| 1 | Dismantling of Earth wire and copper conductors and removing old material fromsite for taking credit. |
| 2 | Dismantling of ACSR or AAC conductors and removing old material from site for taking credit. |
| 3 | Dismantlingconcrete poles/struts of any size and removing old material fromsite for taking credit and making good the disturbed surfaces all as specified/directed by Engr-in-Charge |
| 4 | Dismantling insulators any type, any size and revoming old material from site for taking credit |
| 5 | Dismantling cross arms of MS channel or angle sections etc complete and removing old material from site for taking credit |
| 6 | Dismantling stay assembly complete(demolition of concrete etc and removing old material from site for taking credit. |
| 7 | Demolition of cement concrete unreinforced of any description and in any position not otherwise specially provided for all as directed by Engr-in-Charge |
| 8 | M&L cement concrete in foundation, filling and mass concrete type D2 (1:4:8) 40mm graded aggregate all as directed by Engr-in-Charge |
| 9 | M & L for PCC 1:3:6 type C2 using 20 mm graded stone aggregate for coping of poles/plinth blocks of LT poles etc incl fair finishing the exposed surfaces even and smooth without using extra cement includingnecessary form work complete all as specified & directed. |
| 10 | Excavation in trenches exceeding 1.5m wide andn exc. 3 m in depth for pole foundation/laying cables in Hard/dense soil all as directed. |
| 11 | Excavation in trenches n exc 1.5m wide and n exc 1.5m deepand making goodsurface for laying /removing of cable all as specified and directed by Engr in charge as in |
| 12 | Soft/loose soil |
| 13 | Hard/dense soil |
| 14 | Soft/disintegrated rock. |
| 15 | Returning filling in excavated soil in trenches, watering and well ramming in layers n. exc. 25 cm complete all as specified. |
| 16 | Removal of surplus excavated spoil to distance n exc 50metre all as specified and directed |
| 17 | M & L for bituminous road cutting to a width of 45 cm and depth 50 cm for laying ofpipe for laying of UG cables and making good with PCC (1:3:6) type CI (using 20mm grade stone aggregate) |
| 18 | Supplyingand layingGI tubing light grade of size 40mm dia bore for encasingcables for mechanical protection , laid under Plinth / Floors/ Paths Culverts or fixed on wall or concealed in wall/floor or alongpoles or as street light poles or as street light mounting bracketwith complete accessories such as bends/sockets/reducers/saddlesincl necessary threading/drilling worksall as specified and directed by Engr-in-charge. |
| 19 | Supplyingand layingGI tubing light grade of size 50mm dia bore for encasingcables for mechanical protection , laid under Plinth / Floors/ Paths Culverts or fixed on wall or concealed in wall/floor or alongpoles or as street light poles or as street light mounting bracketwith complete accessories such as bends/sockets/reducers/saddlesincl necessary threading/drilling worksall as specified and directed by Engr-in-charge. |
| 20 | Supply, install and erect in true vertical position (or to be fixed in an inclined position as strut pole) steel tubular swaged poles complete with MS base plate of 6 mm thick of size 300 mm x 300 mm, finial taper plug, pole cap, bolts, nuts and washers and screwed pole made out of FRW MS tubing conforming to IS-2713 (Part-II) 1980 type 410-SP-31 ( 9 meters long ) pole including drilling of holes of required size and Nos for fixing of cross arms, painting with one coat of red oxide primer and two coats of aluminium paint for exposed surfaces and two coats of black bituminous paint for portion embeded in concrete, etc complete all as specified and directed in and incl taking down carefully old deterioiated RCC/steelpole. |
| 21 | Supply , laying and testing cable XLPE insulated screened pvc bedded galvanised steel strip or wire armoured , electric power cables ( heavy duty) with stranded aluminium conductor 1100 volts grade in trenches/ passing through pipe/fixing on walls, floors etc incl connection with proper sizes lugs and gland, suitable clamp of cross sectional area6 core 2 Sqmmin and including taking out old one all as specified and directed. |
| 22 | All as per item No.18 above, but of the size 4 core 10 Sqmm |
| 23 | All as per item No.18 above, but of the size 4 core 16 Sqmm |
| 24 | All as per item No.18 above, but of the size 3.5 core 25 Sqmm |
| 25 | All as per item No.18 above, but of the size 3.5 core 35 Sqmm |
| 26 | All as per item No.18 above, but of the size 3.5 core 50 Sqmm |
| 27 | All as per item No.18 above, but of the size 3.5 core 70 Sqmm |
| 28 | All as per item No.18 above, but of the size 3.5 core 95 Sqmm |
| 29 | All as per item No.18 above, but of the size 3.5 core 150 Sqmm |
| 30 | All as per item No.18 above, but of the size 3.5 core 400 Sqmm |
| 31 | Supply & Laying of Telerex DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 50 mm and inner dia 38 mm polythylene with smooth internal and profiled external surface for non pressure under ground cableincl couplers & bends complete all as specified. Make : REX POLYEXTRUSION LTD or its equivalent as approved |
| 32 | Supply & Laying of Telerex DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 77 mm and inner dia 63 mm polythylene with smooth internal and profiled external surface for non pressure under ground cableincl couplers & bends complete all as specified. Make : REX POLYEXTRUSION LTD or its equivalent as approved |
| 33 | Supply & Laying of Telerex DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 90 mm and inner dia 76 mm polythylene with smooth internal and profiled external surface for non pressure under ground cableincl couplers & bends complete all as specified. Make : REX POLYEXTRUSION LTD or its equivalent as approved |
| 34 | Supply & Laying of Telerex DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 120 mm and inner dia 103 mm polythylene with smooth internal and profiled external surface for non pressure under ground cableincl couplers & bends complete all as specified. Make : REX POLYEXTRUSION LTD or its equivalent as approved |
| 35 | Supply & Laying of Telerex DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 200 mm and inner dia 174 mm polythylene with smooth internal and profiled external surface for non pressure under ground cableincl couplers & bends complete all as specified. Make : REX POLYEXTRUSION LTD or its equivalent as approved |
| 36 | Supply, install, connect, test and commissioning factory made, dust/vermin, weather proof self ventilated, cubical of size 1.5 x 0.50 x1.2 (aps) with frontmade of and rear opening, hinged door for front,and rear with MS angle iron frame 50 x 50 x 5mm for base support, 3.15 mm thick CRCA sheet, LT panel board, (LT KIOSK), CPRI approved out door, cubicle type, floor mounted, double door with neoprene gasket and locking arrangement with canopy including painting with powder coated on steel surfaces internally & externally and provision of two Nos earth terminals on both sides , cable glands and PCC foundation with PCC 1 : 2 : 4, type B1 , and 30 cm all around the outer dimension of panel including gap for insertion of cable having bottom of panel at height of 45 cms above the ground level with cable entry glands to accommodate and includingthe following accessories:- (Main Panel -1, Near Shed No-52) |
| 37 | Copperbus barrectangular 600 Amps full for phase and half for neutral and interconnection of MCCBs to Bus bar mounted on epoxy insulators with colour coding PVC sleeves.-01 job |
| 38 | MCCB 400 Amps, TPN, 415 Volts, 50 Hz ,50 KA- 01 No ( Incoming) |
| 39 | MCCB 315 Amps, TPN, 415 Volts, 50 Hz ,36KA - 01 No ( Outgoing) |
| 40 | MCCB 250 Amps, TPN, 415 Volts, 50 Hz ,36KA - 01 No ( Outgoing) |
| 41 | MCCB 200 Amps,TPN, 415 Volts, 50 Hz ,36KA - 01 No ( Outgoing) |
| 42 | MCCB 100 Amps,TPN, 415 Volts, 50 Hz ,36KA - 01 No ( Outgoing) |
| 43 | MCB SPN 32/40A -Each-01 |
| 44 | RYB LED Indicator Lamp- Set of Three-01 |
| 45 | Volt meter 0-500 Volt with selector switch |
| 46 | Amp meter 0-600 Amp with selector switch with CT-03 Nos |
| 47 | Provision of cubicle to accommodate the above mentioned accessories. |
| 48 | Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable. |
| 49 | Supply, install, connect, test and commissioning factory made, dust/vermin, weather proof self ventilated, cubical of size 1.5 x 0.50 x1.2 (aps) with frontmade of and rear opening, hinged door for front,and rear with MS angle iron frame 50 x 50 x 5mm for base support, 3.15 mm thick CRCA sheet, LT panel board, (LT KIOSK), CPRI approved out door, cubicle type, floor mounted, double door with neoprene gasket and locking arrangement with canopy including painting with powder coated on steel surfaces internally & externally and provision of two Nos earth terminals on both sides , cable glands and PCC foundation with PCC 1 : 2 : 4, type B1 , and 30 cm all around the outer dimension of panel including gap for insertion of cable having bottom of panel at height of 45 cms above the ground level with cable entry glands to accommodate and includingthe following accessories:- (Main Panel -2, Near Shed No-59) |
| 50 | Copperbus barrectangular 600 Amps full for phase and half for neutral and interconnection of MCCBs to Bus bar mounted on epoxy insulators with colour coding PVC sleeves.-01 job |
| 51 | MCCB 400 Amps, TPN, 415 Volts, 50 Hz ,50 KA- 01 No ( Incoming) |
| 52 | MCCB 160 Amps,TPN, 415 Volts, 50 Hz ,36KA - 01 No ( Outgoing) |
| 53 | MCCB 125 Amps,TPN, 415 Volts, 50 Hz ,36KA - 01 No ( Outgoing) |
| 54 | MCCB 63 Amps,TPN, 415 Volts, 50 Hz ,36KA - 03 No ( Outgoing) |
| 55 | MCCB 32 Amps,TPN, 415 Volts, 50 Hz ,36KA - 01 No ( Outgoing) |
| 56 | MCB SPN 32/40A -Each-01 |
| 57 | RYB LED Indicator Lamp- Set of Three-01 |
| 58 | Volt meter 0-500 Volt with selector switch |
| 59 | Amp meter 0-600 Amp with selector switch with CT-03 Nos |
| 60 | Provision of cubicle to accommodate the above mentioned accessories. |
| 61 | Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable. |
| 62 | Supply, install, connect, test and commissioning factory made, dust/vermin, weather proof self ventilated, cubical of size 1.5 x 0.50 x1.2 (aps) with frontmade of and rear opening, hinged door for front,and rear with MS angle iron frame 50 x 50 x 5mm for base support, 3.15 mm thick CRCA sheet, LT panel board, (LT KIOSK), CPRI approved out door, cubicle type, floor mounted, double door with neoprene gasket and locking arrangement with canopy including painting with powder coated on steel surfaces internally & externally and provision of two Nos earth terminals on both sides , cable glands and PCC foundation with PCC 1 : 2 : 4, type B1 , and 30 cm all around the outer dimension of panel including gap for insertion of cable having bottom of panel at height of 45 cms above the ground level with cable entry glands to accommodate and includingthe following accessories:- (Main Panel -3, Near Shed No-57) |
| 63 | Copperbus barrectangular 300 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job |
| 64 | On load change over 160 Amps (Incoming) |
| 65 | MCCB 100Amps, TPN, 415 Volts, 50 Hz ,36 KA- 02 No ( Outgoing) |
| 66 | MCCB 63 Amps,TPN, 415 Volts, 50 Hz ,36KA - 01 No ( Outgoing) |
| 67 | MCCB 32 Amps,TPN, 415 Volts, 50 Hz ,36KA - 02 No ( Outgoing) |
| 68 | RYB LED Indicator Lamp- Set of Three-01 |
| 69 | Volt meter 0-500 Volt with selector switch |
| 70 | Amp meter 0-600 Amp with selector switch with CT-03 Nos |
| 71 | Provision of cubicle to accommodate the above mentioned accessories. |
| 72 | Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable. |
| 73 | Supply, install, connect, test and commissioning factory made, dust/vermin, weather proof self ventilated, cubical of size 1.5 x 0.50 x1.2 (aps) with frontmade of and rear opening, hinged door for front,and rear with MS angle iron frame 50 x 50 x 5mm for base support, 3.15 mm thick CRCA sheet, LT panel board, (LT KIOSK), CPRI approved out door, cubicle type, floor mounted, double door with neoprene gasket and locking arrangement with canopy including painting with powder coated on steel surfaces internally & externally and provision of two Nos earth terminals on both sides , cable glands and PCC foundation with PCC 1 : 2 : 4, type B1 , and 30 cm all around the outer dimension of panel including gap for insertion of cable having bottom of panel at height of 45 cms above the ground level with cable entry glands to accommodate and includingthe following accessories:- (Panel -1 A, Near Shed No-48) |
| 74 | Copperbus barrectangular 300 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job |
| 75 | On load change over 250 Amp, 4 pole, 415 Volts, 50 Hz ,- 01 No ( Incoming) |
| 76 | MCCB 100Amps, TPN, 415 Volts, 50 Hz ,36 KA- 04 No ( Outgoing) |
| 77 | MCCB 63 Amps, TPN, 415 Volts, 50 Hz ,36 KA- 02 No ( Outgoing) |
| 78 | MCCB 32Amps, TPN, 415 Volts, 50 Hz ,36 KA- 02 No ( Outgoing) |
| 79 | Three pole Contactor 63 A Current Rating 70A General use 10A, 415V with coil Make L&T Model MNX 70 Three pole contactor complete. Make L&T cat part No CS97076/Legrand/schneider- 01 N0 |
| 80 | Digital timer switch with inbuilt backup current capacity 16 Amps operated on 415 volts AC 50Hz, Make: Indoasian cat part No TDA43111/ Legrand/Indoasian - 01 No |
| 81 | MCB SPN 32 Amps :- 01 |
| 82 | RYB LED Indicator Lamp- Set of Three-01 |
| 83 | Volt meter 0-500 Volt with selector switch |
| 84 | Amp meter 0-600 Amp with selector switch with CT-03 Nos |
| 85 | Provision of cubicle to accommodate the above mentioned accessories. |
| 86 | Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable. |
| 87 | Supply, install, connect, test and commissioning factory made, dust/vermin, weather proof self ventilated, cubical of size 1.5 x 0.50 x1.2 (aps) with frontmade of and rear opening, hinged door for front,and rear with MS angle iron frame 50 x 50 x 5mm for base support, 3.15 mm thick CRCA sheet, LT panel board, (LT KIOSK), CPRI approved out door, cubicle type, floor mounted, double door with neoprene gasket and locking arrangement with canopy including painting with powder coated on steel surfaces internally & externally and provision of two Nos earth terminals on both sides , cable glands and PCC foundation with PCC 1 : 2 : 4, type B1 , and 30 cm all around the outer dimension of panel including gap for insertion of cable having bottom of panel at height of 45 cms above the ground level with cable entry glands to accommodate and includingthe following accessories:-(Panel -1 B, Near Shed No-41) |
| 88 | Copperbus barrectangular 300 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job |
| 89 | MCCB 100 Amps, TPN, 415 Volts, 50 Hz ,36 KA- 01 No ( Incoming) |
| 90 | MCCB 63 Amps, TPN, 415 Volts, 50 Hz ,36 KA- 01 No ( Outgoing) |
| 91 | MCCB 32Amps, TPN, 415 Volts, 50 Hz ,36 KA- 03 No ( Outgoing) |
| 92 | Volt meter 0-500 Volt with selector switch |
| 93 | Amp meter 0-600 Amp with selector switch with CT-03 Nos |
| 94 | Provision of cubicle to accommodate the above mentioned accessories. |
| 95 | Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable. |
| 96 | Supply, install, connect, test and commissioning factory made, dust/vermin, weather proof self ventilated, cubical of size 1.5 x 0.50 x1.2 (aps) with frontmade of and rear opening, hinged door for front,and rear with MS angle iron frame 50 x 50 x 5mm for base support, 3.15 mm thick CRCA sheet, LT panel board, (LT KIOSK), CPRI approved out door, cubicle type, floor mounted, double door with neoprene gasket and locking arrangement with canopy including painting with powder coated on steel surfaces internally & externally and provision of two Nos earth terminals on both sides , cable glands and PCC foundation with PCC 1 : 2 : 4, type B1 , and 30 cm all around the outer dimension of panel including gap for insertion of cable having bottom of panel at height of 45 cms above the ground level with cable entry glands to accommodate and includingthe following accessories:- (Panel -1 C, Near Shed No-36) |
| 97 | Copperbus barrectangular 300 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job |
| 98 | MCCB 200Amps, TPN, 415 Volts, 50 Hz ,36 KA- 01 No ( Incoming) |
| 99 | MCCB 63Amps, TPN, 415 Volts, 50 Hz ,36 KA- 04 No ( Outgoing) |
| 100 | MCB SPN 32 Amps :- 01 |
| 101 | RYB LED Indicator Lamp- Set of Three-01 |
| 102 | Volt meter 0-500 Volt with selector switch |
| 103 | Amp meter 0-600 Amp with selector switch with CT-03 Nos |
| 104 | Provision of cubicle to accommodate the above mentioned accessories. |
| 105 | Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable. |
| 106 | Supply, install, connect, test and commissioning factory made, dust/vermin, weather proof self ventilated, cubical of size 1.5 x 0.50 x1.2 (aps) with frontmade of and rear opening, hinged door for front,and rear with MS angle iron frame 50 x 50 x 5mm for base support, 3.15 mm thick CRCA sheet, LT panel board, (LT KIOSK), CPRI approved out door, cubicle type, floor mounted, double door with neoprene gasket and locking arrangement with canopy including painting with powder coated on steel surfaces internally & externally and provision of two Nos earth terminals on both sides , cable glands and PCC foundation with PCC 1 : 2 : 4, type B1 , and 30 cm all around the outer dimension of panel including gap for insertion of cable having bottom of panel at height of 45 cms above the ground level with cable entry glands to accommodate and includingthe following accessories:-(Panel -1 D, Near Shed No-43) |
| 107 | Copperbus barrectangular 300 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-01 job |
| 108 | On load Changeover 160Amps,4 pole, 415 Volts, 50 Hz- 01 No ( Incoming) |
| 109 | MCCB 32 Amps, TPN, 415 Volts, 50 Hz ,36 KA- 05 No ( Outgoing) |
| 110 | MCB SPN 32 Amps :- 08 No ( Outgoing) |
| 111 | Three pole Contactor 63 A Current Rating 70A General use 10A, 415V with coil Make L&T Model MNX 70 Three pole contactor complete. Make L&T cat part No CS97076/Legrand/schneider- 01 N0 |
| 112 | Digital timer switch with inbuilt backup current capacity 16 Amps operated on 415 volts AC 50Hz, Make: Indoasian cat part No TDA43111/ Legrand/Indoasian - 01 No |
| 113 | MCB SPN 32 Amps :- 01 |
| 114 | RYB LED Indicator Lamp- Set of Three-01 |
| 115 | Volt meter 0-500 Volt with selector switch |
| 116 | Amp meter 0-600 Amp with selector switch with CT-03 Nos |
| 117 | Provision of cubicle to accommodate the above mentioned accessories. |
| 118 | Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed, 1100 V grade cable with multistranded copper conductor, including provision of lugs/thimbles on either ends of cable. |
| 119 | Supply and fixing street light luminaire energy efficient high power LED type fitting 60 watt having power factor 0.95 extra clear cover and pressure die cast aluminium housing suitable for 230 Volts50 Hz single phase AC supply full IP 66 protection. including taking down old fitting.Make : Havells of ENDURAPEARLNEOSL60WLED757PASYTOPCor equivalent of Philips/Bajaj |
| 120 | Supply and fix pole junction box sheet moulded compound (SMC) type with hinged door and locking arrangement of size 300 X 200 X 105 mm (internal ) comprising, 01 Nos MCB single pole of capacity 6 Amps 240 volts and two Nos terminalfor loop in & loop out suitable for three phase street light systemincluding nuts and bolts and connecting up complete, MS clamp fabricated from 25x3mm MS flat iron all as specified and directed. |
| 121 | Supply andfixing or passing through pipe, 1100 volts grade heavy duty, PVC insulated round 3 core 2.5 sqmm copper cable including electricalconnectioncomplete all as specified and directed by Engr-in-Charge. Make:-Havells/finolex/Plaza |
| 122 | M & L for earthing complete with GI earth plate electrode of size 60 x 60 x 0.6 cms thick burried directly in ground vertically at a depth of not less than 2.25 Mtrs below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanised iton strip of25 x 4 mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full length of earth plate, 40 mm dia GI tubing light grade protection pipe upto test point, 20 mm dia GI watering pipe with funnel and wire mesh, PCCpit 1:3:6 with pit cover of size 30x30 CM made of RCC 1:3:6 with suitable handle, angle iron frame of angle iron size 40 x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, removal of surplus soil and returning filling in all as required at site all as specified in plate No 3 of SSR Part-I and directed by Engr-in-Charge. |
| 123 | M & L for earthing complete with galvanized steel plate electrode 60 cm x 60 cm x 6 mm surrounded by charcoal and salt, buried directly in ground vertically in a pit of depth not less than 2.25 meter below ground level with top edge of the earth plate at a depth of not less than 1.50 meter below ground level connected to galvanized iron or steel earth wire, 4 mm dia (No. 8 SWG) by means of bolts, nuts, check nuts and washers of galvanized iron, earth wire protected by galvanized steel pipe 15 mm dia (Light grade)& connected to mainswitchor main control board all as shown in electrical plate No.3 ofSSR-2009 Part I & including necessary excavation and earth work. The rate also include charcoal and salt in alternate layers 20 mm dia pipe (Light grade) for watering, protection pipe, funnel, wire mesh, PCC chamber in cement concrete (1:3:6) type C-I, 40 mm thick RCC (1:2:4) type B-1 cover and CI frame etc. |
| 124 | Supply & fix MCCB 250 Amp TPN, 415 Volts, 50Hz, 36 KA with enclosure and connectioncomplete all as specified and directed. |
| 125 | Supply & fix MCCB 200 Amp TPN, 415 Volts, 50Hz, 36 KA with enclosure and connectioncomplete all as specified and directed. |
| 126 | Supply & fix distribution layout diagram of external electric supplyprinted on poly carbonated sheet (PVC) fitted with wooden card boardof size 100 CM x 60CMcomplete with fitting arrangment as directed by engr -in charge |