Repair / Maint / Servicing Of Modular Operation Theatre Including Dg Sets Of Various Capacity And Mech Laundry In The Area Of Age E / M ( Hosp ) Under Ge E / M Lucknow Repair / Maint / Servicing Of Modular Operation Theatre Including Dg Sets Of Various , Lucknow-Uttar Pradesh

Military Engineer Services-MES has published Repair / Maint / Servicing Of Modular Operation Theatre Including Dg Sets Of Various Capacity And Mech Laundry In The Area Of Age E / M ( Hosp ) Under Ge E / M Lucknow Repair / Maint / Servicing Of Modular Operation Theatre Including Dg Sets Of Various . Submission Date for this Tender is 28-10-2021. Diesel Generators Tenders in Lucknow Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

29417806
Corrigendum : Repair / Maint / Servicing Of Modular Operation Theatre Including Dg Sets Of Various Capacity And Mech Laundry In The Area Of Age E / M ( Hosp ) Under Ge E / M Lucknow Repair / Maint / Servicing Of Modular Operation Theatre Including Dg Sets Of Various
Open Tender
Indian
Uttar Pradesh
Lucknow
28-10-2021

Tender Details

Repair / Maint / Servicing Of Modular Operation Theatre Including Dg Sets Of Various Capacity And Mech Laundry In The Area Of Age E / M ( Hosp ) Under Ge E / M Lucknow Repair / Maint / Servicing Of Modular Operation Theatre Including Dg Sets Of Various Capacity And Mech Laundry In The Area Of Age E / M ( Hosp ) Under Ge E / M Lucknow

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 21-Oct-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 28-10-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 70000.0 /-
Tender Value
INR 35 Lakhs /-

BOQ Items

Name of Work : REPAIR/MAINT/SERVICING OF MODULAR OPERATION THEATRE INCLUDING DG SETS OF VARIOUS CAPACITY AND MECH LAUNDRY IN THE AREA OF AGE E/M (HOSP) UNDER GE E/M LUCKNOW.
Sl. No. Item Description
1Servicing of DG sets including replacement of fuel filters,oil filters,air filter element,changing oil,cleaning fuel lines,checking leakage and repairing it,replacement of exhaust main fold gasket etc all as per manufacturer/authorised service centre for the 15 KVA capicity of DG sets complete all as specified and directed by Engineer-in- Charge. Note.(i) Rate quoted shall be included attending any fault ( Start /Stop) or other defects on emergency basis by technecian for the entire period of contract .No extra cost will be paid to the contractor for the same.
2All as per item No 1 above but 30KVA
3All as per item No 1 above but55 KVA
4All as per item No 1 above but75 KVA
5All as per item No 1 above but100 KVA
6All as per item No 1 above but125 KVA
7All as per item No 1 above but 160 KVA
8All as per item No 1 above but 200 kVA
9All as per item No 1 above but400kVA
10All as per item No 1 above but625 KVA
11Servicing ofAMF panel with neecessary testing including replacement ofunserviceable partsall as specified and directed by engineer in charge all as per manufacturer/authorised service centre :- Note.(i) Rate quoted shall be included attending any fault ( Start /Stop) or other defects on emergency basis of technecian for the entire period of contract .No extra cost will be paid to the contractor for the same.
12Supply only failure timer as per existing make, complete all as specified and directed by Engineer-in- Charge.
13Supply only auxillary contactor 3 phases suitable for AMF panel as per existing make, complete all as specified and directed by Engineer-in- Charge.
14Supply only NC/NO relay complete as per existing make, complete all as specified and directed by Engineer-in- Charge.
15Supply only Under Voltage Relay as per existing make, complete all as specified and directed by Engineer-in- Charge.
16Supply only time delay Relay as per existing make, complete all as specified and directed by Engineer-in- Charge.
17Supply only C T Coil of 5/150 for 125 Kva DG set as per existing make, complete all as specified and directed by Engineer-in- Charge.
18Supply only C T Coil of 5/50 for 82.5 Kva DG set as per existing make, complete all as specified and directed by Engineer-in- Charge.
19Supply only battary Charger in AMF Panel complete all as specified and directed by Engineer-in- Charge.
20Supply only controller for200 Kva as per existing make, complete all as specified and directed by Engineer-in- Charge.
21Supply only VMR 3 phases for125 Kva as per existing make, complete all as specified and directed by Engineer-in- Charge.
22Supply only contractor Relay for200 KVA complete all as specified and directed by Engineer-in- Charge.
23Supply only HRC fuse complete all as specified and directed by Engineer-in- Charge.
24Supply only Fuse base for DIN type fuse links for200 amps, complete all as specified and directed by Engineer-in- Charge.
25Supply only HRC fuse links 200 Amp, complete all as specified and directed by Engineer-in- Charge.
26M & L for up to 125 KVA DG set, Rewinding of main armature, main field, exiter armature and exiter field with super enamelled copper winding wire of existing size and gauge and adequate number of turns including varnishing including taking down unservicable rewinding material complete all as specified and directed by Engineer-in- Charge.
27M & L for up to 160 KVA to 200 KVA DG set, Rewinding of main armature, main field, exiter armature and exiter field with super enamelled copper winding wire of existing size and gauge and adequate number of turns including varnishing including taking down unservicable rewinding material complete all as specified and directed by Engineer-in- Charge.
28M & L for 320 DG set, Rewinding of main armature, main field, exiter armature and exiter field with super enamelled copper winding wire of existing size and gauge and adequate number of turns including varnishing including taking down unservicable rewinding material complete all as specified and directed by Engineer-in- Charge.
29Supply and fix in repairs Contactor4 pole mcx 43 , 415 volts, complete all as specified and directed by Engineer-in- Charge. Make - L& T or eqvlnt
30Supply and fix in repairs Contactor4 pole MCX41 , 415 volts, complete all as specified and directed by Engineer-in- Charge. Make - L& T or eqvlnt
31Supply and fix in repairs Contactor4 pole MCX34 , 415 volts, complete all as specified and directed by Engineer-in- Charge. Make - L& T or eqvlnt
32Supply and fix in repairs Contactor4 pole MCX23 , 415 volts, complete all as specified and directed by Engineer-in- Charge. Make - L& T or eqvlnt
33Supply and fix in repairs Contactor4 pole MCX13 , 415 volts, complete all as specified and directed by Engineer-in- Charge. Make - L& T or eqvlnt
34Supply and fix in repairs Contactor4 pole MCX04415 volts, complete all as specified and directed by Engineer-in- Charge. Make - L& T or eqvlnt
35S & F Offload change over switch, 200 Amps, 415 volts, 4 pole in sheet metal enclosure conforming to IS:13947 (Part-3); IEC:60947-3 with locking facility including all connecting/ jointing materials and dismantling of existing change over switch, complete all as specified and directed by Engineer-in- Charge. Make havells cat part no . IHBFFE0200 or eqvlnt make as per PS
36S & F On load change over switch, 63 Amps, 415 volts, 4 pole side handle typein sheet metal enclosure conforming to IS:13947 (Part-3); IEC:60947-3 with locking facility including all connecting/ jointing materials and dismantling of existing change over switch, complete all as specified and directed by Engineer-in- Charge. Make havells cat part no. IHBFFE0063
37S & FOff load change over switch (side operated handle) 400 Amps, 415 volts 4 pole in sheet metal enclosure with interlock door and pad lock facility including dismantling of existing change over switch, complete all as specified and directed by Engineer-in- Charge. Make havells cat part no IHBFFE0400.
38MCCBs four pole 16 KA, fixed typeincl taking out unserviceable MCCB"s and connecting,of capacity125 AMPS complete all as specified and directed by Engineer-in- Charge. Legrandscat part no. 4200 56 or eqvlnt as per PS
39MCCBs four pole 16 KA, fixed typeincl taking out unserviceable MCCB"s and connecting,of capacity160AMPS complete all as specified and directed by Engineer-in- Charge. Legrandscat part no. 4200 57 or eqvlnt as per PS
40MCCBs four pole 25KA, fixed typeincl taking out unserviceable MCCB"s and connecting,of capacity200AMPS complete all as specified and directed by Engineer-in- Charge. Legrandscat part no. 4202 48 or eqvlnt as per PS
41MCCBs four pole 25KA, fixed typeincl taking out unserviceable MCCB"s and connecting,of capacity250AMPS complete all as specified and directed by Engineer-in- Charge. Legrandscat part no. 4202 49 or eqvlnt as per PS
42MCCBs four pole 36 KA, fixed typeincl taking out unserviceable MCCB"s and connecting,of capacity400AMPS complete all as specified and directed by Engineer-in- Charge. Legrandscat part no. 4202 49 or eqvlnt as per PS
43M&L Earthing complete with galvanised mild steel earth plate electrode 600x600x6.0mm thick, burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32 x 6 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipments at another end, GI earth strip encased inand including 40 mm dia GI "lightgrade" pipe from upper end of earth plate upto equipments,20 dia bore GI pipe "light grade" as water pipe from earth chamber to upper edge of earth plate, Test point , GI funnel with wire mesh fixed on water pipe andPCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1, duly reinforced with MS TMT bars 8mm dia @ 100 c/c both ways with 10mm dia MS round bar as in lifting handles, excavation, earth work including laying the GI pipe concealed in floor/wall all as describedin electric plate of SSR Part I complete all as specified and directed by Engineer-in- Charge and testing on completion. Note :- Ifthe desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department.
44Removing of lubricating oil from chamber and oil filter chamber of the DG set and cleaning of oil chamber & filter chamber thoroughly to remove all types of deposites and supply & filling of new lubricant oil SAE 20 W/40 W at required level all as directed.Make:Indian oil /BPL).
45Draining out old used water with coolent from the radiator ofGen Set (Kirloskar, Cummins) after disconnection the water connecting pipe, descaling, cleaning properly with high pressure wash to remove greasy substances from water tubes, tank and outer fins remove greasy substances from water tubes, tank and outer fins and refixing the same after servicing complete and renewal of coolant solution complete all as specified and directed by Engineer-in- Charge. (Note :- Water coolant of approved make shall be measured and paid separately under respectative items.)
46Supply and filling coolant for DG set as per DG set manufacturer"s recommendation complete all as specified and directed by Engineer-in- Charge.
47Supply, fixing, connecting, testing battery, 12 volts, 150 AH with lead acid terminals, indication of charging position and terminals for connection etc including initial charging of Battery complete all as specified and directed by Engineer-in- Charge. (Make EXIDE / AMRON) including disconnection ofexiting unserviceable battery and removal to store of AGE (Hosp).
48Supply, fixing, connecting, testing battery, 12 volts, 180 AH with lead acid terminals, indication of charging position and terminals for connection etc including initial charging of Battery complete all as specified and directed by Engineer-in- Charge. (Make EXIDE / AMRON) including disconnection exiting unserviceable battery and removal to store of AGE (Hosp).
49M&L for renewal of battery terminal heavy duty made out of brass suitable for 12 V lead acid battery complete all as specified and directed by Engineer-in- Charge.
50Supply & filling distilled water in batteries as required at various DG Set installations complete all as specified and directed by Engineer-in- Charge.
51Replacement of burnt battery lead heavy duty with & including 2.0 metre long PVC insulated multistranded copper conductor wire , consisiting with suitable size of lugs and heavy duty terminal complete all as specified and directed by Engineer-in- Charge.
52Supply and fixing crocodile clip for battery chargers of required size complete all as specified and directed by Engineer-in- Charge.
53Replacement of RPM/Hour meter on DG set instruement panel including RPM wire / cable and other accessories as required complete all as specified and directed by Engineer-in- Charge.
54Replacement of oil pressure gauge including pressure gauge sensor complete all as specified and directed by Engineer-in- Charge. (Make:- Siemens / Yankay/ Pricol)
55Dismantling the alternator of 160 KVA DG sets from coupling and opening the stator & rotor including cleaning of dust from windings for proper ventilation, renewal of carbon brushes with brush holder and assembling the rotor & stator complete including applying suitable greasing & oil off bearing & moving parts complete all as specified and directed by Engineer-in- Charge.
56Supply of cotton waste for cleaning of DG set and installation complete all as specified and directed by Engineer-in- Charge.
57Dismantling / taking down the governor andinjector assembly including all connected parts from DG set 160 KVAand over hauling calibration of injector assembly,fuel supply system,electronic governor etc(through authorised dealer of O.E.M) complete including renewal of wornout parts such as copper gasket, injector nozzle to maintain the desired fuel supply and provide fluctuation free output complete all as specified and directed by Engineer-in- Charge.
58Replacement of starting switch / ignition switch / push button of any type with key guard necessary wiring complete all as specified and directed by Engineer-in- Charge.
59Taking down and Servicing and overhauling of self starter 24 Volts by replacement of carbon bushes, holder assembly, varnishing in field coil as required and refixing in position and testing complete all as specified and directed by Engineer-in- Charge.
60Disconnecting of unsv/burnt self starterand supply and installation of self starter 24 Volts suitable for DG sets of capacity320 KVAcomplete all as specified and directed by Engineer-in- Charge. Make - LUCAL/Autolex .
61M & L for servicing of incinarator installed at command hospitalincluding Nozzle, spark plug cleaning of chamber,burner, hose pipe etc complete all as specified and directed by Engineer in Charge .
62M & L for Spray Painting of DG Set outerbodywith acreylic paint same coloureas per existingcomplete all as specified and directed by Engineer in Charge .
63Disconnecting all water and electrical connection of the water softener plant by removing all Nuts and bolts and reassemble the same after Changing the resin of the cylinder of softener And cleaning of the pipe line connected to boiler With softener for the smooth functioning complete all as specified and directed by Engineer-in- Charge.
64Taking down the economizer and S&F in replacemnet of economizer on the existing position complete all as specified and directed by Engineer-in- Charge.
65Supply and fixing in replacement of water pump - Triplex type of boiler on the existing position complete all as specified and directed by Engineer-in- Charge. Cat Pt No PGRX60010 Make- Thermax/ Thermo Care/ Sentec
66Supply & Fixingcrystal salt suitable for water Softening plant complete all as specified and directed by Engineer-in- Charge.
67Supply and fixing in replacement of metallic Hose pipe of size 1” of 30” long complete all as specified and directed by Engineer-in- Charge.
68Supply in replacement of V-belt size A-56 complete all as specified and directed by Engineer-in- Charge. Make : Fenner/Navyug/Dunlop
69Supply in replacement of pump seal for boilers size 50 mm Bore complete all as specified and directed by Engineer-in- Charge.
70Supply & Fixing Softeningcompound (Chemical Resin T-40 NA) for removal Of iron, calcium and magnesium from water to avoid scaling inside hot water pipe line complete all as specified and directed by Engineer-in- Charge.
71Supply in replacement of burner nozzle 6.0GPH complete all as specified and directed by Engineer-in- Charge. Make : Danfoss.
72S&F in replacement of Rope non-Asbestos complete all as specified and directed by Engineer-in- Charge.
73Supply in replacement of piston(HTN-1) complete all as specified and directed by Engineer-in- Charge.
74Supply in replacement of photocell 8203 complete all as specified and directed by Engineer-in- Charge.
75Supply in replacement of pressureswitch PM1 complete all as specified and directed by Engineer-in- Charge.
76Supply in replacement of flame coke complete all as specified and directed by Engineer-in- Charge.
77Supply in replacement of digital temperature ammeterRange 0ºC to 250ºC complete all as specified and directed by Engineer-in- Charge.
78Opening dismantling and disconnecting all water Connection and electrical connection of Washer Extractor capacity 60Kg make FABCARE and Reassemble the same for repair after removing nuts and bolts including oiling, greasing and alignment of inner basket, alignment of shaft, pulley alignment, contract set of contractor cleaning, servicing and cleaningm of pneumatic kits, air filter cleaning, cleaning the drain system and turning work and reassemble the same for the smooth functioning of the machine, complete all as specified and directed by Engineer-in- Charge.
79All as per item No 78 above but 1Nos Machine 30kgs capacity.
80Opening dismantling and disconnecting all water connection and electrical connection of Dryingtumbler capacity of 60Kg make FABCARE and reassemble the same for repair after removing nuts and bolts including Oiling, cleaning, servicing and greasing, balancing and alignment of cylindrical basket, balancing of blower, shaft turning, cleaning and servicing of steam radiator for the smooth functioning of the machine, complete all as specified and directed by Engineer-in- Charge.
81Opening dismantling and disconnecting all water Connection and electrical connection of flat work Ironer with double roll make FABCARE and Reassemble the same for repair after removing nuts and bolts including Oiling, cleaning, servicing and greasing, balancing and alignment improvement of chest and rollers, servicing and cleaning of Pneumatic kits, servicing of electrical panel and variable frequency drive for the varying of speed of motor, complete all as specified and directed by Engineer-in- Charge.
82Disconnecting all electrical connection of the air compressor and taking out cylinder from the compressor and repair the same with replacement of Engine oil, key of shaft and re-fixing the same Including testing complete all as specified and directed by Engineer-in- Charge.
83M&L in replacement ofWater solenoid motorized Pneumatic valve 4” of outlet complete all as specified and directed by Engineer-in- Charge. Make: Sant/Kartar/SK
84M&l in replacement ofwater solenoid motorized pneumatic valve 2” of inlet complete all as specified and directed by Engineer-in- Charge. Make: Sant/kartar/SK
85M&L in replacement of angle valve pneumatic 1” complete all as specified and directed by Engineer-in- Charge. Make: Jelpec/Janatics/Akari
86M&L in replacement of angle valve pneumatic¾” complete all as specified and directed by Engineer-in- Charge. Make: Jelpec/Janatics/Akari.
87M &L in replacement of touch screen of panelof washer extractor machine complete all as specified and directed by Engineer-in- Charge. Make : Kinco/Fabtech/Fabcare
88Disconnecting the electric induction motor of from the existing machine of any size and taking out the unserviceable winding wire complete and Cleaning the slots, rewinding the motor with Super enameled copper windings wire of existing Gauge including all other insulating material of capaicty02 HP of any make andre-fixing the same after repair of existing machine Including testing complete all as specified and directed by Engineer-in- Charge
89All as per item No 88 above but of capacity Induction motor 5 HP capacity
90All as per item No 88 above but of capacity Induction motor 10 HP
91All as per item No 88 above but of capacity Induction motor 15 HP
92M&L in replacement of iron steam resting pad of capaicty02 HP complete all as specified and directed by Engineer-in- Charge. Make : Fabcare/Fabtech
93M&L in replacement of MPD for Drying tumbler complete all as specified and directed by Engineer-in- Charge.
94M&L in replacement of branded bearing 6316 (2RS) for AWX 60Kg complete all as specified and directed by Engineer-in- Charge. Make:SKF/NTN
95M&L in replacement of branded bearing6317(2RS) for AWX 60Kg complete all as specified and directed by Engineer-in- Charge. Make SKF/NTN
96M&L in replacement of bearing 6313 (2RS) for AWX-30Kg complete all as specified and directed by Engineer-in- Charge.
97M&L in replacement of bearing 6314 (2RS) complete all as specified and directed by Engineer-in- Charge. Make : SKF/NTN/NBC
98M&L in replacement of bearing 6314 (2RS) complete all as specified and directed by Engineer-in- Charge. Make : SKF/NTN/NBC
99Attendingcomplaints on priroty basis formaintenance of 04 Nos modular and 05 Nos of conventional operation theatre at Command hospital & Base Hospital Lucknowcomprising of anesthesia pendent fixed type-02 Nos and sweivel type-02 (Make: MDD),shadowless light fittings ) having major and satelite dooms of technical specification mentioned hereinafter,shadowless lights for non-conventional OTs-05 Nos(Make:Philips) speripheral lights 2x55 watts (Make:Philips) ,scrub sink-04 Nos (Make:MDD),hermatically sealed sliding doors-04 Nos (Make:Metaflux), all as directed at site by Engr in charge. ( a ) Contractor shall bound to attend the complaint with in one hour after receiving it fromJE and AGE . ( b ) Jointlyvisit shall be arranged by the contractorduring changing any spare parts and allthe OT lights shall be made functional in all respect and necessary report duly signed by the OT incharge of CH(CC) and Base Hospital and JE Concern shall be submitted to AGE Hosp on Same Day . Inspection note shall be endorsed by technician related of repair works to be carriedout. ( c ) Urgent spares partsshall be readly made available at site during all days by the contractor. (d)Whenever Coplaint attend by technitian also included servicingof same items.
100S&F Halogen bulbs , 12 volts50 watts having input voltage 230±230 Votls and out put voltage 10.5 to 12.5 volts on load in 4 steps of 50 Hz, supply suitable for Trilux OT lights haivng light out put of 120000 Lux for major and 70000 Lux for satellite doom complete all as specified and directed by Engineer-in- Charge.
101S&F Halogen medical reflector 24V 150 watts suitable for shadoless light fitting of make Philips having major and standard doom all as required at site, complete all as specified and directed by Engineer-in- Charge.
102S&F in repair thermostatic mixing valve provided for constant water termpreature withdefined setting of adjustable timing of 1, 3, 5, 10 minute complete all as specified and directed by Engineer-in- Charge.
103S&F in repair electrc photo sensor suitable for two bay surgical surb sink for hads free operation with built in range of adjustment complete all as specified and directed by Engineer-in- Charge.
104S&F in repair solenoid valve 24 volt suitable for two bay surgical scurb sink for hands free operation with built in range of adjustment complete all as specified and directed by Engineer-in- Charge.
105Supplying and fixing espagnolet electromagnetic lock mounted on track and on both side key switch suitable for hermatically sealed door having width 3500 mm complete all as specified and directed by Engineer-in- Charge.
106Supplying and fixing microprocessor controlled sensor suitable for electromechanical sliding door having width 3500 mm and total weight 250 Kgs and slow speed 20-120 mm/sec,starting speed 20-220 mm/sec,opening speed 800mm/sec and closing speed 500 mm/sec operated on 3 phase 415 volts 50 Hz AC supply, complete all as specified and directed by Engineer-in- Charge.
107S&F in repair foot switch suitable for hermatically sealed door of modular OT of make Metafluxcomplete all as specified and directed by Engineer-in- Charge.
108S&F in repair runner wheel MF5 suitable for hermatically sealed door of modular OT of make Metafluxcomplete all as specified and directed by Engineer-in- Charge.
109S&F in repair guide roller set MF5 suitable for hermatically sealed door of modular OT of make Metafluxcomplete all as specified and directed by Engineer-in- Charge.
110S&F in repair side sealing gasket suitable for hermatically sealed door of modular OT of make Metafluxcomplete all as specified and directed by Engineer-in- Charge.
111S&F in repair teath beltsuitable for hermatically sealed door of modular OT of make Metafluxcomplete all as specified and directed by Engineer-in- Charge.
112S&F in repair photo cell suitable for hermatically sealed door of modular OT of make Metafluxcomplete all as specified and directed by Engineer-in- Charge.
113S&F in repair motor 370 watts suitable for hermatically sealed door of modular OT of make Metafluxcomplete all as specified and directed by Engineer-in- Charge.
114S&F in repair SDA 04 controller suitable for hermatically sealed door of modular OT of make Metafluxcomplete all as specified and directed by Engineer-in- Charge.
115Supply and fix in repair1.5 sqmm single core, copperwire, multistranded, PVC insulated, unsheathed, 1100 volts grade complete all as specified and directed by Engineer-in- Charge.Make : Havells / Finolex / Seiko .
116Supply and fix in repair 2.5 sqmm single core, copper wire, multistranded, PVC insulated, unsheathed, 1100 volts grade complete all as specified and directed by Engineer-in- Charge. Make : Havells / Finolex / Seiko ..
117Supply and fix in repair 4.0 sqmm single core, copperwire, multistranded, PVC insulated, unsheathed, 1100 volts grade complete all as specified and directed by Engineer-in- Charge. Make : Havells / Finolex / Seiko .
118Supply and fix in repair 6.0 sqmm single core, copperwire , multistranded, PVC insulated, unsheathed, 1100 volts grade complete all as specified and directed by Engineer-in- Charge. Make : Havells / Finolex / Seiko .
119Supply and fix in repair 10.0 sqmm single core, copperwire, multistranded, PVC insulated, unsheathed, 1100 volts grade complete all as specified and directed by Engineer-in- Charge. Make : Havells / Finolex / Seiko .
120Supply and fixing in replacement power contactor MNX 18, 3 phase in existing LT panel complete all as specified and directed by Engineer-in- Charge. (Make :- Siemens or equivalent as approved by GE).
121Taking out carefully defective / burnt power contactor type ML-1.5from the LT panel board and supply & fixing new in position in replacement power contractor ML-1.5 complete all as specified and directed by Engineer-in- Charge. (Make ;- L&T / Siemens).
122S & F of air purfierof capicity85 W Air Purifier with RemoteCoverage Area58 m² (958 square feet) ( especially suitable for Clean Air Delivery Rate (CADR) 500 m³/h (958 square feet) CADR indicates the volume of purified air (in cubic metre) emoves 99.18% allergens & Filtration upto 0.3 microns, 80 times smaller than PM 2.5which an air purifier produces every hourwith9 Stages of Filtration: Pre-Filter, Cold-Catalyst, Activated Carbon, Antibacterial, HEPA, UV and Anion + Humidifier, Anti Bacterial Balls & 4-Color indications for PPM level at which light changes from 1-50 Green, 51-100 Blue, 101-200 Yellow, 201-500 & above Red,Maximum PM count500 , with02 yearswarranty complete all as specified and directed by Engineer-in- Charge.
123S & F Air purifier of40 W Air Purifier with Remote Air Purifier TypeRoomCoverage Area 20 m² (485 square feet) ( especially suitable for bedrooms ) Clean Air Delivery Rate (CADR)180 m³/h (485 square feet) CADR indicates the volume of purified air (in cubic metre) which an air purifier produces every hourremoves 99.18% allergens & Filtration upto 0.3 microns, 80 times smaller than PM 2.5which an air purifier produces every hourwith9 Stages of Filtration: Pre-Filter, Cold-Catalyst, Activated Carbon, Antibacterial, HEPA, UV and Anion + Humidifier, Anti Bacterial Balls & 4-Color indications for PPM level at which light changes from 1-50 Green, 51-100 Blue, 101-200 Yellow, 201-500 & above Red,Maximum PM count500 , with02 yearswarrantycomplete all as specified and directed by Engineer-in- Charge.