| 1 | Electrical Materials : |
| 2 | Erection of steel tubular or rail pole strut in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling and secured with holding clamps, bolts, nuts, etc. as required. |
| 3 | Supplying and erection of stay set complete (galvanised) with 19/ 20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm, thimble, stay clamps, turn buckle ( 20 mm X 60 cm ), 7/ 4.00 mm dia G.I. stay wire and strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavationas and refilling etc. as required. |
| 4 | Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) pole top bracket/ cross arm for single 11 KV over head line conductor complete with 50 mm X 6mm flat iron clamp, bolts, nuts and washers including drilling holes for insulator pins, bolts and nuts etc and painting with primer and finish paint as required. |
| 5 | Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) cross arm for two 11 KV over head line conductors complete with 50 mm X 50 mm X 6 mm (angle iron bracket welded to the channel iron and complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required . |
| 6 | Erection of pole top/ straight two wire/ V shape two wire, angle iron/ channel iron, cross arm on steel tubular/ rail/ PCC pole for 11/22/33 KV as required. |
| 7 | Supplying and erection of 11 KV disc insulator for 11 KV over head lines with galvanised insulator fittings, ball and socket type and complete with galvanised strain clamps, bolts, nuts, washers etc. as required. |
| 8 | Supplying and erection of 11 KV pin insulator complete with largesteel head G.I. pin, nuts, washers etc. as required. |
| 9 | Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) cross arm for 2 wire over head line complete with clamps, bolts, nuts and washer etc including drilling of holes for insulator pins etc (as per drawing) and painting with primer and finished paint as required. |
| 10 | Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) cross arm for 4 wire over head line complete with clamps, bolts, nuts and washer etc including drilling of holes for insulator pins etc (as per drawing) and painting with primer and finished paint as required. |
| 11 | Erection of angle iron/ channel iron cross arm on wood/ RCC/ PCC/ steel tubular/ rail pole etc. as required. |
| 12 | Supplying and erection of 75 mm X 90 mm shackle insulator with G. I. Bolt, nuts and straps etc. as required. |
| 13 | Supply of ACSR (Rabbit) 6/1/3.35 mm conductor. |
| 14 | Erection of ACSR conductor of 7/3.35 mm to 7/4.00 diameter and above including binding etc. as required. |
| 15 | Supply & erection of 2.8 metre long 100mmX50mmX50mmX6mm MS Channel complete with 50mmX6mm M.S flat iron clamps, bolts & nuts including fabrication/drilling holes etc. and painting with approved quality of aluminium paint as required. |
| 16 | Supply & erection of 0.8 metre long 100mmX50mmX50mmX6mm MS Channel complete with 50mmX6mm M.S flat iron clamps, bolts & nuts including fabrication/drilling holes etc. and painting with approved quality of aluminium paint as required. |
| 17 | Supply & erection of 2.8 metre long 75mmX40mmX40mmX6mm MS Channel complete with 50mmX6mm M.S flat iron clamps, bolts & nuts including fabrication/drilling holes etc. and painting with approved quality of aluminium paint as required. |
| 18 | Supply & erection of 11 KV G.O. Switch with handle set complete, 3 Phase including necessary connections etc. as required. |
| 19 | Supply & erction of 11 KV D.O. Fuse Unit, 3 Phaseincluding necessary connections etc. as required. |
| 20 | Supplying and erection of three piece nonlinear resistor type lightning arrestor suitable for 3 wire, 11 KV overhead lines with rated voltage 9 KV (rms) with a nominal discharge current rating of 5 KA and complete with galvanised clamping arrangement, G.I. bolts, nuts, washers etc. as required. |
| 21 | Supply & erection of 3 nos. 200 Amps Cutout and wooden base including necessary connections etc. as required. |
| 22 | Supply of following sizes of 1.1 KV grade single core/multi-core aluminium conductor XLPE insulated and PVC sheathed armored cable conforming to IS 7098 (Part-I) 1988.3.5/4 Core, 70 sq.mm. XLPE Aluminium Cable, |
| 23 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 35 sq. mm and upto 95 sq. mm |
| 24 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25X3 mm MS flat clamp) |
| 25 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3½ X 70 sq. mm (38mm) |
| 26 | Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. (4 nos in each set).3½ X 70 sq. mm |
| 27 | Dismantling, testing, carrying, shifting & commissioning of 100 KVA, 11/0.4 KV Transformer including necessary connection etc. as required. |
| 28 | Supply, installation, testing and commissioning of 160A, Triple Pole & Neutral, 415V AC, 50 HzSwitch Disconnector Fuse Unit (Panel Mounted Cubical Type) in sheet steel enclosure with three Fuses with necessary connection etc. as required. |
| 29 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 30 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 31 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required. |
| 32 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 33 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |