indicator to be installed at UGR and ESR with following specificationRange=0 to 8mtrType =Radar Power Supply=24V DCOut Put=4-20mA Make=E&H/ABB/VEGA. |
| 95 | Supply of Pressure transmeter to be installed at 300 mm dia delivery main with following technical specification. |
| 96 | i,e.Range up to 10 kg/cm2,Type-Sensor,Power Supply-24 DC,Out put-4 to 20mA,Make-E & H/ABB/VEGA. |
| 97 | Installation oflevel indicator& 1 Nos pressure sensor including supply of all required materials like SS mountingplate,laying of PVC pipe, excavation of soil,arrangement for making drill on 250 mm DI pipe for safe installation of instruments with providing Engineering support for programmingetc. as per direction of Engineer-In-charge. |
| 98 | Supplying all labour, materials and tools and plants for installation, testing and commissioning of 3KVA single phase Integrated UPS with Auxiliary panel and 2.00 Hour battery power back up with 10Amp with ACDB panel 230Volt grade with 6 nos of Batteryfor smooth functioning and running of thePLC unit alll complete as per diotrectiuon of Engineer in charge. |
| 99 | Supply & installation of industrial Hooter for emergency situation like (over flow of water & contamination of water) and duly programmed with PLC logic etc. |
| 100 | Supplying all labour, materials andfor laying of 240Sqmm 3 1/2core alluminium armoured cable |
| 101 | Supply and fixing of out door fedder pannel having provision for fixing of 400A Three pole Moulded case Circuit Breaker 36KA-1no 400A Bus Bar(4way)-1no,with all the arrangement for incoming 240Sqmm x 3.5 core from the transformer to fedder Panel and out going cable Pump House as per directction of EIC.(Work will be executed as per detail estimate ) |
| 102 | Design, engineering, procurement of materials and bought out components, manufacturing, assembly at shop, inspection, testing and painting at manufacturer’s works, packing, supply, unloading /transportation/ handling/storage at site, assembly at site, installation including touch-up painting, hook-up, pre-commissioning, commissioning, inspection and testing of the complete of the following capacity(Prime Power) DG sets along with AMF Panels, Acoustic enclosure, supply of all erection & commissioning spares, special tools and tackles (as required),instrumentation, allAuxiliaries, Exhaust system& silencer, Fuel Tank, Fuel piping, cable of required size, 4nos. earthing for each DG , required foundation, good quality (L&T or equivalent) , change over, metering pannel with C.T Mater, all complete etc,with inspection certificate from Electrical Inspector andas per Direction of Engineer-In-charge(Mahindra Power/ Kirloskar/ Ashok Leyland/ Sterling/ Koel Green Jackson etc)250KVA |
| 103 | Supply, Installation, Testing Wiring & Commissioningof 250 KVA AMF with manual changeover CUM PCC with APFC &PLC Compactible SOFTSTARTERpanel including Supply of All materialsT&P and Labour Etc. All completed asper electrical specification and as per direction of EIC.(Work will be executed as per detail estimate ) |
| 104 | SSupply, Installation, Testing& CommissioningofLighting Distributionpanel including Supply of All materials (Work will be executed as per detail estimate ) T&P and Labour Etc. All completed asper electrical specification and as per direction of EIC. |
| 105 | Supply, Laying,testing, OF CABLE TRAY Supply of All materialsT&P and Labour etc. all completed asper electrical specification and as per direction of EIC.(Work will be executed as per detail estimate ) |
| 106 | Supplying fitting & fixing of RITTAL make Outer panel (5mm thick) including power supply , metering unit , data network switch rate including provision for 3 battery UPS with lock & key arrangement. |
| 107 | HDPE PIPE: Supply and Laying of 25MM dia HDPE pipe (Make: Supreme/equvalent) in cable trench as per specification and directions of Site Engineer / Engineer-in-Charge. |
| 108 | OFC: Supply and Laying of 12core unarmoured Optical fibre cable (OFC :fiber glass with F-G 62.5/125micron, 2.6DB/KM F600) to various sites through HDPE pipe /in AIR ( pole to pole ), prelaying testing of each cable drum for each fibre and taking the OTDR traces, submission of OTDR traces (in hard as well as soft copy) to Engineer-in-charge/ Site Engineer. |
| 109 | Supply and Installation of OFC jointing kits as per drawings, specifications and directions of Engineer-in-charge/Site Engineer. |
| 110 | Provision forinstallation ofweb application for online LIVE continious data(one data in every 5 second or as per the instruction) accquition M2M integrated server programme (without 3rd party server support) should be upgraded in exsisting PHEO NIC server. |