| 1 | DISTRIBUTION BOARD |
| 2 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs with MCCB incoming (but without MCBs and incomer) as required.(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)12 way (4 + 36), Double door EachMake: Legrand/Hager/Schnieder |
| 3 | Supply, installation and testing of 100 A,36KA,FPMCCB, (Ics=100% Icu) in the existing MCCB VTPN DB. Make: Legrand/Hager/Schnieder |
| 4 | Supplying and fixing 16A to 32 A rating, Triple pole 240/415 V, 10 kA, \"C\"curve, miniature circuit breaker suitable for inductive load offollowing poles in the existing MCB DB complete withconnections, testing and commissioning etc. as required.Legrand/Hager/Schnieder |
| 5 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator)4wayDB4+12 way DBMake: Legrand/Hager/Schnieder |
| 6 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.SP MCBMake: Legrand/Hager/Schnieder |
| 7 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 Amp 4 Pole RCCBMake: Legrand/Hager/Schnieder |
| 8 | Supplying and fixing following rating, four pole, 415 V, isolatorin the existing MCB DB complete with connections, testing andcommissioning etc. as required.40 Amp 4pole MCB IsolatorMake: Legrand/Hager/Schnieder |
| 9 | Supplying and fixing 4pole double door TPN sheet steel enclosure on surface/ recess along with 63A 240 V \"C\" curve 4P MCB complete with connections, testing and commissioning etc. as required. Make: Legrand/Hager/Schnieder |
| 10 | Supplying and fixing of double door TPN sheet steel enclosure on surface/ recess along with 40/32 A 415 V \"C\" curve TPN MCB complete withconnections, testing and commissioning etc. as required.Make: Legrand/Hager/Schnieder |
| 11 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required along with fixing of 6/16A 6pin socket outlet and 15/16 A Modular switch including installation, fixing of switch and socket and connection 6 Module box and 2nos. of Switch and 2 nos. of socket eachMake: Legrand (Myrius/Mylinc) |
| 12 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required along with fixing of 3nos. of 5/6 amp Modular switch for LED Lights3 Module (100mmX75mm) Make: Legrand (Myrius/Mylinc) |
| 13 | Supply and fixing of high speed 1200 MM sweep opal white color, ceiling mounted Fan.Make: Havells/Almonard/Bajaj |
| 14 | Cable and Wiring |
| 15 | Cable laying for AC DB incomingSupply, Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. 3.5Cx35 Sq MM AL Armoured XLPE Cable Make: Polycab/CCI/RR Kabel |
| 16 | Supplying and making end termination with brass compressiongland and aluminium lugs for following size of PVC insulatedand PVC sheathed / XLPE aluminium conductor cable of 1.1 KVgrade as required.3.5Cx35 SQmm Cable |
| 17 | Cable laying for AC DB incomingSupply, Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. 4Cx25 Sq MM AL Armoured XLPE Cable Make: Polycab/CCI/RR Kabel |
| 18 | Supplying and making end termination with brass compressiongland and aluminium lugs for following size of PVC insulatedand PVC sheathed / XLPE aluminium conductor cable of 1.1 KVgrade as required.3.5Cx25 SQmm Cable |
| 19 | Wiring for circuit/ submain wiring alongwith earth wire with thefollowing sizes of FRLS PVC insulated copper conductor, singlecore cable in surface/ recessed medium class PVC conduit asrequired.4 X 16 sq. mm + 2 X 6 sq. mm earth wireMake: Polycab/Universal/RR/Finolex |
| 20 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (AC\"s wiring and Sub-main ckt wiring for Fan Light)Cable: 4 X 6 sq. mm + 2 X 6 sq. mm earth wireMake: Polycab/Universal/RR/Finolex |
| 21 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (AC\"s wiring and Sub-main ckt wiring for Fan Light)Cable: 2 X 4 sq. mm + 1 X 4 sq. mm earth wireMake: Polycab/Universal/RR/Finolex |
| 22 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (Light Fan and Power point Wiring)Cable: 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire Make: Polycab/Universal/RR/Finolex |
| 23 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (Light Fan and Power point Wiring)Cable: 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire Make: Polycab/Universal/RR/Finolex |
| 24 | LAN Point and Telephone Point Wiring |
| 25 | Supply and fixing of CAT6 Face Plate with RJ45 UTP Jack: Should be 2-port flush mounted, squarefaceplate, High-impact, flame retardant, UL-rated 94 V-0,thermoplastic, UL 94 V-0 with all accessories for fixing on existing race way.Supply and fixing of RJ-45 CAT-6 UTP Jack:Electrical performance guaranteed to meet or exceedlatest TIA/EIA 568 Category 6 and ISO/IEC Category6/Class E specifications, Minimum 750 mating cycle.200 termination cycle, 100 M Ohm, 1.5 A @ 20 °C, 1500 VAC @ 60 Hz, 500 M Ohm, UL listed(UL 94 V-0)Conductor Gauge- 22-26 AWG and ROHS Compliant 2 nos. in each face plateMake:Legrand/Systemey/Panduit |
| 26 | Supply and fixing of Cat-6 UTP Cable for Lan point Unshielded Twisted Pair, Category 6, TIA / EIA 568 C.2 & ISO/IEC 11801 2nd edition, Conductors- 23 AWG Solid bare copper, Insulation-Polyethylene or PolyolefinJacket- LSZH jacket must complying to: Fire rating-IEC60332-3-22, Acid gas- IEC 60754-2 Smoke density- IEC 61034-2, Minimum 250 MHz; ETL report for 4 connector channelperformance up to 250 MHz to be provided. Impedance-100 Ohms + / - 15 ohms, Mutual Capacitance-5.6 NF MAX /100 Meter, Bend Radius- 4 * Cable DiameterDC Resistance- unbalance 5% Max. with ROHS/ELV Compliant Make: Legrand/Systimax/Panduit |
| 27 | SITC of 24 port loaded Patch Panel (Panel : SPCC. 1.5mm thickness with Black (RAL9005) color painted RJ-45 Jack : Housing ABS, UL94-0RJ-45 Jack Contact : Material Phospor Bronze with Nickel Palated)Make: Legrand/Systimax/Panduit |
| 28 | Supply, installation of 19\" Wall mounted 9 U, 600x600mm rack with acrylic glass door with following accessories :a) Four fan position tray with 4 fans (230 V AC) - 1 nob) AC power panel with minimum 6 nos. 6/16 A socket, fuse and 6 switches - 1 panel.Make: Legrand/Systemey/Panduit |
| 29 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess with Telephone RJ11 socket outlet etc. as required.1 or 2 module GI box and cover plate with face plate with telephone socket out let.Make: Legrand |
| 30 | Dedicated Earthing |
| 31 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm diaincluding accessories, and providing masonry enclosure withcover plate having locking arrangement and watering pipe etc.with charcoal/ coke, soft soil and salt as required. |
| 32 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 33 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 34 | Providing and fixing earth bus of 50 mm X 5 mm copper strip onsurface for connections etc. as required. |