Indian Oil Corporation Limited-IOCL has published Oso Engg Design Supply Installation Testing And Commissioning Of Tank Farm Management System For 3 Nos Above Ground Vertical Tanks And Integration With Existing Terminal Automation System Paradeep Terminal Odisha Design Supply Installation Testing And Com. Submission Date for this Tender is 16-10-2021. Application Software Tenders in Paradeep Terminal Odisha Odisha. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 01-Oct-2021 | Date corrigendum -1 | Date | 16-10-2021 |
Sl. No. | Item Description |
1 | TAS WORKS FOR ETHANOL TANKS |
2 | CIVIL WORKS |
3 | Clearing grass and removal of the rubbish outside site premises and at an unobjectionable place. |
4 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30 cm in depth, 1.5m in widthas well as 10 sqm on plan) including taking out and disposal of excavated earth within or outside site to unobjectionable place and lift upto 1.5m, as directed by Engineer-in-charge. Disposed earth to be levelled and neatly dressed. |
5 | i) All kinds of Soil |
6 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, within premises and lift upto 1.5m |
7 | Supplying and filling in plinth with sand within specified grading zone of fine aggregates specified in table 3.1, clause 3.1.3 of attached specifications under floors, etc. in layers not exceeding 20cm in depth, each deposited layer to be compacted by ramming including watering, consolidating and dressing complete. |
8 | i) Local Fine Sand within grading zone IV |
9 | Providing and laying in position cement concrete of specified grade excluding cost of centering & shuttering. All work up to plinth level: |
10 | v) 1:3:6(1 Cement : 3 Coarse Sand : 6 Graded stone aggregate of 20mm) |
11 | Centering and shuttering including strutting, propping etc. and removal of form for : |
12 | i) Foundations,footings,bases of columns, etc. for mass concrete |
13 | GI STRUCTURAL STEEL & GRATING: Structural steel work in built up sections/ framed work in gratings, frames, guard bar, ladder, railings, brackets, gates and similar works including cutting,hoisting,fixing in position. Structure & Gratings shall be duly hot dip galvanized after fabrication given in the detailed specification with minimum thickness of galvanisingof average 85 microns all through the sectional area, & erecting in position and fixing in position mild steel Gratingwelded/ bolted/placedwith adequate clamps wherevever applicable in floors, platforms, staircase steps, trench covers, landings etc. including cutting for openings wherever required as specified and directed at all floors at all levels etc. complete. The grating shall confirm to the typical section details of grating as shown in drawing . This works includessetting in position in Footpath/ Gutter/Drains/Floors to the required level and line over a bed of 20mm Average thick cement mortar (1:3). NOTE: The Grating shall be factory made, i.e. fabricated & Hot dip Gavanised in shop & transported to site for erection. |
14 | Brick work with non modular fly ash bricks conforming to IS:12894, class designation 10 average compressive strength: |
15 | ii) Brick work in Cement mortar 1:6 (1 cement: 6 coarse sand ) IN FOUNDATION AND PLINTH |
16 | ii) Brick work in Cement mortar 1:6 (1 cement: 6 coarse sand ) ABOVE PLINTH |
17 | Providing and laying cement plaster on surfaces with fine sand including curing etc. |
18 | ii)12 mm cement plaster of mix 1:6 (1 cement: 6 fine sand) |
19 | DemolishingPCC/RCC manually/ by mechanical means including disposal of material outside premises at an unobjectionable place as per direction of Engineer-in-charge. |
20 | i) 1:3:6 or richer mix (i/c equivalent design mix) |
21 | Demolishing brick work manually/mechanical means including stacking of serviceable material & disposal of unserviceable material outside premises at an unobjectionable place as / direction of Engg-in-charge |
22 | Dismantling Steel work in single sections including dismembering and stacking within premises |
23 | ii) Channels, angles, tees and flats etc |
24 | Fabrication & Erection of IOC supplied structural steel work riveted, bolted or welded in single/ built up sections,trusses & framed work hoisting, fixing in position and applying a priming coat of approved steel primer all including cutting, complete |
25 | Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface : |
26 | Finishing walls with water proofing cement paint of required shade with Two or more coats applied @ 3.84 kg/10 sqm: |
27 | Providingand laying class-B 50mm dia GI pipe for cable routing under flooring/ EB post leading including sealing both ends with jute and Bitumen |
28 | AUTOMATION SUPPLY |
29 | Tank Farm Management System. |
30 | Supply of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender). |
31 | For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges). |
32 | ETHANOL |
33 | Supply of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. |
34 | With minimum 8 elements temperature sensor (for A/G vertical tanks). |
35 | For Internal Floating Roof vertical tanks/Floating roof vertical tanks |
36 | ETHANOL |
37 | Supply of Density probe along with accessories etc for density measurement of the product in product tanks complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender). |
38 | For A/G vertical tanks - Three elements. |
39 | For Internal Floating Roof vertical tanks/Floating roof vertical tanks |
40 | ETHANOL |
41 | Supply of Tank Side indicator along with mounting accessories etc complete as per specification and tender document for displaying respective tank inventory data. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) |
42 | For A/G Vertical Product tanks - (Primary & Secondary Radar Gauges). |
43 | Supply of top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment, etc complete as per specification and tender document |
44 | For A/G Vertical Product tanks. |
45 | Push Buttons Outside Dyke Walls |
46 | Supply of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS along with FLP double compression gland, Tag plates, TBs, mounting structure, accessories etc complete as per specifications and tender document. |
47 | For ROSOVs (A/G product tank"s inlet, outlet line). |
48 | Hydrocarbon Detection system |
49 | Supply of Flameproof cum weather proof (IP 66 or better) min SIL 2 certified Hydrocarbon vapour detectors along with calibration kit, accessories and structural supports, Aluminium canopy/sunshade etc as per specification and tender document.. |
50 | Point type Infrared detector |
51 | Open path type Infrared detector (0-90 m) along with alignment telescope, configuration & Testing kit etc (For Ethanol tank farm & TLF PH) |
52 | Miscellaneous |
53 | Supply of flameproof cum weather proof to IP 65 or better SIL 2 smart pressure transmitter with in built display, SS manifold, isolation valve, Aluminium canopy/sunshade, other erection material etc as per hook up drawing attached else where in tender complete asper specifications and Tender Document. (Transmitter will have IEC & ATEX certified minimum and any other certification as stated else where in tender) Note:1. Pressure transmitter at suction shall have range from -1 Kg/cm2.2. Underground tank shall have PT in Pump discharge end only. |
54 | TLF pump Suction & Discharge end |
55 | Ethanol tank Sprinkler & Foam Line |
56 | Supply of flameproof cum weather proof to IP 65 or better SIL 2 Smart Differential pressure transmitter with in built display, SS 3way manifold, Aluminium canopy/sunshade, other erection material etc as per hook up drawing attached else where in tender complete as per specifications and Tender Document. (Transmitter will have IEC & ATEX certified minimum and any other certification as stated else where in tender) |
57 | Across TLF pump Strainers |
58 | Cabling, JB, Earthing |
59 | Supply of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc |
60 | Supply of FRLS Armoured Copper Power cable as per tender specifications. |
61 | 12C x 2.5 sqmm |
62 | Supply of FRLS Armoured Copper Control cable as per tender specifications. |
63 | 24C x 1.5 sqmm |
64 | Supply of FRLS Armoured Copper Signal cable as per tender specifications. |
65 | 18P x 1.5 sqmm |
66 | Supply of FS Armoured Copper Power cable as per tender specifications. |
67 | 3C x 2.5 sqmm |
68 | Supply of FS Armoured Copper Control cable as per tender specifications. |
69 | 2C x 1.5 sqmm |
70 | Supply of FS Armoured Copper Signal cable as per tender specifications. |
71 | 1P x 1.5 sqmm |
72 | 2P x 1.5 sqmm |
73 | Supply of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. |
74 | Supply of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. |
75 | Supply of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document |
76 | Supply of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. |
77 | 18 ways JB |
78 | 8 ways JB |
79 | 4 ways JB |
80 | AUTOMATION INSTALLATION |
81 | Tank Farm Management System. |
82 | Installation, testing and commissioning of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender). |
83 | For Internal Floating Roof vertical tanks/Floating roof vertical tanks (Primary and Secondary Radar Gauges). |
84 | ETHANOL |
85 | Installation, testing and commissioning of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. |
86 | With minimum 8 elements temperature sensor (for A/G vertical tanks). |
87 | For Internal Floating Roof vertical tanks/Floating roof vertical tanks |
88 | ETHANOL |
89 | Installation, testing and commissioning of Density probe along with accessories etc for density measurement of the product in product tanks complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender). |
90 | For A/G vertical tanks - Three elements. |
91 | For Internal Floating Roof vertical tanks/Floating roof vertical tanks |
92 | ETHANOL |
93 | Installation, testing and commissioning of Tank Side indicator along with mounting accessories etc complete as per specification and tender document for displaying respective tank inventory data. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) |
94 | For A/G Vertical Product tanks - (Primary & Secondary Radar Gauges). |
95 | Installation, testing and commissioning of top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment, etc complete as per specification and tender document |
96 | For A/G Vertical Product tanks. |
97 | Push Buttons Outside Dyke Walls |
98 | Installation, testing and commissioning of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS along with FLP double compression gland, Tag plates, TBs, mounting structure, accessories etc complete as per specifications and tender document. |
99 | For ROSOVs (A/G product tank"s inlet, outlet line). |
100 | Hydrocarbon Detection system |
101 | Installation, testing and commissioning of Flameproof cum weather proof (IP 66 or better) min SIL 2 certified Hydrocarbon vapour detectors along with calibration kit, accessories and structural supports, Aluminium canopy/sunshade etc as per specification and tender document.. |
102 | Point type Infrared detector |
103 | Open path type Infrared detector (0-90 m) along with alignment telescope, configuration & Testing kit etc (For Ethanol tank farm & TLF PH) |
104 | Miscellaneous |
105 | Installation, testing and commissioning of flameproof cum weather proof to IP 65 or better SIL 2 smart pressure transmitter with in built display, SS manifold, isolation valve, Aluminium canopy/sunshade, other erection material etc as per hook up drawing attached else where in tender complete asper specifications and Tender Document. (Transmitter will have IEC & ATEX certified minimum and any other certification as stated else where in tender) Note:1. Pressure transmitter at suction shall have range from -1 Kg/cm2.2. Underground tank shall have PT in Pump discharge end only. |
106 | TLF pump Suction & Discharge end |
107 | Ethanol tank Sprinkler & Foam Line |
108 | Installation, testing and commissioning of flameproof cum weather proof to IP 65 or better SIL 2 Smart Differential pressure transmitter with in built display, SS 3way manifold, Aluminium canopy/sunshade, other erection material etc as per hook up drawing attached else where in tender complete as per specifications and Tender Document. (Transmitter will have IEC & ATEX certified minimum and any other certification as stated else where in tender) |
109 | Across TLF pump Strainers |
110 | Cabling, JB, Earthing |
111 | Laying, glanding, ferruling, termination of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc |
112 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Power cable as per tender specifications. |
113 | 12C x 2.5 sqmm |
114 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Control cable as per tender specifications. |
115 | 24C x 1.5 sqmm |
116 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Signal cable as per tender specifications. |
117 | 18P x 1.5 sqmm |
118 | Laying, glanding, ferruling, termination of FS Armoured Copper Power cable as per tender specifications. |
119 | 3C x 2.5 sqmm |
120 | Laying, glanding, ferruling, termination of FS Armoured Copper Control cable as per tender specifications. |
121 | 2C x 1.5 sqmm |
122 | Laying, glanding, ferruling, termination of FS Armoured Copper Signal cable as per tender specifications. |
123 | 1P x 1.5 sqmm |
124 | 2P x 1.5 sqmm |
125 | Laying, glanding, ferruling, termination of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. |
126 | Laying, glanding, ferruling, termination of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. |
127 | Laying, glanding, ferruling, termination of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document |
128 | Installation, testing and commissioning of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. |
129 | 18 ways JB |
130 | 8 ways JB |
131 | 4 ways JB |
132 | Design, development, modification, configuration, testing and commissioning of existing TAS software, DCS/PLC logic, GUI etc for implementation of following features after FAT (if required) or during CAMC period as stated in tender document. The job includes necessary tro-& fro travel, lodging, boarding, food etc required for implementation at site complete in all respect and as per directionof EIC. The job includes supply, installation, testing & commissioning of required additional IOs, PLC modules, CIUs and necessary hardwares at Control room for completion of the work. |
133 | Product pump addition |
134 | Product tank addition |
135 | Supplying, fabricating and installing following sizes of perforated GI cable trays with cover including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling and/or fix to steel/RCC columns, beams or any other structure members with MS suspenders, angles, channels, etc complete as per the direction of IndianOil |
136 | i) 100mm x 25mm x 2mm |
137 | ii) 150mm x 25mm x 2mm |
138 | ii) Providing earthing with 80 mm dia,3.0 M long GI (Heavy duty) perforated pipe as per IS:3043 (with latest ammendment) including providing suitable earth bus for interconnection, providing a mixture of salt & charcoal, making earth pit chamber with chequered plate cover as per standard Drwng.etc. all complete as per specif. & direction of Engineer-In-charge |
139 | Supply & drawing/laying, jointing, connecting, testing and commissioning ofearth strip/copper strip/GI wire for earthing and lightning protection under or aboveground complete as per specification for the following : |
140 | 50 x 6 mm G.I.strip |
141 | TAS WORKS FOR OISD COMPLIANCE |
142 | CIVIL WORKS |
143 | Clearing grass and removal of the rubbish outside site premises and at an unobjectionable place. |
144 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30 cm in depth, 1.5m in widthas well as 10 sqm on plan) including taking out and disposal of excavated earth within or outside site to unobjectionable place and lift upto 1.5m, as directed by Engineer-in-charge. Disposed earth to be levelled and neatly dressed. |
145 | i) All kinds of Soil |
146 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, within premises and lift upto 1.5m |
147 | Supplying and filling in plinth with sand within specified grading zone of fine aggregates specified in table 3.1, clause 3.1.3 of attached specifications under floors, etc. in layers not exceeding 20cm in depth, each deposited layer to be compacted by ramming including watering, consolidating and dressing complete. |
148 | i) Local Fine Sand within grading zone IV |
149 | Providing and laying in position cement concrete of specified grade excluding cost of centering & shuttering. All work up to plinth level: |
150 | v) 1:3:6(1 Cement : 3 Coarse Sand : 6 Graded stone aggregate of 20mm) |
151 | Centering and shuttering including strutting, propping etc. and removal of form for : |
152 | i) Foundations,footings,bases of columns, etc. for mass concrete |
153 | GI STRUCTURAL STEEL & GRATING: Structural steel work in built up sections/ framed work in gratings, frames, guard bar, ladder, railings, brackets, gates and similar works including cutting,hoisting,fixing in position. Structure & Gratings shall be duly hot dip galvanized after fabrication given in the detailed specification with minimum thickness of galvanisingof average 85 microns all through the sectional area, & erecting in position and fixing in position mild steel Gratingwelded/ bolted/placedwith adequate clamps wherevever applicable in floors, platforms, staircase steps, trench covers, landings etc. including cutting for openings wherever required as specified and directed at all floors at all levels etc. complete. The grating shall confirm to the typical section details of grating as shown in drawing . This works includessetting in position in Footpath/ Gutter/Drains/Floors to the required level and line over a bed of 20mm Average thick cement mortar (1:3). NOTE: The Grating shall be factory made, i.e. fabricated & Hot dip Gavanised in shop & transported to site for erection. |
154 | Brick work with non modular fly ash bricks conforming to IS:12894, class designation 10 average compressive strength: |
155 | ii) Brick work in Cement mortar 1:6 (1 cement: 6 coarse sand ) IN FOUNDATION AND PLINTH |
156 | ii) Brick work in Cement mortar 1:6 (1 cement: 6 coarse sand ) ABOVE PLINTH |
157 | Providing and laying cement plaster on surfaces with fine sand including curing etc. |
158 | ii)12 mm cement plaster of mix 1:6 (1 cement: 6 fine sand) |
159 | DemolishingPCC/RCC manually/ by mechanical means including disposal of material outside premises at an unobjectionable place as per direction of Engineer-in-charge. |
160 | i) 1:3:6 or richer mix (i/c equivalent design mix) |
161 | Demolishing brick work manually/mechanical means including stacking of serviceable material & disposal of unserviceable material outside premises at an unobjectionable place as / direction of Engg-in-charge |
162 | Dismantling Steel work in single sections including dismembering and stacking within premises |
163 | ii) Channels, angles, tees and flats etc |
164 | Fabrication & Erection of IOC supplied structural steel work riveted, bolted or welded in single/ built up sections,trusses & framed work hoisting, fixing in position and applying a priming coat of approved steel primer all including cutting, complete |
165 | Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface : |
166 | Finishing walls with water proofing cement paint of required shade with Two or more coats applied @ 3.84 kg/10 sqm: |
167 | Providingand laying class-B 50mm dia GI pipe for cable routing under flooring/ EB post leading including sealing both ends with jute and Bitumen |
168 | AUTOMATION SUPPLY |
169 | Tank Farm Management System. |
170 | Supply of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. |
171 | With minimum 8 elements temperature sensor (for A/G vertical product tanks). |
172 | Hydrocarbon Detection system |
173 | Supply of Flameproof cum weather proof (IP 66 or better) min SIL 2 certified Hydrocarbon vapour detectors along with calibration kit, accessories and structural supports, Aluminium canopy/sunshade etc as per specification and tender document.. |
174 | Point type Infrared detector a) At sump pit - 5 nos. (TLF PH, TW PH, IPH, Ref. Exchange pit, Receipt manifold). b) At pump seals - 13 (TLF PH, TW PH, IPH, TW unloading PH) |
175 | Supply of weather proof and Explosion proof Hooter cum beacons/ flash light along with accessories and structural supports as per specification. (Tentative location : For tank dykes - 16, TLF PH - 1, TW PH - 1, IPH - 1, TW unloading PH - 1, Ethanol PH - 1, Ref. Exch. Pit - 1, Receipt manifold - 1) |
176 | Cabling, JB, Earthing |
177 | Supply of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc |
178 | Supply of FRLS Armoured Copper Power cable as per tender specifications. |
179 | 3C x 2.5 sqmm |
180 | 12C x 2.5 sqmm |
181 | Supply of FRLS Armoured Copper Control cable as per tender specifications. |
182 | 2C x 1.5 sqmm |
183 | 4C x 1.5 sqmm |
184 | 12C x 1.5 sqmm |
185 | Supply of FRLS Armoured Copper Signal cable as per tender specifications. |
186 | 2P x 1.5 sqmm |
187 | 6P x 1.5 sqmm |
188 | 1T x 1.5 sqmm |
189 | 8T x 1.5 sqmm |
190 | Supply of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. |
191 | Supply of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. |
192 | Supply of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document |
193 | Supply of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. |
194 | 12 ways JB |
195 | 8 ways JB |
196 | 4 ways JB |
197 | AUTOMATION INSTALLATION |
198 | Tank Farm Management System. |
199 | Installation, testing and commissioning of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. |
200 | With minimum 8 elements temperature sensor (for A/G vertical product tanks). |
201 | Hydrocarbon Detection system |
202 | Installation, testing and commissioning of Flameproof cum weather proof (IP 66 or better) min SIL 2 certified Hydrocarbon vapour detectors along with calibration kit, accessories and structural supports, Aluminium canopy/sunshade etc as per specification and tender document.. |
203 | Point type Infrared detector a) At sump pit - 5 nos. (TLF PH, TW PH, IPH, Ref. Exchange pit, Receipt manifold). b) At pump seals - 13 (TLF PH, TW PH, IPH, TW unloading PH) |
204 | Installation, testing and commissioning of weather proof and Explosion proof Hooter cum beacons/ flash light along with accessories and structural supports as per specification. (Tentative location : For tank dykes - 16, TLF PH - 1, TW PH - 1, IPH - 1, TW unloading PH - 1, Ethanol PH - 1, Ref. Exch. Pit - 1, Receipt manifold - 1) |
205 | SIL VERIFICATION / VALIDATION |
206 | SIL verification from approved third party agencies. (For SIFs as per SIL Assessment study report/detail engg). All required documentation as per specs and other documentation mentioned elsewhere in tender scope has to be submitted. Complete as per specification / tender documents. |
207 | Supply, Installation, Testing, Commissioning of 12 point PLC modules (Analog/Digital for Input/Output) including all accessories for fixing the same in existing PLC. The modules shall be compatible with existing PLC & no separate cost for integration shall be applicable. |
208 | Cabling, JB, Earthing |
209 | Laying, glanding, ferruling, termination of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc |
210 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Power cable as per tender specifications. |
211 | 3C x 2.5 sqmm |
212 | 12C x 2.5 sqmm |
213 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Control cable as per tender specifications. |
214 | 2C x 1.5 sqmm |
215 | 4C x 1.5 sqmm |
216 | 12C x 1.5 sqmm |
217 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Signal cable as per tender specifications. |
218 | 2P x 1.5 sqmm |
219 | 6P x 1.5 sqmm |
220 | 1T x 1.5 sqmm |
221 | 8T x 1.5 sqmm |
222 | Laying, glanding, ferruling, termination of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. |
223 | Laying, glanding, ferruling, termination of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. |
224 | Laying, glanding, ferruling, termination of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document |
225 | Installation, testing and commissioning of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. |
226 | 12 ways JB |
227 | 8 ways JB |
228 | 4 ways JB |
229 | Supplying, fabricating and installing following sizes of perforated GI cable trays with cover including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling and/or fix to steel/RCC columns, beams or any other structure members with MS suspenders, angles, channels, etc complete as per the direction of IndianOil |
230 | i) 100mm x 25mm x 2mm |
231 | ii) 150mm x 25mm x 2mm |
232 | ii) Providing earthing with 80 mm dia,3.0 M long GI (Heavy duty) perforated pipe as per IS:3043 (with latest ammendment) including providing suitable earth bus for interconnection, providing a mixture of salt & charcoal, making earth pit chamber with chequered plate cover as per standard Drwng.etc. all complete as per specif. & direction of Engineer-In-charge |
233 | Supply & drawing/laying, jointing, connecting, testing and commissioning ofearth strip/copper strip/GI wire for earthing and lightning protection under or aboveground complete as per specification for the following : |
234 | 50 x 6 mm G.I.strip |
235 | SOFTWARE MODIFICATION |
236 | Design, development, modification, configuration, testing and commissioning of existing TAS software, DCS/PLC logic, GUI etc for implementation of following features after FAT (if required) or during CAMC period as stated in tender document. The job includes necessary tro-& fro travel, lodging, boarding, food etc required for implementation at site complete in all respect and as per directionof EIC. The job includes supply, installation, testing & commissioning of required additional IOs, PLC modules, CIUs and necessary hardwares, liasioning with TAS vendors of refinery, OMCs, Pipeline division etc. at Control room for completion of the work as directed by EIC. |
237 | Integration Testing and Commissioning of Mass Flow Meter for providing Density, Temperature and allied diagnostics data to TAS and SCADA and utilising the data for posting it to SAP for invoicing purpose. |
238 | Sharing of ESD, MFM, Tank Level and Pipeline pressure Data with OMC (HPCL and BPCL) and Paradeep Refinery utilising existing Micro-PLC at site. Includes development SCADA GUI for display of retrieved information, recording, database etc all complete. |
239 | a) Integration of one number of new Pump (1no.) b) Integration of additive panel |
240 | a) Configuration of Alarms, GUI, etc all complete for New Point Type Hydrocarbon Detection System and existing dyke valve indicators b) Displaying of Density from MFM and utilising the same for Auto - Posting to TAS. c) Configuring reports for generation of critical KPIs and parameters |
241 | Upgrading including Testing and Commissioning of available Communication Interface Unit (NXA) to latest patch version for interfacing new Tank Farm Equipments Complete in all aspects. |
242 | TAS WORKS FOR FO TRANSMIX TANK |
243 | CIVIL WORKS |
244 | Clearing grass and removal of the rubbish outside site premises and at an unobjectionable place. |
245 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30 cm in depth, 1.5m in widthas well as 10 sqm on plan) including taking out and disposal of excavated earth within or outside site to unobjectionable place and lift upto 1.5m, as directed by Engineer-in-charge. Disposed earth to be levelled and neatly dressed. |
246 | i) All kinds of Soil |
247 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, within premises and lift upto 1.5m |
248 | Supplying and filling in plinth with sand within specified grading zone of fine aggregates specified in table 3.1, clause 3.1.3 of attached specifications under floors, etc. in layers not exceeding 20cm in depth, each deposited layer to be compacted by ramming including watering, consolidating and dressing complete. |
249 | i) Local Fine Sand within grading zone IV |
250 | Providing and laying in position cement concrete of specified grade excluding cost of centering & shuttering. All work up to plinth level: |
251 | v) 1:3:6(1 Cement : 3 Coarse Sand : 6 Graded stone aggregate of 20mm) |
252 | Centering and shuttering including strutting, propping etc. and removal of form for : |
253 | i) Foundations,footings,bases of columns, etc. for mass concrete |
254 | GI STRUCTURAL STEEL & GRATING: Structural steel work in built up sections/ framed work in gratings, frames, guard bar, ladder, railings, brackets, gates and similar works including cutting,hoisting,fixing in position. Structure & Gratings shall be duly hot dip galvanized after fabrication given in the detailed specification with minimum thickness of galvanisingof average 85 microns all through the sectional area, & erecting in position and fixing in position mild steel Gratingwelded/ bolted/placedwith adequate clamps wherevever applicable in floors, platforms, staircase steps, trench covers, landings etc. including cutting for openings wherever required as specified and directed at all floors at all levels etc. complete. The grating shall confirm to the typical section details of grating as shown in drawing . This works includessetting in position in Footpath/ Gutter/Drains/Floors to the required level and line over a bed of 20mm Average thick cement mortar (1:3). NOTE: The Grating shall be factory made, i.e. fabricated & Hot dip Gavanised in shop & transported to site for erection. |
255 | Brick work with non modular fly ash bricks conforming to IS:12894, class designation 10 average compressive strength: |
256 | ii) Brick work in Cement mortar 1:6 (1 cement: 6 coarse sand ) IN FOUNDATION AND PLINTH |
257 | ii) Brick work in Cement mortar 1:6 (1 cement: 6 coarse sand ) ABOVE PLINTH |
258 | Providing and laying cement plaster on surfaces with fine sand including curing etc. |
259 | ii)12 mm cement plaster of mix 1:6 (1 cement: 6 fine sand) |
260 | DemolishingPCC/RCC manually/ by mechanical means including disposal of material outside premises at an unobjectionable place as per direction of Engineer-in-charge. |
261 | i) 1:3:6 or richer mix (i/c equivalent design mix) |
262 | Demolishing brick work manually/mechanical means including stacking of serviceable material & disposal of unserviceable material outside premises at an unobjectionable place as / direction of Engg-in-charge |
263 | Dismantling Steel work in single sections including dismembering and stacking within premises |
264 | ii) Channels, angles, tees and flats etc |
265 | Fabrication & Erection of IOC supplied structural steel work riveted, bolted or welded in single/ built up sections,trusses & framed work hoisting, fixing in position and applying a priming coat of approved steel primer all including cutting, complete |
266 | Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface : |
267 | Finishing walls with water proofing cement paint of required shade with Two or more coats applied @ 3.84 kg/10 sqm: |
268 | Providingand laying class-B 50mm dia GI pipe for cable routing under flooring/ EB post leading including sealing both ends with jute and Bitumen |
269 | AUTOMATION SUPPLY |
270 | Tank Farm Management System. |
271 | Supply of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender). |
272 | For Cone Roof Vertical Tanks roof vertical tanks (Primary and Secondary Radar Gauges). |
273 | FO |
274 | Supply of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. |
275 | With minimum 8 elements temperature sensor (for A/G vertical tanks). |
276 | For Cone Roof Vertical Tanks roof vertical tanks |
277 | FO |
278 | Supply of Density probe along with accessories etc for density measurement of the product in product tanks complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender). |
279 | For A/G vertical tanks - Three elements. |
280 | For Cone Roof Vertical Tanks roof vertical tanks |
281 | FO |
282 | Supply of Tank Side indicator along with mounting accessories etc complete as per specification and tender document for displaying respective tank inventory data. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) |
283 | For A/G Vertical Product tanks - (Primary & Secondary Radar Gauges). |
284 | Supply of top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment, etc complete as per specification and tender document |
285 | For A/G Vertical Product tanks. |
286 | Push Buttons Outside Dyke Walls |
287 | Supply of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS along with FLP double compression gland, Tag plates, TBs, mounting structure, accessories etc complete as per specifications and tender document. |
288 | For ROSOVs (A/G product tank"s inlet, outlet line). |
289 | Cabling, JB, Earthing |
290 | Supply of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc |
291 | Supply of FRLS Armoured Copper Power cable as per tender specifications. |
292 | 12C x 2.5 sqmm |
293 | Supply of FRLS Armoured Copper Control cable as per tender specifications. |
294 | 24C x 1.5 sqmm |
295 | Supply of FRLS Armoured Copper Signal cable as per tender specifications. |
296 | 18P x 1.5 sqmm |
297 | Supply of FS Armoured Copper Power cable as per tender specifications. |
298 | 3C x 2.5 sqmm |
299 | Supply of FS Armoured Copper Control cable as per tender specifications. |
300 | 2C x 1.5 sqmm |
301 | Supply of FS Armoured Copper Signal cable as per tender specifications. |
302 | 1P x 1.5 sqmm |
303 | 2P x 1.5 sqmm |
304 | Supply of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. |
305 | Supply of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. |
306 | Supply of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document |
307 | Supply of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. |
308 | 18 ways JB |
309 | 8 ways JB |
310 | 4 ways JB |
311 | AUTOMATION INSTALLATION |
312 | Tank Farm Management System. |
313 | Installation, testing and commissioning of minimum SIL 2 certified Non - contact type Radar level gauges with instrument accuracy of +/- 1 mm or better along with mounting accessories etc complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender). |
314 | For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges). |
315 | FO |
316 | Installation, testing and commissioning of multi point temperature averaging sensor with integrated water interface probe (MSTW) along with mounting accessories etc complete as per specification and tender document. |
317 | With minimum 8 elements temperature sensor (for A/G vertical tanks). |
318 | For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges). |
319 | FO |
320 | Installation, testing and commissioning of Density probe along with accessories etc for density measurement of the product in product tanks complete as per specification and tender document. (Transmitter will have IEC & ATEX certified minimum along with any other certification as stated else where in tender). |
321 | For A/G vertical tanks - Three elements. |
322 | For Cone Roof Vertical Tanks (Primary and Secondary Radar Gauges). |
323 | FO |
324 | Installation, testing and commissioning of Tank Side indicator along with mounting accessories etc complete as per specification and tender document for displaying respective tank inventory data. (TSI will have IEC & ATEX certified minimum along with any other certification as stated else where in tender) |
325 | For A/G Vertical Product tanks - (Primary & Secondary Radar Gauges). |
326 | Installation, testing and commissioning of top mounted minimum SIL2 certified Overfill detector (vibrating fork type) of suitable probe length along with mounting accessories, spool piece of minimum 500mm, proof testing equipment, etc complete as per specification and tender document |
327 | For A/G Vertical Product tanks. |
328 | Push Buttons Outside Dyke Walls |
329 | Installation, testing and commissioning of Exd/FLP Local Push button station cum indication lamp out side tank farm dyke wall for remote opening and closing of ROSOVs from LPBS along with FLP double compression gland, Tag plates, TBs, mounting structure, accessories etc complete as per specifications and tender document. |
330 | For ROSOVs (A/G product tank"s inlet, outlet line). |
331 | Cabling, JB, Earthing |
332 | Laying, glanding, ferruling, termination of cables shall be along with accessories like certified double compression cable glands with PVC shrouds, plugs for excess entries, SS 316 engraved tag plate, mounting clamp, SS 316 fasteners , OFC accessories (like 12/24 port LIU, splice trays, loaded adaptor and blank plates, UTP and optical patch cords, pigtails, media converters etc), LAN face plates, conduits, structural steel for mounting of equipments, making RCC trenches with cover wherever required, hume pipes, Aluminium tags, lugs, ferrules, etc |
333 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Power cable as per tender specifications. |
334 | 12C x 2.5 sqmm |
335 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Control cable as per tender specifications. |
336 | 24C x 1.5 sqmm |
337 | Laying, glanding, ferruling, termination of FRLS Armoured Copper Signal cable as per tender specifications. |
338 | 18P x 1.5 sqmm |
339 | Laying, glanding, ferruling, termination of FS Armoured Copper Power cable as per tender specifications. |
340 | 3C x 2.5 sqmm |
341 | Laying, glanding, ferruling, termination of FS Armoured Copper Control cable as per tender specifications. |
342 | 2C x 1.5 sqmm |
343 | Laying, glanding, ferruling, termination of FS Armoured Copper Signal cable as per tender specifications. |
344 | 1P x 1.5 sqmm |
345 | 2P x 1.5 sqmm |
346 | Laying, glanding, ferruling, termination of 6 core single mode armoured optical fibre cable as per tender specifications and instructions of Engineer in charge. |
347 | Laying, glanding, ferruling, termination of CAT 6 Ethernet armoured cable as per tender specifications and instructions of Engineer in charge. |
348 | Laying, glanding, ferruling, termination of 1C x 6 Sq. mm FRLS Flexible copper insulated green wire for earthing instruments and junction boxes etc complete as per specification and tender document |
349 | Installation, testing and commissioning of Exd/FLP Junction Box (Power/Control/Signal JB) with IP 65 as per specification suitable for hazardous area of zone 1, group IIA/IIB, T3 or better having CCOE/CMRI approval. It shall be complete in all respect. Accessories like certified double compression cable glands with PVC shrouds & plugs for excess entries, SS 316 engraved tag plate, mounting clamp & SS 316 fasteners. Complete as per specification / tender documents. |
350 | 18 ways JB |
351 | 8 ways JB |
352 | 4 ways JB |
353 | Design, development, modification, configuration, testing and commissioning of existing TAS software, DCS/PLC logic, GUI etc for implementation of following features after FAT (if required) or during CAMC period as stated in tender document. The job includes necessary tro-& fro travel, lodging, boarding, food etc required for implementation at site complete in all respect and as per directionof EIC. The job includes supply, installation, testing & commissioning of required additional IOs, PLC modules, CIUs and necessary hardwares at Control room for completion of the work. |
354 | Product tank addition |
355 | Supplying, fabricating and installing following sizes of perforated GI cable trays with cover including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling and/or fix to steel/RCC columns, beams or any other structure members with MS suspenders, angles, channels, etc complete as per the direction of IndianOil |
356 | i) 100mm x 25mm x 2mm |
357 | ii) 150mm x 25mm x 2mm |
358 | ii) Providing earthing with 80 mm dia,3.0 M long GI (Heavy duty) perforated pipe as per IS:3043 (with latest ammendment) including providing suitable earth bus for interconnection, providing a mixture of salt & charcoal, making earth pit chamber with chequered plate cover as per standard Drwng.etc. all complete as per specif. & direction of Engineer-In-charge |
359 | Supply & drawing/laying, jointing, connecting, testing and commissioning ofearth strip/copper strip/GI wire for earthing and lightning protection under or aboveground complete as per specification for the following : |
360 | 50 x 6 mm G.I.strip |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy