}

Providing Electrical Installation Work, 250 Kva Dg Set, 250 Kva Stabilizer & Medical Oxygen Gas Pipe Line For Services Of Installation For 800 Lpm Medical Oxygen Generation Plant At Central Jail No.3 Tihar Jail, New Delhi., Work-Delhi

Public Works Department-PWD has published Providing Electrical Installation Work, 250 Kva Dg Set, 250 Kva Stabilizer & Medical Oxygen Gas Pipe Line For Services Of Installation For 800 Lpm Medical Oxygen Generation Plant At Central Jail No.3 Tihar Jail, New Delhi.. Submission Date for this Tender is 25-09-2021. Electrical Maintenance Tenders in Work Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

29249952
Providing Electrical Installation Work, 250 Kva Dg Set, 250 Kva Stabilizer & Medical Oxygen Gas Pipe Line For Services Of Installation For 800 Lpm Medical Oxygen Generation Plant At Central Jail No.3 Tihar Jail, New Delhi.
Open Tender
Indian
Delhi
Work
25-09-2021

Tender Details

Providing Electrical Installation Work, 250 Kva Dg Set, 250 Kva Stabilizer & Medical Oxygen Gas Pipe Line For Services Of Installation For 800 Lpm Medical Oxygen Generation Plant At Central Jail No.3 Tihar Jail, New Delhi.

Key Value

Document Fees
Refer document
EMD
Refer document
Tender Value
INR 1.15 Crore /-

BOQ Items

Name of Work: Providing EI work, 250 KVA DG Set, 250 KVA Stabilizer & Medical Oxygen gas pipe line for services of installation for 800 LPM Medical Oxygen Generation plant at Central Jail No.3 Tihar Jail, New Delhi.
Sl. No. Item Description
1SH-I (E.I. Work) Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
2Group C
3Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
4Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.
52 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
6Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
7Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
8Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
9Single pole
10Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
118 way, Double door
1212 way, Double door
13Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
1440 A
1563 A
16Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with testing and commissioning etc. as required.
17For 8 way, Double door SPN MCBDB
18For 10 way, Double door SPN MCBDB
19Supplying, installation, testing and commissioning of 380 mm sweep heavy duty exhaust fan with 900 RPM, double ball bearing, energy efficient motor working on 230V, 50 Hz, AC supply with louver/shutter including all accessories connection with 3 core flexible wire in the existing opening, including making the hole to suit the size of the above fan, making good the damage etc. complete as required.
20Supply, installation, testing and commissioning of 1200 mm sweep Energy Saving ceiling fan working on 240V, 50 Hz, AC supply i/c wiring the down rods of standard length (upto 30 cm) with 1.5 sqmm FRLS PVC insulated copper conductor, single core cable with all accessories double ball bearings, blades, down rod, shackle insulator, canopy etc. complete as required.
21Supplying, Installation, testing and commissioning of 40 watt, Industrial LED Batten luminaire made out of PDC aluminimum body with mimimum lumen 100 per watt suitable for cool day white light having minimum CCT 5700K-6500K, power factor= 0.90, CRI = 75 complete with all accessories suitable for working on 240 V, 50 Hz, AC supply i/c fixing the same directly on surface / ceiling including connection with 1.5 sqmm, PVC insulated, FRLS copper conductor, single core cable etc. complete as required.
22Supplying, Installation, testing and commissioning of 32-36 watt 2 x 2, full glow glare free diffuser LED of PDC aluminimum body with minimum lumen 100 per watt suitable for cool day white light having minimum CCT 5700K - 6500K, power factor = 0.90, CRI = 70 complete with all accessories suitable for working on 240 V, 50 Hz, AC supply i/c fixing the same directly on false ceiling including connection with 1.5 sqmm, PVC insulated, FRLS copper conductor, single core cable etc. complete as required.
23Supplying, installation, testing and commissioning of50 Watt LED flood light luminaire made out of PDC aluminimum body with minimum lumen 100 per watt suitable for cool day white light having minimum CCT 5700K - 6500K, power factor = 0.90, CRI = 70, THD = 10% with IP65/66 protection suitable for working on 240 V, 50 Hz,AC supply on ceiling / wall / surface / angle frame with fastner complete with all accessories including connection etc. complete as required.
24Fabricating Supplying, Installation, Testing and Commissioning of floor mounted double door both side openable outdoor type Feeder Pillar of 450 mm deepwith canopy made out of 2mm thick CRCA Sheet, mounting on angle iron frame work of size 50mmx 50mm x 6mm thick dust and vermin proof, duly compact without bus bar duly powder coated paint of approved colour and shade providing earth stud at both end, louvers and mesh on both side of feeder pillarfor ventilation purposei/c provision for fixing of 400A, 4 pole on load change over switch i/c earthing etc as required.
25SITC of400Amp Open execution type On load Four Pole Changeover switch suitable for 440 Volt 3 phase 50 Hz AC supply, fixed in the above Feeder pillar i/c connections etc as required.
26Fabricating Supplying, Installation, Testing and Commissioning of wall / floor mounted cubicle panelminimum 300mm deep made out of 2mm thick CRCA Sheet, thick dust and vermin proof, duly compact with 400 Amp TPN Al. bus bar of panel duly powder coated paint of approved colour and shade providing earth stud at both end, louvers and mesh on both side of panel board for ventilation purpose i/c connection and interconnection, earthing complete etc. as required.
27SITC of following accessories in the above panel i/c connections etc as required.
28Incomer 400 A, 50kA, FPMCCB
29Outgoing 400 A, 50kA, FPMCCB
30Outgoing 63 AMP 10KA DPMCB C-Series
31Outgoing Digital type VAF
32Outgoing LED type indicating lamp RYB
33Outgoing 400/ 5 A CT - 3 Nos.
34Fabricating Supplying, Installation, Testing and Commissioning of floor mounted double door both side openable outdoor type Feeder Pillar of 450 mm deepwith canopy made out of 2mm thick CRCA Sheet, mounting on angle iron frame work of size 50mmx 50mm x 6mm thick dust and vermin proof, duly compact with 500 Amp Al. bus bar duly powder coated paint of approved colour and shade providing earth stud at both end, louvers and mesh on both side of feeder pillarfor ventilation purposei/c provision for fixing of following accessories / switch i/c earthing, danger notice plate etc as required.
35SITC of following accessories in the above panel i/c connections etc as required.
36Incomer 400 A, 50 kA, FP MCCB with thermal magnetic release with rotary handle and spreader links.
37Outgoing 400 A, 50 kA, FP MCCB with thermal magnetic release with rotary handle and spreader links.
38Outgoing 250 A, 50kA, FPMCCB
39Outgoing LED type Phase indicating lamps (RYB)
40Outgoing Digital type VAF Meter
41Outgoing 3 Nos CT 400/5Amp
42SITC of 300 amp automatic phase sequence corrector in sheet steel encloser made out of 2mm thick CRCA sheet painting with powder coated paint, connection- interconnection with copper bus bar as per incommer complete with 400 Amp, 50 KA 4 Pole MCCB - 1 No, 330 Amp, 4 Pole Contactor - 2 Nos, Phase Sequence relay - 1 No, LED Indication Lamp - 1 Set, Minimum size of sheet steel encloser shoud be 800mm x 800mm x 300mm deep, earthing stud on both side, louvers and mesh on both side of panel board for ventilation purposeetc. complete as required.
43SITC of Carbon Dioxide (CO2) gas type fire extinguisher of 4.5 Kg. capacity with initial charge i/c discharge hose and horn, squeeze grip release valve, locking arrangement, bracket with two screw and sleeve i/c fixing on wall as required. (Fire extinguisher shall be ISI marked confirming to IS: 15683)
44Supplying & fixing of powder type fire extinguisher (stored pressur type confirming to IS:15683:2006) 4 Kg. capacity with initial refill of ISI marked ABC power completed with squeeze grip, release valve, discharge pipe, pressure gauge, locking safety clip, mounting bracket etc. i/c fixing on wall as required.
45Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
46Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
47Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
48Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
49Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
50Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
51Supplying and Laying of 3.5 x 300 Sq.mm XLPE insulated and PVC sheathed Aluminium conductorarmoured power cable of 1.1 KV grade conf. to IS 7098 (Part-I)in the following Ways etc complete as required.
52In the existing RCC/ HUME/ METAL pipe
53Open duct
54Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) includingexcavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
55120 mm dia (OD-120 mm & ID-103 mm nominal)
56Supplying and Laying of 3.5 x 185 Sq.mm XLPE insulated and PVC sheathed copperconductorarmoured power cable of 1.1 KV grade conf. to IS 7098 (Part-I)in the following Ways etc complete as required.
57In the existing RCC/ HUME/ METAL pipe
58Open duct
59On Surface
60Supplying and Laying of following size XLPE insulated and PVC sheathed Aluminimum unarmoured power cable of 1.1 KV grade conf. to IS 7098 (Part-I)/ IS 1554 (Part-I) and ISI Marked only on the existing surface / wall etc. complete as required.
613 x 6 Sq.mm
62Supplying and Laying of 3 x 6 sq.mm. XLPE insulated and PVC sheathed Copper armoured power cable of 1.1 KV grade conf. to IS 7098 (Part-I)and ISI Marked only in the following ways etc.as required.
63In Open Duct
64On Surface
65SH-II (D.G. Set & AMF Panel) Supplying, Installation, Testing and Commissioning of "Silent Type" Diesel Generating set having Prime Power Rating of 250 KVA, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, three phase system & for 0.85 Load factor and consisting of the followings:
66a) Diesel Engine: Diesel engine 4 stroke Water cooled, electric start, of suitable BHP at 1500 RPM suitable for above output of alternator at 48 Degree C, 50% RH & at 1000 Meter MSL and conforming to BS 5514, BS 649, IS 10000, capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be fitted complete with all the required accessories. b) Engine mounted Instrument Panel fitted with and having digital display for following: (i) Start-stop switch with key (ii) Engine temperature indication (iii) Lubrication oil pressure indication (iv) Lubrication oil temperature indication (v) Battery charging indication (vi) RPM indication (vii) Over speed indication (viii) Low lub. Oil trip indication (ix) Engine Hours indication c) Alternator : Synchronous alternator rated at 250 KVA, 415 volts at 1500 RPM, three phase 50 Hz, AC supply with 0.8 lagging power factor at 48 Degree C, 50% RH & at 1000 Meter MSL. The alternator shall be having SPDP enclosure, brushless, continuous duty, self-excited and self-regulated through AVR conforming to IS: 4722/BS 2613 suitable for tropical conditions and with class-F/H insulation. d) Base Frame & Foundation: Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer. e) Fuel Tank: Daily service fuel tank for 12 Hrs. continious run on full load capacity fabricated out of 3mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class "C" pipes of suitable dia. complete with valves, level indications & accessories as required as per specifications. f) Exhaust System: Dry exhaust mainfold with residential exhaust silencer and catalytic convertor. g) Starting System: 12V DC starting system comprising of starter motors, voltage regulator and arrangement for initial excitation complete with suitable nos. of batteries (180 Amp. Hour capacity lead acid type) as required as per specifications. h) Accoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere as per specifications.
67Fabricating, Installing, Testing & Commissioning of automatic mains failure control panel including manual by-pass panel, suitable for 250 KVA silent type DG set complete with relays, timers, set of CTs for metering & protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, KVARH & provision for overload, short circuit, restricted earth fault, under frequency, relay control cabling from AMF panel to diesel engine and elsewhere, if required, all complete and inter locking including the following:
68a) 400 Amp 4 pole MCCB 35 KA = 3 Nos b) 400 Amp 415 volt AC 3 duty 4 pole contactor = 2 Nos c) AMF Controller for control of DG Set (Main supply failure monitor, Supply failure timer, Restoration timer, Control unit with three impulse automatic engine start/ stop and failure to start lockout.) = 1 Set d) Auto/ Manual selector switch = 1 Set e) Control ON/OFF selector switch with indicator = 1 Set f) Voltage monitoring relay for DG Supply & Main Supply = 1 Set g) Current transformers 50/5 Amp. 3 Nos. = 1 Set h) Energy analyser unit to indicate current voltage frequency power factor and KWH = 1 Set i) Indicating lamps for load on mains and load on set = 1 Set j) Indicating lamps for load ON = 1 Set k) Indicating lamps for battery charger ON/OFF = 1 Set l) Indicating lamps for RYB = 2 Set m) Fuse for instruments (MCB "C" Curve 10KA) n) Battery charger complete with D.C. voltmeter and ammeter = 1 Set o) Impulse counter with locking and reset facility p) Control Cable from AMF to D.G.Set q) Audio/Video annunciation for i) High water temperature ii) Low lubricating oil pressure iii) Engine over speed iv) Engine fails to start v) Full load/ maximum load warning
69SH-III (Servo Voltage Stabilizer) Supplying, installation, testing & commissioning of 250 KVA Servo Control Voltage Stabilizer 3 phase 50 Hz ,Balance Type copper wound for automatic controlling/ regulating of voltage comprising of auto transformer, servo motor, solid state control circuit, oil filled and other accessories as:- 1. Voltmeter (1 No.) to read input & output voltage per phase. 2. CT operated Amp. Meter. (600 Amp.) 3. Selector Switch to measure the load independently. 4. Main/ Low/ High Indicator. 5. Manual increase/ decrease push switch. 6. Auto/ Manual Switch. 7. Output Voltage adjustment in auto mode. Technical Specification :- Input Voltage : 300V-480V Output Voltage: 415V +1% Cooling :Oil Cooled Capacity: 250 KVA (1st Filling of Transformer Oil.)
70SH-IV (Medical Oxygen Gas pipe line System) PART-A: GAS PLANT EQUIPMENT OXYGEN SUPPLY SYSTEM Supply Installation Testing and Commissioning of Oxygen Manifold minimum of 8+8 Cylinders Banks as (Left side 8 Cylinders + Right side 8 Cylinders) complete with top frame comprising of high pressure copper pipe with high pressure pig tail pipes andnon- return valves at all headers racks The cylinder should be placed with the help of cylinder brackets and fixing chains which should be zinc plated, etc. complete as per direction of Engineer in Charge at site.
71Supply Installation Testing and Commissioning ofOxygen HTM Digital Fully Automatic Changeover Control Panel of minimum 800 lpm at 50 to 60 psig with LCD display.It should have auto-ignition test certificate for manifolds and control panel and Automatic Change Manifold. Automatic Changeover Manifolds are intended to provide a continuous supply of medical gases for respiratory, clinical and surgical use in healthcare facilities. The system shall be duplex such that the supply is maintained in single fault condition. The Automatic Changeover Manifolds shall be supplied pre-piped, pre-wired and fully tested as perHTM 02- 01 andC11. standard duly EMC, Adiabatic tested. It should have halogen polymers free and having Digital 3.5’ colorful display. It should have Integrated & protected test point. Central regulators panel with cylinder headers each side. It should have headers which shall be complete with gas specific cylinder tailpipes. Pre-wired for alarm connection to BMS outputs. All components degreased for oxygen use etc. complete as per direction of Engineer in Charge at site.
72Supply Installation Testing and Commissioning of Emergency oxygen ManifoldHeader Bars, Tail Pipes: Oxygen Manifold Supply System (Cylinder Manifold Unit) of 4+4 cylinders (Left side 4 Cylinders + Right side 4 Cylinders) complete with top frame comprising of high pressure copper pipefor each cyclinder1no for high pressure regulatorcomplete with pig tell pipe and 8 nosnon- return valves at all headers racks complete as per direction of Engineer in Charge at site.
73Supply Installation Testing and Commissioning of gas outlet point ( Walloutlet/console outlet) for oxygen duly CE markedand meets with the requirements of the Health Technical Memorandum 02-01 (HTM 02-01) standards only comply with 93/42/EEC Medical CE Cetification andcomplete as per direction of Engineer in Charge at site.
74Supply Installation Testing and Commissioning ofOxygen Flow Meter (0-15lpm) :comply and meets with active medical device of classEN ISO 15002: 2008 standard, duly CE marked and comply with 93/42/EEC Medical CE Cetification with the specified notified body. It should be imported oxygen flow meter. It should have pressure compensated to prevent back pressure. It should having cartridge knob, extremely reliable, easy-to-clean and ensuring an optimized adjustment. Perfect tightness of the knob. The knob was tested under pressurized working conditions during more than 10,000 cycles without showing any leakage after closing. Expanded scale providing higher reading accuracy. Durable polycarbonate flow tube with cover. Monoblock scale cover made of polyamide for a higher sturdiness and a greater safety. The inopportune unscrewing of the monoblock scale cover is not possible. Body made of nickel-plated brass, very strong.Flowmeter should be MRI compatible. Flow meter should be placed in the vertical position. The flow meters should be MRI Competivale it should be placed in vertical position it shold haveof 0-15 LPM range for oxygen and with inlet pressure 50-60psi. (4.5 bar) complete as per direction of Engineer in Charge at site.
75Supply Installation Testing and Commissioning ofof Oxygen Gas specific adaptor with fixing arraganment as per Intetnation/BISstandards omplete as per direction of Engineer in Charge at site.
76Supply Installation Testing and Commissioning ofHumidifier Bottle : made out by Polysulphone 250ccunbreakable reusable to disinfectantscomplete as per direction of Engineer in Charge at site.
77Supply Installation Testing and Commissioning of Oxygen Gas Area alarm . :Technical Memorandum 02-01 (HTM 02-01) standards andduly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body. . It should have anti microbial coating labels for touch control.capable of monitoring up to 6 gas services by means of pressure sensorsfrom the normal operating limits. It shoiuld havethe dispalyed for thenormal ‘Normal’ (green) and ‘Low’and high pressure (red) . Failure indicators shall be displayed by flashing lights and normal indications steady. It should have the Audio indication as well as fall your indication witha mute switchcomplete as per direction of Engineer in Charge at site.
78Supply Installation Testing and Commissioning ofdual presure switch /sensor for Oxygen gas with CE Cetification,Helth techinical Memorandum 02-01 ( HTM 02-01) Standard complete as per direction of Engineer in Charge at site.
79Supply Installation Testing and Commissioning of Copper Piping Medical Grade BS EN 13348:2016 BSI Kite Markduly CE Certified Copper Pipes.i/c fixing arragement on wall/ partition/inground,cutting and refilling the trench as per site requirement with accessories like Tee,elbow,Socket,reducer for fully fuctional with seamless operation of oxygen supplying facilitycomplete as per direction of Engineer in Charge at site.
8015 mm OD
8122 mm OD
8228 mm OD
8342 mm OD
84Supply Installation Testing and Commissioning of Isolation valve -( Lockabale)Cerified by helthtechinicalMemorandum 02-01 (HTM 02-01) standards andduly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body. complete withcopper Stub pipes forease of installtion fitted with flat faced unions fitted with nitrile O-ring seals complete with falnge connetes end cap and stem complete in all rerspect for fully fuctional for thhe oxygen/ other gas system complete as per direction of Engineer in Charge at site.
8515 mm
8622 mm
8728 mm
8842 mm
89Supply Installation Testing and Commissioning of 4 inch diaPressure Guage upto15 barcomplete as per direction of Engineer in Charge at site.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail