Supply, Installation, Testing, Commissioning Of Medical Gas Pipeline System ( Oxygen Only ) At District Hospital Bijnor, District Hospital Bijnor-Uttar Pradesh
TDR : 29317058
Tender Notice
BOQ
Expired
District Hospital Bijnor
Uttar Pradesh
Supply, Installation, Testing, Commissioning Of Medical Gas Pipeline System ( Oxygen Only ) At District Hospital Bijnor
Name of Work:Supply, Installation, Testing and Commissioning of Medical Gas pipeline system (Oxygen only), at District Hospital Bijnor.
Sl. No.
Item Description
1
Oxygen Manifold extenble type with middle frame along with tall pipe as size given, having top frame comprising of high pressure copper pipe with high pressure brass fitting made of high tensile brass, NRV and high pressure Copper tailpiece nade of high prssure copper pipe. One bank shall be a reserve source of oxygen supply. It shall automatically supply the pipeline when primary bank becomes exhausted or fails due to any reason. The system shall have source shut-off valve for easy changing and positioning. The cylinder should be placed with the help of cylinder brackets and fixing chins which should be zinc plated appropriate. (Gas cylinders are not in the scope of this work). Product should be as per specification.
2
8+8 Size
3
The oxygen emergency sytem contains bulk Gas cylinder manifold along with copper header, Brass Non Return Valve & High pressure copper tail pipe for each cylinder complete. System must be equiped with high pressure regulator. Product should be as per specification.
4
2+2 Cylinder
5
High Pressure Regulator for oxygen Emergency Manifold system as per specification below mention capacity.
6
1000 LPM at 400 Kpa
7
Fully Automatic Changeover Panel for OxygenNotified CE marked compliant with ISO 7396, Oxygen changeover reduction box (Automatic control panel) of Digital fully Automatic type, capable of swicting from \"Bank in use\" to \"Reserve Bank\" without fluctuation in delivery line pressure and without the need for external electrical power. The changeover panel shall be rated for minimum capacity as mentioned below and shall include the mention accessories. Panel shall comply with HTM/ISO & as per specification.Main Component/ feature of system are as belowPower Supply module to provide power supply for alarm system display.signaling module for pressure monitoring and alarm activationDouble line pressure regulatorHigh and low limit pressure switches.changeover and safety valvePressure gauge for working pressure indicationMin 750 LPM at 4 Bar / 400 Kpa
8
Gas Outlet/ Terminal UnitTerminal outlets:-Terminal outlets gas specific for the services indicated (viz. O2, Air & Vacuum) and to accept only compatible quick connect pin/Geometric index type adapters as per ISO 7396 standard, Manufactured in compliance with CE and ISO 13485 as per specification.
9
Oxygen Outlet
10
Copper Piping : Copper pipes for medical Gases, Complete with elbows, flanges, Specials, others fittings, ad steel supports, The coper pipe should be of solid drawn seamless deoxidized un-arsenical tempered and of degreased material conforming to BS-EN 13348/ASTM 8819 of copper pipe must be certified and inspected by third party inspection agency like LLoyds/SGS/TUV etc.
11
12 mm OD x 0.9 mm
12
15 mm OD x 1 mm
13
22 mm OD x 1 mm
14
Floor/Area Isolation valve-All valves are to e ball valves type and PTFE or teflon seals, They Shall be suitabke for a working pressure of 10.2 kg/cm2 gauge. Valves shall be fitted into the pipeline by means of capillary hard soldered joints containing silver. it should be open/close with help of handle with rotation of 90 degree.Isolatio valve - All valves are to be ball valves type and PTFE or teflon seals. They shall be suitable for a workig pressure of 10.2 kg /cm2 gauge. Valves shall be fitted into the pipelie by means of capillary hard soldered joints containing silver. It should be open/close with help of handle with rotation of 90 degree.
15
12 mm
16
15 mm
17
22 mm
18
Oxygen flow Meter- made for brass, chrome plated. It shall be back pressure compensated type having housing of Polycarbonate autoclavable reusable flow range 0-15 LPM. Fitted with matching adopter for oxygen outlet point and humidifier shall be compatible with flowmeter and reusable and as per specifications and as requred . Product should be as per specification. As per approved make attached.
19
Supply, Installation, testing & Commissioning of single gas alarm system.