| 1 | INTERNAL SERVICES/ WORKS |
| 2 | M&L Point Wiring with 1.5 Sqmm (nominal area) 1100 Volt grade PVC insulated unsheathed FRLSH multi-stranded single core Copper Conductor Cable with 1.5 Sqmm (nominal area) 1100 Volt grade PVC insulated unsheathed FRLSH multi-stranded Single Core Copper Conductor Cable (Green Colour) as Earth Continuity Wire, drawn in and including PVC Casing Capping (ISI marked) of suitable size (approx 25/32/40mm width) along with all Fitting/ Fixtures as Tee, Bend, Elbow, Socket, Saddles, etc. complete with PVC Board of suitable size for accommodating Switches, Sockets, Regulators, etc. Earth Continuity Wire connected to Common Earth dolly for ONE FAN POINT controlled by One 1-way Switch 6 Amp, complete all as specified and as directed. |
| 3 | M&L Sub-main Wiring with 2-Runs of 2.5 Sqmm (nominal area) 1100 Volt PVC insulated unsheathed FRLSH multi-stranded Single Core Copper Conductor Cable and 1-Run of 1.5 Sqmm (nominal area) 1100 Volt PVC insulated unsheathed FRLSH multi-stranded Single Core Copper Conductor Cable (Green Colour) as Earth Continuty Conductor drawn through and including PVC Casing Capping (ISI Marked) of suitable size (approx 25/32mm width) along with all Fitting/ Fixtures as Tee, Bend, Elbow, Socket, Saddles, etc. and Making Good Disturbed Surfaces of Walls/ Roofs/ Floors, etc. so as to match with the Existing Finishes, complete all as specified and as directed.NOTE :-(a)Cost of 3-Runs of Cables & 1-Run of PVC Casing Capping will deem to be included in the Quoted Unit Rate and the same also Mesured as ONE UNIT.(b)Sub-main Wiring will be measured existing PVC Casing Capping only. Wire required for looping, etc. as ordered will deem to be included in the Quoted UNIT RATE. |
| 4 | S&F Switch Piano 6 Amp, Single Pole, Flush type, 1-way, 230 Volt AC and connecting up, complete all as specified and as directed. |
| 5 | S&F Ceiling Rose Surface type, Bakelite 65x50mm, 3 Terminals suitable for 230 Volt AC, 6 Amp and connecting up, complete all as specified and as directed. |
| 6 | S&F Ceiling Fan Regulator, Dimmar Switch type, Rotary Stepped, Electronic type 120/280 Volt, 230 Volt AC and connecting up, complete all as specified and as directed. |
| 7 | Supply & Hanging BLDC Ceiling Fan 1200mm Sweep, 26 Watt with Squirrel Cage Induction Motor, having 3 Blades, Holding Down Rod and Accessories, 230 Volt, pproviding Electric Connection from Ceiling Rose to Ceiling Fan with and including Copper Conductor Cable of suitable Size and Length, 3 Core, complete all as specified and as directed.MAKE : HAVELLS (EFFCIENCIA NEO (BLDC 26W) or equivalent in Make : BAJAJ/ CG/ USHA (as approved by GE) |
| 8 | S&F Wall Fan 300mm Sweep, 1360 RPM, Single Phase, 45 Watt, 230/240 Volt with Fixing Arrangement using Fastener, complete all as specified and as directed. |
| 9 | S&F Metallic Body Exhaust Fan 300mm Sweep with Louver, Single Phase, 230/240 Volt with Fixing Arrangement using Fastener, Providing Electric Connection from Ceiling Rose to Exhaust Fan with and including Copper Conductor Cable of suitable Size and Length, 3 Core, complete all as specified and as directed. |
| 10 | S&F MCB 6 to 32 Amp, Single Pole, 50 Hz, 10 kA, 240 Volt, \"C\" Series and connecting up, complete all as specified and as directed. |
| 11 | S&F RCBOs 40 Amp, 30 mA, Double Pole for Earth Leakage, Overload and Short Circuit Protection and connecting up, complete all as specified and as directed. |
| 12 | EXTERNAL SERVICES/ WORKS |
| 13 | Dismantling unserviceable LT Steel Tubular Pole of any description and any size including Demolition Cement Concrete (if required on Ground) and Made Good disturbed Ground, complete all as specified and as directed.NOTE : Unserviceable Pole will be dismantled at Ground Level and disturbed Ground will Made Good as directed for which Earthwork, Demolition Cement Concrete, etc. will not be Measured and Paid separately. |
| 14 | Dismantling/ Taking down Cross Arms, Mild Steel Channel, Angle Section, Flat Iron, Mild Steel Rod, etc., complete all as specified and as directed. |
| 15 | Dismantling/ Taking down Insulator of any description, complete all as specified and as directed. |
| 16 | Dismantling/ Taking down ACSR Conductor including Line Spacers of OH Electric Lines from LT Electric Poles of any description, complete all as specified and as directed. |
| 17 | Dismantling/ Taking down GI Earth Wire, Cradles Guards of any size and shape at any Position from LT Electric Poles of any description, complete all as specified and as directed. |
| 18 | Dismantling Stay Assembly of any description, complete all as specified and as directed.NOTE : Unserviceable Stay Assembly will be dismantled at Ground Level and disturbed Ground will Made Good as directed for which Earth Works, Demolition Cement Concrete, etc. will not be Measured & Paid separately. |
| 19 | Disconnecting & Taking down/out unserviceable LT Cable of any size and any description including GI Pipes, Cable Protection Cover, etc. from Trenches, Floors, Poles, Walls, complete all as specified and as directed.NOTE : Necessary Earth Works will be Measured & Paid under appropriate Items. |
| 20 | Excavating in Trenches, not exc. 1.50 Metre Wide and Depth not exc. 1.50 Metre for Taking out/up and Laying of Water Mains, Cables, Electric Poles, etc., Forming Surfaces to required Foundation, etc. and getting out as in Soft/Loose Soil, complete all as specified and as directed. |
| 21 | Excavating in Trenches, not exc. 1.50 Metre Wide and Depth exc. 1.50 Metre but not exc. 3.00 Metre for Electric Poles, etc., Forming Surfaces to required Foundation, etc. and getting out as in Soft/Loose Soil, complete all as specified and as directed. |
| 22 | Returning, Filling in including Spreading, Levelling, Watering, Well Ramming in Layers not exc. 25 Cm, Providing Heaps along the Route of the Water Mains, Cable Lines, etc. with Surplus Soil in Soft/Loose Soil, complete all as specified and as directed. |
| 23 | Removing Excavated Materials (Soils) not exc. 50.00 Metre and depositing where directed at a level not exc. 1.50 Metre above the Starting Point in Soil, complete all as specified and as directed. |
| 24 | M&L Cement Concrete 1:4:8 (40mm graded stone aggregate) in Foundation, Filling and Mass Concrete, etc. including Use and Waste of Formwork as required/ ordered, complete all as specified and as directed.NOTE : Cost of Formwork is deem to be include in the Quoted UNIT RATE. |
| 25 | M&L Cement Concrete 1:3:6 (40mm graded stone aggregate) in Foundation, Filling and Mass Concrete, etc. including Use and Waste of Formwork as required/ ordered, complete all as specified and as directed.NOTE : Cost of Formwork is deem to be include in the Quoted UNIT RATE. |
| 26 | M&L Cement Concrete 1:2:4 (20mm graded stone aggregate) in Copping of Electric Poles, etc., weathering slightly rounded or chamfered angle and throating, finishing all Exposed Faces of Concrete including necessary Formwork, complete all as specified and as directed.NOTE : Cost of Formwork is deem to be include in the Quoted UNIT RATE. |
| 27 | M&L Steel Tubular Swaged Pole Type 410 SP-31 (9.0 Metre long) complete with Mild Steel Base Plate, Finial Taper Plug, Bolts, Nuts & Screws, etc. as specified including One coat Aluminium Paint over One Coat of Red Oxide Zinc Chrome Primer, providing 3 No. Band/ Strap with Paint Black/ Yellow Colour 300mm apart from Plinth Block and numbering of Pole/ Painting embedded portion of Pole with One coat of Bituminous Paint, complete all as specified and as directed.NOTE : Necessary Earth Work & PCC will be Measured and Paid separately under relevent Items. |
| 28 | M&L Cross Arms, Bracings, Supports, Clamps and Back Plates, fabricated from Structural Steel Sections including Nuts, Bolts, Washers, etc., welding, bending cold or hot, drilling holes for Bolts, in any shape or size as indicated or directed and applying Two coats of Aluminium Paint over a coat of Red Oxide Zinc Chrome Primer after preparation of Surfaces, complete all as specified and as directed. |
| 29 | S&F Insulator Pin type, 100mm height, 65mm dia for 1100 Volt grade, Porcelain, Vitreous, white, brown or green including One Galvanised Mild Steel Spindle Two Galvanised Iron Washer and One Galvanised Iron Nut, complete all as specified and as directed. |
| 30 | S&F Insulator Shackle type, Porcelain, Vitreious (White, Brown or Green) of Size 75mm High & 90mm dia including Galvanised Mild Steel Straps of Section 31x3.0mm, 12mm dia Insulator Bolts, Nuts, Washer, etc. for Working Pressure 1100 Volt grade, complete all as specified and as directed. |
| 31 | M&L ACSR Conductor of any size for LT Over Head Line including Stringing Conductor fixed on Poles and binding with Aluminium Binding Wire, etc., complete all as specified and as directed.NOTE : Sizes of Conductor will be as per Site requirement/ as directed. |
| 32 | M&L Galvanised Iron Wire 4.0mm dia (8 SWG) as Continuous Earth Wire, Guards and Cradles (Hexagonal/ Rectangular), etc, binding with and including GI Binding Wire 1.6mm dia, complete all as specified and as directed. |
| 33 | S&F PVC Fibre Separator for LT Line 1100 Volt Over Head Conductor 3/4-Wire System for Horizontal Spacing of Conductor complete with Nut and Bolts minimum 2 No. to prevent the Lines Touching Each Other on Heavy Winds as a Preventive Arrangement to the Existing System, complete all as specified and as directed. |
| 34 | M&L Stay Assembly complete with all Accessories such as Mild Steel Galvanised Flat Iron Stay Clamp, Galvanised Stay Wire 7/3.15mm stranded, One Insulator Loop type Porcelain Vitreous (White, Brown or Green) Overall Dimensions 65x90mm and Clearance of Hole 16mm, Stay Grips, Mild Steel Galvanised Stay Bow, Thimbles of suitable, 16mm dia Mild Steel Galvanised Stay Rod 1900mm long and Mild Steel Galvanised Stay Plate of Size 300x300x6.0mm all as shown in Electrical Plate No. 1 of MES Schedule Part-I, complete all as specified and as directed.NOTE : Necessary Earth Work, Cement Concrete, etc. will be Measured and Paid separately under relevant Items. |
| 35 | M&L Street Light Fitting Bracket made out from GI Pipe 40mm Bore (dia), Light Grade, not exc. 1.20 Metre long, bend to required shape and fixing to Poles, etc. with and including Mild Steel Flat Iron Clamps 40x5mm of suitable Length, 2 No. Nuts, Bolts, Washers, etc. including Painting with One coat of Red Oxide Zinc Chrome Primer and Two coats of Aluminium Paint to all Mild Steel Works including Taking down Unserviceable Street Light Fitting Bracket of any description from any Height, complete all as specified and as directed. |
| 36 | S&F LED Street Light Fitting 30 Watt, New Generation, Energy Saving, Long Life, Environmental Friendly, made up of Pressure Die-cast Aluminium Housing with High Power LEDs as Lighting Source and Lens embeded PC Cover having Top Opening with separate Driver Compartment, IP-65 Protection, Impact Resistance of IK-07, providing Electric Connections including Taking down Unserviceable Street Light Fitting of any description and from any Height, complete all as specified and as directed.MAKE : HAVELLS, Cat No. ENDURAPEARLSL30WLED757SASYTOPCMP or equivalent Model in Make : BAJAJ/ CG/ C&S/ PHILIPS (as approved by GE) |
| 37 | S&F Shock Proof, Rust Proof, Fire Retradrant, Non-transparent Kiosks Pole Box of size 310x210x120mm made of Engineering Plastic on Piece moulding for Outdoor type, Heavy duty with 4 No. insulated Alunminium Bus-bar of 60 Amp capacity, mounted on Unbreakable Insulators MCB 10 Amp, SP, complete with Aluminium Lugs of suitable size upto 50 Sqmm including 2 No. Flat Iron 40x3mm Clamps with suitable size Mild Steel Bolts, Nuts & Washers, etc. and duly Painted on Both Sides with Two Coats of Synthetic Enemel Paint over a Coat of Red Oxide Zinc Chrome Primer including Taking down Unserviceable Pole Mounted Box of any description from any Height, complete all as specified and as directed.MAKE : HENSEL/ SCHNEIDER/ SINTEX (as approved by GE) |
| 38 | M&L PVC Insulated, Multi-stranded, FRLS Copper Conductor Cable of size 1.0 Sqmm 3 Core, fixing from Fitting to Junction Box including Taking down Unserviceable PVC Cable of any description from any Situation, complete all as specified and as directed. |
| 39 | M&L XLPE insulated, armouredheavy duty, Electric Cable with Aluminium Conductor, 1100 Volt grade, Cross-sectional Area 10 Sqmm, 2 Core, laid in Trenches/Ducts or Passing through Pipes or Fixing on Poles, etc., complete all as specified and as directed. NOTE : Necessary Earth Works, Sand Cushioning, Cable Protection Cover & GIPipe, etc. will be Measured and Paid separately under relevent Items. |
| 40 | M&L XLPE insulated, armouredheavy duty, Electric Cable with Aluminium Conductor, 1100 Volt grade, Cross-sectional Area 16 Sqmm, 4 Core, laid in Trenches/Ducts or Passing through Pipes or Fixing on Poles, etc., complete all as specified and as directed. NOTE : Necessary Earth Works, Sand Cushioning, Cable Protection Cover & GIPipe, etc. will be Measured and Paid separately under relevent Items. |
| 41 | M&L XLPE insulated, armouredheavy duty, Electric Cable with Aluminium Conductor, 1100 Volt grade, Cross-sectional Area 35 Sqmm, 4 Core, laid in Trenches/Ducts or Passing through Pipes or Fixing on Poles, etc., complete all as specified and as directed. NOTE : Necessary Earth Works, Sand Cushioning, Cable Protection Cover & GIPipe, etc. will be Measured and Paid separately under relevent Items. |
| 42 | M&L Sand Cushioning (Dry) in Trenches/Ducts for Protection of UG Cables (below, above and around the UG Cable laid) of 23 Cm Spread thickness (8 Cm in depth before laying the Cable and 15 Cm in depth after laying the Cable) and consolidated (punned) upto 180mm thickness, complete all as specified and as directed.NOTE : For the purpose of Payment, Punned thickness of Sand Cushioning only will be Measured. |
| 43 | Supply & Laying Unreinforced Pre-cast Concrete Cable Cover of size 250x150x40mm thick, Class LV, Type 1, Flat, Concrete grade M-20 minimum, complete all as specified and as directed. |
| 44 | M&L Galvanised Steel Tubing Pipe 40mm bore (dia), light grade with Bend, laid in Trenches or under Roads/ Flooring/ Culverts and/or fixing to Electric Poles with suitable size Mild Steel Flat Iron Clamps, Bolts, Nuts, Washers, etc., complete all as specified and as directed. |
| 45 | M&L Galvanised Steel Tubing Pipe 50mm bore (dia), light grade with Bend, laid in Trenches or under Roads/ Flooring/ Culverts and/or fixing to Electric Poles with suitable size Mild Steel Flat Iron Clamps, Bolts, Nuts, Washers, etc., complete all as specified and as directed. |
| 46 | S&F On Load Change Over Switch (Side Handle) in Sheet Metal Enclouser, 100 Amp rating, 4 Pole, 415 Volt, conforming to IS:13947 (Part-I & II) and connecting up including Taking down/out Unserviceable Change Over Switch of any description from any Situation, complete all as specified and as directedMAKE : HAVELLS/ L&T/ SEIMENS |
| 47 | M&L Factory Made LT Feedder Piller Box made out of 3.15mm thick CRCA Sheet with Mild Steel Angle Iron Frame 50x50x6.0mm, Outdoor type, Powder coated Weather Proof type, Totally Enclosed, having Front Opening Shutter with proper Locking Arrangements suitable for 415 Volt, 3 Phase, 4-Wire System, 50 Hz Supply having 4 No. Copper Bus-bars 250 Amp rated, Dust Proof and Vermin Proof (IP-54), Mild Steel Angle Iron Frame painted with Two Coats of Synethetic Enamel Paint over a Coat of Red Oxide Zinc Chrome Primer and fixing with and including Mild Steel Bolts, Nuts, Washers, etc. on Cement Concrete 1:2:4 (20mm graded Stone aggregate) Platform and grouting Mild Steel Angle Iron Legs in Floor, providing all Electric Connections and Testing, Comprising with and including following Accessories, complete all as specified and as directed:-INCOMING :-(a) Copper Bus-bar 250 Amp rating of 4 Strip 45 Cm long -01 Set(b) MCCB 160 Amp, 4 Pole, 25 kA, 415 Volts-01 No.(c) Digital type Voltmeter 0 to 500 Volts, Square Flush pattern -01 No.(d) Digital type Ampmeter 0 to 250 Amps, Square Flush pattern -01 No.(e) LED type Indicating Lamp in Incoming Phases-01 SetOUT-GOING :-(a) MCB 63 Amp, TPN, 10 kA, 230 Volts-03 No.(b)Automatic Star Delta Starter 10 HP, 7.5 KW, 415 Volt, 50 Hz, -02 No. Relay 15 Amp with Outgoing and Incoming Cable ConnectionNOTE : Cement Concrete Platform shall be minimum 450mm in Height from Natural Ground Level and 450mm Below Natural Ground Level leaving space minimum 100mm all around the Feedder Piller Box.Cost of Cement Concrete Platform will deem to be include in the Quoted UNIT RATE. |
| 48 | M&L Earthing with Galvanised Earth Plate Electrode 600x600x6.0mm thick, buried directly in Ground vertically to a depth not less than 2.25 Metre below Ground Level with Top Edge of Earth Plate at depth not less than 1.50 Metre below normal Ground Level, connectedto Galvanised Earth Lead Wire 4.0mm dia by means of Bolts, Nuts, Check, Nuts and Washers of Galvanised Iron or Steel and Earth Wire protected with and including GI Pipe 15mm bore (dia) Light grade, connected to Test Point upto 7.50 Metre away from Earth Electrode situated, Earth Plate surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt in alternate layers of not exc.150mm thick, PCC Pit in Cement Concrete 1:3:6 (20mm graded stone aggregate) and Pre-cast RCC Cover Slab of size 350x350x50mm in Cement Concrete 1:2:4 (20mm graded stone aggregate), Reinforced with 10mm dia TMT Bars @ 100mm Centre to Centre in both ways, GI Wire Mesh, PGI Funnel with GI Watering Pipe 20mm bore (dia) Medium grade including necessary Excavation in Soft/ Loose Soil, Returning, Filling in and Removal of surplus Spoil upto a distance of 50.00 Metre and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on Completion including Taking down/out Unserviceable Earthing of any description, complete all as specified and as directed. |
| 49 | M&L Galvanised Steel Water Tubing 80 mm bore (dia), ‘Medium grade’ with screwed Socket Joints, together with all Tube Fillings (such as Bends, Elbows, Tees, Short Pieces, Connectors, Backnuts, as required at Site, laid in Trenches or fixed on Walls, Ceiling or laid in Floors or any other Situation, complete as all specified and as directed. |
| 50 | M&L Cast Iron Butter-fly Valve 80mm bore (dia), Wafer type, Flanged and drilled both Ends, ISI marked, conforming to IS:13095 with all Jointing Materials such as suitable size Mild Steel Nuts, Bolts, GI Washers, Rubber Gasket, etc. and Testing against Leakage, complete all as specified and as directed. |
| 51 | Supply, Installation & Commissioning Horizontal Monoblock Pump 10 HP capacity, 2 Stage, Suction and Delivery Size 80mm x 65mm having Discharge 20 LITERS PER SECOND at 40.00 Metre Head suitable for Working Voltage 415 Volts, 3 Phase and Testing, complete all as specified and as directed.MAKE : KIRLOSKAR, Model No. KDS-1040 or equivalent in Make : CROMPTON GREAVES/ KSB/ SIEMENS (as approved by GE) |
| 52 | S&F PVC insulated, sheathed Stranded Copper Conductor Water Proof Cable, Flat, Cross-sectional Area 6.0 Sqmm, 3 Core, 1100 Volt grade, conforming to IS:694 for suitable for Monoblock Pump & Motor Assembly 10 HP capacity, complete all as specified and as directed. |