| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bellpoint with 1.5 sq.mm FRLS PVC insulated copper conductorsingle core cable in surface / recessed medium class PVCconduit, with piano type switch, phenolic laminated sheet,suitable size M.S. box and earthing the point with 1.5 sq.mm.FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 2 | Rewiring for light point/ fan point/ exhaust fan point/ call bellpoint with 1.5 sq.mm FRLS PVC insulated copper conductorsingle core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/recessed steel/PVC conduit including dismantling as required.Group C |
| 3 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. 5/6 amps switch |
| 4 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 5 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 1.14.4 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 6 | Supplying and fixing 20 A, 240 V, SPN Industrial type socketoutlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 7 | Wiring for circuit/ submain wiring alongwith earth wire with thefollowing sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. A) 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 8 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm diaincluding accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc.with charcoal/ coke and salt as required. |
| 9 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 10 | Supply,Installation,testing and commissioning of 1200mm sweep BEE 5star rated,ceiling fan with brush less Direct current(BLDC) Motor,class of insulation:B,3 nos blades,30cm Long down rod,2 nos canopies,shackle kit,safety rope,copper winding,power factor not less 0.9,service value(CMM/W) minimum 6.85,air delivery minimum 215CMM,350 RPM(tolerance as per IS:374-2019),THD less than 10%,remotte or electronic regulator unit for speed control and all remaining accessories including,safety pin,nut bolts,washers,temperature rise=75 degree C(Max),insulation resistance more than 2 mega Ohm,suitable for 230V,50Hz,Single phase Ac supply,earthing etc.complete as required |
| 11 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 12 | Providing and fixing 6 SWG dia GI wire on surface or in recess for loop earthing along with surface/recessed conduit/submain wiring/cable as required. |
| 13 | S/F installation of cubical panel board 16 SWG sheet M.S depth 30 cm to 60 cm with A1. bus bar and interconnection suitable for switch gears i/c and making foundation etc as required |
| 14 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminalspreaders in existing cubicle panel board including drilling holesin cubicle panel, making connections, etc. as required.200 Amp, 16 KA,TPMCCB |
| 15 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C”curve, miniature circuit breaker suitable for inductive load offollowing poles in the existing MCB DB complete withconnections, testing and commissioning etc. as required. Single Pole |
| 16 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. A) 40 A |
| 17 | B) 63 A |
| 18 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.100 amps |
| 19 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar,din bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB/Isolator) a) 12 Way Double Door |
| 20 | SITC OF LED Tube type luminarie 20 watt rating complete with extruded aluminium Batten prewired with high efficient LEDs with the following:a) Total system wattage 20watt+/-5% (b)Luminious efficiancy lumens/watt>=95(c) Power factor>=.95 |
| 21 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 22 | Laying and fixing of one number PVC insulated and PVCsheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 23 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing masonry open duct as required. Upto 35 sq. mm |
| 24 | Supply of XLPE insulated and PVC Sheathed AL Conductor armoured 1.1KV gradeconfirming to IS: 7098of following sizes:2 x 16 sqmm |
| 25 | 4 x 25 sqmm |