Construction Of Ioc Captive Pol And Lpg Marine Jetty At Kamarajar Port Construction Of Ioc Captive Pol And Lpg Marine Jetty And Associated Mechanical Electrical Fire Fighting And Instrumentation Facilities At Kamarajar Port Limited Ennore Tamil Nadu

Tender Notice

29156511
Corrigendum : Construction Of Ioc Captive Pol And Lpg Marine Jetty At Kamarajar Port Construction Of Ioc Captive Pol And Lpg Marine Jetty And Associated Mechanical Electrical Fire Fighting And Instrumentation Facilities At Kamarajar Port Limited Ennore Tamil Nadu
Indian
Tamil Nadu
19-10-2021
29-10-2021
06-10-2021

Tender Details

Construction Of Ioc Captive Pol And Lpg Marine Jetty At Kamarajar Port Construction Of Ioc Captive Pol And Lpg Marine Jetty And Associated Mechanical Electrical Fire Fighting And Instrumentation Facilities At Kamarajar Port Limited Ennore Tamil Nadu

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 13-Sep-2021 Revised Piping Works Technical Bid 04-10-2021
2 22-Sep-2021 Extension of bid submission date Date 19-10-2021
3 30-Sep-2021 Integrity Agreement Document Other 19-10-2021
4 11-Oct-2021 Fine aggregates specs Other 19-10-2021
5 13-Oct-2021 Extension of date of submission Date 29-10-2021
6 19-Oct-2021 Unit of Measurement for item Other 29-10-2021

Key Value

Document Fees
Refer document
EMD
Refer document
Tender Value
INR 788.04 Crore /-

Attachment

FileName File Description File Size
75f49ef6-ef1b-402f-902f-5920fa78ab7b.html Tender Notice 53.4 KB
BOQ_150727.xls Tender Document 3.5 MB
FAQs-IOCL-Online-EMD.pdf Tender Document 559.5 KB
Special_Instructions_to_t.pdf Tender Document 1.5 MB
Tender-Acceptance-Format.pdf Tender Document 84.2 KB
Tendernotice_1.pdf Tender Document 383.6 KB
VOLUME1_NIT.pdf Tender Document 2.1 MB
VOLUME2_GCC.pdf Tender Document 3.4 MB
VOLUME3_SPECS.pdf Tender Document 23.5 MB
VOLUME4_Billofqty.pdf Tender Document 118.5 KB
VOLUME5_Site_information.pdf Tender Document 137.8 KB
75f49ef6-ef1b-402f-902f-5920fa78ab7b.html Tender Notice 53.4 KB
BOQ_150727.xls Tender Document 3.5 MB
FAQs-IOCL-Online-EMD.pdf Tender Document 559.5 KB
Special_Instructions_to_t.pdf Tender Document 1.5 MB
Tender-Acceptance-Format.pdf Tender Document 84.2 KB
Tendernotice_1.pdf Tender Document 383.6 KB
VOLUME1_NIT.pdf Tender Document 2.1 MB
VOLUME2_GCC.pdf Tender Document 3.4 MB
VOLUME3_SPECS.pdf Tender Document 23.5 MB
VOLUME4_Billofqty.pdf Tender Document 118.5 KB
VOLUME5_Site_information.pdf Tender Document 137.8 KB

Other Information

Attachments
Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

BOQ Items

Name of Work: CONSTRUCTION OF CAPTIVE POL/ LPG MARINE JETTY AND ASSOCIATED MECHANICAL, ELECTRICAL, FIRE FIGHTING & INSTRUMENTATION FACILITIES AT KAMARAJAR PORT LIMITED, ENNORE, TAMIL NADU
Sl. No. Item Description
1Part A- SUPPLY OF ITEMS General Notes: a. All items under this section shall be quoted for supply as per enclosed Technical Specification & Data Sheets including packaging& forwarding, loading, freight, insurance, import duty, unloading at a designated place within the Project Site, spares, etc. b. The rates to be quoted shall also be inclusive of software upgrades for the supplied softwares, for a period of 3 years beyond the date of issuance of Mechanical Completion. b. Third party inspection for the supply items shall be in tenderer"s scope. Approval of TPI agency to be engaged shall be obtained from IOCL on award of contract. c. Refer Particular Technical Specification / Datasheets given in the tender for all details including warranty. d. All materials to be supplied shall be based on compliance to Particular Technical Specification / Data Sheet to be submitted by successful bidder including applicable QAP / ITP with prior clearance / approval by IOCL/ its Consultant.
2SECTION 1: MECHANICAL
3Marine Loading Arms
4Marine Loading Arm, Size 12", 300#, Product: LPG (Propane & Butane), Material: LTCS, Electro-Hydraulic operated, including spare parts for commissioning and spare parts for 2 years operation, Emergency Release Coupling (ERC) and Hydraulic Quick Connect/ Disconnect Cargo Couplers (QC/DC).
5Marine Loading Arm, Size 12", 300#, Product: POL (MS, HSD, ATF & SKO), Material: Carbon Steel, Electro-Hydraulic operated, including spare parts for commissioning and spare parts for 2 years operation, Emergency Release Coupling (ERC) and Hydraulic Quick Connect/ Disconnect Cargo Couplers (QCDC).
6Hydraulic Power Unit (HPU) common for all the above MLAs
7Gangway Tower
8Hydraulic operated telescopic type Ship Access Gangway Tower with steel tower, platform, inclined ladder, bulwark ladder, hydraulic cylinder, HPU, top side jib crane with ground pendant switch control, combination starter, and all associated accessoriesincluding spare parts for commissioning and spare parts for 2 years operation. Upper Level: 19.5 m CD Down Level: 2.1 m C.D Jib Crane Capacity: 2.5 MT Max./Min. Radius of Jib Crane: 19 m / 3.5 m
9Pig Launcher cum Receiver
10Design, Engineering, Manufacture & fabrication, Procurement of materials & bought out components, assembly at shop, inspection, testing at manufacturer"s works, preparation of shipment / packing, transport, delivery of the Bi-directional launcher cum receiver suitable for accomodating intelligent pigs & other cleaning / displacement / gauging pigs, fitted with Quick Opening End Closure (QOEC) suitable for horizontal installation including all accessories required to make Bi-Directional Launcher & Receiver system complete operational and QOEC shall be hand operated by a single lever operation and operable by one operator. Scope of supply shall include but not limited to supply & placement of perforated SS Tray inside the Bi-Directional Launcher & Receiver, supply and mounting of Pig Signaller on the Bi-Directional launcher & receiver, supply of Pig Signaller for mounting on pipeline, supply of Pig Handling (insertion / retraction) System including supply of mating flanges for all the flanged end Nozzle. Required studs, Nuts, bolts, Gaskets and foundation Bolts for Bi-Directional Launcher & receiver and associated accessories for all the items as detailed below :
11Bi-directional Pig Launcher cum Receiver (of size 36" x 30" NB & ANSI Class 150) along with Band lock type Quick Opening End Closure (QOEC), all required Nozzles, vent, drain, flanges, gaskets and bolting - 2 Nos
12Non-intrusive type (Ultrasonic) Pig Signaller mounted on Pig Launcher cum Receiver- 2 Nos
13Supply of Door Seal for Quick Opening End Closure (QOEC) [Commissioning Spares] - 4 Nos
14Non-intrusive type (Ultrasonic) Pig Signaller mounted on 30" NB Pipeline - 2 Nos
15Jib Crane of capacity 3T to suit the pig handling for scrapper trap as specified above - 1 No
16Pig Handling System with insertion / retraction facilities for inserting / pulling the SS Tray / Pigs to suit the scrapper trap - 2 Nos
17EOT Crane (for Fire Water Pump House)
1810T Capacity Double Girder EOT Crane including bridge structure, travelling mechanism, hoisting mechanism, service platform, brake mechanism, electric motors, trailing cables, AC variable frequency controls for all motions, lighting fixtures and all other necessary accessories. Building Span: 15.70 m Bay Length: 44.00 m Lifting Height: 6.40 m ArNo Classification: Non-Hazardous Operation: Pendant + Radio Remote Control
19Slop Tanks
20Design, Engineering, Manufacture & fabrication, Procurement of materials & bought out components, assembly at shop, inspection, testing at manufacturer"s works, preparation of shipment / packing, transport, delivery of Horizontal, cylindrical, pit mounted (below deck) POL Slop Tanks (one each for MS, HSD, ATF & SKO) incl. shell, flat ends, nozzles, boot for slop pump mounting, manhole with davit arrangement, saddle supports, stiffener plates and RF pads, internal piping, earthing cleats, nameplates, anchor bolts etc. Design Standard: IS 10987 (latest edition) Internal Diameter: 2200 mm Length: 9000 mm Material: MS (IS 2062 Gr.B)
21Design, Engineering, Manufacture & fabrication, Procurement of materials & bought out components, assembly at shop, inspection, testing at manufacturer"s works, preparation of shipment / packing, transport, delivery of Horizontal, cylindrical, pit mounted (below deck) POL Slop tank incl. shell, flat ends, Nozzles, boot for slop pump mounting, manhole with davit arrangement, saddle supports, stiffener plates and RF pads, internal piping, Northing clNots, nameplates, anchor bolts etc. Design Standard: IS 10987 (latest edition) Internal Diameter: 1700 mm Length: 8500 mm Material : MS (IS 2062 Gr.B)
22Slop Pumps
23Vertical, Extended Shaft, Submerged Sump Pump (VS-4) type vessel mounted Slop pumps for POL products (one each for MS, HSD, ATF & SKO) including drive motor, coupling with coupling guard, common base frame for each pump and motor, complete sealing / cooling / lubrication system, counter flanges with bolts, nuts & gaskets, Local Control Panel (LCP) etc. Rated Flowrate: 36 m3/hr. TDH: 100 MLC MOC: ASTM A48 CL 30 (Casing) / ASTM A351 CF8 (Impeller)
24Vertical, Extended Shaft, Submerged Sump Pump (VS-4) type vessel mounted slop pumps including drive motor, coupling with coupling guard, common base frame for each pump and motor, complete sealing / cooling / lubrication system, counter flanges with bolts, nuts & gaskets, Local Control Panel (LCP) etc. Rated Flowrate: 10 m3/hr. TDH: 100 MLC MOC: ASTM A48 CL 30 (Casing) / ASTM A351 CF8 (Impeller)
25Instrument Air System
26Oil Flooded, Rotary Screw type Compressor complete with electric motor, common baseplate or skid for compressor with all components, individual suction air filters, oil filter, air cooled intercooler & aftercooler, Auto drain traps with bypass valve, safety valves, instruments & controls, microprocessor based local control unit for each compressor etc. Capacity (each) / FAD : 200 Nm3/hr. (incl. purge air loss) Guaranteed output at package outlet terminal point : 170 Nm3/hr. Discharge Pressure at package outlet: 7 barg
27Vertical, cylindrical, dished end type air receiver (one at compressor discharge and two at dryer discharge) complete with manhole, pressure indicators, temperature indicators, automatic drain trap, block valves for instruments, manual drain line with valve etc. Capacity of Compressed Wet Air Receiver : Bidder to decide Capacity of each Instrument Dry Air Receiver : 5 m3 MOC: IS 2002 Gr. 2A/2B or IS 2062
28Heatless purge type air drier including twin towers with a pressure / temperature safety relief valve, pressure indicator, purge volume control valve, purge flow meter, silencer, thermostatic devices, dew point alarm and indication equipment, control and alarm circuit etc. Following items are also included: a) 1 (One) set of pre-filter for each drier including differential pressure indicator, automatic drain traps with bypass, and block valves for maintenance b) 1 (One) set of After-filter for each drier including differential pressure indicator, alarm, automatic drain traps with bypass, and block valves for maintenance c) 1 (One) relay based control system for Air Drier
29Supply of all integral piping including necessary internal pipes, fittings, instruments, drains and vents with isolation valve, supports within package unit
30Vapour Eliminators
31Vertical, Cylindrical type Vapour Eliminators to separate any carry over liquid in the incoming nitrogen gas supply including all necessary accessories. Design Pressure: 6 barg MOC: Carbon Steel (ASTM A516 Gr.70) Dimension (Approx.): 2 m (Dia) x 3.5 m (Height) Inlet: 16" Vapour Outlet: 10"
32Flame Arresters
33Vertical, inline Flame Arrestor Assembly complete with all necessary accessories (Suitable for Zone 2 Gas Group IIA/IIB, Temperature Class: T3) :
3410", 150#, MOC: Carbon Steel (Body) / Flame Element (SS 316L)
352", 150#, MOC: Carbon Steel (Body) / Flame Element (SS 316L)
36Air Operated Double Diaphragm Pump
37Portable Metallic Air Operated Double Diaphragm Pump with all necessary accessories. Housing: Carbon Steel Working Fluid: POL Capacity: 10000 LPH Discharge Head: 20 MLC
38Nitrogen System
39Design, Engineering, Manufacture & fabrication, Procurement of materials & bought out components,inspection, testing at manufacturer"s works, preparation of shipment / packing, transport, delivery of Nitrogen system comprising ofmodules of liquid Nitrogen storage tank with vaporisers as per Particular Technical Specification along with integral and interconnecting piping and instrumentation, civil foundations and installation cost. Note: The successful bidder shall get the entire design done and approved by IOCL prior to procurement and installation of Nitrogen Storage System.
40SECTION 2 : PIPING
41Supply of CS Seamless Pipes to API 5L Gr. X52, Dim. ASME B36.10
42750mm NB SCH THK. 10.3mm Bevel ends
43Supply of CS Seamless Pipes to ASTM A106 Gr.B, Dim. ASME B36.10
4425mm NB SCH S-80 Plain ends
4550mm NB SCH S-80 Bevel ends
4680mm NB SCH S-STD Bevel ends
47100mm NB SCH S-STD Bevel ends
48150mm NB SCH S-STD Bevel ends
49200mm NB SCH S-STD Bevel ends
50250mm NB SCH S-STD Bevel ends
51300mm NB SCH S-STD Bevel ends
52400mm NB SCH S-STD Bevel ends
53500mm NB SCH S-STD Bevel ends
54600mm NB SCH S-STD Bevel ends
55Supply of CS Seamless Pipes to ASTM A333 Gr.6, Dim. ASME B36.10
5625mm NB SCH S-160 Plain ends
57450mm NB SCH S-30 Bevel ends
58300mm NB SCH S-40 Bevel ends
5950mm NB SCH S-80 Bevel ends
60Supply of CS Galvanized Seamless Pipes to ASTM A106 Gr.B, Dim. ASME B36.10
6125mm NB SCH S-80 MTE
6225mm NB SCH S-80 PE X MTE 100 mm Long
6350mm NB SCH S-STD Bevel Ends
6480mm NB SCH S-STD Bevel Ends
65Supply of SSSeamless Pipes to ASTM A312 Gr.TP316L, Dim. ASME B36.19
6650mm NB SCH S-40S Bevel Ends
6725mm NB SCH S-40S Plain Ends
6825mm NB SCH S-40S Plain Ends X MTE 100 mm LONG
69PIPEFITTINGS: Supplying the following sizes of Elbows/ Tees/ Reducer made of seamless pipes with ends as per tender specifications for the following sizes Note: The fittings shall be Socket Welded for Sizes Less than 2" as per ASME B 16.11 and Bevel ends for 2" andabove and dimensions as per ASME B 16.9
7090 Deg BEND API5L Gr.X52 (Hot Pulled Bend fabricated out of supplied pipes)
71750mm NB SCH THK. 10.3mm
7290 Deg LR ElbowASTM A234 Gr.WPB
7325mm NB Class 3000
7450mm NB Class 3000
7580mm NB SCH S-STD
76100mm NB SCH S-STD
77150mm NB SCH S-STD
78200mm NB SCH S-STD
79250mm NB SCH S-STD
80300mm NB SCH S-STD
81400mm NB SCH S-STD
82500mm NB SCH S-STD
83600mm NB SCH S-STD
8490 Deg LR Elbow ASTM A420 Gr.WPL6
85450mm NB SCH S-30
86300mm NB SCH S-40
8750mm NB SCH S-80
8890 Deg LR Elbow ASTM A234 Gr.WPB (GALV.)
8925mm NB SCH S-80 MTE
9050mm NB SCH S-STD
9180mm NB SCH S-STD
9290 Deg LR ElbowASTM A403 Gr.WP316L
9325mm NB SCH S-40S
9450mm NB SCH S-40S
9545 Deg BEND API5L Gr.X52
96750mm NB SCH THK. 10.3mm
9745 Deg LR ElbowASTM A234 Gr.WPB
9850mm NB SCH S-80 Plain ends
99200mm NB SCH S-STD
100250mm NB SCH S-STD
101300mm NB SCH S-STD
102400mm NB SCH S-STD
10345 Deg LR ElbowASTM A420 Gr.WPL6
104450mm NB SCH S-30
10550mm NB SCH S-80
10645 Deg LR ElbowASTM A234 Gr.WPB (GALV.)
10750mm NB SCH S-STD
10880mm NB SCH S-STD
10945 Deg LR Elbow ASTM A403 Gr.WP316L
11050mm NB SCH S-40S
111Equal Tee ASTM A234 Gr.WPB
11250mm NB Class 3000
113100mm NB SCH S-STD
114150mm NB SCH S-STD
115250mm NB SCH S-STD
116300mm NB SCH S-STD
117400mm NB SCH S-STD
118600mm NB SCH S-STD
119Equal Tee ASTM A420 Gr.WPL6
120300mm NB SCH S-40
121Equal Tee ASTM A234 Gr.WPB (GALV.)
12280mm NB SCH S-STD
123Equal Tee ASTM A403 Gr.WP316L
12450mm NB SCH S-40S
125Reducing Tee ASTM A234 Gr.WPB
12650 X 15 mm NB CL 3000
12750 X 25 mm NB CL 3000
128100 X 50 mm NB S-STD x S-80
129150 X 80 mm NBS-STD x S-STD
130150 X 100 mm NBS-STD x S-STD
131200 X 100 mm NBS-STD x S-STD
132250 X 100 mm NBS-STD x S-STD
133300 X 200 mm NBS-STD x S-STD
134400 X 200 mm NBS-STD x S-STD
135600 X 400 mm NBS-STD x S-STD
136Reducing Tee ASTM A234 Gr.WPB (GALV.)
13750 X 25 mm NBS-STD x S-80
13880 X 50 mm NBS-STD x S-80
139Reducing Tee (1.5D) ASTM A403 Gr.WP316L
14050 X 25 mm NBS-40S x S-40S
141Concentric Reducer ASTM A234 Gr.WPB
142100 X 50 mm NB S-STD x S-80
143500 X 300 mm NBS-STD x S-STD
144600 X 500 mm NBS-STD x S-STD
145Concentric Reducer ASTM A420 Gr.WPL6
14650 X 25 mm NBS-80 x S-80
14780 X 50 mm NBS-80 x S-80
148Coupling ASTM A105
14925mm NB Class 3000 SWE
150Coupling ASTM A105 (GALV.)
15125mm NB Class 3000 FTE
15250mm NB Class 3000 FTE
153Coupling ASTM A182 Gr.F316L
15425mm NB Class 3000 SWE
155Plug ASTM A105 (GALV.)
15625mm NB Class 3000 FTE
15750mm NB Class 3000 FTE
158PIPEFITTINGS: Supplying the following sizes of Olets made of as per MSS SP 97 specifications for the following sizes
159SOCKOLET ASTM A105
160100 X 20 Class 3000
161100 X 25 Class 3000
162150 X 50 Class 3000
163300 X 25 Class 3000
164300 X 50 Class 3000
165600 X 40 Class 3000
166750 X 40 Class 3000
167SOCKOLETASTM A350 Gr.LF2
168300 X 40 Class 3000
169SOCKOLET ASTM A105 (GALV.)
17080 X 15 Class 3000
171Weldolet ASTM A105
172600 X 50 SCH S-80
173400 X 100 SCH S-STD
174600 X 80 SCH S-STD
175600 X 100 SCH S-STD
176WeldoletASTM A350 Gr.LF2
177300 X 50 SCH S-80
178Supply of following Socket Weld type - SWRF 125 AARH as per ASTM A105 DIM. ASME B16.5 Class 150
17925mm NB
18050mm NB
181Supply of following Socket Weld type - SWRF 125 AARH as per ASTM A350 Gr.LF2 DIM. ASME B16.5 Class 300
18225mm NB
183Supply of following Weld neck type- WNRF 125 AARH as per ASTM A105 DIM. ASME B16.5 Class 150
18480mm NB SCH S-STD
185100mm NB SCH S-STD
186150mm NB SCH S-STD
187200mm NB SCH S-STD
188250mm NB SCH S-STD
189300mm NB SCH S-STD
190400mm NB SCH S-STD
191500mm NB SCH S-STD
192600mm NB SCH S-STD
193Supply of following Weld neck type - WNRF 125 AARH as per ASTM A350 Gr.LF2 DIM. ASME B16.5 Class 150
19450mm NB SCH S-80
195Supply of following Weld neck type - WNRF 125 AARH as per ASTM A350 Gr.LF2 DIM. ASME B16.5 Class 300
196450mm NB SCH S-30
197300mm NB SCH S-40
19850mm NB SCH S-80
199Supply of following Weld neck type - WNRF 125 AARH as per ASTM A 694 Gr. F52 DIM. ASME B16.47 Series B Class 150
200750mm NB SCH THK. 10.3mm
201Supply of following Slip On type - SORF 125 AARH as per ASTM A105 (GALV.) DIM. ASME B16.5 Class 150
20250mm NB SCH S-STD
20380mm NB SCH S-STD
204Supply of following Weld neck type - WNRF 125 AARH as per ASTM A182-F316L DIM. ASME B16.5 Class 150
20550mm NB SCH S-40S
206Supply of following BLRF 125 AARH flanges as per ASTM A105 DIM. ASME B16.5 Class 150
20750mm NB
208100mm NB
209150mm NB
210300mm NB
211600mm NB
212Supply of following BLRF 125 AARH flanges as per ASTM A350 Gr.LF2 DIM. ASME B16.5 Class 150
21350mm NB
214Supply of following BLRF 125 AARH flanges as per ASTM A105 (GALV.) DIM. ASME B16.5 Class 150
21580mm NB
216Supply of following BLRF 125 AARH flanges as per ASTM A182-F316L DIM. ASME B16.5 Class 150
21750mm NB
218Supply of following GASKET, 4.5mm Thck Spiral Wound 316 Outer & Inner Ring with Graphite Filler, ASME B16.20, CLASS 150
21925mm NB
22050mm NB
22180mm NB
222100mm NB
223150mm NB
224200mm NB
225250mm NB
226300mm NB
227400mm NB
228500mm NB
229600mm NB
230750mm NB
231Supply of following GASKET, 4.5mm Thck Spiral Wound 316 Outer & Inner Ring with Graphite Filler, ASME B16.20, CLASS 300
23225mm NB
23350mm NB
234300mm NB
235450mm NB
236Supply of following HEXAGONAL NUT, ASTM A194 Gr.2H, ASME B18.2.2, FTE, Hot Dip Galvanized
2371" Dia
2381/2" Dia
2391-1/4" Dia
2401-1/8" Dia
2413/4" Dia
2425/8" Dia
2437/8" Dia
244Supply of following HEXAGONAL NUT, ASTM A194 Gr.8M, ASME B18.2.2, FTE
2455/8" Dia
246Supply of following STUD BOLT, ASTM A193 Gr.B7, ASME B18.2.1, MTE, Hot Dip Galvanized
2471" Dia150 MM LONG
2481/2" Dia75 MM LONG
2491-1/4" Dia185 MM LONG
2501-1/8" Dia175 MM LONG
2513/4" Dia110 MM LONG
2523/4" Dia120 MM LONG
2533/4" Dia200 MM LONG
2545/8" Dia100 MM LONG
2555/8" Dia95 MM LONG
2567/8" Dia130 MM LONG
2577/8" Dia135 MM LONG
2581-1/8" Dia160 MM LONG
2595/8" Dia95 MM LONG
260Supply of following STUD BOLT,ASTM A193 Gr.B8M CL.2, ASME B18.2.1, MTE
2615/8" Dia95 MM LONG
262Supplying the following sizes of CS Manual Ball Valves (ASTM A105 flanged # 800 ) as per Specification
26315 mm Dia
26425 mm Dia
26550 mm Dia
266Supplying the following sizes of CS Motor Operated Ball Valves (ASTM A 216WCB flanged # 150 ) as per Specification
267100 mm Dia
268150 mm Dia
269200 mm Dia
270250 mm Dia
271300 mm Dia
272Supplying the following sizes of CS Manual Globe Valves (ASTM A105 flanged # 800 ) as per Specification
27325 mm Dia
274Supplying the following sizes of CS Motor Operated Globe Valves (ASTM A 216WCB flanged # 150 ) as per Specification
275200 mm Dia
276250 mm Dia
277Supplying the following sizes of CS Manual Globe Valves (ASTM A 352 Gr. LCB flanged # 800 ) as per Specification
27825 mm NB
279Supplying the following sizes of CS Manual Ball Valves (ASTM A 352 Gr. LCB flanged # 150 ) as per Specification
28050 mm NB
281Supplying the following sizes of CS Manual Ball Valves (ASTM A 352 Gr. LCB flanged # 300 ) as per Specification
28250 mm NB
283Supplying the following sizes of SS Manual Ball Valves (ASTM A182 Gr. F316L flanged # 150 ) as per Specification
28425 mm NB
285Supplying the following sizes of SS Manual Globe Valves (ASTM A182 Gr. F316L flanged # 800 ) as per Specification
28625 mm NB
287Supplying the following sizes of SS Manual Ball Valves (ASTM A351 GR CF3 flanged # 150 ) as per Specification
28850 mm NB
289Supplying the following sizes of SS Manual Globe Valves (ASTM A351 GR CF3 flanged # 150 ) as per Specification
29050 mm NB
291Supplying the following sizes of CS Check Valves (ASTM A105 flanged # 800 ) as per Specification
29225 mm NB
293Supplying the following sizes of CS Check Valves (ASTM A216WCB flanged # 150 ) as per Specification
29450 mm Dia
295100 mm Dia
296200 mm Dia
297300 mm Dia
298600 mm Dia
299Supplying the following sizes of CS Excess Flow Check Valves (ASTM A 352 Gr. LCB flanged # 300 ) as per Specification
300300 mm dia
301Supply of Thermal relief valves (ASTM A 352 Gr. LCB flanged # 300 ) as per Specification
30225mm X 50mm Dia TRV
303Supply of Thermal relief valves (ASTM A 216WCB flanged # 150 ) as per Specification
30425mm X 50mm Dia TRV
305Supply of Pressure relief valves (ASTM A 216WCB flanged # 150 ) as per Specification
30650mm X 50mm Dia SRV
307100mm X 150mm Dia SRV
308Supplying the following sizes of CS Motor Operated Ball Valves (ASTM A216WCB flanged # 150 ) as per Specification
30950 mm Dia
310100 mm Dia
311150 mm Dia
312400 mm Dia
313600 mm Dia
314750 mm Dia
315Supplying the following sizes of CS Motor Operated Ball Valves (ASTM A 352 Gr. LCB flanged # 300 ) as per Specification
316300 mm Dia
317450 mm Dia
318600 mm Dia
319Supplying the following sizes of CS Motor Operated Globe Valves (ASTM A216WCB flanged # 150 ) as per Specification
320600 mm Dia
321Supplying the following sizes of CS Electro Hydraulic Butterfly Valves (ASTM A216WCB flanged # 150 ) as per Specification
322600 mm Dia
323Supplying the following sizes of CS Pneumatic Control Globe Valves (ASTM A216WCB flanged # 150 ) as per Specification
324250 mm Dia
325500 mm Dia
326Supplying the following sizes of CS Pneumatic Control Ball Valves (ASTM A 352 Gr. LCB flanged # 300 ) as per Specification
327300 mm Dia
328U-Bolt
32915 mm Dia
33025 mm Dia
33150 mm Dia
33280 mm Dia
333100 mm Dia
334TEFLON PAD ASSEMBLY
335ORIFICE PLATE 3MM & 6MM #300,
33680 mm Dia
337100 mm Dia
338SPECTACLE BLIND
33925 mm Dia
34050 mm Dia
34180 mm Dia
342100 mm Dia
343FLOW TEE
344Material :- ASTM A234 Gr.WPB (Pipe Material API5L Gr.X52,) Size : -DN 750 X DN 600 Schedule :- 10.3mm THK X STD
345SECTION 3 : ELECTRICAL
346Supply of 2 POLE STRUCTURE: 2 pole Structure including RSJs, ISMCs for 11 kV Incoming Power Supply with Gang operated isolator, D.O. fuse with base, lightning arrestors, earthing, padlocking for 2 Pole structure as per attached specification, data sheet including supply of commissioning spares, as required.
347Supply of HT Panel:
34811 kV, 630 A, 3 phase, 3 wire, 25 kA for 1 sec. rated switchgear with all accessories and spares as per single line diagram, specification and data sheet as attached with the tender document.
34911 kV, 630 A, 3 phase, 3 wire, 25 kA for 1 sec. rated single VCB cubicle (ICOG type panel) with all accessories and spares as per single line diagram , specification and data sheet as attached with the tender document.
350Distribution Transformer: Distribution of the following ratings as per attached specification, data sheetincluding supply of spares, as required.
351200 kVA, 11/0.433 kV dry type transformer with all fittings and accessories as per specification. Location: 5 acre plot substation room
352630 kVA, 11/0.433 kV dry type transformer with all fittings and accessories as per specification.Location : Substation room at jetty control building
353Supply of DG Set
354125 kVA, 415 V, 3 phase, 0.8 PF DG Set & AMF Panel with all fittings and accessories like lube oil system, cooling system, diesel oil system, all required piping, exhaust piping & support structure, day oil tank each along with all pipings with magnetic level switch,inter connecting cables and cable accessories, base channels etc. as per attached specification, data sheet & SLD including supply of spares, as required, First filling of engine oil, lubricant etc. The supply includes Residential silencer & spark arrestor. Location: DG Shed of 5 acre plot
355600 KVA, 415V, 3 phase, 0.8 PF DG Set & AMF Panel complete with all required accessories like lube oil system, cooling system, diesel oil system, all required piping, day oil tank along with all pipings with magnetic level switch,inter connecting cables and cable accessories, base channels etc. as per attached specification, data sheet & SLD including supply of spares, as required, First filling of engine oil, lubricant etc. The supply includes Residential silencer & spark arrestor. Location: DG Room at jetty control building
356Supply of MV & LV Switch board/Panels/Sub Distribution Boards.
357EPMCC Panel: 415 V, 400 A, 3 phase, 4 wire, 25 kA for 1 sec. rated Onshore EPMCC with all accessories and spares as per single line diagram, specification and data sheet. Location - 5 acre plot substation room
358EPMCC Panel: 415 V, 1250 A, 3 phase, 4 wire, 40 kA for 1 sec. rated Jetty EPMCC with all accessories and spares as per single line diagram, specification and data sheet. Location - Substation room at jetty control building
359Onshore ACDB: 415 V, 100 A, 3 phase, 4 wire, 25 kA for 1 sec. rated Onshore ACDB with all accessories as per single line diagram, specification and data sheet. Location - 5 acre plot substation room
360Jetty ACDB: 415 V, 200 A, 3 phase, 4 wire, 40 kA for 1 sec. rated Jetty ACDB with all accessories and spares as per single line diagram, specification and data sheet Location - Substation Room at Jetty Control Building
361MOV DB: 415 V, 200 A, 3 phase, 4 wire, 40 kA for 1 sec. rated MOV DB with all accessories and spares as per single line diagram, specification and data sheet Location - Substation room at Jetty Control Building
362HVAC DB: 415 V, 200 A, 3 phase, 4 wire, 40 kA for 1 sec. rated HVAC DB with all accessories and spares as per single line diagram, specification and data sheet Location - Substation room at Jetty Control Building
363APFC Panel: 25 kVAR, 415 V Capacitor bank with APFC as per specification, data sheet and single line diagram Location - Substation room at Jetty Control Building
364Supply of Lighting Distribution Board & Lighting Panel
365LDB: 415 V, 63 A, 3 phase, 4 wire, 10 kA for 1 sec. rated onshore area lighting DB with 25 kVA 0.415/0.433 kV lighting transformer and with all accessories as per specification. Incomer: 63 A, 3 phase, 1 No. Outgoing: 32 A, 3 phase, 6 Nos.. Location - 5 acre plot substation room
366LDB: 415 V, 100 A, 3 phase, 4 wire, 10 kA for 1 sec. rated jetty area lighting DB with 50 kVA 0.415/0.433 kV lighting transformer and with all accessories as per specification. Incomer: 100 A, 3 phase 1 No. Outgoing: 63 A, 3 phase 9 Nos. Location - Substation room at jetty control building
367LP: Indoor Non FLP type lighting panel as per specification with all accessories. Incomer: 32 A, 3 phase, 1 No.; Outgoing: 16 A, 1 phase, 6 Nos.
368LP: Indoor Non FLP type lighting panel as per specification with all accessories. Incomer: 63 A, 3 phase, 1 No.; Outgoing: 16 A, 1 phase, 9 Nos.
369LP: Outdoor FLP type (Ex-d, IIA/IIB, T3) as per specification with all accessories. Incomer: 63 A, 3 phase, 1 No.; Outgoing: 16 A, 1 phase, 9 Nos.
370LP: Outdoor Non FLP type as per specification with all accessories. Incomer: 63 A, 3 phase, 1 No.; Outgoing: 16 A, 1 phase, 9 Nos.
371Supply of UPS System
3722x100% 10 kVA, 240 V AC UPS with maintenance bypass and UPSDB for onshore area as per single line diagram, specification and data sheet (including supplying the required capacity of VRLA SMF type battery and spares for UPS) Location - 5 acre plot substation room
3732x100% 20 kVA, 230 V AC UPS with maintenance bypass and UPSDB for Jetty area as per single line diagram, specification and data sheet ( including supplying the required capacity of VRLA SMF type battery and spares for UPS ) Location- Substation room at Jetty Control Building
374SWITCH BOARD WORKS: Supplying Modular switch frame with inner and outer face plates and accessories as per following details of approved includingflush metal boxes/surface mounting boxes, plates, etc. all complete as per manufacturer"s specification and direction of PMC Engineer/ Owner.
375Flush mounted “ON/OFF’ switch board made of 16SWG GI concealed sheet metal box with Cover of reputed make consisting of following items as per manufacturer"s specification and direction of PMC Engineer/ Owner. note: All switch/socket mentioned below are indicative, however,Bidder has to supply the switch/socket as per requirement.
3763 modular switch frame including 6A, 1 No. 3 pin socket, as per specifications and direction of PMC Engineer/ Owner.
3776 modular switch frame including 6A, 1 No. 3 pin socket, as per specifications and direction of PMC Engineer/ Owner.
3789 modular switch frame including 6A, 1 No. 3 pin socket, as per specifications and direction of PMC Engineer/ Owner.
379GI & Stainless steel Prefabricated Ladder/Perforated Type Cable Tray & other cable raceway material
380Supply of the following cable tray material including supply of coupler plates, nut, bolts, saddle, clamps, welding rods and other fixing accessories as per specification
381600 (W) x 100 (H) ladder type GI cable tray
382600 (W) x 100 (H) perforated type GI cable tray
383300 (W) x 100 (H) ladder type GI cable tray
384300 (W) x 100 (H) perforated type GI cable tray
385150 (W) x 50 (H) ladder type GI cable tray
386150 (W) x 50 (H) perforated type GI cable tray
38750 (W) x 50 (H) perforated type GI cable tray
388600 (W) x 100 (H) ladder type Stainless steel cable tray
389600 (W) x 100 (H) perforated type Stainless steel cable tray
390300 (W) x 100 (H) ladder type Stainless steel cable tray
391300 (W) x 100 (H) perforated type Stainless steel cable tray
392150 (W) x 50 (H) ladder type Stainless steel cable tray
393150 (W) x 50 (H) perforated type Stainless steel cable tray
39450 (W) x 50 (H) perforated type Stainless steel cable tray
39590 degree Vertical bend for 600 (W) x 100 (H) ladder type GI cable tray
39690 degree Vertical bend for 600 (W) x 100 (H) perforated type GI cable tray
39790 degree Vertical bend for 300 (W) x 100 (H) ladder type GI cable tray
39890 degree Vertical bend for 300 (W) x 100 (H) perforated type GI cable tray
39990 degree Vertical bend for 150 (W) x 50 (H) ladder type GI cable tray
40090 degree Vertical bend for 150 (W) x 50 (H) perforated type GI cable tray
40190 degree Vertical bend for 600 (W) x 100 (H) ladder type Stainless steel cable tray
40290 degree Vertical bend for 600 (W) x 100 (H) perforated type Stainless steel cable tray
40390 degree Vertical bend for 300 (W) x 100 (H) ladder type Stainless steel cable tray
40490 degree Vertical bend for 300 (W) x 100 (H) perforated type Stainless steel cable tray
40590 degree Vertical bend for 150 (W) x 50 (H) ladder type Stainless steel cable tray
40690 degree Vertical bend for 150 (W) x 50 (H) perforated type Stainless steel cable tray
40790 degree Horizontal bend for 600 (W) x 100 (H) ladder type GI cable tray
40890 degree Horizontal bend for 600 (W) x 100 (H) perforated type GI cable tray
40990 degree Horizontal bend for 300 (W) x 100 (H) ladder type GI cable tray
41090 degree Horizontal bend for 300 (W) x 100 (H) perforated type GI cable tray
41190 degree Horizontal bend for 150 (W) x 50 (H) ladder type GI cable tray
41290 degree Horizontal bend for 150 (W) x 50 (H) perforated type GI cable tray
41390 degree Horizontal bend for 600 (W) x 100 (H) ladder type Stainless steel cable tray
41490 degree Horizontal bend for 600 (W) x 100 (H) perforated type Stainless steel cable tray
41590 degree Horizontal bend for 300 (W) x 100 (H) ladder type Stainless steel cable tray
41690 degree Horizontal bend for 300 (W) x 100 (H) perforated type Stainless steel cable tray
41790 degree Horizontal bend for 150 (W) x 50 (H) ladder type Stainless steel cable tray
41890 degree Horizontal bend for 150 (W) x 50 (H) perforated type Stainless steel cable tray
419Tee for 600 (W) x 100 (H) ladder type GI cable tray
420Tee for 600 (W) x 100 (H) perforated type GI cable tray
421Tee for 300 (W) x 100 (H) ladder type GI cable tray
422Tee for 300 (W) x 100 (H) perforated type GI cable tray
423Tee for 150 (W) x 50 (H) ladder type GI cable tray
424Tee for 150 (W) x 50 (H) perforated type GI cable tray
425Tee for 600 (W) x 100 (H) ladder type Stainless steel cable tray
426Tee for 600 (W) x 100 (H) perforated type Stainless steel cable tray
427Tee for 300 (W) x 100 (H) ladder type Stainless steel cable tray
428Tee for 300 (W) x 100 (H) perforated type Stainless steel cable tray
429Tee for 150 (W) x 50 (H) ladder type Stainless steel cable tray
430Tee for 150 (W) x 50 (H) perforated type Stainless steel cable tray
431Pre-fabricated cover for 600 (W) x 100 (H) tray
432Pre-fabricated cover for 300 (W) x 100 (H) tray
433Pre-fabricated cover for 150 (W) x 50 (H) tray
434ISA 50x50x6
435ISMC 100
4366 mm thick chequred plate
437MCT block with wall frame assembly for 11/11 kV 3Cx240 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
438MCT block with wall frame assembly for 1kV 2Cx2.5 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
439MCT block with wall frame assembly for 1kV 2Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
440MCT block with wall frame assembly for 1kV 3Cx2.5 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
441MCT block with wall frame assembly for 1kV 3Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
442MCT block with wall frame assembly for 1kV 4Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
443MCT block with wall frame assembly for 1kV 3Cx16 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
444MCT block with wall frame assembly for 1kV 4Cx16 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
445MCT block with wall frame assembly for 1kV 3.5Cx35 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
446MCT block with wall frame assembly for 1kV 3Cx50 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
447MCT block with wall frame assembly for 1kV 3.5Cx50 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
448MCT block with wall frame assembly for 1kV 3.5Cx70 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
449MCT block with wall frame assembly for 1kV 3Cx120 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
450MCT block with wall frame assembly for 1kV 3Cx240 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
451MCT block with wall frame assembly for 1kV 1Cx400 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
452MCT block with wall frame assembly for 1kV 3Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
453MCT block with wall frame assembly for 1kV 5Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
454MCT block with wall frame assembly for 1kV 12Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
455Supply of Fire sealing compound
456Outdoor Lighting: note: The successful tenderer shall make use of the items under this section and obtain design sufficiency from the electrical lighting & luminaire manufactures for achieving necessary lighting lux level at various areas as per the OISD requirements. Galvanisation is 610 gms/sq. mtr
457Supply of High Mast and Street Light Pole
458Hot dip galvanised High Mast lighting tower (30m height) including foundation bolts, all accessories including 16 Nos x 350 watt LED fixture with lamp, head frame, Twin Aviation Obstruction lamps, Lightening Arrestor with down conductors, stainless steel rope, double drum winch, junction boxes, FLP plugs and sockets, FLP Feeder box, galvanised lantern carrier arrangement, Lighting fixtures, double compression steel glands and accessories, tinned copper cable lugs of suitable size and type, cables and cable accessories from light fittings upto FLP feeder box etc. as per specification an standard installation details including supply of commissioning spares, as required.
4599 Mtr GI street Lighting Pole(Octagonal or polygonal section; Galvanisation of610 gms/sq. mtr) for ground mounting, complete with base plate, foundation bolts, all accessories, weather proof JBs at the foot of the pole & terminal block (as applicable), Zinc passivated hardware for fixtures support & pole support, GI pipe for cable (Class B) protection, clamps, nuts, bolts, etc. including supply of commissioning spares, as required as per specification and standard installation details.
4604.5 Mtr Swan Neck GI Lighting Pole (50mm as per IS 1239 - Medium duty; Galvanisation of 610 Gms/ sqm)for structural mounting, complete with all clamping arrangements for cables including accessories, Zinc passivated hardware for fixtures support & pole support, clamps, nuts, bolts, etc. including supply of commissioning spares, as per specification, data sheet and standard installation details.
461Supply of Junction Box
462Two way FLP type junction boxes as per specification including the glands, lugs and terminal blocks of required cable size. (Max. incoming cable size 3.5Cx70 sq. mm, Max. outgoing Cable size 3Cx6 sq. mm )
463Three way FLP type junction boxes as per specificationincluding the glands, lugs and terminal blocks of required cable size. (Max. incoming cable size 3.5Cx70 sq. mm, Max. outgoing Cable size 3Cx6 sq. mm )
464Four way FLP type junction boxes as per specification including the glands, lugs and terminal blocks of required cable size. (Max. incoming cable size 3.5Cx70 sq. mm, Max. outgoing Cable size 3Cx6 sq. mm )
465Supply of Local Control Station
466Flameproof (Ex’d’) Local Control Station with components as listed below and with Aluminium alloy (LM6 grade) enclosure as per Specification, Data Sheet and direction of PMC Engineer/ Owner.
467With Start and Emergency Stop Push Button and Ammeter
468With Start and Emergency Stop Push Button
469Supply of Non FLP Local Control Station with components as listed below and with sheet steel enclosure as per Specification, Data Sheet and direction of Engineer-in-charge.
470With Start and Emergency Stop Push Button and Ammeter
471With Start and Emergency Stop Push Button
472Supply of FLP & Non FLP type Switch Socket & Plug
473Supply of FLP Interlocking type switch sockets and plugs as per attached specifications & data sheets. All switch sockets shall be provided with 3mm thick FRP caNopy with side cover and FLP stopping plug as per specification and direction of PMC Engineer/ Owner.
474415V, 3 phase 63A FLP switch socket and plug suitable for 3.5CX95 Sq.mm. cable entry
475415V, 3 phase 63A Non FLP switch socket and plug suitable for 3.5CX95 Sq.mm. cable entry
476240 V, 1 phase, 5/15A,FLP Switch Socket and plug and suitable for 3 C x 4 sqmm cable entry
477240 V, 1 phase, 5/15A,Non FLP Switch Socket and plug and suitable for 3 C x 4 sqmm cable entry
478Supply of Other Lighting Material
479Heavy duty PVC Coduits - 19 mm for concealed wiring as per specification
480Heavy duty PVC Coduits - 25 mm for concealed wiring as per specification
481Rigid steel Coduits - 19 mm for exposed wiring for fire water pump house and wire house as per specification
482Rigid steel Coduits - 25 mm for exposed wiring for fire water pump house and wire house as per specification
483Flexible PVC conduit
484Flexible steel conduit
4853 way Circular JB/pull box as per specification
4864 way Circular JB/pull box as per specification
487Ceiling Fan
4881200mm Sweep ceiling Fan with Down Rod
489Regulator for sweep ceiling Fan
490900mm Sweep ceiling Fan with Down Rod
491300mm. Sweep Wall Fan
492Supply of HT/ LT Power and Control cables with Aluminium / Copper conductor XLPE insulated FRLS/FS armoured cables of different voltage grade and types of the following sizes in directly buried / supported on structure / pull through pipes including supply and fixing of strip number tags, supply and fixing of clamps, saddles and saddle bars, etc., including transportation from store/yard to site at the place of installation, unpacking, including all labour and materials, as per approved drawings, specifications of this tenderand directions of PMC Engineer/ Owner.
49311 kV (UE) armoured, XLPE, FRLS Power Cable of following size:-
49411/11 kV 3Cx240 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
4951.1 KV Grade, Armoured, XLPE, FRLS Aluminium/ Copper Power Cable of following sizes:
4961kV 1Cx400 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
4971kV 3.5Cx70 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
4981kV 3.5Cx50 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
4991kV 3.5Cx35 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
5001kV 4Cx16 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5011kV 4Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5021kV 3Cx240 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
5031kV 3Cx50 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
5041kV 3Cx16 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5051kV 3Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5061kV 3Cx2.5 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5071kV 2Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5081kV 2Cx2.5 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5091.1 KV Grade, Armoured, PVC, FRLS Copper Control Cable of following sizes
5101kV 12Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
5111kV 7Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
5121kV 5Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
5131kV 3Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
5141.1 KV XLPE, FRLS Lighting Cable / Flexible cable/ Wires of following size
5153Cx2.5 (CU) PVC FLEXIBLE cable(unarmoured)
5161Cx2.5(CU) FRLS PVC WIRE
5171.1kV, XLPE, FS armoured, Cable of following size:-
5181kV 2Cx2.5 sq. mm Cu FS cable
5191kV 3Cx6 sq. mm Cu FS cable
5201kV 3Cx120 sq. mm Al FS cable
521Supply of Double compression, weather proof (Non FLP), brass cable glands suitable for following XLPE/PVC , FRLS cable sizes & as per relevant IS for Indoor/outdoor use.
5221.1 KV Grade, Armoured, XLPE, FRLS Aluminium/ Copper Power Cable of following sizes:
5231kV 1Cx400 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
5241kV 3.5Cx70 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
5251kV 3.5Cx50 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
5261kV 3.5Cx35 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
5271kV 4Cx16 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5281kV 4Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5291kV 3Cx240 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
5301kV 3Cx50 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
5311kV 3Cx16 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5321kV 3Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5331kV 3Cx2.5 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5341kV 2Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5351kV 2Cx2.5 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5361.1 KV Grade, Armoured, PVC, FRLS Copper Control Cable of following sizes
5371kV 12Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
5381kV 7Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
5391kV 5Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
5401kV 3Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
5411.1kV, XLPE, FS armoured, Cable of following size:-
5421kV 2Cx2.5 sq. mm Cu FS cable
5431kV 3Cx6 sq. mm Cu FS cable
5441kV 3Cx120 sq. mm Al FS cable
545Supply of FLP double compression brass Cable Gland for hazardous area
5461.1 KV Grade, Armoured, XLPE, FRLS Aluminium/ Copper Power Cable of following sizes:
5471kV 3.5Cx70 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
5481kV 3.5Cx50 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
5491kV 3.5Cx35 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
5501kV 4Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5511kV 3Cx50 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
5521kV 3Cx16 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5531kV 3Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5541kV 3Cx2.5 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5551kV 2Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5561kV 2Cx2.5 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
5571.1kV armoured XLPE, FRLS Control Cable of following size:-
5581kV 12Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
5591kV 7Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
5601kV 5Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
5611kV 3Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
5621.1kV armoured XLPE, FRLS Lighting Cable of following size:-
5633CX2.5 SQMM Cu
564Supply of HT End Termination & Jointing Kit
565Heat shrinkable end termination kit/jointing kit suitable for 11 kV (UE) XLPE, FRLS armoured cables of following sizes.
566Outdoor type heat shrinkable termination kit for 11/11 kV 3Cx240 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
567Indoor type heat shrinkable termination kit for 11/11 kV 3Cx240 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
568Jointing kit for 11/11 kV 3Cx240 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
569Supply of GI Pipe for cable Protection Class-B Galvanized Iron (G.I. pipes) complete with accessories (bends, reducers, couplers etc.) of following sizes:-
570150 mm NB
571100 mm NB
57275 mm NB
57350 mm NB
57425 mm NB
575Earth Pit: Supplying earth pit material as per IS-3043 standard specifications with following sizes medium quality, Class-B, GI pipe ( 65mm dia, 3 mtr. long continuous pipe and Not welded in parts) fabricated as per IS. The job includes supply of charcoal or coke dust mixed with salt clay (salt 0.5%) including all hardware, accessories as per specifications and drawings
576Earth Pit for electronic earthing: Supplying 600x600x3 copper plate earth pit material as per IS-3043 standard specifications. The job includes supply of charcoal or coke dust mixed with salt clay (salt 0.5%) including all hardware, accessories as per specifications and drawings
577Supply of Hot Dip Galvanized G.I./Cu earth strips (Galvanisation of 610 gm/ sqm of exposed area), PVC insulated Cu cable of following sizes for earthing and lightning protection.
57850x6 mm GS flat as main earth grid conductor and earthing of major equipment
57950x6 mm Cu flat as earthing conductor for coonection with pile reinforment bar which will act as earth grid termination with sea water
5808 SWG Solid GI Wire
58110MM GI wire rope
58235X6 mm GI Flat for earthing & lightning protection conductor
58325 sq.mm. Braided Cu Flexible Cable
584Hot dip galvanized GI earth bus bar of size 400 X 75X 6 thick with fixing materials as per Drg.
58525 mm dia 1 m long GI rod for vertical air termination
586Flexible cable for static earth - 20 m long 25 sq. mm flexible Cu cable with lug at one end and crocodile clip at other end
587Test Linkboxfor lightning protection
588SAFETY ITEMS: Supply & installation of Following items for electrical and general safety
58911kV, 1000mm wide, electric grade floor rubber mat conforming to relevant IS. ISI mark to be available on rubber mat.
5901.1KV, 1000mm wide, electric grade floor rubber mat (in pieces of length Not less than 2 mtrs.) conforming to relevant IS:15652. ISI mark shall be there on rubber mat.
591Discharge rod (11kV) telescopic fiber glass heavy duty with necessary earthing facilities & wires.
592Shock treatment chart ( laminated type) as per IS:5216 in trilingual language (Hindi /English/Tamil) duly laminated on a hard back ground to be hung at various places
593Rubber Hand Glovesof 11kV grade
594Rubber Hand Glovesof 1.1kV grade
595Vitreous enamel caution boards (HINDI/ ENGLISH/TAMIL) as per IS 2551
59611000 V
597440 V
598Firstaidboxof GI as per IS:13115, 18 SWG sheetwith necessaryitems.
599LED Lighting Fixtures & Accessories
600Supply of Weather proof Lighting Fixtures, Lamps & accessories as per specifications. (All Lighting fixtures shall be provided with required No. of double compression cable glands and stopper plugs as required including tinned copper cable lugs of suitable type for termination)
60140W Linear LED Light (Bajaj Cat No.- BLTRU 40W VIVA or approved equivalent)
60236W Planner Recess Mounting Type LED Light suitable for false celling ( Bajaj BCTBLR 36W LED or approved equivalent)
603100W High bay LED Fitting (BAJAJ 13499 BGHB 100W future or approved equivalent)
6043W Single Side Display LED EXIT with ARROW (with 2HR. Battery backup)
60510W LED Suspended Mounting Weatherproof Bulkhead Luminaries(BAJAJ BIBWP 10W LED or approved equivalent)
60620W LED surface mounted Normal Luminaries(PHILIPS SM134VPSD W60L60 or approved equivalent)
60730W Peripheral LED Light ( Bajaj Cat No.- BCLST 30W LED or approved equivalent)
608100 W LED street light type fixture as per specification ( Bajaj Cat No.- BRTFG 100W LED I or approved equivalent)
609120 W LED Flood Light (Bajaj Cat No- BAR FEG 120 W or approved equivalent) including all accessories
610Flame proof Lighting Fixture & Accessories
61150W LED Well glass Light fittings ( Baliga Cat. No.-FLPW-1245L LED 50W or approved equivalent)
61236 W surface mounted flameproof type LED fixture (NoTON cat. No.TFC 6135Z NoTON-TUFFLITE IP66 or approved equivalent)
613Supply of Solar Power Generation System
614Design, Detail Engineering, Supply of required equipment and material for solar power generation system using a plot of 50 m x 20 m as per specification (Doc No. P.011265-E-11097-01 ) and single line diagram (Drg. No. P.011265-E-21004-001). Minimum Power generation: 100 kWpeak Location - 5 acre plot
615SECTION 4 : FIREFIGHTING
616Supply of Remote Controlled Tower mounted water cum foam monitor (UL Listed) with Fire Proof Structure (25 m high) as per specifications and data sheets Flowrate: 2000 GPM
617Complete Foam System including Vertical Cylindrical, coned bottom type Foam Tanks (2 x 12 m3 capacity each), 2 Nos. Electric motor driven Rotary Gear type Foam Pumps of 600 LPM Capacity & 15 bar head, Inline Balanced Pressure Proportioner (4 Nos.), 1 (one) No. Foam Filling Pump (25 m3/hr. capacity & 20 MLC head), 1 (one) No. flexible hose of 15 m length, piping, fittings, valves, instruments, etc. complete
618Vertical Wet Pit type, Diesel Engine Driven Fire Water Pumps of Capacity950 m3/hr & TDH 120 MLC including water cooled diesel engine, fuel piping, fuel tank, lube oil system, air intake system, industrial silencer, exhaust piping with insulation & aluminium cladding, caisson pipe, companion flanges, air release valve, PRV, controller with pressure sensing line with two check valves, etc. Design Standard: NFPA 20 Casing Material: Duplex SS Main FW Pumps shall be Non-UL Listed/ Non-FM Approved type.
619Vertical Wet Pit type, Electric Motor driven Jockey Pumps of Capacity 190 m3/hr & TDH 125 MLC including drive motor, starter, caisson pipe, companion flanges, air release valve, controller with pressure sensing line with two check valves, etc. Design Standard: NFPA 20 Casing Material: Duplex SS Jockey Pumps shall Not be UL Listed.
620Supply of Jumbo Curtain Nozzles on the unloading platform. Discharge Capacity: 6000 LPM @ 7 kg/cm2 g Working Pressure Range: 7 - 11 kg/cm2 g Horz. Traverse / Vertical Traverse: 40/15 m Angle of Spray: 180 Deg MOC: SS 316
621Supply of two numbers single outlet landing valve of size 63 mm diaas per IS:5290, Type-A of SS material including supply and Installation of stand post of size 100 NB with pipe, elbow, cross, RF pad Plate (for pipe to pipe connection) and necessary fittings & flanges including connecting / welding / installing the same in hydrant.
622Centralized Clean Agent (Novec 1230) based suppression system including Cylinders, cylinder racks, manifolds, Gas Release Panel, Nozzles, MRS, Abort Switch, pipes, fittings, valves etc. as per NFPA 2001 for the following Rooms: Jetty Control Building: a) Battery Room (Min. Risk Volume - 104 m3) b) Laboratory Room (Min. Risk Volume - 150 m3) c) UPS Room (Min. Risk Volume - 170 m3) d) Equipment Room (Min. Risk Volume - 240 m3) e) Control Room (Min. Risk Volume - 336 m3)
623Supply of Valves
624Supplying the following sizes of SS Manual Ball Valves (ASTM A182 F316L flanged # 800 ) as per Specification
62515 mm dia
62620 mm dia
62725 mm dia
62850 mm dia
629Supplying the following sizes of SS Manual Ball Valves (ASTM A351 GR CF3M flanged # 150 ) as per Specification
630100 mm dia
63165 mm dia
63280 mm dia
633Supplying the following sizes of CS Glass Flake Lining Manual Butterfly Valves (ASTM A216 WCB flanged # 150) as per Specification
634100 mm dia
635150 mm dia
636250 mm dia
637350 mm dia
638Supplying the following sizes of CS Glass Flake Lining Motorized Butterfly Valves (ASTM A216 WCB flanged # 150) as per Specification
639200 mm dia
640400 mm dia
641Supplying the following sizes of SSMotorized Globe Valves (ASTM A351 CF3M flanged # 150 ) as per Specification
642100 mm dia
643Supplying the following sizes of SS Pneumatic Ball Valves (ASTM A351 GR CF3M flanged # 150 ) as per Specification
64480 mm dia
645Supplying the following sizes of Duplex SS Manual Gate Valves (ASTM A182 F51 flanged # 800 ) as per Specification
64650 mm dia
647Supplying the following sizes of CS Check Valves Glass Flake Lining (ASTM A216 WCB flanged # 150 ) as per Specification
648150 mm dia
649350 mm dia
650Supplying the following sizes of SS Check Valves (ASTM A351 GR CF3M flanged # 150 ) as per Specification
65150 mm dia
65280 mm dia
653Supply of Pressure relief valves (ASTM A 182 F316L flanged # 150 ) as per Specification
65450mm X 25mm dia SRV
655Seamless & Welded Pipes
656Supply of Duplex SS Seamless Pipes to ASTM A790 S318032, Dim. ASME B36.10
65715 mm NB SCH S-40S Plain ends
65825 mm NB SCH S-40S Plain ends
65950 mm NB SCH S-40S Bevel ends
66080 mm NB SCH S-10S Bevel ends
661Supply of CS Seamless Pipes to ASTM A106 Gr.B Poly Glass Flake Lining, Dim. ASME B36.10
662100mm NB SCH S-STD Bevel ends
663150mm NB SCH S-STD Bevel ends
664200mm NB SCH S-STD Bevel ends
665250mm NB SCH S-STD Bevel ends
666350mm NB SCH S-STD Bevel ends
667400mm NB SCH S-STD Bevel ends
668600mm NB SCH S-STD Bevel ends
669Supply of SS Seamless Pipes to ASTM A312 Gr.TP 316L, Dim. ASME B36.19
67015mm NB SCH S-40S Plain Ends
67120mm NB SCH S-40S Plain Ends
67225mm NB SCH S-40S Plain Ends
67350mm NB SCH S-40S Bevel Ends
67480mm NB SCH S-10S Bevel Ends
675100mm NB SCH S-10S Bevel Ends
676PIPEFITTINGS: Supplying the following sizes of Elbows/ Tees/ Reducer made of seamless pipes with ends as per enclosed specifications for the following sizes note: The fittings shall be Socket Welded for Sizes Less than 2" as per ASME B 16.11 and Bevel ends for 2" andabove and dimensions as per ASME B 16.9
67790 Deg LR ElbowASTM A182 F51
67815mm NB Class 3000
67925mm NB Class 3000
68090 Deg LR ElbowASTM A815 WPS31803
68150mm NB SCH S-10S
68280mm NB SCH S-10S
68390 Deg LR ElbowASTM A234 Gr.WPB Poly Glass Lined
684100mm NB SCH S-STD
685150mm NB SCH S-STD
686200mm NB SCH S-STD
687250mm NB SCH S-STD
688350mm NB SCH S-STD
689400mm NB SCH S-STD
690600mm NB SCH S-STD
69190 Deg LR ElbowASTM A403 Gr.WP316L
69215mm NBClass 3000
69350mm NB SCH S-40S
69480mm NB SCH S-10S
695100mm NB SCH S-10S
69645 Deg LR ElbowASTM A182F51
69725mm NB Class 3000
69845 Deg LR Elbow ASTM A234 Gr.WPB Poly Glass Lined
699200mm NB SCH S-STD
700600mm NB SCH S-STD
70145 Deg LR ElbowASTM A403 Gr.WP316L
70250mm NB SCH S-40S
70380mm NB SCH S-10S
704Equal Tee ASTM A815WPS31803
70550mm NB SCH S-10S
70680mm NB SCH S-10S
707Equal Tee ASTM A234 Gr.WPB Poly Glass Lined
708100mm NB SCH S-STD
709150mm NB SCH S-STD
710250mm NB SCH S-STD
711Equal Tee ASTM A403 Gr.WP316L
71250mm NB SCH S-40S
71380mm NB SCH S-10S
714100mm NB SCH S-10S
715Reducing Tee ASTM A234 Gr.WPB Poly Glass Lined
716100 X 50 mm NBS-STD x S-STD
717100 X 80 mm NBS-STD x S-STD
718150 X 100 mm NBS-STD x S-STD
719350 X 200 mm NBS-STD x S-STD
720350 X 250 mm NBS-STD x S-STD
721400 X 200 mm NBS-STD x S-STD
722600 X 350 mm NBS-STD x S-STD
723600 X 400 mm NBS-STD x S-STD
724Reducing TeeASTM A403 Gr.WP 316L
72550 X 20 mm NBS-40S x S-40S
72680 X 5 mm NBS-10S x S-40S
727Concentric Reducer ASTM A182 F51
72825 X 15 mm NB Class 3000
729Concentric Reducer ASTM A815 WPS31803
73050 X 25 mm NB S-40S x S-40S
731Concentric Reducer ASTM A234 Gr.WPB Poly Glass Lined
732100 X 50 mm NBS-STD x S-STD
733150 X 100 mm NBS-STD x S-STD
734350 X 200 mm NBS-STD x S-STD
735350 X 250 mm NBS-STD x S-STD
736Concentric Reducer ASTM A182 Gr.F316L
73750 X 25 mm NB S-40S x S-40S
738Concentric Reducer ASTM A403 Gr.WP316L
73980 X 50 mm NB S-10S x S-40S
740100 X 50 mm NB S-10S x S-40S
741Coupling ASTM A182F51
74225mm NB Class 3000 SWE
743Union ASTM A182F51
74425mm NB Class 3000 FTE
745Cap ASTM A815WPS31803
74650 mm NB SCH S-40S Bevel ends
747PIPEFITTINGS: Supplying the following sizes of Olets made of as per MSS SP 97 specifications for the following sizes
748SOCKOLET ASTM A182 Gr. F316L
74950 X 15 Class 3000
75050 X 20 Class 3000
75180 X 15 Class 300
75280 X 20 Class 3000
75380 X 50 Class 3000
754100 X 15 Class 3000
755100 X 20 Class 3000
756Weldolet ASTM A105 Poly Glass Lining
757150 X 50 SCH S-STD
758200 X 50 SCH S-STD
759350 X 50 SCH S-STD
760350 X 100 SCH S-STD
761400 X 150 SCH S-STD
762600 X 50 SCH S-STD
763600 X 100 SCH S-STD
764600 X 150 SCH S-STD
765600 X 200 SCH S-STD
766ThreadoletASTM A182 Gr.F51
76750 X 15 Class 3000
76880 X 25 Class 3000
769Supply of following Socket Weld type- SWRF 125 AARH as perASTM A182 Gr.F51 DIM. ASME B16.5 Class 150
77015mm NB
77125mm NB
77250mm NB
773Supply of following Socket Weld type- SWRF 125 AARH as perASTM A182 Gr.F316L DIM. ASME B16.5 Class 150
77415mm NB
77520mm NB
776Supply of following Socket Weld type- SWRF 125 AARH as perASTM A182 Gr.F316L DIM. ASME B16.5 Class 300
77725mm NB
77850mm NB
779Supply of following Weld neck type- WNRF 125 AARH as per ASTM A182 Gr.F51 DIM. ASME B16.5 Class 150
78080mm NB SCH S-10S
781Supply of following Weld neck type- WNRF 125 AARH as per ASTM A105 DIM. ASME B16.5 Class 150 Poly Glass Lined
782100mm NB SCH S-STD
783150mm NB SCH S-STD
784200mm NB SCH S-STD
785250mm NB SCH S-STD
786350mm NB SCH S-STD
787400mm NB SCH S-STD
788600mm NB SCH S-STD
789Supply of following Weld neck type- WNRF 125 AARH as per ASTM A182 Gr.F316L DIM. ASME B16.5 Class 150
79050mm NB SCH S-40S
791100mm NB SCH S-10S
792Supply of following Weld neck type- WNRF 125 AARH as per ASTM A182 Gr.F316L DIM. ASME B16.5 Class 300
79380mm NB SCH S-10S
794Supply of following BLRF 125 AARH flanges as per ASTM A182 Gr.F316L DIM. ASME B16.5 Class 150
795100mm NB
796Supply of following BLRF 125 AARH flanges as per ASTM A182 Gr.F51 DIM. ASME B16.5 Class 150
79750mm NB
798Supply of following Orifice Flange WNRF 125 AARH flanges as per ASTM A182 F316L DIM. ASME B16.36 Class 300
79980mm NB
800Supply of following GASKET, 4.5mm Thck Spiral Wound 316 Outer & Inner Ring with Graphite Filler, ASME B16.20, CLASS 150
80115mm NB
80220mm NB
80325mm NB
80450mm NB
80580mm NB
806100mm NB
807150mm NB
808200mm NB
809250mm NB
810350mm NB
811400mm NB
812600mm NB
813Supply of following GASKET, 4.5mm Thck Spiral Wound 316 Outer & Inner Ring with Graphite Filler, ASME B16.20, CLASS 300
81425mm NB
81550mm NB
81680mm NB
817Supply of following HEXAGONAL NUT, ASTM A194 Gr.2H, ASME B18.2.2, FTE, Hot Dip Galvanized
8181" Dia
8191-1/4" Dia
8203/4" Dia
8215/8" Dia
8227/8" Dia
823Supply of following HEXAGONAL NUT, ASTM A194 Gr.3M, ASME B18.2.2, FTE
8241/2" Dia
8255/8" Dia
826Supply of following STUD BOLT, ASTM A193 Gr.B7, ASME B18.2.1, MTE, Hot Dip Galvanized
8271" Dia150 MM LONG
8281-1/4" Dia 185 MM LONG
8293/4" Dia 110 MM LONG
8303/4" Dia 120 MM LONG
8315/8" Dia 100 MM LONG
8327/8" Dia 130 MM LONG
833Supply of following STUD BOLT,ASTM A193 Gr.B8M CL.2, ASME B18.2.1, MTE
8341/2" Dia 65 MM LONG
8351/2" Dia 75 MM LONG
8365/8" Dia95 MM LONG
8375/8" Dia100 MM LONG
838Supply of following STUD BOLT,ASTM A193 Gr.B3M, ASME B18.2.1, MTE
8391/2" Dia 65 MM LONG
8401/2" Dia 75 MM LONG
8413/4" Dia120 MM LONG
8425/8" Dia95 MM LONG
8435/8" Dia85 MM LONG
8445/8" Dia100 MM LONG
845Supply of Deluge Valve System
846150 NB Deluge Valve Assembly
847Supply of Ni-Al Bronze deluge valve system including its pnuematic trim and DV shall be auto reset type. Each Deluge valve system shall consist of following:
848Pneumatically actuated flange type Ni-Al Bronze deluge valves suitable for seawater application
84915 NB Gunmetal Non-return valve Spring loaded suitable for pneumatic application 10.5 kg/Sq-cm rating.
85015 NB SS/GI heavy grade pipe alongwith forged screwed elbows, unions and other fittings for Trim assembly
851Deluge valve trims, Test & drain trims, pneumatic trims, 15 NB ball valve sets for local operation of Deluge valve.
852Pressure gauge with 6" Dial Size with SS needle valve with necessary fittings & mountin 0-07 kg/cm2 range (for air) - 1 No. 0-15 kg/cm2 pressure range (for water - 1 No.)
853Supply & fixing of 3 Nos. 1/2" NPT (F) needle valve in instrument box for mounting 2 Nos. pressure transmitters and1 No. ofsoleNoid valve.
854Supply of 2 Nos. pressure transmitters and1 No. ofsoleNoid valve.
85515 mm SS pipe, Heavy duty with required forged screwed fittings as required.
856Air filter regulator
857Water motor gong along with inlet strainer, 25 NB piping and outlet pipe of 3 meter.
858Orifice plate of required size & fittings
859Item includes installation and assembly of thedeluge valve with the above mentioned components, supply of material, welding, making flange connections using gaskets(with 200% gaskets SPARE QUANTITY), studs-nuts & washers and necessary couplings, clamps and similar items as may be required including making connection with hydrant net work.
860Supply of MVW Spray System
861Medium Velocity Water Spray Nozzle Type: Open & Non-clog Orifice Size: 1/2" (M) Body Material: Al-Bronze Nozzle K-factor: Later Spray Angle: Later UL Listed
862Quartzoid Bulb (QB) Detector Type: Pendant Response: Standard Response Body Material: Forged Brass End Connection: 1/2" (M) Temperature Rating: 79 Deg C UL Listed
863SECTION 5 : CONTROL AND INSTRUMENTATION
864Supply of Field Instruments
865Pressure transmitter
866Pressure transmitterwith SIL 2 rating
867Pressure Transmitter with Hastelloy C for fire water application
868Pressure gauge
869Pressure gauge wih Hastelloy C for fire water application
870Temperature Element (RTD) with thermowell
871Temperature Transmitter
872Temp gauge with theromowell
873Dp type level transmitter
874Level Transmitter GWR
875Top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment, etc complete
876Orifice flow meter with DPT, Orifice plate, manifold etc.
877Orifice flow meter with DPT, Orifice plate , manifold etc.Hastelloy C fire water application
878Pressure switch Hastelloy C for fire water application
879Pressure switch for potable water
8802", 2 m3/hr, electromagnetic flow meter for portable water
881Ultrasonic type flow transmitterfor portable water
882Float typel level switch for portable water
883Supply of Impluse tubing ,Fittings, Manifolds etc.
884SS 316 Impluse tubing, fittings, Manifolds etc Manifold 2 way SS316 Manifold 5 way SS316 1/2"OD tube(5 mtr per instru) 1/2" SS Union Tee 1/2" OD x 1/2" NPT male connector 1/2" ball valve Note: Refer P.011265-I-21003-001_Rev-A_Hook up installation Drawing, bidder shall evaluate quantity from drawing
885Supply of GI perforated Cable trays along with cover
88650 mm (W) X 50 mm (H)
887100 mm (W) X 75 mm (H)
888300 mm (W) X 75 mm (H)
889Supply of Penumatic pressure control valves with smart poisitioner
890Control valve (2") with smart positioner
891Control valve (6-8") with smart positioner
892Supply of Junction boxes
893Junction Box Ex proof with glands
894Junction Box WP with glands
895Supply of Instrumentation Cables
896FRLS Instruments cables and power cable with cable glands for field instruments, MOV , control valves etc 1P x 1.5mm2, 2P x 1.5 mm2, 6Px 1.5mm2, 12P x 1.5 mm2, 3C x 2.5 mm2, 12C x 1.5 mm2,1Q x 1.5.
897Fire resistance Instruments cables and power cable with cable glands for gas detection, fire detection, valves ROSOV etc 1P x 1.5mm2, 2P x 1.5 mm2, 6Px 1.5mm2, 12P x 1.5 mm2, 3C x 2.5 mm2, 1T x 1.5 mm2 and 12T x 1.5mm2
898Supply of Optical Fiber Cable
89924 Core Optical Fiber cable
900Fiber terminal closure with pig tail
901Inspection chember/ splicing chember
902Joint closure/splice closure
903electronic marker
904Marker Locator
90550mm HDPE Duct along with fittings
906Supply of Corrosion Monitoring system
907CMS system with copoun, probe, barriers, access fittings, panel mounted indicator/receiver, copoun holder, service kit, Retriever kit Note: Refer Part 09: Instrumentation and Control Works (Technical specification and data sheets for all the instrumentation)
908Supply of Metering system for POL and LPG Line
90912" Coriolis flow meter skid with Flow computer, strainer Air eliminator,pressure transmitter, temperature transmitter with element and thermowell, skid valves, WCB piping & valve material for POL line
91010" Coriolis flow meter skid with Flow computer, strainer Air eliminator,pressure transmitter, temperature transmitter with element and thermowell, skid valves, LTCS piping & valve material for LPG line
911MFM Master flow meter skid with trolly for POL
912Supply of Fire detection System
913Controller with cabinet, Repeater panel
914Multisensor (smoke & heat detectors)
915smoke detectors
916Response indicator
917Manual call points Ex proof
918Manual call points WP
919Hooter & Beacon
920Siren
921Flame detectors
922ESD Push Buttons
923Exit Sign
92424 Hrs battery
925Supply of Gas detection System
926Controller with wall mounted cabinet
927Open path gas detector with mounting stand with Ex Proof Loop indicator
928Point gas detectors IR type with mounting stand
929Calibration and alignment kit
930Supply of Control & Monitoring system-SCADA SYSTEM incuding below equipment as per system architecture and tender specification at Jetty control building and 5 Acre Plot:
931Server Sum Engineering work station/Operator work station with 20000 tags- 1 Nos
932Operator Work station for Process control & monitoring system- 2 Nos
933Operator Work station for safety control & monitoring system- 2 Nos
934Process PLC with redundant processor, power supply along with cabinet wiring size 2100(H){2000+100 plinth} x800(D)x1000(W), colour RAL 7035- 1 Nos
935ESD SIL -3 PLC with redundant processor, power supply along with cabinet wiring size 2100(H){2000+100 plinth} x800(D)x1000(W), colour RAL 7035 - 1 Nos
936RTU cabinet wiring size 2100(H){2000+100 plinth} x800(D)x1000(W), colour RAL 7035- 1 Nos
937Complete Furniture with chair at Jetty control room and 5 Acre plot as per control room layoutand consol drawing - Lot
938Communication cable SCADA system- Lot
93924 Port LAN switch - 4 Nos
940Alarm Annaciator- 1 Nos
941Supply of SDH Telecommunication system as per below items and tender specification
942SDH Equipment redundant STM -4 with two number addition STM-4 for further IOCL SCADA connectivity, 48 V DC PSU,cabinet etc.
943EMS client & server , Cabinet mounted server,IT equipments with application software and 21" monitor
944Supply of CCTV System as per below items and tender specification
945PTZ colour day/night cameras WP-IP 65 with POE and mounting poles -(Outdoor hazardous area)
946Fix colour Cameras WP IP 65 with POE and mounting accessories- WP IP65 Fixed colour cameras (outdoor safe area)
947Fix colour Cameras WP IP 65, Ex proof with POE and mounting accessoriers- (Outdoor hazardous area)
948Video monitoring system(VMS) server with analytics software , Network video recorder (NVR)21" Monitor , cabinet, mouse, joysticks,32 port LAN L2/L3 switch
949Big screen 65"
950Optical cable,conduit, Ethernet cable, power cable , optical to ethernet converters long with cable laying, accessories as per site conditions.
951Supply of EPABX System
952IP EPABX 100 line equipment with CO cards, IP trunk line,PRI Line
953Analog Phone
954IP phone
955Supply of PAGA System
956PAGA system with central exchange, gooseneck station, controller,WP field call stations, flame proof call stations, interface with EPABX, cables and juncation box at Jetty and 5 acre plot
957WP IP 54 horn loudspeaker with receiver handset- 3 Nos
958WP IP 65 & Ex proof horn loudspeaker with receiver handset - 48 Nos
959Indoor horn loudspeaker with receiver handset- 3 Nos
960Indoor horn loudspeaker -11 Nos
961Master control unit -1 Nos
962Supply of Ship to Shore link
963ESL link between ship and shore with controller with display cabinet
964Supply of EX-Proof Mobile
965Ex proof mobile phone for hzardous area communication
966Supply of Walky-Talky including below equipments and cables
967Base station- 3 Nos
968RepNoter station-2 Nos
969Ex Proof Handsets- 15 Nos
970Handset charger- 2 Nos
971softwareLicense charges-1 Nos
972Supply of Access Control system including below equipments and cables
973Access Contoller
974Client Operator work station
975Proximity card reader entry
976Proximity card reader for exit
977Exit push button
978Electro-magnetic door lock
979Battery
980Surge relief skid along with surge relief valves, nitrogen cylinders, control panel, pressure transmitter, pressure gauge, flow switches, isolation valves and material test certificates for 1 Nos each for POL and LPG line.
981SECTION 6 : HVAC
982Supply of HVAC System of Control Building at Jetty area
983Supply of wall mounted air cooled Non duct-able split air conditioners complete with hermetically sealed rotary compressors (suitable for R-407C / R-410A /R-32 refrigerant) of inverter driven and air cooled condensers in the Outdoor unit with powder coated GI casing, built-in electrical items & supports and Indoor unit housing dry panel type HDPE filters (efficiency 90% down to 10 micron), cooling coils, evaporator fans with two speed drive motors, control console, all encased in powder coated GI casings with swivelling type supply air grilles and decorative RA grilles and interconnecting refrigerant piping (duly insulated) between outdoor and indoor units and insulated drain piping, microprocessor based cordless remote control panel and plug top with connecting cable for each split unit. As required including the structural steel framework, pedestal/ bracket to mount the indoor & outdoor units, supports & clamps for indoor & outdoor units, refrigerant piping/cables, stabilizer, hold down nuts & bolts.
984Split AC units located at Cabin-1: Total cooling capacity: 1.0 TR Dehumidified air quantity: 500 CMH
985Split AC units located at UPS room: Total cooling capacity: 2.0 TR Dehumidified air quantity: 1050 CMH
986Split AC units located at Laboratory: Total cooling capacity: 2.0 TR Dehumidified air quantity: 1050 CMH
987Split AC units located at Office: Total cooling capacity: 1.5 TR Dehumidified air quantity: 750 CMH
988Supply of ceiling mountedcassette type air cooled Non duct-able split air conditioners complete with hermetically sealed rotary compressors (suitable for R-407C / R-410A /R-32 refrigerant) of inverter driven and air cooled condensers in the Outdoor unit with powder coated GI casing, built-in electrical items & supports and Indoor unit housing dry panel type HDPE filters (efficiency 90% down to 10 micron), cooling coils, evaporator fans with two speed drive motors, control console, all encased in powder coated GI casings with swivelling type supply air grilles and decorative RA grilles and interconnecting refrigerant piping (duly insulated) between outdoor and indoor units and insulated drain piping, microprocessor based cordless remote control panel and plug top with connecting cable for each split unit. As required including the structural steel framework, pedestal/ bracket to mount the indoor & outdoor units, supports & clamps for indoor & outdoor units, refrigerant piping/cables, stabilizer, hold down nuts & bolts.
989Split AC units located at Custom room: Total cooling capacity: 3.0 TR Dehumidified air quantity: 1650 CMH
990Split AC units located at Control room: Total cooling capacity: 2.0 TR Dehumidified air quantity: 1250 CMH
991Split AC units located at Equipment room: Total cooling capacity: 3.0 TR Dehumidified air quantity: 1650 CMH
992Split AC units located at Office: Total cooling capacity: 2.0 TR Dehumidified air quantity: 1250 CMH
993Supply of fan filter unit located at Transformer & Switchgear room: The supply fan-filter unit shall consist of wall mounted tube axial flow fan, drive motor, Inlet Louver, pre-filter, supply cowl with protective wire netting inside the room, supports and supporting structures, nuts and bolts, vibration isolators. Fan capacity: 10000 CMH Static pressure: 20 mmWG
994Back draft damper located at Transformer & Switchgear room: The wall mounted back draft damper shall be made galvanized steel of frame thickness 16G & Blade thickness 18G. Size: 1450 mm x 550 mm
995Transfer air grille located at Transformer & Switchgear room: The wall mounted transfer air grille shall be made galvanized steel of frame thickness 16G & Blade thickness 18G. Size: 1450 mm x 550 mm
996Supply of Wall mounted exhaust fan shall consist of tube axial flow fan, drive motor, protective wire netting inside the room, rain protection cowl with bird screen, supports and supporting structures, nuts and bolts, vibration isolators, etc.
997Exhaust fan located at DG room: Fan capacity: 8000 CMH Static pressure: 8 mmWG
998Exhaust fan located at Air compressor room: Fan capacity: 6500CMH Static pressure: 8 mmWG
999Exhaust fan located at Battery room: Wall mounted Exhaust fan shall consist of bifurcated type axial flow fan, drive motor (flame proof type), protective wire netting inside the room, gravity louver at fan outlet, rain protection cowl with bird screen, supports and supporting structures, nuts and bolts, vibration isolators, etc. All parts of this system coming in contact with acid fumes shall be epoxy painted. Fan capacity: 1500 CMH Static pressure: 10 mmWG
1000Supply of wall mounted air intake louver shall be made galvanized steel of frame thickness 16G & Blade thickness 18G.
1001Intake louver located at DG room: Size: 1750 mm x 550 mm
1002Intake louver located at Air compressor room: Size: 850 mm x 550 mm
1003Intake louver located at Battery room: Size: 750 mm x 450 mm
1004Intake louver located at Laboratory: Size: 750 mm x 450 mm
1005Supply of Wall mounted propeller fan shall consist of propeller fan, drive motor, gravity louver at fan outlet, supports, nuts and bolts, vibration isolators etc.
1006Propeller type exhaust fan located at BCW toilet: Fan capacity: 450 CMH Static pressure: 4 mmWG
1007Propeller type exhaust fan located at BCW WC: Fan capacity: 150 CMH Static pressure: 2.5 mmWG
1008Propeller type exhaust fan located at Toilet: Fan capacity: 550 CMH Static pressure: 4 mmWG
1009Propeller type exhaust fan located at Laboratory: Fan capacity: 1000 CMH Static pressure: 6 mmWG
1010Duct mounted In-line centrifugal / axial flow exhaust fan located at Pantry: Duct mounted In-line centrifugal / axial flow exhaust fan shall consist of fan, drive motor, ducting with grille, supports, nuts and bolts, vibration isolators etc. Fan capacity: 200 CMH Static pressure: 5 mmWG
1011Supply of HVAC system of Fire water pump house at Jetty area
1012Exhaust fan located at Fire water pump house: Wall mounted exhaust fan shall consist of tube axial flow fan, drive motor, protective wire netting inside the room, rain protection cowl with bird screen, supports and supporting structures, nuts and bolts, vibration isolators, etc. Fan capacity: 10000 CMH Static pressure: 8 mmWG
1013Intake louver located at Fire water pump house: The wall mounted air intake louver shall be made galvanized steel of frame thickness 16G & Blade thickness 18G. Size: 1800 mm x 600 mm
1014Supply of HVAC system of Electrical cum Control Building at 5 Acre Plot
1015The wall mounted air cooled Non duct-able split air conditioners complete with hermetically sealed rotary compressors (suitable for R-407C / R-410A /R-32 refrigerant) of inverter driven and air cooled condensers in the Outdoor unit with powder coated GI casing, built-in electrical items & supports and Indoor unit housing dry panel type HDPE filters (efficiency 90% down to 10 micron), cooling coils, evaporator fans with two speed drive motors, control console, all encased in powder coated GI casings with swivelling type supply air grilles and decorative RA grilles and interconnecting refrigerant piping (duly insulated) between outdoor and indoor units and insulated drain piping, microprocessor based cordless remote control panel and plug top with connecting cable for each split unit. As required including the structural steel framework, pedestal/ bracket to mount the indoor & outdoor units, supports & clamps for indoor & outdoor units, refrigerant piping/cables, stabilizer, hold down nuts & bolts.
1016Split AC units located at Equipment room: Total cooling capacity: 2.0 TR Dehumidified air quantity: 1050 CMH
1017Split AC units located at Control room: Total cooling capacity: 1.5 TR Dehumidified air quantity: 750 CMH
1018Split AC units located at Work station area: Total cooling capacity: 1.5 TR Dehumidified air quantity: 750 CMH
1019Split AC units located at Waiting room: Total cooling capacity: 1.0 TR Dehumidified air quantity: 500 CMH
1020Split AC units located at Meeting room: Total cooling capacity: 1.0 TR Dehumidified air quantity: 500 CMH
1021Supply offan-filter unit shall consist of wall mounted tube axial flow fan, drive motor, Inlet Louver, pre-filter, supply cowl with protective wire netting inside the room, supports and supporting structures, nuts and bolts, vibration isolators.
1022Supply fan filter unit located at Transformer & PMCC room: Fan capacity: 5000 CMH Static pressure: 20 mmWG
1023Supply fan filter unit located at MV Switchgear room: Fan capacity: 5000 CMH Static pressure: 20 mmWG
1024Supply of wall mounted back draft damper shall be made galvanized steel of frame thickness 16G & Blade thickness 18G.
1025Back draft damper located at Transformer & PMCC room: Size: 800 mm x 500 mm
1026Back draft damper located at Transformer & PMCC room: Size: 650 mm x 300 mm
1027Back draft damper located at MV Switchgear room: Size: 650 mm x 500 mm
1028Exhaust fan located at Battery room: Wall mounted Exhaust fan shall consist of bifurcated type axial flow fan, drive motor (flame proof type), protective wire netting inside the room, gravity louver at fan outlet, rain protection cowl with bird screen, supports and supporting structures, nuts and bolts, vibration isolators, etc. All parts of this system coming in contact with acid fumes shall be epoxy painted. Fan capacity: 2000 CMH Static pressure: 10 mmWG
1029Intake louver located at Battery room: The wall mounted air intake louver shall be made galvanized steel of frame thickness 16G & Blade thickness 18G. Size: 750 mm x 450 mm
1030Supply of Wall mounted propeller fan shall consist of propeller fan, drive motor, gravity louver at fan outlet, supports, nuts and bolts, vibration isolators etc.
1031Propeller type exhaust fan located at Guard toilet: Fan capacity: 150 CMH Static pressure: 2.5 mmWG
1032Propeller type exhaust fan located at Store: Fan capacity: 150 CMH Static pressure: 2.5 mmWG
1033Propeller type exhaust fan located at Gents Toilet: Fan capacity: 400 CMH Static pressure: 4 mmWG
1034Supply of HVAC system of Warehouse at 5 Acre Plot
1035Exhaust fan located at Warehouse: Wall mounted exhaust fan shall consist of tube axial flow fan, drive motor, protective wire netting inside the room, rain protection cowl with bird screen, supports and supporting structures, nuts and bolts, vibration isolators, etc. Fan capacity: 2500 CMH Static pressure: 8 mmWG
1036Intake louver located at Warehouse: The wall mounted air intake louver shall be made galvanized steel of frame thickness 16G & Blade thickness 18G. Size: 750 mm x 450 mm
1037Supply of HVAC system of Box Culvert
1038The cabinet type supply fan-filter unit shall consist of direct driven / belt driven centrifugal flow fan, drive motor, Inlet Louver, pre-filter, VCD at fan outlet, supports and supporting structures, nuts and bolts, vibration isolators. The fan outlet shall be connected to ducting system. Fan capacity: 24000 CMH Static pressure: 33 mmWG
1039TheRoof Extractor shall consist of roof mounted axial flow exhaust fan, drive motor, rain protection hood with bird screen, supports & supporting structure, grouting frame, bolts, nuts, transition piece (if required), vibration isolators, water sealing arrangement at the base and inspection door. The fan inlet shall be connected to ducting system. The exhaust fan shall be spark proof construction & motor shall be flame proof type. Fan capacity: 24000 CMH Static pressure: 22 mmWG
1040Supply of HVAC items for duct works
1041Supply of Ducting: Ductingshall be made of G.I. sheet of at least grade 180 as per IS 277. Specified quantity is indicative only. Bidder shall estimate the final quantity & quote the ducting quantity, hanger support etc. according to "Air conditioning & Ventilation layout of Control Building (Dwg. No. P.011265-M-21006-502)" and "Ventilation layout of Box Culvert (Dwg. No. P.011265-M-21006-505)".
104218G
104320G
104422G
104524G
1046Supply air Grille: The supply air grille shall be made up of Aluminium construction and painted with two (2)coats of powder coating paints. Supply air grille shall be provided with volume control damper. The grille frame and louvers shall be manufactured of at least 20G and 22G respectively.
1047Size: 800 x 300
1048Supply of Return air Grille: The return air grille shall be made up of Aluminium construction and painted with two (2)coats of powder coating paints. Return air grille shall be provided without volume control damper. The grille frame and louvers shall be manufactured of at least 20G and 22G respectively.
1049Size: 600 x 300
1050Size: 300 x 300
1051Supply of Flexible connection: Flexible connectionshall be fire retardant type. Flexible connections of at least 150 mm length shall be provided at each connection between ductwork and fan units. Thequantity shall be estimated according to "Air conditioning & Ventilation layout of Control Building (Dwg. No. P.011265-M-21006-502)" and "Ventilation layout of Box Culvert (Dwg. No. P.011265-M-21006-505)".
1052PART B - INSTALLATION / ERECTION, TESTING AND COMMISSIONING OF FOLLOWING ITEMS For all the items under Part B of this schedule, the rates to be quoted include:- (A)For all the items under Part B of this schedule, the rates to be quoted include charges towards Installation & Erection works including supply of all erection equipment & materials, tools, tackles and labour; (B) Cutting, aligning to plumb & levels, fabrication, welding, erection, etc. as per site requirements; Testing and Commissioning of all items / equipment as per attached specifications, data sheets, codes and directions of PMC Engineer/ Owner; Chipping of walls, drilling, making holes, patching up works with plastering including bringing the surfaces to original condition etc.
1053SECTION 1 : MECHANICAL
1054Marine Loading Arms
1055Marine Loading Arm, Size 12", 300#, Product: LPG (Propane & Butane), Material: LTCS, Electro-Hydraulic operated, including spare parts, Emergency Release Coupling and Hydraulic Quick Connect/ Disconnect Cargo Couplers.
1056Marine Loading Arm, Size 12", 300#, Product: POL (MS, HSD, ATF & SKO), Material: Carbon Steel, Electro-Hydraulic operated, including spare parts, Emergency Release Coupling and Hydraulic Quick Connect/ Disconnect Cargo Couplers.
1057Hydraulic Power Unit (HPU) common for all MLAs
1058Supervision Service
1059Gangway Tower
1060Hydraulic operated telescopic type Ship Access Gangway Tower with steel tower, platform, inclined ladder, bulwark ladder, hydraulic cylinder, HPU, typside jib crane with ground pendant switch control, combination starter, and all associated accessories. Upper Level: 19.5 m CD Down Level: 2.1 m C.D Jib Crane Capacity: 2.5 MT Max./Min. Radius of Jib Crane: 19 m / 3.5 m
1061Supervision Service
1062Pig Launcher cum Receiver
1063Bi-directional launcher cum receiver suitable for accomodating intelligent pigs & other cleaning / displacement / gauging pigs, fitted with Quick Opening End Closure (QOEC) suitable for horizontal installation including all accessories required to make Bi-Directional Launcher & Receiver system complete operational and QOEC shall be hand operated by a single lever operation and operable by one operator, including placement of perforated SS Tray inside the Bi-Directional Launcher & Receiver, mounting of Pig Signaller on the Bi-Directional launcher & receiver, Pig Handling (insertion / retraction) System includingmating flanges for all the flanged end Nozzle. Required studs, Nuts, bolts, Gaskets and erection of the following withfoundation Bolts and associated accessories including commissioning tha same etc. complete.
1064Bi-directional Pig Launcher cum Receiver (of size 36" x 30" NB & ANSI Class 150) along with Quick Opening End Closure (QOEC), all required Nozzles, vent, drain, flanges, gaskets and bolting - 2 Nos.
1065Non-intrusive type (Ultrasonic) Pig Signaller mounted on Pig Launcher cum Receiver- 2 Nos.
1066Supply of Door Seal for Quick Opening End Closure (QOEC) [Commissioning Spares]- 4 Nos.
1067Non-intrusive type (Ultrasonic) Pig Signaller mounted on 30" NB Pipeline- 2 Nos.
1068Jib Crane of capacity 3T to suit the pig handling for scrapper trap as specified above- 1 No.
1069Pig Handling System with insertion / retraction facilities for inserting / pulling the SS Tray / Pigs to suit the scrapper trap- 2 Nos.
1070EOT Crane (for Fire Water Pump House)
107110T Capacity Double Girder EOT Crane incl. bridge structure, travelling mechanism, hoisting mechanism, service platform, brake mechanism, electric motors, trailing cables, AC variable frequency controls for all motions, lighting fixtures and all other necessary accessories. Building Span: 15.7 m Bay Length: 44 m Lifting Height: 6.4 m Area Classification: Non-Hazardous Operation: Pendant + Radio Remote Control
1072Slop Tanks
1073Horizontal, cylindrical, pit mounted (below deck) POL Slop Tanks (one each for MS, HSD, ATF & SKO) incl. shell, flat ends, Nozzles, boot for slop pump mounting, manhole with davit arrangement, saddle supports, stiffener plates and RF pads, internal piping, earthing cleats, nameplates, anchor bolts etc. Design Standard: IS 10987 (latest edition) Internal Diameter: 2200 mm Length: 9000 mm Material: MS (IS 2062 Gr.B)
1074Horizontal, cylindrical, pit mounted (below deck) POL Slop tank incl. shell, flat ends, Nozzles, boot for slop pump mounting, manhole with davit arrangement, saddle supports, stiffener plates and RF pads, internal piping, earthing cleats, nameplates, anchor bolts etc. Design Standard: IS 10987 (latest edition) Internal Diameter: 1700 mm Length: 8500 mm Material : MS (IS 2062 Gr.B)
1075Slop Pumps
1076Vertical, Extended Shaft, Submerged Sump Pump (VS-4) type vessel mounted slop pumps for POL products (one each for MS, HSD, ATF & SKO) including drive motor, coupling with coupling guard, common base frame for each pump and motor, complete sealing / cooling / lubrication system, counter flanges with bolts, nuts & gaskets, Local Control Panel (LCP) etc. Rated Flowrate: 36 m3/hr. TDH: 100 MLC MOC: ASTM A48 CL 30 (Casing) / ASTM A351 CF8 (Impeller)
1077Vertical, Extended Shaft, Submerged Sump Pump (VS-4) type vessel mounted slop pumps including drive motor, coupling with coupling guard, common base frame for each pump and motor, complete sealing / cooling / lubrication system, counter flanges with bolts, nuts & gaskets, Local Control Panel (LCP) etc. Rated Flowrate: 10 m3/hr. TDH: 100 MLC MOC: ASTM A48 CL 30 (Casing) / ASTM A351 CF8 (Impeller)
1078Instrument Air System
1079Oil Flooded, Rotary Screw type Compressor complete with electric motor, common baseplate or skid for compressor with all components, individual suction air filters, oil filter, air cooled intercooler & aftercooler, Auto drain traps with bypass valve, safety valves, instruments & controls, microprocessor based local control unit for each compressor etc. Capacity (each) / FAD : 200 Nm3/hr. (incl. purge air loss) Guaranteed output at package outlet terminal point : 170 Nm3/hr. Discharge Pressure at package outlet: 7 barg
1080Vertical, cylindrical, dished end type air receiver (one at compressor discharge and two at dryer discharge) complete with manhole, pressure indicators, temperature indicators, automatic drain trap, block valves for instruments, manual drain line with valve etc. Capacity of Compressed Wet Air Receiver : Bidder to decide Capacity of each Instrument Dry Air Receiver : 5 m3 MOC: IS 2002 Gr. 2A/2B or IS 2062
1081Heatless purge type air drier including twin towers with a pressure / temperature safety relief valve, pressure indicator, purge volume control valve, purge flow meter, silencer, thermostatic devices, dew point alarm and indication equipment, control and alarm circuit etc. Following items are also included: a) One (1) set of pre-filter for each drier including differential pressure indicator, automatic drain traps with bypass, and block valves for maintenance b) One (1) set of After-filter for each drier including differential pressure indicator, alarm, automatic drain traps with bypass, and block valves for maintenance c) One (1) relay based control system for Air Drier
1082Erection, Testing & Commissioning of all integral piping including necessary internal pipes, fittings, instruments, drains and vents with isolation valve, supports within package unit
1083Vapour Eliminators
1084Vertical, Cylindrical type Vapour Eliminators to separate any carry over liquid in the incoming nitrogen gas supply including all necessary accessories. Design Pressure: 6 barg MOC: Carbon Steel (ASTM A516 Gr.70) Dimension (Approx.): 2 m (Dia) x 3.5 m (Height) Inlet: 16" Vapour Outlet: 10"
1085Flame Arresters
1086Vertical, inline Flame Arrestor Assembly complete with all necessary accessories (Suitable for Zone 2 Gas Group IIA/IIB, Temperature Class: T3) :
108710", 150#, MOC: Carbon Steel (Body) / Flame Element (SS 316L)
10882", 150#, MOC: Carbon Steel (Body) / Flame Element (SS 316L)
1089Nitrogen System
1090Nitrogen system comprising ofmodules of liquid Nitrogen storage tank with vaporisers as per Particular Technical Specification along with integral and interconnecting piping and instrumentation, civil foundations and installation cost.
1091SECTION 2 : PIPING
1092Welding, testing and commissioning of Carbon steel/ Stainless steel MOVs/ GATE VALVE/ GLOBE VALVE/ NRV/ ROSOV/ DBBV/ BALL VALVES/ ARC VALVE/ DELUGE VALVE/ BUTTERFLY VALVE/ PUPPET VALVES/ AIR RELEASE VALVE/ STRAINER, etc. on the pipeline including supplying and fixinggaskets, studs, nutswashers of approved make, all leads & lifts etc., complete as per specifications and instructions of PMC Engineer/ Owner. Note: a) Rate includes painting with approved make, colour, shade including colour coding as per specifications. b) Rate includes providing 8 SWG bare Cu wire for bonding between flanges for sizes for all Product pipelines
1093Erection, Testing & Commissioning the following sizes of CS Manual Ball Valves (ASTM A105 flanged # 800 ) as per Specification
109415 mm dia
109525 mm dia
109650 mm dia
1097Erection, Testing & Commissioning the following sizes of CS Manual Ball Valves (ASTM A 216WCB flanged # 150 ) as per Specification
1098100 mm dia
1099150 mm dia
1100200 mm dia
1101250 mm dia
1102300 mm dia
1103Erection, Testing & Commissioning the following sizes of CS Manual Globe Valves (ASTM A105 flanged # 800 ) as per Specification
110425 mm dia
1105Erection, Testing & Commissioning the following sizes of CS Manual Globe Valves (ASTM A 216WCB flanged # 150 ) as per Specification
1106200 mm dia
1107250 mm dia
1108Erection, Testing & Commissioning the following sizes of CS Manual Globe Valves (ASTM A 352 Gr. LCB flanged # 800 ) as per Specification
110925 mm NB
1110Erection, Testing & Commissioning the following sizes of CS Manual Ball Valves (ASTM A 352 Gr. LCB flanged # 150 ) as per Specification
111150 mm NB
1112Erection, Testing & Commissioning the following sizes of CS Manual Ball Valves (ASTM A 352 Gr. LCB flanged # 300 ) as per Specification
111350 mm NB
1114Erection, Testing & Commissioning the following sizes of SS Manual Ball Valves (ASTM A182 Gr. F316L flanged # 150 ) as per Specification
111525 mm NB
1116Erection, Testing & Commissioning the following sizes of SS Manual Globe Valves (ASTM A182 Gr. F316L flanged # 800 ) as per Specification
111725 mm NB
1118Erection, Testing & Commissioning the following sizes of SS Manual Ball Valves (ASTM A351 GR CF3 flanged # 150 ) as per Specification
111950 mm NB
1120Erection, Testing & Commissioning the following sizes of SS Manual Globe Valves (ASTM A351 GR CF3 flanged # 150 ) as per Specification
112150 mm NB
1122Erection, Testing & Commissioning the following sizes of CS Check Valves (ASTM A105 flanged # 800 ) as per Specification
112325 mm NB
1124Erection, Testing & Commissioning the following sizes of CS Check Valves (ASTM A216WCB flanged # 150 ) as per Specification
112550 mm dia
1126100 mm dia
1127200 mm dia
1128300 mm dia
1129600 mm dia
1130Erection, Testing & Commissioning the following sizes of CS Excess Flow Check Valves (ASTM A 352 Gr. LCB flanged # 300 ) as per Specification
1131300 mm dia
1132Erection, Testing & Commissioning of Thermal relief valves (ASTM A 352 Gr. LCB flanged # 300 ) as per Specification
113325mm X 50mm dia TRV
1134Erection, Testing & Commissioning of Thermal relief valves (ASTM A 216WCB flanged # 150 ) as per Specification
113525mm X 50mm dia TRV
1136Erection, Testing & Commissioning of Pressure relief valves (ASTM A 216WCB flanged # 150 ) as per Specification
113750mm X 50mm dia SRV
1138100mm X 150mm dia SRV
1139Erection, Testing & Commissioning the following sizes of CS Motor Operated Ball Valves (ASTM A216WCB flanged # 150 ) as per Specification
114050 mm dia
1141100 mm dia
1142150 mm dia
1143400 mm dia
1144600 mm dia
1145750 mm dia
1146Erection, Testing & Commissioning the following sizes of CS Motor Operated Ball Valves (ASTM A 352 Gr. LCB flanged # 300 ) as per Specification
1147300 mm dia
1148450 mm dia
1149600 mm dia
1150Erection, Testing & Commissioning the following sizes of CS Motor Operated Globe Valves (ASTM A216WCB flanged # 150 ) as per Specification
1151600 mm dia
1152Erection, Testing & Commissioning the following sizes of CS Electro Hydraulic Butterfly Valves (ASTM A216WCB flanged # 150 ) as per Specification
1153600 mm dia
1154Erection, Testing & Commissioning the following sizes of CS Pneumatic Control Globe Valves (ASTM A216WCB flanged # 150 ) as per Specification
1155250 mm dia
1156500 mm dia
1157Erection, Testing & Commissioning the following sizes of CS Pneumatic Control Ball Valves (ASTM A 352 Gr. LCB flanged # 300 ) as per Specification
1158300 mm dia
1159Welding and laying of Above GroundProductSteel Pipelines on pipeline trestle/ pedastals/sleepers/overhead pipe rack/structures/within culvert, etc. The pipeline laying includes cutting, beveling, positioning, setting, fixing the pipe fittings, such as, elbows, bends tees, reducers, etc., complete with supports as per drawings and hydro testing the pipelines as per specifications. Note: a. Welding of pipeline should conformto Radiography quality. b. Pipe length indicated against each size is actual as per drawing. Payment will be made for the actual quantity executed at site. c. Pipe fittings shall form the part of the measured length of pipeline. No additional payment shall be made for erection/ installation of pipe fittings. d. Pipeline colour coding shall be carried out as per IOC specifications at No extra cost for product piping.
1160Erection, Welding, Testing & Commisioning of CS Seamless Pipes to API5L Gr.X52, Dim. ASME B36.10
1161750mm NB SCH THK. 10.3mm Bevel ends
1162Erection, Welding, Testing & Commisioning of CS Seamless Pipes to ASTM A106 Gr.B, Dim. ASME B36.10
116325mm NB SCH S-80 Plain ends
116450mm NB SCH S-80 Bevel ends
116580mm NB SCH S-STD Bevel ends
1166100mm NB SCH S-STD Bevel ends
1167150mm NB SCH S-STD Bevel ends
1168200mm NB SCH S-STD Bevel ends
1169250mm NB SCH S-STD Bevel ends
1170300mm NB SCH S-STD Bevel ends
1171400mm NB SCH S-STD Bevel ends
1172500mm NB SCH S-STD Bevel ends
1173600mm NB SCH S-STD Bevel ends
1174Erection, Welding, Testing & Commisioning of CS Seamless Pipes to ASTM A333 Gr.6, Dim. ASME B36.10
117525mm NB SCH S-160 Plain ends
1176450mm NB SCH S-30 Bevel ends
1177300mm NB SCH S-40 Bevel ends
117850mm NB SCH S-80 Bevel ends
1179Erection, Welding, Testing & Commisioning of CS Galvanized Seamless Pipes to ASTM A106 Gr.B, Dim. ASME B36.10
118025mm NB SCH S-80 MTE
118125mm NB SCH S-80 PE X MTE 100 mm Long
118250mm NB SCH S-STD Bevel Ends
118380mm NB SCH S-STD Bevel Ends
1184Erection, Welding, Testing & Commisioning of SSSeamless Pipes to ASTM A312 Gr.TP316L, Dim. ASME B36.19
118550mm NB SCH S-40S Bevel Ends
118625mm NB SCH S-40S Plain Ends
118725mm NB SCH S-40S Plain Ends X MTE 100 mm LONG
1188Supplying & application of painting of piping after surface prepartion by grit blasting -SA 2- 1/2. Primer: Self priming surface tolerant Polyamine/ Amide cured HB modified Aluminium filled Epoxy Mastic Primer. 100 micron. Intermediate coat: Glass flakes coating with resin/ medium as liquid Epoxy cured with Polyamine/ Amide/ Amino-amide or Isophthalic Polyster/ Acrylic Copolymer. 200 micron Finish coat: Two components Aliphatic Acrylic re- coatable Polyurethane. 2 x 35 micron= 70 micron.
1189Supplying and Erection of Insulation  for the following above ground Propane/Butanepipelines withinsulation of 200 mm thickness (100 mm Preformed PIR  followed by 100 mm cast-insiitu PIR) and the final layer  shall be finished with 0.4mm thick SS-316 sheet as per the Technical specifications and datasheet.
1190450 mm dia
1191300 mm dia
1192100 mm dia
119350 mm dia
1194Supplying and Erection of High Density PUF support block for 450 mm dia / 300 mm dia Propane/ Butane Pipelines with insulation thickness of 200 mm * 400 mm long of density 250 kg/m3 and supplied in two half sections including any mechanical clamp/ steel part, etc. complete as per specifications and datasheet.
1195450 mm dia
1196300 mm dia
1197Supply, Fabrication and Erection Of Structural Steel (Including Cradle Supports, U Bolts, Structural Supports, Embedded Steel Etc.)
1198U-Bolt
119915 mm dia
120025 mm dia
120150 mm dia
120280 mm dia
1203100 mm dia
1204TEFLON PAD ASSEMBLY
1205SUPPLY OF SPECIALITIES
1206SUPPLY & INSTALLATION OF SAFETY SHOWER/ EYEWASH UNIT (as per IS 10592)
1207ORIFICE PLATE 3MM & 6MM #300,
120880 mm dia
1209100 mm dia
1210SPECTACLE BLIND
121125 mm dia
121250 mm dia
121380 mm dia
1214100 mm dia
1215Flow Tee ASTM A234 Gr.WPB (Pipe Material API5L Gr.X52
1216DN 750 X DN 600 10.3mm THK X STD
1217RADIOGRAPHY :- Performance of radiographic inspection on Piping of following Sizes & thicknesses including providing or hiring of all necessary equipments andpersonnels, etc. even though not expressly mentioned but required to perform the work as per specifications and instructions of PMC Engineer/ Owner. Radiographs shall be submitted to the PMC Engineer/ Owner. (Repeat Radiography due to defective radiograph on repaired joints due to Contractor"s fault and for additional radiography necessitated due to poor performance of contractor"s welders shall be done at contractor"s cost) Note: Unit for Radiography quantity is "Nos of each circumferencial weld joints" in the pipes.
1218100mm NB
1219150mm NB
1220200mm NB
1221250mm NB
1222300mm NB
1223400mm NB
1224450mm NB
1225500mm NB
1226600mm NB
1227750mm NB
1228Welding flanges of the following sizes on the Product pipelines including positioning, setting, welding with min. three runs outside and all leads & lifts etc., complete as per specifications and instructions at site. Radiography will be done for 10% of joints for which payment will made under separate item.
1229Welding of following Socket Weld type- SWRF 125 AARH as per ASTM A105 DIM. ASME B16.5 Class 150
123025mm NB
123150mm NB
1232Welding of following Socket Weld type- SWRF 125 AARH as per ASTM A350 Gr.LF2 DIM. ASME B16.5 Class 300
123325mm NB
1234Welding of following Weld neck type- WNRF 125 AARH as per ASTM A105 DIM. ASME B16.5 Class 150
123580mm NB SCH S-STD
1236100mm NB SCH S-STD
1237150mm NB SCH S-STD
1238200mm NB SCH S-STD
1239250mm NB SCH S-STD
1240300mm NB SCH S-STD
1241400mm NB SCH S-STD
1242500mm NB SCH S-STD
1243600mm NB SCH S-STD
1244Welding of following Weld neck type- WNRF 125 AARH as per ASTM A350 Gr.LF2 DIM. ASME B16.5 Class 150
124550mm NB SCH S-80
1246Welding of following Weld neck type- WNRF 125 AARH as per ASTM A350 Gr.LF2 DIM. ASME B16.5 Class 300
1247450mm NB SCH S-30
1248300mm NB SCH S-40
124950mm NB SCH S-80
1250Welding of following Weld neck type- WNRF 125 AARH as per ASTM A 694 Gr. F52 DIM. ASME B16.47 Series B Class 150
1251750mm NB SCH THK. 10.3mm
1252Welding of following Slip On type- SORF 125 AARH as per ASTM A105 (GALV.) DIM. ASME B16.5 Class 150
125350mm NB SCH S-STD
125480mm NB SCH S-STD
1255Welding of following Weld neck type- WNRF 125 AARH as per ASTM A182-F316L DIM. ASME B16.5 Class 150
125650mm NB SCH S-40S
1257Making flanged joints (both for flanges & blind flanges) of the following sizes including supplying and fixing 3 mm thk Spiral Wound & Graphite Filled Metallic gaskets, studs, nuts, washers of approved make, all leads & lifts etc., complete as per specifications and instructions at site for Product lines & AFFF Pipe joints. Note: a. Item includes providing 8 SWG bare Cu wire for bonding between flanges for sizes up to & including 100 mm dia for Product pipelines
1258Making Joints of following Socket Weld type- SWRF 125 AARH as per ASTM A105 DIM. ASME B16.5 Class 150
125925mm NB
126050mm NB
1261Making Joints of following Socket Weld type- SWRF 125 AARH as per ASTM A350 Gr.LF2 DIM. ASME B16.5 Class 300
126225mm NB
1263Making Joints of following Weld neck type- WNRF 125 AARH as per ASTM A105 DIM. ASME B16.5 Class 150
126480mm NB SCH S-STD
1265100mm NB SCH S-STD
1266150mm NB SCH S-STD
1267200mm NB SCH S-STD
1268250mm NB SCH S-STD
1269300mm NB SCH S-STD
1270400mm NB SCH S-STD
1271500mm NB SCH S-STD
1272600mm NB SCH S-STD
1273Making Joints of following Weld neck type- WNRF 125 AARH as per ASTM A350 Gr.LF2 DIM. ASME B16.5 Class 150
127450mm NB SCH S-80
1275Making Joints of following Weld neck type- WNRF 125 AARH as per ASTM A350 Gr.LF2 DIM. ASME B16.5 Class 300
1276450mm NB SCH S-30
1277300mm NB SCH S-40
127850mm NB SCH S-80
1279Making Joints of following Weld neck type- WNRF 125 AARH as per ASTM A 694 Gr. F52 DIM. ASME B16.47 Series B Class 150
1280750mm NB SCH THK. 10.3mm
1281Making Joints of following Slip On type- SORF 125 AARH as per ASTM A105 (GALV.) DIM. ASME B16.5 Class 150
128250mm NB SCH S-STD
128380mm NB SCH S-STD
1284Making Joints of following Weld neck type- WNRF 125 AARH as per ASTM A182-F316L DIM. ASME B16.5 Class 150
128550mm NB SCH S-40S
1286SECTION 3 - ELECTRICAL
12872 POLE STRUCTURE: 2 pole Structure including RSJs, ISMCs for 11 kV Incoming Power Supply with Gang operated isolator, D.O. fuse with base, lightning arrestors, earthing, padlocking for 2 Pole structure as per attached specification, data sheet including supply of commissioning spares, as required.
1288Installation, Testing and Commissioning of trivector meter for tariff metering including metering enclosure. Note: The TVM shall be supplied by TANGEDCO.
1289HT Switchboard :
129011 kV, 630 A, 3 phase, 3 wire, 25 kA for 1 sec. rated switchgear with all accessories as per single line diagram, specification and data sheet as attached with the tender document.
129111 kV, 630 A, 3 phase, 3 wire, 25 kA for 1 sec. rated single VCB cubicle (ICOG type panel) with all accessories as per single line diagram , specification and data sheet as attached with the tender document.
1292Distribution Transformer : Distribution / Lightingtransformer of the following ratings as per attached specification, data sheetincluding supply of commissioning spares, as required.
1293200 kVA, 11/0.433 kV dry type transformer with all fittings and accessories as per specification Location: 5 acre plot substation room
1294630 kVA, 11/0.433 kV dry type transformer with all fittings and accessories as per specificationLocation : Substation room at jetty control building
1295DG Set :
1296125 kVA, 415 V, 3 phase, 0.8 PF DG Set & AMF Panel with all fittings and accessories like lube oil system, cooling system, diesel oil system, all required piping, exhaust piping & support structure, day oil tank each along with all pipings with magnetic level switch,inter connecting cables and cable accessories, base channels etc. as per attached specification, data sheet & SLD including supply of commissioning spares, as required, First filling of engine oil, lubricant etc. The supply includes Residential silencer & spark arrestor. Location: DG Shed of 5 acre plot
1297600 KVA, 415V, 3 phase, 0.8 PF DG Set & AMF Panel complete with all required accessories like lube oil system, cooling system, diesel oil system, all required piping, day oil tank along with all pipings with magnetic level switch,inter connecting cables and cable accessories, base channels etc. as per attached specification, data sheet & SLD including supply of commissioning spares, as required, First filling of engine oil, lubricant etc. The supply includes Residential silencer & spark arrestor. Location: DG Room at jetty control building
1298MV & LV Switch board/Panels/Sub Distribution Boards :
1299EPMCC Panel: 415 V, 400 A, 3 phase, 4 wire, 25 kA for 1 sec. rated Onshore EPMCC with all accessories as per single line diagram, specification and data sheet. Location - 5 acre plot substation room
1300EPMCC Panel: 415 V, 1250 A, 3 phase, 4 wire, 40 kA for 1 sec. rated Jetty EPMCC with all accessories as per single line diagram, specification and data sheet. Location - Substation room at jetty control building
1301Onshore ACDB: 415 V, 100 A, 3 phase, 4 wire, 25 kA for 1 sec. rated Onshore ACDB with all accessories as per single line diagram, specification and data sheet. Location - 5 acre plot substation room
1302Jetty ACDB: 415 V, 200 A, 3 phase, 4 wire, 40 kA for 1 sec. rated Jetty ACDB with all accessories as per single line diagram, specification and data sheet Location - Substation room at jetty control building
1303MOV DB: 415 V, 200 A, 3 phase, 4 wire, 40 kA for 1 sec. rated MOV DB with all accessories as per single line diagram, specification and data sheet Location - Substation room at jetty control building
1304HVAC DB: 415 V, 200 A, 3 phase, 4 wire, 40 kA for 1 sec. rated HVAC DB with all accessories as per single line diagram, specification and data sheet Location - Substation room at jetty control building
1305APFC Panel: 25 kVAR, 415 V Capacitor bank with APFC as per specification, data sheet and single line diagram Location - Substation room at jetty control building
1306Lighting Distribution Board & Lighting Panel :
1307LDB: 415 V, 63 A, 3 phase, 4 wire, 10 kA for 1 sec. rated onshore area lighting DB with 25 kVA 0.415/0.433 kV lighting transformer and with all accessories as per specification. Incomer: 63 A, 3 phase, 1 No. Outgoing: 32 A, 3 phase, 6 Nos.. Location - 5 acre plot substation room
1308LDB: 415 V, 100 A, 3 phase, 4 wire, 10 kA for 1 sec. rated jetty area lighting DB with 50 kVA 0.415/0.433 kV lighting transformer and with all accessories as per specification. Incomer: 100 A, 3 phase 1 No. Outgoing: 63 A, 3 phase 9 Nos. Location - Substation room at jetty control building
1309LP: Indoor Non FLP type lighting panel as per specification with all accessories. Incomer: 32 A, 3 phase, 1 No.; Outgoing: 16 A, 1 phase, 6 Nos.
1310LP: Indoor Non FLP type lighting panel as per specification with all accessories. Incomer: 63 A, 3 phase, 1 No.; Outgoing: 16 A, 1 phase, 9 Nos.
1311LP: Outdoor FLP type (Ex-d, IIA/IIB, T3) as per specification with all accessories. Incomer: 63 A, 3 phase, 1 No.; Outgoing: 16 A, 1 phase, 9 Nos.
1312LP: Outdoor Non FLP type as per specification with all accessories. Incomer: 63 A, 3 phase, 1 No.; Outgoing: 16 A, 1 phase, 9 Nos.
1313UPS System :
13142x100% 10 kVA, 240 V AC UPS with maintenance bypass and UPSDB for onshore area as per single line diagram, specification and data sheet Location - 5 acre plot substation room
13152x100% 20 kVA, 230 V AC UPS with maintenance bypass and UPSDB for Jetty area as per single line diagram, specification and data sheet Location- Substation room at jetty control building
1316BATTERY :
1317Placing of cells on stand in proper sequence, cleaning of cells, making inter cell/ tier/ row connections, filling up with electrolyte, charging, testing & commissioning of BATTERY as per manufacturer"s instructions and other associated work, labour & materials complete:
1318VRLA SMF type Battery Bank suitable for 2x10 kVA UPS
1319VRLA SMF type Battery Bank suitable for 2x20 kVA UPS
1320LED Lighting Fixtures & Accessories :
1321Weather proof Lighting Fixtures, Lamps & accessories as per specifications. (All Lighting fixtures shall be provided with required No. of double compression cable glands and stopper plugs as required including tinned copper cable lugs of suitable type for termination)
1322Note: Rate to include mounting of light fixtures of all types on walls/ structural brackets/ high masts/ street light poles/ platforms/ lighting poles/ pendants and all similar such places;Supply & fixing pipes/ GI chains, neoprene/ rubber/ PVC bushes at fixtures and JBs; supply & fixing double compression cable glanding & termination using tinned copper lugs of suitable size & type, crimping of lugs & connections at fixtures/ control gears; Down rods with ball and socket arrangements as required; Fixing arrangements with anchor fasteners; supply of all erection materials including necessary accessories like chokes, starters, condensers, internal & external reflectors, igniter, canopy etc., complete as per drawings and documents, specifications, codes & standards and instructions/ directions of PMC Engineer/ Owner.
132340W Linear LED Light (Bajaj Cat No.- BLTRU 40W VIVA or approved equivalent)
132436W Planner Recess Mounting Type LED Light suitable for false celling ( Bajaj BCTBLR 36W LED or approved equivalent)
1325100W High bay LED Fitting (BAJAJ 13499 BGHB 100W future or approved equivalent)
13263W Single Side Display LED EXIT with ARROW (with 2HR. Battery backup)
132710W LED Suspended Mounting Weatherproof Bulkhead Luminaries(BAJAJ BIBWP 10W LED or approved equivalent)
132820W LED surface mounted Normal Luminaries(PHILIPS SM134VPSD W60L60 or approved equivalent)
132930W Peripheral LED Light (Bajaj Cat No.- BCLST 30W LED or approved equivalent)
1330100 W LED street light type fixture as per specification ( Bajaj Cat No.- BRTFG 100W LED I or approved equivalent)
1331120 W LED Flood Light (Bajaj Cat No- BAR FEG 120 W or approved equivalent) including all accessories
1332Flame proof Lighting Fixture & Accessories
133350W LED Well glass Light fittings ( Baliga Cat. No.-FLPW-1245L LED 50W or approved equivalent)
133436 W surface mounted flameproof type LED fixture (NoTON cat. No.TFC 6135Z NoTON-TUFFLITE IP66 or approved equivalent)
1335Other Lighting Material:
13363 modular switch frame including 6A, 1 No. 3 pin socket, as per specifications and direction of Engineer in Charge.
13376 modular switch frame including 6A, 1 No. 3 pin socket, as per specifications and direction of Engineer in Charge.
13389 modular switch frame including 6A, 1 No. 3 pin socket, as per specifications and direction of Engineer in Charge.
133930 m high mast lighting structure includingfoundation, fixingof base plate and complete erection, testing and commisioning
13409 Mtr GI street Lighting Pole includingfoundation, fixingof base plate and complete erection, testing and commisioning
13414.5 Mtr Swan Neck GI Lighting Pole includingfoundation, fixingof base plate and complete erection, testing and commisioning
1342Heavy duty PVC Coduits - 19 mm for concelled wiring as per specification
1343Heavy duty PVC Coduits - 25 mm for concelled wiring as per specification
1344Rigid steel Coduits - 19 mm for exposed wiring for fire water pump house and wire house as per specification
1345Rigid steel Coduits - 25 mm for exposed wiring for fire water pump house and wire house as per specification
1346Flexible PVC conduit
1347Flexible steel conduit
13483 way Circular JB/pull box as per specification
13494 way Circular JB/pull box as per specification
1350GI/SS Prefabricated Ladder type and Perforated Type Cable Tray
1351GI/SS prefabricated ladder type cable trays & their accessories (like tray cover, Coupler plate, Tray Fixing clamp, Fastener, nut, bolt washer etc. as required ) of following sizes as per drawing, data sheet. Rate shall include fixing of cable tray support also.
1352600 mm
1353300 mm
1354150 mm
1355GI/SS prefabricated perforated type cable trays & their accessories( like tray cover, Coupler plate, Tray Fixing clamp, Fastener, nut, bolt washer etc. as required ) of following sizes as per drawing, data sheet. Rate shall include fixing of cable tray support also :
135650 mm
1357150 mm
1358300 mm
1359600 mm
1360Junction Box :
1361Two way FLP type junction boxes as per specification including the glands, lugs and terminal blocks of required cable size. (Max. incoming cable size 3.5Cx70 sq. mm, Max. outgoing Cable size 3Cx6 sq. mm )
1362Three way FLP type junction boxes as per specificationincluding the glands, lugs and terminal blocks of required cable size. (Max. incoming cable size 3.5Cx70 sq. mm, Max. outgoing Cable size 3Cx6 sq. mm )
1363Four way FLP type junction boxes as per specification including the glands, lugs and terminal blocks of required cable size. (Max. incoming cable size 3.5Cx70 sq. mm, Max. outgoing Cable size 3Cx6 sq. mm )
1364Local Control Station :
1365Flameproof (Ex’d’) Local Control Station with components as listed below and with Aluminium alloy (LM6 grade) enclosure as per Specification, Data Sheet and direction of Engineer-in-charge :
1366With Start and Emergency Stop Push Button and Ammeter
1367With Start and Emergency Stop Push Button
1368Non FLP Local Control Station with components as listed below and with sheet steel enclosure as per Specification, Data Sheet and direction of Engineer-in-charge :
1369With Start and Emergency Stop Push Button and Ammeter
1370With Start and Emergency Stop Push Button
1371FLP & Non FLP type Switch Socket & Plug :
1372FLP Interlocking type switch sockets and plugs as per attached specifications & data sheets. All switch sockets shall be provided with 3mm thick FRP caNopy with side cover and FLP stopping plug as per specification and direction of PMC Engineer/ Owner :
1373415V, 3 phase 63A FLP switch socket and plug suitable for 3.5CX95 Sq.mm. cable entry
1374415V, 3 phase 63A Non FLP switch socket and plug suitable for 3.5CX95 Sq.mm. cable entry
1375240 V, 1 phase, 5/15A,FLP Switch Socket and plug and suitable for 3 C x 4 sqmm cable entry
1376240 V, 1 phase, 5/15A,Non FLP Switch Socket and plug and suitable for 3 C x 4 sqmm cable entry
1377Ceiling Fan :
13781200mm Sweep ceiling Fan with Down Rod
1379Regulator for sweep ceiling Fan
1380900mm Sweep ceiling Fan with Down Rod
1381300mm Sweep Wall Fan
1382HT/ LT Power and Control cables laying: Horizontal and Vertical Laying of FRLS, XLPE/ PVC cables on cable racks, trenches,directly buried; in floor slits; in G.I. conduit (including chipping of floor wherever required), cable risers, supports, hangers, saddles etc.; Laying through cable protection pipes; Sealing of wall and pipe openings and pipe sleeves, sand filling after cable layingetc. whereever required; cable clamps in vertical and horizontalruns;fixingof cable identification tags as per specifications; testing of cables before and after laying; installation of; Measurement of cables to be taken before cutting the cable from drum to avoid cable joint/ waste. Charges to include LT cable joints only if essential and unavoidable; Testing of cables and submission of megger reports for each run of cable laid; Works to be completed as per specifications and directions of PMC Engineer/ Owner. Rates are inclusive of fixing the supplied MCT block and providing necessary firesealing compound/silicon sealant compound for sealing purposes
138311 kV (UE) armoured, XLPE, FRLS Power Cable of following size:-
138411/11 kV 3Cx240 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
13851.1 KV Grade, Armoured, XLPE, FRLS Aluminium/ Copper Power Cable of following sizes:
13861kV 1Cx400 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
13871kV 3.5Cx70 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
13881kV 3.5Cx50 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
13891kV 3.5Cx35 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
13901kV 4Cx16 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
13911kV 4Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
13921kV 3Cx240 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
13931kV 3Cx50 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
13941kV 3Cx16 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
13951kV 3Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
13961kV 3Cx2.5 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
13971kV 2Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
13981kV 2Cx2.5 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
13991.1 KV Grade, Armoured, PVC, FRLS Copper Control Cable of following sizes
14001kV 12Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
14011kV 7Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
14021kV 5Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
14031kV 3Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
14041.1 KV XLPE, FRLS Lighting Cable / Flexible cable/ Wires of following size
14053Cx2.5 (CU) PVC FLEXIBLE cable(unarmoured)
14061Cx2.5(CU) FRLS PVC WIRE
14071.1kV, XLPE, FS armoured, Cable of following size:-
14081kV 2Cx2.5 sq. mm Cu FS cable
14091kV 3Cx6 sq. mm Cu FS cable
14101kV 3Cx120 sq. mm Al FS cable
1411Termination of Aluminium / Copper conductor PVC/XLPE insulated FRLS armoured cables (up to 1100 V grade) and connection of leads including fixing ofdouble compression cable glands, cutting and stripping of cable insulation, supplying & crimping the tinned copper lug on to the conductor, clamping of the cable-cores, marking with wire number, providing the cable tag as per specification, ferrules etc., including all labour and materials, as per approved drawings & specifications and directions of Engineer-in-Charge. Note : One (1) No. termination means both end termination of one cable
14121kV 2Cx2.5 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed/FS Cable
14131kV 2Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
14141kV 3Cx2.5 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
14151kV 3Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed/FS Cable
14161kV 4Cx6 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
14171kV 3Cx16 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
14181kV 4Cx16 sq. mm Cu cable with XLPE insulated armoured FRLS PVC sheathed
14191kV 3.5Cx35 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
14201kV 3Cx50 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
14211kV 3.5Cx50 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
14221kV 3.5Cx70 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
14231kV 3Cx120 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed/FS Cable
14241kV 3Cx240 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
14251kV 1Cx400 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
14261kV 3Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
14271kV 5Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
14281kV 12Cx2.5 sq. mm Cu cable with PVC insulated armoured FRLS PVC sheathed
1429Termination of HT Cable i.e. fixing of HT End Termination Kit
1430Heat shrinkable end termination kit/jointing kit suitable for 11 kV (UE) XLPE, FRLS armoured cables of following sizes.
1431Outdoor type heat shrinkable termination kit for 11/11 kV 3Cx240 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
1432Indoor type heat shrinkable termination kit for 11/11 kV 3Cx240 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
1433Jointing kit for 11/11 kV 3Cx240 sq. mm Al cable with XLPE insulated armoured FRLS PVC sheathed
1434Laying of following sizes of G.I. Pipes (medium) complete with accessories (bends, reducers, couplers etc.) in required length fixed on steel, concrete or similar structure, laid in trenches, ready to be buried in concrete including cutting, threading, bending and similar works, supply of clamps, small iron structures, spacers and installation of seats, plugs, bushings etc., small civil works, including all labour and materials, as per approved drawings, specifications of this tender and directions of PMC Engineer/ Owner.
1435GI Pipe for cable Protection Class-B Galvanized Iron (G.I. pipes) complete with accessories (bends, reducers, couplers etc.) of following sizes:-
1436150 mm NB
1437100 mm NB
143875 mm NB
143950 mm NB
144025 mm NB
1441Normal earth pit with GI perforated pipe (work includes all civil work like constrcution of the RCC chamber, CI cover, )
1442Earth pit for electronic earthing with copper plate
1443Laying of Hot Dip Galvanized G.I./Cu earth strips (Galvanisation of 610 gm/ sqm of exposed area), PVC insulated Cu cable of following sizes for earthing and lightning protection.
144450x6 mm GS flat as main earth grid conductor and earthing of major equipment
144550x6 mm Cu flat as earthing conductor for coonection with pile reinforment bar which will act as earth grid termination with sea water
14468 SWG Solid GI Wire
144710MM GI wire rope
144835x6 mm GI Flat for earthing & lightning protection conductor
144925 sq.mm. Braided Cu Flexible Cable
1450Hot dip galvanized GI earth bus bar of size 400 X 75X 6 thick with fixing materials as per Drg.
145125 mm dia 1 m long GI rod for vertical air termination
1452Flexible cable for static earth - 20 m long 10 sq. mm flexible Cu cable with lug at one end and crocodile clip at other end
1453Test Linkboxfor lightning protection
1454Installation of the following material for filling of uncovered portion of the trench etc.
14556 mm thick chequred plate
1456Installation, Testing & Commissiong of Motors of following rating:
1457i) 0.37 kW to 3.7 kW.
1458ii) 5.5 kW to 22 kW.
1459iii) Above 22 kW to 50 kW.
1460iii) Above 50 kW
1461Installation, testing, commissioning of solar power generation system including intergration with existing grid/EDG power supply system
146250mx20 m area at 5 acre plot, Minimum Power Generation 100 kW peak
1463Charges towards the folllowing: a) Meter testing to be carried as per requirements of TANGEDCO c) Liasoning with TANGEDCO for incoming power supply - Co ordination with TANGEDCO for collecting TVM, charging of the electrical installation upon obtaining safety certificates, all incidentals connected to the services. d) Liasoning work for CEA/CEIG & PESO Clearance - Arranging for inspection of electrical installation by CEA/CEIG authorities & PESO including co-ordination and all incidental costs involved towards the same. Statutory fee shall be paid by IOCL. e) Preparation of electrical single line diagram including lamination with hard background and fixing the same at the sub station.
1464SECTION 4 : FIREFIGHTING
1465Remote Controlled Tower mounted water cum foam monitor (UL Listed) with Fire Proof Structure (25 m high) Flowrate: 2000 GPM
1466Complete Foam System including Vertical Cylindrical, coned bottom type Foam Tanks (2 x 12 m3 capacity each), 2 Nos. electric motor driven rotary gear type Foam Pumps of 600 LPM Capacity & 15 bar head, inline balanced pressure proportioner (4 Nos.), one (1) No. Foam Filling Pump (25 m3/hr. capacity & 20 MLC head), one (1) No. flexible hose of 15 m length, piping, fittings, valves, instruments etc.
1467Vertical Wet Pit type, Diesel Engine Driven Fire Water Pumps of Capacity 950 m3/hr & TDH 120 MLC including water cooled diesel engine, fuel piping, fuel tank, lube oil system, air intake system, industrial silencer, exhaust piping with insulation & aluminium cladding, caisson pipe, companion flanges, air release valve, PRV, controller with pressure sensing line with two check valves, etc. Design Standard: NFPA 20 Casing Material: Duplex SS Main FW Pumps shall be Non-UL Listed/ Non-FM Approved
1468Vertical Wet Pit type, Electric Motor driven Jockey Pumps of Capacity 190 m3/hr & TDH 125 MLC including drive motor, starter, caisson pipe, companion flanges, air release valve, controller with pressure sensing line with two check valves, etc. Design Standard: NFPA 20 Casing Material: Duplex SS Jockey Pumps shall Not be UL Listed.
1469Fixing of Jumbo Curtain Nozzles on the unloading platform. Discharge Capacity: 6000 LPM @ 7 kg/cm2 g Working Pressure Range: 7 - 11 kg/cm2 g Horz. Traverse / Vertical Traverse: 40/15 m Angle of Spray: 180 Deg MOC: SS 316
1470Fixing of two numbers single outlet landing valve of size 63 mm diaas per IS:5290, Type-A of SS material including supply and Installation of stand post of size 100 NB with pipe, elbow, cross, RF pad Plate (for pipe to pipe connection) and necessary fittings & flanges including connecting / welding / installing the same in hydrant.
1471Installation of FRP hose box of size 900 X 600 X 250 mm with structural support for mounting the box at minimum 1 M above the ground level including grouting the post complete.
1472Water monitors with 38 mm dia Nozzle, 2580 LPM as per IS: 8442, 150 NB pipe, elbow, reducer, RF pad Plate (for pipe to pipe connection) and necessary fittings & flanges including Connecting/welding/installation of same in hydrant net work as per drawing.
1473Fixing of 9 Kg DCP Fire Extinguisher
1474Fixing of 4.5 Kg CO2 Fire Extinguisher
1475Centralized Clean Agent (Novec 1230) based suppression system including Cylinders, cylinder racks, manifolds, Gas Release Panel, Nozzles, MRS, Abort Switch, pipes, fittings, valves etc. as per NFPA 2001 for the following Rooms: Jetty Control Building: a) Battery Room (Min. Risk Volume - 104 m3) b) Laboratory Room (Min. Risk Volume - 150 m3) c) UPS Room (Min. Risk Volume - 170 m3) d) Equipment Room (Min. Risk Volume - 240 m3) e) Control Room (Min. Risk Volume - 336 m3)
1476Valves :
1477Erection, Commisioning & testing of the following sizes of SS Manual Ball Valves (ASTM A182 F316L flanged # 800 ) as per Specification
147815 mm dia
147920 mm dia
148025 mm dia
148150 mm dia
1482Erection, Commisioning & testing of the following sizes of SS Manual Ball Valves (ASTM A351 GR CF3M flanged # 150 ) as per Specification
1483100 mm dia
148465 mm dia
148580 mm dia
1486Erection, Commisioning & testing of the following sizes of CS Glass Flake Lining Manual Butterfly Valves (ASTM A216 WCB flanged # 150) as per Specification
1487100 mm dia
1488150 mm dia
1489250 mm dia
1490350 mm dia
1491Erection, Commisioning & testing of the following sizes of CS Glass Flake Lining Motorized Butterfly Valves (ASTM A216 WCB flanged # 150) as per Specification
1492200 mm dia
1493400 mm dia
1494Erection, Commisioning & testing of the following sizes of SSMotorized Globe Valves (ASTM A351 CF3M flanged # 150 ) as per Specification
1495100 mm dia
1496Erection, Commisioning & testing of the following sizes of SS Pneumatic Ball Valves (ASTM A351 GR CF3M flanged # 150 ) as per Specification
149780 mm dia
1498Erection, Commisioning & testing of the following sizes of Duplex SS Manual Gate Valves (ASTM A182 F51 flanged # 800 ) as per Specification
149950 mm dia
1500Erection, Commisioning & testing of the following sizes of CS Check Valves Glass Flake Lining (ASTM A216 WCB flanged # 150 ) as per Specification
1501150 mm dia
1502350 mm dia
1503Erection, Commisioning & testing of the following sizes of SS Check Valves (ASTM A351 GR CF3M flanged # 150 ) as per Specification
150450 mm dia
150580 mm dia
1506Erection, Commisioning & testing of Pressure relief valves (ASTM A 182 F316L flanged # 150 ) as per Specification
150750mm X 25mm dia SRV
1508Seamless & Welded Pipes
1509Erection, Commisioning & testing of Duplex SS Seamless Pipes to ASTM A790 S318032, Dim. ASME B36.10
151015 mm NB SCH S-40S Plain ends
151125 mm NB SCH S-40S Plain ends
151250 mm NB SCH S-40S Bevel ends
151380 mm NB SCH S-10S Bevel ends
1514Erection, Commisioning & testing of CS Seamless Pipes to ASTM A106 Gr.B Poly Glass Flake Lining, Dim. ASME B36.10
1515100mm NB SCH S-STD Bevel ends
1516150mm NB SCH S-STD Bevel ends
1517200mm NB SCH S-STD Bevel ends
1518250mm NB SCH S-STD Bevel ends
1519350mm NB SCH S-STD Bevel ends
1520400mm NB SCH S-STD Bevel ends
1521600mm NB SCH S-STD Bevel ends
1522Erection, Commisioning & testing of SS Seamless Pipes to ASTM A312 Gr.TP 316L, Dim. ASME B 36.19
152315mm NB SCH S-40S Plain Ends
152420mm NB SCH S-40S Plain Ends
152525mm NB SCH S-40S Plain Ends
152650mm NB SCH S-40S Bevel Ends
152780mm NB SCH S-10S Bevel Ends
1528100mm NB SCH S-10S Bevel Ends
1529PIPEFITTINGS: Welding, Erection and Testing of the following sizes of Elbows/ Tees/ Reducer made of seamless pipes with ends as per enclosed specifications for the following sizes Note: The fittings shall be Socket Welded for Sizes Less than 2" as per ASME B 16.11 and Bevel ends for 2" andabove and dimensions as per ASME B 16.9
153090 Deg LR Elbow ASTM A182 F51
153115mm NB Class 3000
153225mm NB Class 3000
153390 Deg LR Elbow ASTM A815 WPS31803
153450mm NB SCH S-10S
153580mm NB SCH S-10S
153690 Deg LR Elbow ASTM A234 Gr.WPB Poly Glass Lined
1537100mm NB SCH S-STD
1538150mm NB SCH S-STD
1539200mm NB SCH S-STD
1540250mm NB SCH S-STD
1541350mm NB SCH S-STD
1542400mm NB SCH S-STD
1543600mm NB SCH S-STD
154490 Deg LR Elbow (1.5D) ASTM A403 Gr.WP316L
154515mm NBClass 3000
154650mm NB SCH S-40S
154780mm NB SCH S-10S
1548100mm NB SCH S-10S
154945 Deg LR Elbow (1.5D) ASTM A182F51
155025mm NB Class 3000
155145 Deg LR Elbow (1.5D) ASTM A234 Gr.WPB Poly Glass Lined
1552200mm NB SCH S-STD
1553600mm NB SCH S-STD
155445 Deg LR Elbow (1.5D) ASTM A403 Gr.WP316L
155550mm NB SCH S-40S
155680mm NB SCH S-10S
1557Equal Tee ASTM A815WPS31803
155850mm NB SCH S-10S
155980mm NB SCH S-10S
1560Equal Tee ASTM A234 Gr.WPB Poly Glass Lined
1561100mm NB SCH S-STD
1562150mm NB SCH S-STD
1563250mm NB SCH S-STD
1564Equal Tee ASTM A403 Gr.WP316L
156550mm NB SCH S-40S
156680mm NB SCH S-10S
1567100mm NB SCH S-10S
1568Reducing Tee ASTM A234 Gr.WPB Poly Glass Lined
1569100 X 50 mm NBS-STD x S-STD
1570100 X 80 mm NBS-STD x S-STD
1571150 X 100 mm NBS-STD x S-STD
1572350 X 200 mm NBS-STD x S-STD
1573350 X 250 mm NBS-STD x S-STD
1574400 X 200 mm NBS-STD x S-STD
1575600 X 350 mm NBS-STD x S-STD
1576600 X 400 mm NBS-STD x S-STD
1577Reducing TeeASTM A403 Gr.WP 316L
157850 X 20 mm NBS-40S x S-40S
157980 X 5 mm NBS-10S x S-40S
1580Concentric Reducer ASTM A182 F51
158125 X 15 mm NB Class 3000
1582Concentric Reducer ASTM A815 WPS31803
158350 X 25 mm NB S-40S x S-40S
1584Concentric Reducer ASTM A234 Gr.WPB Poly Glass Lined
1585100 X 50 mm NBS-STD x S-STD
1586150 X 100 mm NBS-STD x S-STD
1587350 X 200 mm NBS-STD x S-STD
1588350 X 250 mm NBS-STD x S-STD
1589Concentric Reducer ASTM A182 Gr.F316L
159050 X 25 mm NB S-40S x S-40S
1591Concentric Reducer ASTM A403 Gr.WP316L
159280 X 50 mm NB S-10S x S-40S
1593100 X 50 mm NB S-10S x S-40S
1594Coupling ASTM A182F51
159525mm NB Class 3000 SWE
1596Union ASTM A182F51
159725mm NB Class 3000 FTE
1598Cap ASTM A815 WPS 31803
159950 mm NB SCH S-40S Bevel ends
1600PIPEFITTINGS: Supplying the following sizes of Olets made of as per MSS SP 97 specifications for the following sizes
1601SOCKOLET ASTM A182 Gr. F316L
160250 X 15 Class 3000
160350 X 20 Class 3000
160480 X 15 Class 300
160580 X 20 Class 3000
160680 X 50 Class 3000
1607100 X 15 Class 3000
1608100 X 20 Class 3000
1609Weldolet ASTM A105 Poly Glass Lining
1610150 X 50 SCH S-STD
1611200 X 50 SCH S-STD
1612350 X 50 SCH S-STD
1613350 X 100 SCH S-STD
1614400 X 150 SCH S-STD
1615600 X 50 SCH S-STD
1616600 X 100 SCH S-STD
1617600 X 150 SCH S-STD
1618600 X 200 SCH S-STD
1619ThreadoletASTM A182 Gr.F51
162050 X 15 Class 3000
162180 X 25 Class 3000
1622Erection, Commisioning & testing of following Socket Weld type- SWRF 125 AARH as perASTM A182 Gr.F51 DIM. ASME B16.5 Class 150
162315mm NB
162425mm NB
162550mm NB
1626Erection, Commisioning & testing of following Socket Weld type- SWRF 125 AARH as perASTM A182 Gr.F316L DIM. ASME B16.5 Class 150
162715mm NB
162820mm NB
1629Erection, Commisioning & testing of following Socket Weld type- SWRF 125 AARH as perASTM A182 Gr.F316L DIM. ASME B16.5 Class 300
163025mm NB
163150mm NB
1632Erection, Commisioning & testing of following Weld neck type- WNRF 125 AARH as per ASTM A182 Gr.F51 DIM. ASME B16.5 Class 150
163380mm NB SCH S-10S
1634Erection, Commisioning & testing of following Weld neck type- WNRF 125 AARH as per ASTM A105 DIM. ASME B16.5 Class 150 Poly Glass Lined
1635100mm NB SCH S-STD
1636150mm NB SCH S-STD
1637200mm NB SCH S-STD
1638250mm NB SCH S-STD
1639350mm NB SCH S-STD
1640400mm NB SCH S-STD
1641600mm NB SCH S-STD
1642Erection, Commisioning & testing of following Weld neck type- WNRF 125 AARH as per ASTM A182 Gr.F316L DIM. ASME B16.5 Class 150
164350mm NB SCH S-40S
1644100mm NB SCH S-10S
1645Erection, Commisioning & testing of following Weld neck type- WNRF 125 AARH as per ASTM A182 Gr.F316L DIM. ASME B16.5 Class 300
164680mm NB SCH S-10S
1647Erection, Commisioning & testing of following BLRF 125 AARH flanges as per ASTM A182 Gr.F316L DIM. ASME B16.5 Class 150
1648100mm NB
1649Erection, Commisioning & testing of following BLRF 125 AARH flanges as per ASTM A182 Gr.F51 DIM. ASME B16.5 Class 150
165050mm NB
1651Erection, Commisioning & testing of following Orifice Flange WNRF 125 AARH flanges as per ASTM A182 F316L DIM. ASME B16.36 Class 300
165280mm NB
1653Erection, Commisioning & testing of following GASKET, 4.5 mm Thck Spiral Wound 316 Outer & Inner Ring with Graphite Filler, ASME B16.20, CLASS 150
165415mm NB
165520mm NB
165625mm NB
165750mm NB
165880mm NB
1659100mm NB
1660150mm NB
1661200mm NB
1662250mm NB
1663350mm NB
1664400mm NB
1665600mm NB
1666Erection, Commisioning & testing of following GASKET, 4.5mm Thck Spiral Wound 316 Outer & Inner Ring with Graphite Filler, ASME B16.20, CLASS 300
166725mm NB
166850mm NB
166980mm NB
1670Erection, Commisioning & testing of following HEXAGONAL NUT, ASTM A194 Gr.2H, ASME B18.2.2, FTE, Hot Dip Galvanized
16711" DIA
16721-1/4" DIA
16733/4" DIA
16745/8" DIA
16757/8" DIA
1676Erection, Commisioning & testing of following HEXAGONAL NUT, ASTM A194 Gr.3M, ASME B18.2.2, FTE
16771/2" DIA
16785/8" DIA
1679Erection, Commisioning & testing of following STUD BOLT, ASTM A193 Gr.B7, ASME B18.2.1, MTE, Hot Dip Galvanized
16801" DIA150 MM LONG
16811-1/4" DIA 185 MM LONG
16823/4" DIA 110 MM LONG
16833/4" DIA 120 MM LONG
16845/8" DIA 100 MM LONG
16857/8" DIA 130 MM LONG
1686Erection, Commisioning & testing of following STUD BOLT,ASTM A193 Gr.B8M CL.2, ASME B18.2.1, MTE
16871/2" DIA 65 MM LONG
16881/2" DIA 75 MM LONG
16895/8" DIA95 MM LONG
16905/8" DIA100 MM LONG
1691Erection, Commisioning & testing of following STUD BOLT,ASTM A193 Gr.B3M, ASME B18.2.1, MTE
16921/2" DIA 65 MM LONG
16931/2" DIA 75 MM LONG
16943/4" DIA120 MM LONG
16955/8" DIA95 MM LONG
16965/8" DIA85 MM LONG
16975/8" DIA100 MM LONG
1698DELUGE VALVE SYSTEM :
1699Erection, Commisioning & testing of 150 NB Ni-Al Bronze deluge valve assembly including its pnuematic trim and DV shall be auto reset type.
1700MVW Spray System :
1701Medium Velocity Water Spray Nozzle Type: Open & Non-clog Orifice Size: 1/2" (M) Body Material: Al-Bronze Nozzle K-factor: Later Spray Angle: Later UL Listed
1702QB Detector Type: Pendant Response: Standard Response Body Material: Forged Brass End Connection: 1/2" (M) Temperature Rating: 79 Deg C UL Listed
1703SECTION 5 : CONTROL AND INSTRUMENTATION
1704Erection & Installation along with supply & Fabrication of mounting accessories, Poles etc and commissioning ofField Instruments
1705Erection & Installation along with supply & fabrication of mounting accessories etc and commissioning ofcontrol valves
1706Erection & Installation along with supply & fabrication of mounting accessoriesincluding erection material for Junction box
1707Instrument cables Installation & Laying, testing & commissioning , loop testing with cable tray laying, supports, cable glandings, lugs,ferruling and termination, clamping, tagging including supply of cable gland, PVC hood structural support material etc
1708Optical fiber cable & HDPE duct Installation & Laying/blowing inside HDPE duct, excavation, restoration, testing & commissioning ,OTDR, installation of route marker, splicing, erection of splice chamber, termination, with cable tray laying, supports, cable glanding, lugs, ferruling and termination, clamping, tagging including supply of cable gland, PVC hood structural support material etc.
1709Corrosion Monitoring system Erection & Installation, configruation, commissioning, trial run, along with supply and fabrication of mounting accessories including erection material for CMS system
1710Metering system for POL and LPG Line Erection & Installation, along with supply and fabrication of mounting accessories including erection material for Metering system.
1711Fire detection system Erection & Installation, configruation, commissioning, trial run, along with supply and fabrication of mounting accessories including erection material for Fire detection system.
1712Gas detection system Erection & Installation, configruation, commissioning, trial run, along with supply and fabrication of mounting accessories including erection material for Gas detection system.
1713SCADA system Erection & Installation, configruation, commissioning, trial run, along with supply and fabrication of mounting accessories including erection material for SCADA system
1714Telecom system Erection & Installation, configruation, commissioning, trial run, along with supply and fabrication of mounting accessories including erection material for Telecom system
1715CCTV system Erection & Installation, configruation, commissioning, trial run, along with supply and fabrication of mounting accessories including erection material
1716EPABX system Erection & Installation, configruation, commissioning, trial run, along with supply and fabrication of mounting accessories including erection material
1717PAGA system Erection & Installation, configruation, commissioning, trial run, along with supply and fabrication of mounting accessories including erection material
1718Ship to shore link Erection & Installation, configruation, commissioning, trial run, along with supply and fabrication of mounting accessories including erection material
1719Walky-Talky system Erection & Installation, configruation, commissioning, trial run, along with supply and fabrication of mounting accessories including erection material
1720Surge relief system Erection & Installation, configruation, commissioning, trial run, along with supply and fabrication of mounting accessories including erection material.
1721Barrier Gate with Boom and Proximity Card including card readers etc complete as per specifications.
1722SECTION 6 : HVAC
1723Erection, testing and commissioning of wall mounted air cooled Non duct-able split air conditioners complete with hermetically sealed rotary compressors (suitable for R-407C / R-410A /R-32 refrigerant) of inverter driven and air cooled condensers in the Outdoor unit with powder coated GI casing, built-in electrical items & supports and Indoor unit housing dry panel type HDPE filters (efficiency 90% down to 10 micron), cooling coils, evaporator fans with two speed drive motors, control console, all encased in powder coated GI casings with swivelling type supply air grilles and decorative RA grilles and interconnecting refrigerant piping (duly insulated) between outdoor and indoor units and insulated drain piping, microprocessor based cordless remote control panel and plug top with connecting cable for each split unit. As required including the structural steel framework, pedestal/ bracket to mount the indoor & outdoor units, supports & clamps for indoor & outdoor units, refrigerant piping/cables, stabilizer, hold down nuts & bolts.
1724Split AC units located at Cabin-1: Total cooling capacity: 1.0 TR Dehumidified air quantity: 500 CMH
1725Split AC units located at UPS room: Total cooling capacity: 2.0 TR Dehumidified air quantity: 1050 CMH
1726Split AC units located at Laboratory: Total cooling capacity: 2.0 TR Dehumidified air quantity: 1050 CMH
1727Split AC units located at Office: Total cooling capacity: 1.5 TR Dehumidified air quantity: 750 CMH
1728Erection, testing and commissioning of ceiling mountedcassette type air cooled Non duct-able split air conditioners complete with hermetically sealed rotary compressors (suitable for R-407C / R-410A /R-32 refrigerant) of inverter driven and air cooled condensers in the Outdoor unit with powder coated GI casing, built-in electrical items & supports and Indoor unit housing dry panel type HDPE filters (efficiency 90% down to 10 micron), cooling coils, evaporator fans with two speed drive motors, control console, all encased in powder coated GI casings with swivelling type supply air grilles and decorative RA grilles and interconnecting refrigerant piping (duly insulated) between outdoor and indoor units and insulated drain piping, microprocessor based cordless remote control panel and plug top with connecting cable for each split unit. As required including the structural steel framework, pedestal/ bracket to mount the indoor & outdoor units, supports & clamps for indoor & outdoor units, refrigerant piping/cables, stabilizer, hold down nuts & bolts.
1729Split AC units located at Custom room: Total cooling capacity: 3.0 TR Dehumidified air quantity: 1650 CMH
1730Split AC units located at Control room: Total cooling capacity: 2.0 TR Dehumidified air quantity: 1250 CMH
1731Split AC units located at Equipment room: Total cooling capacity: 3.0 TR Dehumidified air quantity: 1650 CMH
1732Split AC units located at Office: Total cooling capacity: 2.0 TR Dehumidified air quantity: 1250 CMH
1733Erection, testing and commissioning of Supply fan filter unit located at Transformer & Switchgear room: The supply fan-filter unit shall consist of wall mounted tube axial flow fan, drive motor, Inlet Louver, pre-filter, supply cowl with protective wire netting inside the room, supports and supporting structures, nuts and bolts, vibration isolators. Fan capacity: 10000 CMH Static pressure: 20 mmWG
1734Erection, testing and commissioning of Back draft damper located at Transformer & Switchgear room: The wall mounted back draft damper shall be made galvanized steel of frame thickness 16G & Blade thickness 18G. Size: 1450 mm x 550 mm
1735Erection, testing and commissioning of Transfer air grille located at Transformer & Switchgear room: The wall mounted transfer air grille shall be made galvanized steel of frame thickness 16G & Blade thickness 18G. Size: 1450 mm x 550 mm
1736Erection, testing and commissioning of Wall mounted exhaust fan shall consist of tube axial flow fan, drive motor, protective wire netting inside the room, rain protection cowl with bird screen, supports and supporting structures, nuts and bolts, vibration isolators, etc.
1737Exhaust fan located at DG room: Fan capacity: 8000 CMH Static pressure: 8 mmWG
1738Exhaust fan located at Air compressor room: Fan capacity: 6500CMH Static pressure: 8 mmWG
1739Erection, testing and commissioning of Exhaust fan located at Battery room: Wall mounted Exhaust fan shall consist of bifurcated type axial flow fan, drive motor (flame proof type), protective wire netting inside the room, gravity louver at fan outlet, rain protection cowl with bird screen, supports and supporting structures, nuts and bolts, vibration isolators, etc. All parts of this system coming in contact with acid fumes shall be epoxy painted. Fan capacity: 1500 CMH Static pressure: 10 mmWG
1740Erection, testing and commissioning of wall mounted air intake louver shall be made galvanized steel of frame thickness 16G & Blade thickness 18G.
1741Intake louver located at DG room: Size: 1750 mm x 550 mm
1742Intake louver located at Air compressor room: Size: 850 mm x 550 mm
1743Intake louver located at Battery room: Size: 750 mm x 450 mm
1744Intake louver located at Laboratory: Size: 750 mm x 450 mm
1745Erection, testing and commissioning of Wall mounted propeller fan shall consist of propeller fan, drive motor, gravity louver at fan outlet, supports, nuts and bolts, vibration isolators etc.
1746Propeller type exhaust fan located at BCW toilet: Fan capacity: 450 CMH Static pressure: 4 mmWG
1747Propeller type exhaust fan located at BCW WC: Fan capacity: 150 CMH Static pressure: 2.5 mmWG
1748Propeller type exhaust fan located at Toilet: Fan capacity: 550 CMH Static pressure: 4 mmWG
1749Propeller type exhaust fan located at Laboratory: Fan capacity: 1000 CMH Static pressure: 6 mmWG
1750Erection, testing and commissioning of Duct mounted In-line centrifugal / axial flow exhaust fan located at Pantry: Duct mounted In-line centrifugal / axial flow exhaust fan shall consist of fan, drive motor, ducting with grille, supports, nuts and bolts, vibration isolators etc. Fan capacity: 200 CMH Static pressure: 5 mmWG
1751HVAC for Fire water pump house at Jetty area
1752Erection, testing and commissioning of Exhaust fan located at Fire water pump house: Wall mounted exhaust fan shall consist of tube axial flow fan, drive motor, protective wire netting inside the room, rain protection cowl with bird screen, supports and supporting structures, nuts and bolts, vibration isolators, etc. Fan capacity: 10000 CMH Static pressure: 8 mmWG
1753Erection, testing and commissioning of Intake louver located at Fire water pump house: The wall mounted air intake louver shall be made galvanized steel of frame thickness 16G & Blade thickness 18G. Size: 1800 mm x 600 mm
1754HVAC for Electrical cum Control Building at 5 Acre Plot
1755Erection, testing and commissioning of wall mounted air cooled Non duct-able split air conditioners complete with hermetically sealed rotary compressors (suitable for R-407C / R-410A /R-32 refrigerant) of inverter driven and air cooled condensers in the Outdoor unit with powder coated GI casing, built-in electrical items & supports and Indoor unit housing dry panel type HDPE filters (efficiency 90% down to 10 micron), cooling coils, evaporator fans with two speed drive motors, control console, all encased in powder coated GI casings with swivelling type supply air grilles and decorative RA grilles and interconnecting refrigerant piping (duly insulated) between outdoor and indoor units and insulated drain piping, microprocessor based cordless remote control panel and plug top with connecting cable for each split unit. As required including the structural steel framework, pedestal/ bracket to mount the indoor & outdoor units, supports & clamps for indoor & outdoor units, refrigerant piping/cables, stabilizer, hold down nuts & bolts.
1756Split AC units located at Equipment room: Total cooling capacity: 2.0 TR Dehumidified air quantity: 1050 CMH
1757Split AC units located at Control room: Total cooling capacity: 1.5 TR Dehumidified air quantity: 750 CMH
1758Split AC units located at Work station area: Total cooling capacity: 1.5 TR Dehumidified air quantity: 750 CMH
1759Split AC units located at Waiting room: Total cooling capacity: 1.0 TR Dehumidified air quantity: 500 CMH
1760Split AC units located at Meeting room: Total cooling capacity: 1.0 TR Dehumidified air quantity: 500 CMH
1761Erection, testing and commissioning of supply fan-filter unit shall consist of wall mounted tube axial flow fan, drive motor, Inlet Louver, pre-filter, supply cowl with protective wire netting inside the room, supports and supporting structures, nuts and bolts, vibration isolators.
1762Supply fan filter unit located at Transformer & PMCC room: Fan capacity: 5000 CMH Static pressure: 20 mmWG
1763Supply fan filter unit located at MV Switchgear room: Fan capacity: 5000 CMH Static pressure: 20 mmWG
1764Erection, testing and commissioning of wall mounted back draft damper shall be made galvanized steel of frame thickness 16G & Blade thickness 18G.
1765Back draft damper located at Transformer & PMCC room: Size: 800 mm x 500 mm
1766Back draft damper located at Transformer & PMCC room: Size: 650 mm x 300 mm
1767Back draft damper located at MV Switchgear room: Size: 650 mm x 500 mm
1768Erection, testing and commissioning of Exhaust fan located at Battery room: Wall mounted Exhaust fan shall consist of bifurcated type axial flow fan, drive motor (flame proof type), protective wire netting inside the room, gravity louver at fan outlet, rain protection cowl with bird screen, supports and supporting structures, nuts and bolts, vibration isolators, etc. All parts of this system coming in contact with acid fumes shall be epoxy painted. Fan capacity: 2000 CMH Static pressure: 10 mmWG
1769Erection, testing and commissioning of Intake louver located at Battery room: The wall mounted air intake louver shall be made galvanized steel of frame thickness 16G & Blade thickness 18G. Size: 750 mm x 450 mm
1770Erection, testing and commissioning of Wall mounted propeller fan shall consist of propeller fan, drive motor, gravity louver at fan outlet, supports, nuts and bolts, vibration isolators etc.
1771Propeller type exhaust fan located at Guard toilet: Fan capacity: 150 CMH Static pressure: 2.5 mmWG
1772Propeller type exhaust fan located at Store: Fan capacity: 150 CMH Static pressure: 2.5 mmWG
1773Propeller type exhaust fan located at Gents Toilet: Fan capacity: 400 CMH Static pressure: 4 mmWG
1774HVAC for Warehouse at 5 Acre Plot
1775Erection, testing and commissioning of Exhaust fan located at Warehouse: Wall mounted exhaust fan shall consist of tube axial flow fan, drive motor, protective wire netting inside the room, rain protection cowl with bird screen, supports and supporting structures, nuts and bolts, vibration isolators, etc. Fan capacity: 2500 CMH Static pressure: 8 mmWG
1776Erection, testing and commissioning of Intake louver located at Warehouse: The wall mounted air intake louver shall be made galvanized steel of frame thickness 16G & Blade thickness 18G. Size: 750 mm x 450 mm
1777HVAC for Box Culvert
1778Erection, testing and commissioning of cabinet type supply fan-filter unit shall consist of direct driven / belt driven centrifugal flow fan, drive motor, Inlet Louver, pre-filter, VCD at fan outlet, supports and supporting structures, nuts and bolts, vibration isolators. The fan outlet shall be connected to ducting system. Fan capacity: 24000 CMH Static pressure: 33 mmWG
1779Erection, testing and commissioning of Roof Extractor shall consist of roof mounted axial flow exhaust fan, drive motor, rain protection hood with bird screen, supports & supporting structure, grouting frame, bolts, nuts, transition piece (if required), vibration isolators, water sealing arrangement at the base and inspection door. The fan inlet shall be connected to ducting system. The exhaust fan shall be spark proof construction & motor shall be flame proof type. Fan capacity: 24000 CMH Static pressure: 22 mmWG
1780HVAC for duct works
1781Erection, testing and commissioning of Ducting: Ductingshall be made of G.I. sheet of at least grade 180 as per IS 277. Bidder shall estimate & quote the ducting quantity, hanger support etc. according to "Air conditioning & Ventilation layout of Control Building (Dwg. No. P.011265-M-21006-502)" and "Ventilation layout of Box Culvert (Dwg. No. P.011265-M-21006-505)".
178218G
178320G
178422G
178524G
1786Erection, testing and commissioning of Supply air Grille: The supply air grille shall be made up of Aluminium construction and painted with two (2)coats of powder coating paints. Supply air grille shall be provided with volume control damper. The grille frame and louvers shall be manufactured of at least 20G and 22G respectively.
1787Size: 800 x 300
1788Erection, testing and commissioning of Return air Grille: The return air grille shall be made up of Aluminium construction and painted with two (2)coats of powder coating paints. Return air grille shall be provided without volume control damper. The grille frame and louvers shall be manufactured of at least 20G and 22G respectively.
1789Size: 600 x 300
1790Size: 300 x 300
1791Erection, testing and commissioning of Flexible connection: Flexible connectionshall be fire retardant type. Flexible connections of at least 150 mm length shall be provided at each connection between ductwork and fan units. Thequantity shall be estimated according to "Air conditioning & Ventilation layout of Control Building (Dwg. No. P.011265-M-21006-502)" and "Ventilation layout of Box Culvert (Dwg. No. P.011265-M-21006-505)".
1792PART C - COMPOSITE WORKS
1793SECTION 1: MARINE CIVIL WORKS
1794PRELIMINARY SITE WORKS
1795Positioning of sufficient quantity of structural steel material for piling gantries along with suitable piling rigs includingjackupplatform and other necessary accessories for installing vertical piles of dia 1200 to 1400mm bored cast - insitu piles.
1796Positioning of sufficientnumberofBatching Plant, Floating Transit Mixers, Concrete Pumps and Concrete Accessories etc. for concrete works in sea and land.
1797Positioning of sufficientnumberof Cranes (suitable capacity), equipment and accessories for precasting yard.
1798Positioning ofsufficient number of Marine transport Barges and tugs for carrying materials and precast elements.
1799Positioning of sufficient number of equipment for erection of precast element including Barge mounted cranes etc. and establishing site office for Client.
1800DEMOBILIZATION
1801Demobilisationfrom site of all piling plant & equipment aftercompletionbroughtunderitem1.1 (a) above.
1802Demobilisation from site of all Batching Plant, Floating TransitMixers,ConcretePumpsand ConcreteAccessoriesetc.aftercompletionbrought under item No.1.1 (b) above.
1803Demobilisationfrom site of all Cranes (suitable capacity), equipment and accessories for precasting yard after completion brought under item 1.1 (c) above.
1804Demobilisation from site of all Marine transport Barges and tugs after completion brought under item 1.1 (d) above.
1805Demobilisation from site of all Barge mounted cranes etc. after completionbrought under item 1.1 (e) above.
1806PRELIMINARIES
1807Carrying out Geodetic survey for as-built location of piles and deck slab of : a) MLT-1 approach trestle b) MLT-1 approach bridge connecting the jetty and N. Breakwater c) LNG jetty approach trestle d) MD-6 of LNG jetty to identify the location with coordinates of each of the existing piles of the above structures, including all equipment like survey boat, dGPS, total station including incorporating the details of the survey in the autocad version of the Layout/Bathymetry drawings, etc complete .
1808Carrying out geotechnical investigation for confirmatory boreholes by drilling in to existing seabed consisting of all types of soil at the specified locations as shown in the borehole location drawing. The boreholes should be drilled upto a sound stratum or hard soil (minimum and maximum drill depth shall be 25m and 50m respectively) as per the specifications enclosed in the tender using jackup rigs, soil boring machines, sampling tools, taking undisturbed samples at every 1.5m, carrying out SPT at every 1.5m and conducting laboratory tests on collected soil samples to determine their engineering properties such as moisture content, Atterberg limits, density, shear strength, unconfined compressive strength, particle size distribution, chemical properties, electrical resistivity, chloride and sulphate content in soil and water and preparing report for engineering and physical properties etc all complete in accordance with IS 1892, IS 4651 and other relevant codes and standards under the supervision of PMC Engineer/ Site Engineer.
1809Carrying out bathymetric survey at the specified location covering an area as shown in the drawings, including required equipment like dGPS, multi beam echo sounder, motion sensor, sound velocity profiler, navigation equipment, data logging and processing equipment, etc complete as per specifications.
1810MARINE CIVIL WORKS - SUBSTRUCTURE AND MARINE DECK
1811PART 1: PILING
1812Shifting and setting up of piling plant and equipment using gantry and platform or jackup rig, tripods, winch / rile driving rig, rotary drilling rig, bailers, chisellers etc (as per the methodology of work) at each pile location for breasting and mooring dolphins for providing of 1200mm and 1400 mm vertical MS steel liner for boring work and for concreting the piles including fabrication and erection of pile driving plant, staging with various steel plates, girders, angles, channels etc., including cost of steel items, welding charges, strutting and fixing in position at each location, cost of mobilization and demobilization of all equipment, transportation charges of all materials to worksite, all labour charges andtools etc. complete.
1813For 1200mm dia piles:
1814Unloading Platform
1815Approach Bridge
1816Access Trestle
1817Jetty Control Building
1818Fire Water Pump House
1819Approach Trestle - Zone 2
1820Approach Trestle - Zone 3
1821Approach Trestle - Zone 4
1822Walkways
1823For 1400mm dia piles:
1824Breasting Dolphins
1825Mooring Dolphins
1826Providing, Fabricating and delivering of 8mm thick MS liner with 8 mm thick stiffeners at bottom of liners, as per drawing, for 1400mm / 1200mm dia vertical cast-in-situ RCC pile for each pile in unloading platform, breasting and mooring dolphins, access trestle, approach bridge, pump house, jetty control building and approach trestle including cost of supply ofsteel plates confirming to IS: 2062, Grade E250, cost of all other materials, transportation charges of structural steel plate to Work Site, all labour charges, hire charges,tools, rolling, cutting, welding etc., complete.
1827Unloading Platform
1828Approach Bridge
1829Access Trestle
1830Jetty Control Building
1831Fire Water Pump House
1832Approach Trestle - Zone 2
1833Approach Trestle - Zone 3
1834Approach Trestle - Zone 4
1835Walkways
1836Breasting Dolphins
1837Mooring Dolphins
1838Boring / drilling through all types of soil and including soil removal for vertical piles for unloading platform, breasting and mooring dolphins, access trestle, approach bridge, marine deck for jetty control building and pumphouse building, approach trestle (Zone 2 to Zone 4) from the existing sea bed level to founding level (firm stratum) including cost of winch / Pile driving rig, rotary drilling machine, RCD machine. Note: 1) The sample of bored materials at regular interval shall be collected and produced for verification at No extra cost and in case of any dispute the samples so collected shall be referred to an authorised / registered laboratory approved/selected by Owner and the decision of such authorised laboratory is final and binding on both the parties, however the cost of testing shall be borne by the contractor. Pile terminal shall be decided in consultation with the PMC Engineer.
18391200 mm Dia
1840Unloading Platform
1841Approach Bridge
1842Access Trestle
1843Jetty Control Building
1844Fire Water Pump House
1845Approach Trestle - Zone 2
1846Approach Trestle - Zone 3
1847Approach Trestle - Zone 4
1848Walkways
18491400 mm Dia
1850Breasting Dolphins
1851Mooring Dolphins
1852Providing and laying design mix concrete of RCC M40 grade in accordance with IS 456 (Latest Edition) using coarse aggregate, sand and 53 grade Ordinary Portland cement confirming to IS 455 for RCC piles in unloading platform, breasting and mooring dolphins, access trestle, approach bridge, pump house, jetty control building and approach trestle by using tremie with hopper arrangements, excluding cost of fabrication, fixing of reinforcement, which will be paid separatelybut including cost of cement, stone chips, sand, cost of all labour charges, centering and shuttering,mixing, conveying, placing, consolidation, screening and washing of coarse aggregate and sand, transportation charges of all materials to the Work Site, hire charges and running charges of batching plant, vibrator, consumables and all other equipment, cost of tools etc. complete including curing. (The design mix shall be provided by the contractor from the approved laboratory of Govt. of India/ IITs/ NITs/ NABL Accredited Labs ). Note : Payment shall only be made for the concrete work from pile founding level to the pile cut-off level including 600mm above the cut-off level. Any concrete above the 600mm shall Not paid.
1853Unloading Platform
1854Approach Bridge
1855Access Trestle
1856Jetty Control Building
1857Fire Water Pump House
1858Approach Trestle - Zone 2
1859Approach Trestle - Zone 3
1860Approach Trestle - Zone 4
1861Walkways
1862Breasting Dolphins
1863Mooring Dolphins
1864Supply, deliver and transportation of reinforcement steel with a minimum yield strength of 500 N/mm2 and minimum elongation of 16% or equivalent confirming to IS 1786 with corrosion resistant element for Fabrication and fixing of reinforcement cages as per drawing for cast-in-situ piles for unloading platform, breasting and mooring dolphins, access trestle, approach bridge, pump house, jetty control building and approach trestle, including cost of fabrication, fixing dowels, shear ties, cutting, bending, tying, lapping and welding in position wherever necessary with black 18 SWG annealed binding wire, all labour charges, transportation charges of all materials to Work Site, cost of binding wires, all other items required for the work andtools etc. complete.
1865Unloading Platform
1866Approach Bridge
1867Access Trestle
1868Jetty Control Building
1869Fire Water Pump House
1870Approach Trestle - Zone 2
1871Approach Trestle - Zone 3
1872Approach Trestle - Zone 4
1873Walkways
1874Breasting Dolphins
1875Mooring Dolphins
1876Dressing / chipping of the RCC pile head of 1400mm / 1200 mm dia including cutting of steel liners & trimming of extra concreted pile above the designed cut off level and exposing the reinforcement to receive fresh concrete for beams, bracing, pile muffs etc., bending the reinforcement for new works, cost of all equipment, all labour charges,tools etc. complete.
1877Unloading Platform
1878Approach Bridge
1879Access Trestle
1880Jetty Control Building
1881Fire Water Pump House
1882Approach Trestle - Zone 2
1883Approach Trestle - Zone 3
1884Approach Trestle - Zone 4
1885Walkways
1886Breasting Dolphins
1887Mooring Dolphins
1888Supply, transport to site, deliver, install testing arrangements, equipments and spares, barges, working platforms and access ways as necessary with provision of specialist personal, to carry out Non-destructive (low strain) dynamic integrity testing of bored cast in – situ RCC working piles (dia 1200 to 1400 mm) selected by PMC Engineer/ Site Engineer including necessary test reports, interpretations with all other test reports etc. as per specification complete.
1889Unloading Platform
1890Approach Bridge
1891Access Trestle
1892Jetty Control Building
1893Fire Water Pump House
1894Approach Trestle - Zone 2
1895Approach Trestle - Zone 3
1896Approach Trestle - Zone 4
1897Walkways
1898Breasting Dolphins
1899Mooring Dolphins
1900Supply, transport to site, deliver, construct test and anchor piles/system, install testing arrangements equipment and spares, barges, reaction anchors, structural frame systems with working platforms and access ways as necessary with provision of specialist personal, to carry out initial and routine static vertical pile load test on test pile (bored cast in-situ pile) selected by PMC Engineer/ Owner including construction of test pile, anchor pile, anchorage system, kent ledge frame, testing equipment, labour, etc with interpretation of test results complete. The cost of all materials such as RCC (cement, sand, aggregate, water), reinforcement, structural steel, nuts and bolts, prestressing wires, testing equipment, etc all complete shall be paid under this item. Test load for initial pile load test shall be 2.5 times the working load on piles (2.5 x 500MT (min) = 1250 MT min). Test load for routine pile load test shall be 1.5 times the working load on piles (1.5 x 500MT (min) = 750 MT min). Test pile and anchor piles or anchorage system if any shall be completely cut and removed above seabed after the completion of test. Note : Test pile shall be carried out prior to any working pile construction and the location of test pile shall Not obstruct the working pile.
1901Routine Static Vertical Pile Load Test
1902Unloading Platform
1903Approach Trestle - Zone 2
1904Approach Trestle - Zone 3
1905Initial Static Vertical Pile Load Test
1906Approach Trestle - Zone 4
1907Carrying out high strain Routine Dynamic load test on vertical pile in unloading platform, approach trestle, breasting and mooring dolphins and pump house with test load and testing procedure as per ASTM 4945 latest, including cost of all materials for making platform with steel members, weight materials, all labour charges, workmanship instrumentation, electronic devices, mechanical handling equipment, all other materials required for successful completion of load test, including removal of added portion of pile for testing after completion of test. Note : Dynamic load test shall be carried out on working piles and the pile head shall be extended by at least 2m above the pile cut-off level. The test piles shall be selected by the PMC Engineer/Owner for each structure based his judgement and it is to be treated as final.
1908Unloading Platform
1909Approach Bridge
1910Access Trestle
1911Jetty Control Building
1912Fire Water Pump House
1913Approach Trestle - Zone 2
1914Approach Trestle - Zone 3
1915Approach Trestle - Zone 4
1916Breasting Dolphins
1917Mooring Dolphins
1918Supply, transport to site, deliver, construct test and anchor piles/system, install testing arrangements equipment and spares, barges, reaction anchors, structural frame systems with working platforms and access ways as necessary with provision of specialist personal, to carry out initial pull-out pile load test on test pile (bored cast in-situ pile) selected by PMC Engineer/ Site Engineer including construction of test pile, anchor pile, anchorage system, kent ledge frame, testing equipment, labour, etc with interpretation of test results complete. The cost of all materials such as RCC (cement, sand, aggregate, water), reinforcement, structural steel, nuts and bolts, prestressing wires, testing equipment, etc all complete shall be paid under this item. Load test shall be conducted on test piles with a maximum load of 150 MT. Test pile and anchor piles or anchorage system if any shall be completely cut and removed above seabed after the completion of test. Note : Test pile shall be carried out prior to any working pile construction and the location of test pile shall Not obstruct the working pile.
1919Supply, transport to site, deliver, construct test and anchor piles/system, install testing arrangements equipment and spares, barges, reaction anchors, structural frame systems with working platforms and access ways as necessary with provision of specialist personal, to carry out initial horizontal pile load test on test pile (bored cast in-situ pile) selected by PMC Engineer/ Site Engineer including construction of test pile, anchor pile, anchorage system, kent ledge frame, testing equipment, labour, etc with interpretation of test results complete. The cost of all materials such as RCC (cement, sand, aggregate, water), reinforcement, structural steel, nuts and bolts, prestressing wires, testing equipment, etc all complete shall be paid under this item. Load test shall be conducted on test piles with a maximum load of 2 times the working load on piles (2 x 10MT=20MT). Test pile and anchor piles or anchorage system if any shall be completely cut and removed above seabed after the completion of test. Note : Test pile shall be carried out prior to any working pile construction and the location of test pile shall Not obstruct the working pile.
1920PART 2: PILE MUFFS, DECK SLAB AND BEAMS
1921Providing cast – in situ reinforced cement concrete of design mix grade M40 in accordance with IS 456 (Latest Edition) using coarse aggregate, sand and 53 grade Ordinary Portland cement confirming to IS 455, as per design mix in cast-in-situ for portion of beams, slabs, Column etc for unloading platform, breasting and mooring dolphins, access trestle, approach bridge, pump house, jetty control building and approach trestle as indicated in the drawing, excluding cost of fabrication, fixing of reinforcement, but including cost of cement, stone chips, sand,centering and shuttering cost of all labour charges, mixing, conveying, placing, consolidation, screening and washing of coarse aggregate and sand, transportation charges of all materials to the Work Site, hire charges and running charges of batching plant, vibrator, consumables and all other equipment, cost of tools etc. complete including curing. (The design mix shall be provided by the contractor from the approved laboratory of Govt. of India IITs/ NITs/ NABL Accredited labs.
1922Unloading Platform
1923Approach Bridge
1924Access Trestle
1925Jetty Control Building
1926Fire Water Pump House
1927Approach Trestle - Zone 2
1928Approach Trestle - Zone 3
1929Approach Trestle - Zone 4
1930Walkways
1931Breasting Dolphins
1932Mooring Dolphins
1933Providing pre-cast reinforced cement concrete of design mix grade M40 in accordance with IS 456 (Latest Edition) using coarse aggregate , sand and 53 grade Ordinary Portland cement confirming to IS 455, as per design mix in cast-in-situ beams, slabs, Column etc for unloading platform, breasting and mooring dolphins, pump house and approach trestle as indicated in the drawing, excluding cost of fabrication, fixing of reinforcement, but including cost of cement, stone chips, sand, cost of centering and shuttering, cost of all labour charges, mixing, conveying, placing, consolidation, screening and washing of coarse aggregate and sand, transportation charges of all materials to the Work Site, hire charges and running charges of batching plant, vibrator, consumables and all other equipment, cost of tools etc. complete including curing. (The design mix shall be provided by the contractor from the approved laboratory of Govt. of India/ IITs/ NITs/ NABL Accredited labs).
1934Unloading Platform
1935Approach Bridge
1936Access Trestle
1937Jetty Control Building
1938Fire Water Pump House
1939Approach Trestle - Zone 2
1940Approach Trestle - Zone 3
1941Approach Trestle - Zone 4
1942Walkways
1943Breasting Dolphins
1944Mooring Dolphins
1945Providing and laying design mix concrete of RCC M30 grade in accordance with IS 456 (Latest Edition) using coarse aggregate, sand and 53 grade Ordinary Portland cement confirming to IS 455, as per design mix for screed (wearing coat) in approach trestle as indicated in the drawing, excluding cost of fabrication, fixing of reinforcement,but including cost of cement, stone chips, sand, cost of all labour charges, mixing, conveying, placing, centering and shuttering, consolidation, screening and washing of coarse aggregate and sand, transportation charges of all materials to the Work Site, hire charges and running charges of batching plant, vibrator, consumables and all other equipment, cost oftools etc. complete including curing. (The design mix shall be provided by the contractor from the approved laboratory of Govt. of India / IITs/ NITs/ NABL Accredited labs).
1946Unloading Platform
1947Approach Bridge
1948Access Trestle
1949Approach Trestle - Zone 2
1950Approach Trestle - Zone 3
1951Approach Trestle - Zone 4
1952Supply, deliver and transportation of reinforcement steel with a minimum yield strength of 500 N/mm2 and minimum elongation of 16% or equivalent confirming to IS 1786 with corrosion resistant element for Fabrication and fixing of reinforcement in superstructure works including pile muff, beams, slabs, Column etc for unloading platform, breasting and mooring dolphins, access trestle, approach bridge, pump house, jetty control building and approach trestle, including cost of fabrication & fixing, cost of corrosion resistant deformed bars, all handling charges, cutting, bending, lapping, tying and welding in position wherever necessary with black 18 SWG annealed binding wire, all labour charges, cost of binding wire, transportation charges for all materials to worksite, all other items required for the work and tools etc. complete.
1953Unloading Platform
1954Approach Bridge
1955Access Trestle
1956Jetty Control Building
1957Fire Water Pump House
1958Approach Trestle - Zone 2
1959Approach Trestle - Zone 3
1960Approach Trestle - Zone 4
1961Walkways
1962Breasting Dolphins
1963Mooring Dolphins
1964PART 3: BERTH FITTINGS
1965Supplying, Testing and fixing of quick releasing mooring hooks (QRMH) of capacity as per specifications and at the required locations as per the approved drawings, including cost of mooring hook, cost of all labour charges, transportation charges andtools etc., complete.
1966Breasting Dolphins
1967Mooring Dolphins
1968Supplying, Testing and fixing of bollards of capacity as per specifications and at the required locations as per the approved drawings, including cost of mooring hook, cost of all labour charges, transportation charges andtools etc., complete.
1969Fire Water Pump House
1970Supplying, Testing and fixing of cone fenders of having Energy absorption capacity of 2350 kN-m with Not to exceed reaction of 2175 kN including all required accessories etc a, including cost of fender with all its accessories, all labour charges, transportation charges up to site andtools etc., complete.
1971Breasting Dolphins
1972Supplying, Testing and fixing of arch fenders of having Energy absorption capacity of 26 kN-m with Not to exceed reaction of 200 kN including all required accessories etc a, including cost of fender with all its accessories, all labour charges, transportation charges up to site and tools etc., complete.
1973Fire Water Pump House
1974Supply, fabricate and fix in position according to the drawings and specifications rubberised steel ladders from approved manufacturer using anchor bolts and resin sleeves and as directed at site of work, including all labour, materials, tools, equipments, fuel, transport, curing etc., all complete
1975Breasting Dolphins
1976Mooring Dolphins
1977Supply, fabricate, transport, handle and erect in position stainless steel handrails using pipes and toe plates using stainless steel conforming to SS316L including profile cutting, assembling, hoisting, fixing in position, welding, inspection and applying a priming coat of approved steel primer and top coat of minimum thickness as specified in the specifications made of approved paint all as per specifications and drawings including cost of all materials, fitting charges, all labour charges, transportation charges and tools etc. complete. The cost shall include all fabrication, transportation of the steel structure assembly in part or as a whole, lifting using floating crafts and cranes, erection and fixing on the concrete structure with appropriate supporting arrangement, base plates and anchor bolts etc complete.
1978Unloading Platform
1979Approach Bridge
1980Access Trestle
1981Jetty Control Building
1982Fire Water Pump House
1983Approach Trestle - Zone 2
1984Approach Trestle - Zone 3
1985Approach Trestle - Zone 4
1986Walkways
1987Breasting Dolphins
1988Mooring Dolphins
1989Supplying, Testing and fixing of Docking AId System (DAS) as per specifications and at the required locations as per the approved drawings, including cost of all equipment, cost of all labour charges, transportation charges andtools etc., complete.
1990Breasting Dolphins
1991Supplying, Testing and fixing of Mooring Load Monitoring System (MLMS) as per specifications and at the required locations as per the approved drawings, including cost of all equipment, cost of all labour charges, transportation charges andtools etc., complete.
1992Mooring Dolphins
1993PART 4: MISCELLANEOUS ITEMS
1994Supply, fabricate, transport, handle and erect in position catwalk / walkway structure made of structural steel hollow members of any dimension with a minimum yield strength of 310 N/mm2 and/or shapes, plates, anchor bolts and built up sections conforming to IS 2062 E350 including profile cutting, assembling, hoisting, fixing in position, welding, inspection and hot dip galvanizing as specified in the specifications made of approved paint all as per specifications and drawings including cost of all materials, fitting charges, all labour charges, transportation charges and tools etc. complete. The cost shall include all fabrication, transportation of the catwalk assembly, lifting using floating crafts and cranes, erection and fixing on the concrete structure with appropriate sliding and pin arrangement etc complete.
1995Walkways
1996Providing and fixing in position Steel angle ISA 50x50x6 with anchors in to edge concrete and providing and fixing 12 mm thick bitumen impregnated fibre board confirming to IS 1838 including cost of sealing compound in expansion joints as per the direction of PMC Engineer/ Owner etc., including the cost of 12 mm thick bitumen impregnated fibre board, all labour charges,tools, transportation charges of all materials to work site etc. complete.
1997Unloading Platform
1998Approach Trestle - Zone 2
1999Approach Trestle - Zone 3
2000Approach Trestle - Zone 4
2001Supply, fabricate, transport, handle and install in position Hot dip Galvanised Anchor bolts of minimum diameter and length as specified in the drawings and as per specifications including cost of all materials, fitting charges, all labour charges, transportation charges andtools etc. complete. The cost shall include all fabrication, cutting and drilling holes in the base plates, erection and fixing on the new concrete structure. Note: The anchor bolts, Washers and nuts shall conform to IS 1363 Grade 8.8.
2002Unloading Platform
2003Walkways
2004Breasting Dolphins
2005Mooring Dolphins
2006Providing and laying approved brand of epoxy grout of minimum compressive strength 100 MPa for a minimum thickness of 30mm (or shown in the drawing) below the base plates for all structures including shuttering on sides, cost of all labour charges, mixing, conveying, placing, consolidation, consumables and all other equipment, cost of tools etc. complete.
2007Unloading Platform
2008Walkways
2009Breasting Dolphins
2010Mooring Dolphins
2011Supply, fabricate, transport, handle and erect in position Galvanisedwith minimum 85 micron total coated thickness Electro forged Grating purchased from approved manufacturer and thickness as shown in construction drawings and all as per specifications including clips, supports using steel conforming to IS 2062 Grade E250 A/B including cutting, hoisting, fixing in position and including cost of all materials, fitting charges, all labour charges, transportation charges and tools etc. complete.
2012Unloading Platform
2013Approach Bridge
2014Access Trestle
2015Fire Water Pump House
2016Walkways
2017Supply, fabricate, transport, handle and weld on to the bottom and top base plates of walkway support with Flourogold bearing plate of thickness 2.4 mm as per drawings and specifications including cutting, hoisting, fixing in position and including cost of all materials, fitting charges, all labour charges, transportation charges and tools etc. complete.
2018Walkways
2019Supply, fabricate, transport, handle and install UPVC drain pipes of diameter 100 mm as per drawings and specifications including cutting, hoisting, fixing in position and including cost of all materials, fitting charges, all labour charges, transportation charges and tools etc. complete.
2020Unloading Platform
2021Approach Bridge
2022Access Trestle
2023Jetty Control Building
2024Fire Water Pump House
2025Approach Trestle - Zone 2
2026Approach Trestle - Zone 3
2027Approach Trestle - Zone 4
2028Breasting Dolphins
2029Mooring Dolphins
2030Supply, fabricate, transport and install edge Nosing (protection) of circular pipe of minimum thickness 16mm with full butt weld including F12mm dia (450mm long) MS lugs @150mm c/c as per drawings and specifications including cutting, fixing in position and including cost of all materials, fitting charges, all labour charges, transportation charges and tools etc. complete.
2031Breasting Dolphins
2032Mooring Dolphins
2033Providing and laying rockfill revetment as primary armour using stones of size of 500kg to 1000kg in layer Not exceeding 1400mm thick to the required slope, line and level including packing filling the gaps with smaller boulders as per specifications & drawings, etc. including cost of all materials, all labour charges, transportation charges and tools etc. complete. as directed by the PMC Engineer.
2034Approach Bridge
2035Providing and laying Non-woven geotextile layer as filter layer under the footing as indicated in the drawings and specifications to the required line and level including packing filling the gaps etc. including cost of all materials, all labour charges, transportation charges and tools etc. complete. as directed by the PMC Engineer.
2036Approach Bridge
2037MARINE CIVIL WORKS - SUPERSTRUCTURE
2038Providing cast – in situ reinforced cement concrete of design mix grade M35 in accordance with IS 456 (Latest Edition) using coarse aggregate, sand and 53 grade Ordinary Portland cement confirming to IS 455, as per design mix in cast-in-situ for portion of beams, slabs, Column etc for unloading platform, breasting and mooring dolphins, access trestle, approach bridge, pump house, jetty control building and approach trestle as indicated in the drawing, excluding cost of fabrication, fixing of reinforcement,but including cost of cement, stone chips, sand, cost of all labour charges, centering and shuttering, mixing, conveying, placing, consolidation, screening and washing of coarse aggregate and sand, transportation charges of all materials to the Work Site, hire charges and running charges of batching plant, vibrator, consumables and all other equipment, cost of tools etc. complete including curing. (The design mix shall be provided by the contractor from the approved laboratory of Govt. of India/ IITs/ NITs/ NABL Accredited labs).
2039Unloading Platform
2040Control Building
2041Fire Water Pump House
2042Marine Approach Trestle
2043Supply, deliver and transportation of reinforcement steel with a minimum yield strength of 500 N/mm2 and minimum elongation of 16% or equivalent confirming to IS 1786 with corrosion resistant element for Fabrication and fixing of reinforcement in superstructure works including pile muff, beams, slabs, Column etc for unloading platform, breasting and mooring dolphins, access trestle, approach bridge, pump house, jetty control building and approach trestle, including cost of fabrication & fixing, cost of corrosion resistant deformed bars, all handling charges, cutting, bending, lapping, tying and welding in position wherever necessary with black 18 SWG annealed binding wire, all labour charges, cost of binding wire, transportation charges for all materials to worksite, all other items required for the work and tools etc. complete.
2044Unloading Platform
2045Control Building
2046Fire Water Pump House
2047Marine Approach Trestle
2048Supply, Fabricating and erection of structural steel work in rolled sections like joists, channels, angles, tees and trusses. RHS, SHS, or CHS etc. with caps, bases mild steel plates, angle brackets, cleats, gusset plates, anchor bolts etc. as per detailed designs and drawing or as directed including cutting, fabrication, hoisting, erecting, fixing in position, making riveted / bolted / welded connections and hot dip galvanizing as per technical specifications. Weight of bolt / welding shall Not be considered for payment. Welding shall be done by approved electrodes only .
2049Fire Water Pump House
2050Marine Approach Trestle
2051Supplying, handling, transporting to site of work and fixing approved MECHANICAL ANCHOR FASTENERS M.S.bolts of Grade 5.8 or more, GALVANIZED with minimum thickness of 5 microns (approved for use in cracked concrete), of 16mm dia or more upto 32mm at specified positions on concrete floors, roofs, beams (sides and bottom), walls, columns etc. according to manufacturer"s specifications including all accessories like nuts, washers etc. of required size, testing, necessary scaffolding, drilling of the holes in concrete surface with electric drill, cleaning of holes with air blowout & wire-brush, and making good any damage done to the structure etc. all complete for all heights, depths and locations as specified and directed.
2052Marine Approach Trestle
2053Supply, fabricating and fixing of embedments, MS inserts,pipes,sleeves, flats, guide rails, angle / beamspieces, rungs of various diameters, plates of dimensions as requiredincluding cost of all labour, materials and equipment, transportation, loading, unloading, handling, welding, cutting, drilling, scaffolding and setting complete as per specifications, drawings and as directed by PMC Engineer/ Owner.
2054Fire Water Pump House
2055Marine Approach Trestle
2056SECTION 2 : ONSHORE CIVIL WORKS
2057AREA CLEARANCE Area clearance including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 300 mm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared.
2058BACK FILLING Filling available excavated earth (excluding rock), in foundations and plinths, with Normal soil in layers of 150mm thickness, including watering, ramming well with mechanical roller / rammers and consolidating etc. complete, as per specifications, drawings and as directed by PMC Engineer/ Owner.
2059Admin Cum Control Building
2060Box Culvert
2061Pipe Trestle
2062Boundary Wall
2063Warehouse Building
2064DG Shed
2065Underground Tank
2066Nitrogen Facility
2067Road
2068Recharge Pit
2069Lighting Post
2070Pipe Bridges PB1, PB2 & PB3
2071EXCAVATION for foundation in earth, soil of all types, sand, gravel and soft murrum, including removing the excavated material up to a distance of 1.0 km. beyond the building area & stacking and spreading as directed within the yard area, dewatering, preparing the bed for the foundation and necessary backfilling, ramming, watering including shoring and strutting etc. complete as per specification and as directed by PMC Engineer/ Owner. Payment will be paid as per PCC Plan area for lift more than 3.0m.
2072Admin Cum Control Building
2073Box Culvert
2074Pipe Trestle
2075Boundary Wall
2076Warehouse Building
2077DG Shed
2078Underground Tank
2079Nitrogen Facility
2080Road
2081Recharge Pit
2082Lighting Post
2083Pipe Bridges PB1, PB2 & PB3
2084Providing & laying Plain Cement Concrete (PCC) of Grade M10 with 20 mm and down size graded machine crushed stone aggregate including placing, compacting, finishing the surface in smooth finish to the correct level and curing with contractors labour, materials, plants, machinery and equipment with all lead and lift including shuttering compacting and curing etc. complete as per specification and as directed by PMC Engineer/ Owner.
2085Nitrogen Facility
2086Road
2087Providing & laying Plain Cement Concrete (PCC) of Grade M20 with 20 mm and down size graded machine crushed stone aggregate including placing, compacting, finishing the surface in smooth finish to the correct level and curing with contractors labour, materials, plants, machinery and equipment with all lead and lift including shuttering compacting and curing etc. complete as per specification and as directed by PMC engineer/ Owner.
2088Admin Cum Control Building
2089Box Culvert
2090Pipe Trestle
2091Boundary Wall
2092Warehouse Building
2093DG Shed
2094Underground Tank
2095Nitrogen Facility
2096Recharge Pit
2097Lighting Post
2098Pipe Bridges PB1, PB2 & PB3
2099Providing cast – in situ reinforced cement concrete of design mix grade M35 in accordance with IS 456 (Latest Edition) using coarse aggregate, sand and 53 grade Ordinary Portland cement confirming to IS 455, as per design mix in cast-in-situ for portion of beams, slabs, Column etc forAdmin cum Control Building, Pipe trestle, Boaundary wall, warehouse bulding, etc. as indicated in the drawing, excluding cost of fabrication, fixing of reinforcement,but including cost of cement, stone chips, sand, cost of all labour charges, mixing, centering and shuttering,conveying, placing, consolidation, screening and washing of coarse aggregate and sand, transportation charges of all materials to the Work Site, hire charges and running charges of batching plant, vibrator, consumables and all other equipment, cost of tools etc. complete including curing. (The design mix shall be provided by the contractor from the approved laboratory of Govt. of India/ IITs/ NITs/ NABL Accredited Labs).
2100Admin Cum Control Building
2101Box Culvert
2102Pipe Trestle
2103Boundary Wall
2104Warehouse Building
2105DG Shed
2106Underground Tank
2107Nitrogen Facility
2108Lighting Post
2109Pipe Bridges PB1, PB2 & PB3
2110Supply, deliver and transportation of reinforcement steel with a minimum yield strength of 500 N/mm2 and minimum elongation of 16% or equivalent confirming to IS 1786 with corrosion resistant element for Fabrication and fixing of reinforcement in superstructure worksfor Admin cum Control Building, Pipe trestle, Boaundary wall, warehouse bulding, etc including cost of fabrication & fixing, cost of corrosion resistant deformed bars, all handling charges, cutting, bending, lapping, tying and welding in position wherever necessary with black 18 SWG annealed binding wire, all labour charges, cost of binding wire, transportation charges for all materials to worksite, all other items required for the work andtools etc. complete.
2111Admin Cum Control Building
2112Box Culvert
2113Pipe Trestle
2114Boundary Wall
2115Warehouse Building
2116DG Shed
2117Underground Tank
2118Nitrogen Facility
2119Lighting Post
2120Pipe Bridges PB1, PB2 & PB3
2121Supply, Fabricating and erection of structural steel work in rolled sections like joists, channels, angles, tees and trusses. RHS, SHS, or CHS etc. with caps, bases mild steel plates, angle brackets, cleats, gusset plates, anchor bolts etc. as per detailed designs and drawing or as directed including cutting, fabrication, hoisting, erecting, fixing in position, making riveted / bolted / welded connections and hot dip galvanizing as per technical specifications. Weight of bolt / welding shall Not be considered for payment. Welding shall be done by approved electrodes only.
2122Boundary Wall
2123DG Shed
2124Pipe Bridges PB1, PB2 & PB3
2125Supplying, handling, transporting to site of work and fixing approved MECHANICAL ANCHOR FASTENERS M.S.bolts of Grade 5.8 or more, GALVANIZED with minimum thickness of 5 microns (approved for use in cracked concrete), of 16mm dia or more upto 32mm at specified positions on concrete floors, roofs, beams (sides and bottom), walls, columns etc. according to manufacturer"s specifications including all accessories like nuts, washers etc. of required size, testing, necessary scaffolding, drilling of the holes in concrete surface with electric drill, cleaning of holes with air blowout & wire-brush, and making good any damage done to the structure etc. all complete for all heights, depths and locations as specified and directed.
2126DG Shed
2127Pipe Bridges PB1, PB2 & PB3
2128Supply, fabricating and fixing of embedments, MS inserts,pipes,sleeves, flats, guide rails, angle / beamspieces, rungs of various diameters, plates of dimensions as requiredincluding cost of all labour, materials and equipment, transportation, loading, unloading, handling, welding, cutting, drilling, scaffolding and setting complete as per specifications, drawings and as directed by PMC Engineer/ Owner.
2129DG Shed
2130Pipe Bridges PB1, PB2 & PB3
2131MISCELLANEOUS ITEMS
2132PREPARING SUB GRADE WITH ROAD ROLLER Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 centimetre depth, dressing to camber and consolidating with road roller to achieve minimum of 95% proctor density including making good the undulations etc. And re-rolling the sub grade and disposal of surplus earth with lead upto 50 metres all complete as per specification and direction of PMC Engineer.
2133Road
2134WET MIX MACADAM Providing & laying 225mm thick WMM with well graded crushed stone aggregate including placing, compacting as per IRC:58to the correct level and curing with contractors labour, materials, plants, machinery and equipment with all lead and lift including shuttering compacting and curing etc. complete as per specification and as directed by PMC Engineer.
2135Road
2136RCC PAVING Providing & laying 300mm thick RCC Pavment (M30 Grade) with well graded crushed stone aggregate including placing, compacting to the correct level and curing with contractors labour, materials, plants, machinery and equipment with all lead and lift including shuttering compacting and curing etc. complete as per specification and as directed by PMC Engineer/ Owner.
2137Nitrogen Facility
2138SAND FILLING Providing & laying 150mm thick sand above well compacted sub grade as per IRC:58 with with contractors labour, materials, plants, machinery and equipment with all lead and lift including compacting and curing etc. complete as per specification and as directed by PMC Engineer/ Owner.
2139Road
2140CONCRETE PAVERS IN ROAD SHOULDER AREA Laying and fixing of 100mm thick, M40 grade cement concrete pavers blocks including 40mm thick sand bedding and gap between blocks shall be filled with well sieved fine sand, compaction with vibratory plate compactors as per IRC:SP:63-2004, cleaning the top surface for any debris, blocks etc. including materials, labours, tools, tackles and plants complete as per specifications and as directed by PMC Engineer/ Owner.
2141Road
2142ARCHITECTURAL WORKS
2143JETTY CONTROL BUILDING
2144Brick Work (Rate is inclusive of curing of masonry including supplying & providing water, scaffolding as required & associated labour)
2145Brick work with Class Designation 50 bricks in Cement mortar 1:4 (1 cement : 4 coarse sand) in superstructureABOVE PLINTH ANDUP TO FLOOR V LEVEL
2146Half brick masonry (115 mm thick) with Class designation 50 bricks in Cement mortar 1:4 ( 1 cement : 4 coarse sand) IN superstructureABOVEPLINTH & UP TO FLOOR V LEVEL inlcuding providing and placing in position 2 Nos. 6mm dia. M.S. bars, includingproviding 75mm thk. horizontal band in CC mix 1:2:4 atevery third course of half brick masonry.
2147Plastering & Finishing Note: a. Rate is inclusive of curing of plaster including supplying & providing water, scaffolding as required & associated labour. Providing and laying cement plaster on surfaces with Coarse/ Fine sand (as applicable) including curing, scaffolding etc.
2148In 18 mm thick cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement: 5 coarse sand) and a top layer 6mm thick cement plaster 1:3 (1 cement: 3 coarse sand) finished rough with sponge.
2149In 12 mm thick Cement plaster of mix1:4 (1 cement: 4 coarse sand)
2150In 6 mm thick plaster of mix 1:3 (1 cement: 3 fine sand)
2151Providing and fixing 150 mm wide 24 SWG Chicken Wire mesh between junctions of column/beam and walls, fixed with U nails 150 mm centre to centre before plastering the junction.
2152Painting & Finishing (including Scaffolding & Curing) Note: All rates are inclusive of executing in a required pattern to be approved by IOC & all colour shades to be used as part of the pattern.
2153Providing and applying plaster of Paris putty of 2 mm average thickness over plastered surface to prepare the surface even and smooth complete
2154Applying one coat of Acrylic emulsion compatible primer of approved brand and make on wall surface & painting with silicon & acrylic emulsion based water thinnable interior paint with 2 or more coats.
2155Finishing walls with Acrylic Smooth exterior paint (Anti-fungus & Weatherproof) of required shade with Two or more coat applied @ 1.67 ltr/10 sqm over & including base coat of water proofing cement paint applied @ 2.20kg/10 sqm.
2156Melamine polishing on wood work (one or more coat).
2157Flooring & Finishing Note: a. Payment shall be made on finished floor area/ dado/ skirting & finishing only. No extra payment shall be made towards additional thickness of bedding to match level of adjoining floors. b. Flooring shall be laid including patterns/ all colours to be provided during execution of works & as such cost quoted to include the same. c. Sample of Granite/Kota stones, Tiles, flooring sheets, wooden panel floors etc shall be approved by Site Engineer before ordering & delivering to site. d. Job includes supplying & providing water for curing as applicable.
2158Providing 52 mm thick cement concrete flooring with concrete hardener topping under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm Nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix :2gradedstoneaggregate6mmNominalsize)byvolume, hardening compound is mixed @ 2 litre per 50kg of cement or as per manufacturers specifications. This includes cost of cement slurry, 2mm thick PVC strip at desired spacing, cost of Nosing in steps Complete. Note: Item rate includes supplying and providing skin reinforcement in weld mesh 3 mm dia, 50 mm x 50 mm square to be provided in 40 mm thick CC floor mentioned above.
2159Providing Shock/Sound/Fire proof/ Anti-slip/ Hard wearing/floor made of Rubber (recycled SBR) mat of approved make & Nominal thickness 20 mm over Structural flooring in Control Room area including laying, jointing with adhesives, finsihing etc complete & as per the directions of the PMC Engineer/ Owner
2160Supplying & Providing Stone flooring with 18mm thick Granite stone (sample of stone shall be approved by Site Engineer) over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry including polishing. Note: Item rate includes providing Mirror polishing to the exposed surface of the Granite stone & also grey cement slurry mixed with pigment to match the shade of Granite stone.
2161Providingandfixing18mmthickgangsawcutmirrorpolished premoulded and prepolished) machine cut for kitchen platforms, vanity counters,sills, jambs, soffits, facias, dado, skirting, risers & similar locations of required size of shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated with white cement mixed with matching pigment,epoxy touch ups, including rubbing,curing moulding & polishing to edge to give high gloss finish etc. complete at all levels. Note: a. Item rate includes providing Mirror polishing to the exposed surface of the Granite stone & also grey cement slurry mixed with pigment to match the shade of Granite stone. b. Item rate also includes providing opening of required size & shape for wash basins/ kitchen sink in kitchen platform, vanity counters & similar location in Granite/stone work including necessary holes for pillar taps etc.including rubbing and polishing of cut edges etc.complete
2162Providing and laying Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement 3 coarse sand) jointed with grey cement slurry mixed with pigment to match the shade of the slabs,including rubbing wax polishing complete. Note: Item rate includes providing Kota stone in treads of steps and risers using single length (Not exceeding 2 m).
2163Providing & laying vitrified floor tile (10-12 mm thick as per manufactirer) in different sizes with water absorption"s less than 0.08% and conforming to IS : 15622 of approved make in all colours and shades, laid on 20mm thick cement mortar as specified with coarse sand, including grouting the joints with white cement and matching pigments etc., complete for flooring/skirting as specified. Note: a. For WC area, the tiles shall be Anti-skid type at No extra cost to IOC.
2164Flooring with size of Tiles up to 60 x 60 CM in cement mortar 1:4
2165Skirting/ Dado with size of Tiles up to 60 x 60 CM in cement mortar 1:3
2166Providing & fixing Ist quality ceramic glazed wall tiles conforming to IS : 15622 (thickness as specified by the manufacturer ) of approved make in all colours,shades except burgundy,bottle green,black of any size as approved by Site Engineer in skirting,risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm including pointinginwhite cementmixed withpigment ofmatchingshade.
2167Providing and fixing with 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding, and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of PMC Engineer.
2168Flooring Tiles with size up to 60 x 60 CM in 10 mm thick cement mortar 1:4
2169Skirting/ Dado Tiles with size up to 60 x 60 CM in 12 mm thick cement mortar 1:4
2170Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar refractive index) > 78, solar reflection > 0.70 and initial emittance > 0.75 on waterproof and sloped surface of terrace, laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1 cement : 4 coarse sand) and grouting the joints with mix of white cement & marble powder in ratio of 1:1, including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting upto 150 mm height along the parapet walls in the same manner.
2171Supply and Installation of “Kebao” Access Type False flooring system with accessories: Supply of FS 800 “Kebao” Steel Cement Cavity Flooring system (Imported) manufactured by M/s. Kebao International Industrial Group Ltd. (Shanghai) of Tile size 600mm x 600mm x 35mm thick. Finish-Top covering with 1mm high pressure antistatic hot pressed laminate. Edge bonded with black conductive PVC beading factory finish. The finish height of floor will be 600mm. Point Load 360Kgs UDL 1600Kgs (as per specification).
2172Supplying & Installing of Kebao Access Type False flooring system (Bare Finish):- Supply of FS 800 “Kebao” Steel Cement Cavity Flooring system (Imported) manufactured by M/s. Kebao International Industrial Group Ltd. (Shanghai) of Tile size 600mm x 600mm x 33mm thick. Bare finish with gray colour special weather coating on tile. Edge bonded with black conductive PVC beading factory finish. The finish height of floor will be 600 mm. Point Load 360 Kgs. Uniform Load 1600 Kgs (as per manufacture specification).
2173Light weightFilling (Toilet / Pantry) as per IS 9142
2174Doors/ Windows/ Ventilators/ Partitions/ False Ceiling/ Rolling Shutter/ Grills/ Gates/ Structural Steel/ Fencing/ Roof sheeting/ SS Hand railing works Note: a. All Aluminium sections to be used shall be out of Magnesium Silicon Alloy with matt finish & with aNodised film of approved colour of thickness Not less than 15 microns. b. Alluminium doors and windows shall be fixed on granite/ marble framework. The items shall also include providing and fillingapprovedsilicon sealant as required to ensurewater tightness,protection ofinstalled items. c. No extra payment will be made towards wastage.
2175Providing & Fixing 15mm thick densified regular edged eco friendly light weight calcium silicate false ceiling tiles of approved texture spintone/cosmos / Hexa or equivalent of size 595 x 595 mm in true horizontal level suspended on inter locking metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per sqm including both side) consisting of main "T" runner suitably spaced at joints to get requiredlengthandofsize24x38mm madefrom 0.33mm thick (minimum) sheet, spaced 1200mm centre to centre, and cross "T" of size 24x28mm made out of 0.33mm (Minimum) sheet, 1200mm long spaced between main"T" at 600mm centre to centre to form a grid of 1200x600mm and secondary cross "T" of length 600mm andsize 24 x28mm made of 0.33mm thick (Minimum) sheet to be inter locked at middle of the 1200x 600mm panel to from grid of size 600x600mm resting on periphery walls / partitions on Perimeterwall angle pre- coated steel of size(24x24X3000mm made of 0.40mm thick (minimum) sheet with the help of rawl plugs at 450mm centre to centre with 25mm long dry wall screws @ 230mm interval and laying 15mm thick densified edges calcium silicate ceiling tiles of approved texture (Spintone/Cosmos/hexa) in the grid including,cutting/ making opening for services like diffusers, grills,light fittings, fixtures, smoke detectors etc., wherever required, Main "T" runners to be suspended from ceiling using G.I. slotted cleats of size 25x35x1.6mm ceiling with 12.5 mm dia and 50mm long dash fasteners, 4mm G.I. adjustable rods with galvanised steel level clips of size 85x30x0.8 mm spaced at 1200mm centre to centre along main"T", bottom exposed with 24mm of all T-sections shall be pre-painted with polyester baked paint for all heights,as per specifications,drawings & as directed by engineer-in- charge. Note :- Only calcium silicate false ceiling area will be measured from wall to wall. No deduction shall be made for exposed frames /opening (cut outs) having area less than 0.30 sqm.The calcium silicate tile shall have NRC value
2176of 0.50(Minimum), light reflection > 85%, Non - combustible as per B.S. 476 part IV, 100% humidity resistance & also having thermal conductivity<0.043 w/m 0 KC
2177Providing & fixing false ceiling at all height including providing & fixing of framework made of special section, power pressed from M.S. sheets and galvanised with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleat of size 25mm wide x 1.6mm thick with flanges of 27mm and 37mm, at 1200mm c/c, one flange fixed to the ceiling with dash fastener 12.5mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25 x10 x0.50mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I chanels 45 x15 x 0.90mm running at the spacing of 1200 mm c/c, to which the ceiling section 0.5mm thick bottom wedge of 80mm with tapered flanges of 26 mm each having lips of 10.5mm, at 450mm c/c, shall be fixed in a direction perpendicular to G.I intermediate channel with connecting clip made out of 2.64mm dia x 230mm long G.I wire at every junction, including fixing perimeter channels 0.50mm thick 27mm high having flanges of 20mm and 30mm long, the perimeter of ceiling fixed to wall/ partitions with the help of Rawl plugs at 450mm centre, with 25mmlong dry wall screws @ 230mm interval, including fixing of Calcium Silicate Board to ceiling section and perimeter channels with the help of dry wall screws of size 3.5 x25mm at 230mm c/c, including jointing & finishing to a flush finish of tapered and square edges of the board with recommended jointing compounds, jointing tapes,finishing with jointing compounds in three layers covering up to 150mm on both sides of joints and two coats of primer suitable for boards, all as per manufacture"s specification and also including the cost of making opening for light fittings, grills, diffusers, cut outs made with frame of perimeter channels suitably fixed, all complete as per drawings, specificaton and direction of the Engineer in charge but excluding the cost of painting with: 1 8 mm thick Calcium Silicate Board made with Calcareous & Siliceous materials reinforced with cellulose fiber manufactured through autoclaving process.
2178Providing wood work in frames of doors, windows, clerestory windows & other frames, wrought framed and fixed in position with Sal wood
2179Providing and fixing panelling or panelling and glazing in panelled or panelled & glazed shutters using Decorative plywood ,5 ply, 9 mm thick both side decorative veneer (Type 1) conforming to IS 1328 BWR type for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured). Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick :
2180Providing & fixing ISI mark flush door shutters with 35mm thick including ISI marked Stainless Steel butt hinges with necessary screws conforming to IS:2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains/cross bands & face veneers on both faces of shutters
2181Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions,at top, bottom & sides with with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be ANodized, Coloured, smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing/panelling, C.P. brass/stainless steel screws including fixingall complete as per drawing & the directions of PMC Engineer. (Cost of glazing or panels to be paid for separately)
2182For shutters of doors, windows & ventilators with Powder coated aluminium sections including providing fixing hinges/ pivots & making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately)
2183Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of PMC Engineer . (Cost of aluminium snap beading shall be paid in basic item):
2184With float glass panes of 4.0 mm thickness
2185With float glass panes of 6.0 mm thickness
2186Providing and fixing double action hydraulic floor spring With stainless steel cover plate of approved brand and manufacture IS : 6315 marked, for doors including cost of cutting floors as required, embedding in floors and cover plates with brass pivot & single piece M.S. sheet outer box with slide plate etc. complete as per the direction of PMC Engineer/ Owner
2187Providing and fixing aluminium handles, ISI marked, aNodised (anodic coating Not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete : 9.100.1 125 mm
2188Providing and fixing aluminium tower bolts, ISI marked, aNodised (aNodic coating Not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 9.97.4 150x10 mm
2189Providing and fixing bright finished brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete.
2190Providing and fixing bright finished brass tower bolts (barrel type) with necessary screws etc. complete : 9.74.2 200x10 mm
2191Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of PMC Engineer (Door handle, Pivot, lock and stopper etc. are included in the item except Floor spring). Note: a. Rate to include water tight sealing of glass to glass joints with Sillicone sealants whereever applicable. b. Glazing of Control room West side is to be operated under same item at No extra cost to IOC including all SS clamps/ brackets between glass panels.
2192Providing & fixing fire resistant door frame of section 143x57mm having built in rebate made out of 16 S.W.G. GI sheet (zinc coating Not less than 120gm/sqm) duly filled with vermuculite based concrete mix, suitable for mounting 60 minutes fire rated door shutters. The frame is fitted with intumuscent fire seal strip of size 10X4 mm (minimum) alround the frame & fixing with dash fastner of approved brand fire resistant primer etc. complete as per direction. (Dash fastner to be paid seperately.
2193Providing and fixing 50mm thick glazed fire resistant door shutters of 60 minutes fire rating conforming to IS:3614 (Part-II) tested and certified as per laboratory approved by Site In-Charge, with suitable munting on door frame consisting of vertical stiles, lock rail, top rail 100mm wide, bottom rail 200mm wide, made out of 16 SWG G.I. sheet (zinc coating Not less than 120gm/sqm, duly filled FR insulationmaterial and fixing withnecessary S.S. ball bearing hinges of approved make, including applying a coat of approved fire resistant primer etc. complete as per direction of PMC Engineer/ Owner (panelling to be paid for seperately.
2194Providing and fixing glazing in fire resistant door shutters, fixed panels, ventilators and partitions etc. with with clear fire resistant glass panes 6mm thick of approved brand, having minimum 60 minutes fire resistance, G.I. beadingof appropriate size made out of 20mm G.I. sheet (zinc coating Not less than 120gm/sqm), fire resistant sealant, including applying a coat off fire resistant primer on G.I. beading etc., complete in all respect as per direction of PMC Engineer/ Owner
2195Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating Not less than 120 gm/m²) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c , including applying a coat of approved fire resistant primer/powder coating of Not less than 30 micron on G.I. beading, & special ceramic tape of 5 x 20 mm size etc complete in all respect as per NBC 2016, IS 16231 (Part 3):2016 and as per direction of Engineer-in-charge with glass of required thickness having 120 minutes of fire resistance both integrity & radiation control (EW120) and minimum 20 minutes of insulation (EI20). The manufacturer have to give test report/certification of fire glass and the glass should have the stamp showing the value of E, EW & EI. The glass shall be tested in approved NABL accredited lab or by any other accreditation body which operates in accordance with ISO/IEC 17011 and accredits labs as per ISO/IEC 17025 for testing and calibration scopes shall be eligible. The maximum glazing size shall Not be more than 1100x2200 mm (w x h) or 2.42 sqm.
2196Providing and fixing panic bar/ latch (double point) fitted with a single body, Trim Latch and Lock on back side of Panick Latch of approved brand having minimum 60 minutes fire resistance.
2197Supplying and fixing rolling shutters of approved make, madeof required size M.S. laths interlocked together through their entire length,jointed together at the end by end locks mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete including the cost of providing and fixing necessary 27.5cm long wire as per IS 4454 Part-I & M.S. top cover of required thickness for rolling shutters:- 80x1.25mm MS laths with1.25 mm thick top cover. Note: Item rate includes mechanical device chain and crank operation for operating rolling shutters.
2198Extra for providing grilled rolling shutters manufactured out of 8 mm dia. M.S. bar instead of laths as per design approved by Engineer-in- charge.(area of grill to be measured).
2199Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.).
2200Providing and applying fibre reinforced elastomeric liquid water proofing membrane with resilient acrylic polymers having Sun Reflectivity Index (SRI) of 105 on top of concrete roof in three coats @10.76 litre/ 10 sqm. One coat of self-priming of elastomeric waterproofing liquid (dilution with water in the ratio of 3:1) and two coats of undiluted elastomeric waterproofing liquid (dry film thickness of complete application/system Not less than 500 microns). The operation shall be carried out after scrapping and properly cleaning the surface to remove loose particles with wire brushes, complete in all respect as per the direction of Engineer-in-Charge.
2201Providing and fixing 50 mm thick extruded polystyrene rigid insulation board of required size underdeck on ceiling surface, complying with ISO 4898:2008 & ASTM C 578-08b - type VI, having thermal conductivity of 0.0289 W/m K as per ASTM C 578 (measured as per IS 3346), compressive strength of > 350 kPa listed as per ASTM D 1621, density of 34-36 kg/cum as per ASTM D 1622, water absorptions < 1% by volume as per ASTM D 2842, oxygen index of 24.1 to 28.1 listed as per ASTM D 2863, cell size 0.4 mm of dia (max) as per ASTM D 3576. Fire retardent property as per DIN 4102, Part 1 of class B2 and as per ASTM E84 class A, fixed with suitable water based adhesive and fastener, complete in all respect as per the direction of Engineer-in-Charge.
2202Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized system of structural glazing (with open joints) for linear as well as curvilinear portions of the building for all heights and all levels, including: (a) Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)-cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including: (b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers. (c) Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment, including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass.
2203(d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight. (e) Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete.
2204Providing, assembling and supplying vision glass panels (IGUs) comprising of hermetically-sealed 6-12- 6 mm insulated glass (double glazed) vision panel units of size and shape as required and specified, comprising of an outer heat strengthened float glass 6mm thick, of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade, an inner Heat strengthned clear float glass 6mm thick, spacer tube 12mm wide, dessicants, including primary seal and secondary seal (structural silicone sealant) etc. all complete for the required performances, as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the PMC Engineer. The IGUs shall be assembled in the factory/ workshop of the glass processor. (Payment for fixing of IGU Panels in the curtain glazing is included in cost of item No.25.2) For payment, only the actual area of glass on face # 1 of the glass panels (excluding the areas of the grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm. (i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement.
2205Providing and fixing partition upto ceiling height consisting of G.I. frame and required board, including providing and fixing of frame work made of special section power pressed/ roll form G.I. sheet with zinc coating of 120 gms/ sqm(both side inclusive), consisting of floor and ceiling channel 50mm and ceiling at the spacing of 610 mm centre to centre with dash fastener of 12.5 mm dia meter 50 mm length or suitable anchor fastener or metal screws with nylon plugs and the studs 48 mm wide having one flange of 34 mm and other flange 36 mm and 0.50 mm thick fixed vertically within flanges of floor and ceiling channel and placed at a spacing of 610 mm centre to centre by 6 mm dia bolts and nuts, including fixing of studs along both ends of partition fixed flush to wall with suitable anchor fastener or metal screws with nylon plugs at spacing of 450 mm centre to centre, and fixing of boards to both side of frame work by 25 mm long dry wall screws on studs, floor and ceiling channels at the spacing of 300 mm centre to centre. The boards are to be fixed to the frame work with joints staggered to avoid through cracks, Galvanised M.S. fixing channel of 99 mm width (0.9 mm thick having two flanges of 9.5 mm each with zinc coating of 120 gms/sqm(both side inclusive)) to be provided at the horizontal joints of two boards, fixed to the studs using metal to metal flat head screws, including jointing and finishing to a flush finish with recommended jointing compound, jointing tape, angle beads at corners (25 mm x 25 mm x 0.5 mm), joint finisher and two coats of primer suitable for board as per manufacture"s specification and direction of PMC Engineer all complete.
2206Providing & Fixing GRC Jali
2207Supplying & Installation of Passenger Lift(6 persons)
2208FIREWATER PUMPHOUSE AND ONSHORE BUILDINGS
2209BRICK MASONRY Note: Rate is inclusive of curing of masonry including supplying & providing water, scaffolding as required & associated labour. Brick work with Class Designation 50 bricks in Cement mortar 1:4 (1 cement : 4 coarse sand) in superstructureABOVE PLINTH ANDUP TO FLOORLEVEL
2210Admin Cum Control Building
2211Boundary Wall
2212Warehouse Building
2213Jetty-FWPH Structure
2214Recharge Pit
2215Half brick masonry (115 mm thick) with Class designation 50 bricks in Cement mortar 1:4 ( 1 cement : 4 coarse sand) IN superstructureABOVEPLINTH & UP TO FLOOR LEVEL inlcuding providing and placing in position 2 Nos. 6mm dia. M.S. bars, includingproviding 75mm thk. horizontal band in CC mix 1:2:4 atevery third course of half brick masonry.
2216Admin Cum Control Building
2217PLASTERING & FINISHING Note: Rate is inclusive of curing of plaster including supplying & providing water, scaffolding as required & associated labour. In 18 mm thick cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement: 5 coarse sand) and a top layer 6mm thick cement plaster 1:3 (1 cement: 3 coarse sand) finished rough with sponge.
2218Admin Cum Control Building
2219Warehouse Building
2220Jetty-FWPH Structure
2221In 12 mm thick Cement plaster of mix1:4 (1 cement: 4 coarse sand)
2222Admin Cum Control Building
2223Warehouse Building
2224Jetty-FWPH Structure
2225In 6 mm thick plaster of mix 1:3 (1 cement: 3 fine sand) in ceiling
2226Admin Cum Control Building
2227Warehouse Building
2228Jetty-FWPH Structure
2229PAINTING & FINISHING (INCLUDING SCAFFOLDING & CURING) Note: All rates are inclusive of executing in a required pattern to be approved by IOC & all colour shades to be used as part of the pattern.
2230Applying one coat of Acrylic emulsion compatible primer of approved brand and make on wall surface & painting with silicon & acrylic emulsion based water thinnable interior paint with 2 or more coats.
2231Admin Cum Control Building
2232Warehouse Building
2233Jetty-FWPH Structure
2234Finishing walls with textured exterior paint (Anti-fungus & Weatherproof) of required shade with Two or more coats applied @ 3.28 ltr/10 sqm, over and including base coat of water proofing cement paint applied @ 2.20kg/10 sqm.
2235Admin Cum Control Building
2236Warehouse Building
2237Jetty-FWPH Structure
2238FLOORING & FINISHING Note: a. Payment shall be made on finished floor area/ dado/ skirting & finishing only. No extra payment shall be made towards additional thickness of bedding to match level of adjoining floors. b. Flooring shall be laid including patterns/ all colours to be provided during execution of works & as such cost quoted to include the same. c. Sample of Granite/Kota stones, Tiles, flooring sheets, wooden panel floors etc shall be approved by Site Engineer before ordering & delivering to site. d. Job includes supplying & providing water for curing as applicable.
2239Providing 52 mm thick cement concrete flooring with concrete hardener topping under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm Nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix :2gradedstoneaggregate6mmNominalsize)byvolume, hardening compound is mixed @ 2 litre per 50kg of cement or as per manufacturers specifications. This includes cost of cement slurry, 2mm thick PVC strip at desired spacing, cost of Nosing in steps Complete. Note: Item rate includes supplying and providing skin reinforcement in weld mesh 3 mm dia, 50 mm x 50 mm square to be provided in 40 mm thick CC floor mentioned above.
2240Admin Cum Control Building
2241Jetty Unloading Platform
2242Warehouse Building
2243DG Shed
2244Jetty-FWPH Structure
2245Providing and laying Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement 3 coarse sand) jointed with grey cement slurry mixed with pigment to match the shade of the slabs,including rubbing wax polishing complete. Note: Item rate includes providing Kota stone in treads of steps and risers using single length (Not exceeding 2 m).
2246Admin Cum Control Building
2247Providing & laying vitrified floor tile (10-12 mm thick as per manufactirer) in different sizes with water absorption"s less than 0.08% and conforming to IS : 15622 of approved make in all colours and shades, laid on 20mm thick cement mortar as specified with coarse sand, including grouting the joints with white cement and matching pigments etc., complete for flooring/skirting as specified. Note: a. For WC area, the tiles shall be Anti-skid type at No extra cost to IOC.
2248Flooring with size of Tiles up to 60 x 60 CM in cement mortar 1:4
2249Admin Cum Control Building
2250Skirting/ Dado with size of Tiles up to 60 x 60 CM in cement mortar 1:3
2251Admin Cum Control Building
2252Providing & fixing Ist quality ceramic glazed wall tiles conforming to IS : 15622 (thickness as specified by the manufacturer ) of approved make in all colours,shades except burgundy,bottle green,black of any size as approved by Site Engineer in skirting,risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm including pointinginwhite cementmixed withpigment ofmatchingshade.
2253Admin Cum Control Building
2254Providing and fixing with 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding, and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of Site Engineer.
2255Flooring Tiles with size up to 60 x 60 CM in 10 mm thick cement mortar 1:4
2256Admin Cum Control Building
2257Skirting/ Dado Tiles with size up to 60 x 60 CM in 12 mm thick cement mortar 1:4
2258Admin Cum Control Building
2259DOORS/ WINDOWS/ VENTILATORS/ PARTITIONS/ FALSE CEILING / ROLLING SHUTTER/GRILLS/ GATES/FENCING/ROOF SHEETING /SS HAND RAILING WORKS Note: a. All Aluminium sections to be used shall be out of Magnesium Silicon Alloy with matt finish & with aNodised film of approved colour of thickness Not less than 15 microns. b. Alluminium doors and windows shall be fixed on granite/ marble framework. The items shall also include providing and fillingapprovedsilicon sealant as required to ensurewater tightness,protection ofinstalled items. c. No extra payment will be made towards wastage.
2260Providing & Fixing 15mm thick densified regular edged eco friendly light weight calcium silicate false ceiling tiles of approved texture spintone/cosmos / Hexa or equivalent of size 595 x 595 mm in true horizontal level suspended on inter locking metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per sqm including both side) consisting of main "T" runner suitably spaced at joints to get requiredlengthandofsize24x38mm madefrom 0.33mm thick (minimum) sheet, spaced 1200mm centre to centre, and cross "T" of size 24x28mm made out of 0.33mm (Minimum) sheet, 1200mm long spaced between main"T" at 600mm centre to centre to form a grid of 1200x600mm and secondary cross "T" of length 600mm andsize 24 x28mm made of 0.33mm thick (Minimum) sheet to be inter locked at middle of the 1200x 600mm panel to from grid of size 600x600mm resting on periphery walls / partitions on Perimeterwall angle pre- coated steel of size(24x24X3000mm made of 0.40mm thick (minimum) sheet with the help of rawl plugs at 450mm centre to centre with 25mm long dry wall screws @ 230mm interval and laying 15mm thick densified edges calcium silicate ceiling tiles of approved texture (Spintone/Cosmos/hexa) in the grid including,cutting/ making opening for services like diffusers, grills,light fittings, fixtures, smoke detectors etc., wherever required, Main "T" runners to be suspended from ceiling using G.I. slotted cleats of size 25x35x1.6mm ceiling with 12.5 mm dia and 50mm long dash fasteners, 4mm G.I. adjustable rods with galvanised steel level clips of size 85x30x0.8 mm spaced at 1200mm centre to centre along main"T", bottom exposed with 24mm of all T-sections shall be pre-painted with polyester baked paint for all heights,as per specifications,drawings & as directed by PMC Engineer.
2261Note :- Only calcium silicate false ceiling area will be measured from wall to wall. No deduction shall be made for exposed frames /opening (cut outs) having area less than 0.30 sqm.The calcium silicate tile shall have NRC value of 0.50(Minimum), light reflection > 85%, Non - combustible as per B.S. 476 part IV, 100% humidity resistance & also having thermal conductivity<0.043 w/m 0 KC
2262Admin Cum Control Building
2263Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions,at top, bottom & sides with with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be ANodized, Coloured, smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing/panelling, C.P. brass/stainless steel screws including fixingall complete as per drawing & the directions of Site In-Charge. (Cost of glazing or panels to be paid for separately)
2264Admin Cum Control Building
2265Warehouse Building
2266Jetty-FWPH Structure
2267Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Site In-Charge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 6.0 mm thickness
2268Admin Cum Control Building
2269Warehouse Building
2270Supplying and fixing rolling shutters of approved make, madeof required size M.S. laths interlocked together through their entire length,jointed together at the end by end locks mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete including the cost of providing and fixing necessary 27.5cm long wire as per IS 4454 Part-I & M.S. top cover of required thickness for rolling shutters:- 80x1.25mm MS laths with1.25 mm thick top cover. Note: Item rate includes mechanical device chain and crank operation for operating rolling shutters.
2271Admin Cum Control Building
2272Warehouse Building
2273Jetty-FWPH Structure
2274Providing & fixing fire resistant door frame of section 143x57mm having built in rebate made out of 16 S.W.G. GI sheet (zinc coating Not less than 120gm/sqm) duly filled with vermuculite based concrete mix, suitable for mounting 60 minutes fire rated door shutters. The frame is fitted with intumuscent fire seal strip of size 10X4 mm (minimum) alround the frame & fixing with dash fastner of approved brand fire resistant primer etc. complete as per direction. (Dash fastner to be paid seperately.
2275Admin Cum Control Building
2276SECTION 4: PLUMBING, WATER SUPPLY, SEWERAGE AND STORM DRAINAGE WORKS
2277Supply , Installation, testing, commissioning of Package Type Sewage Treatment Plant of Capcity 3 KLD in FRP . The STP compries of (1) Primary settling tank 2) Aeration Zone (3)secondary Sedimentation Zone, 4) Transfer Pumps 5)MBBR Media 6) Electrical Cable, earthing, Panel 7) Diffusers 8) Manhole, 9) uPVC Pipes 10) Manhole Cover 11) Collection Tank 12) Bar Screen 13) Air Blower and any other accessriers to complete the work.
2278Supply , Installation, testing, commissioning of Package Type Sewage Treatment Plant of Capcity 1 KLD in FRP . The STP compries of (1) Primary settling tank 2) Aeration Zone (3)secondary Sedimentation Zone, 4) Transfer Pumps 5)MBBR Media 6) Electrical Cable, earthing, Panel 7) Diffusers 8) Manhole, 9) uPVC Pipes 10) Manhole Cover 11) Collection Tank 12) Bar Screen 13) Air Blower and any other accessriers to complete the work.
2279Supply , Installation, testing, commissioning of Sewage Collection Tank in FRP 2000 mm (Dia) X 1200 MM (Height)
2280Supply , Installation, testing, commissioning of Treated Water Tank in FRP 2000 mm (Dia) X 1200 MM (Height)
2281Supply , Installation, testing, commissioning of skid mounted Potable Water pumps in SS 304 with capcity 1.0 m3/hr @ 30 m heard
2282Erection, Testing & Commissioning the following sizes of Gun Metal Gate Valves as per Specification
228350 mm dia
2284Erection, Testing & Commissioning the following sizes ofGun Metal Check Valves as per Specification
228550 mm dia
2286Supply and laying above ground/underground threaded MS Galvanized Pipes including all fittings as per IS 1239
228750mm dia
2288Supplying and providing Porta Cabin of size 3M x 3M x 2.5 M with Toilet Inbuilt with EWC & washbasin including provision of door, windows, AC, lighting, furnishers, flooring etc as per description in Technical Specification with Transporation etc complete.
2289PART-D - COMMISSIONING & HAZOP STUDY
2290HAZOP STUDY
2291Carrying out HAZOP study for the equipment, Pipe line and associated systems, Recommending modification as required, Preparation of Report by Chairman of HAZOP Study.
2292COMMISSIONING
2293Successful Commissioning activity for Loading / Unloading of Vessels, Pigging, etc. subsequent to completion of individual Equipment and System commissioning acitivities including the following: a) Review of commissioning status, jointly with Owner personnel and obtaining all required Clearences. b) All necessary coordination/ liaison with IOCL/KPL/Statutory Authorities etc. forcompleting the planned operations including deputing necessary engineers of various disciplines along with supervisory staffs/blue collar workmen.The deployment plan to be submitted in advance prior to commissioning and approved by IOCL.
2294For LPG Vessels (2 Nos.)
2295For POL Vessels (2 Nos.) including Pigging of Pipelines post vessel Unloading/Loading Operations