| 1 | Distribution wiring in 3 x 22/0.3 (1.5 sqmm) single core stranded \"FR\" PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit \"FR\" (Precision make), to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board with top cover plate and 2 no. suitable size “Ph & N” copper bar and \"L\" sahped insulator chair & earthing attachment fixed on wall incl. mending good damages to original finish. [equivalet to PWD/GS Page: E-24 Item: I/1] |
| 2 | Average run: 10 Mtr. |
| 3 | Supply & Fixing 240 V, 4 nos. 16 A, 3 pin Modular type plug socket with 4 nos. 16A Modular type switch (Brand approved by EIC), 20A Modular switch type SP MCB (C-Curve) and Indicator without plug top on 2 row 18 Module GI Modular type switch board with 2 row 18 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [PWD/GS Page: E-19 Item: 15 ] |
| 4 | S&F 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.[PWD/GS Page: E-18 Item: 9/b ] |
| 5 | S&F 240 V, 6 A, 3 pin Modular type plug socket (Brand approved by EIC) with 6A Modular type switch, without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.[PWD/GS Page: E-18 Item: 9/a] |
| 6 | Supply & Fixing 240 V, 25A Modular type socket, 25 A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (C-Curve) and 6 Module GI Modular type switch board with 6 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. |
| 7 | Distribution wiring in 1.1 KV single core stranded \"FR\" PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit \"FR\" (Precision make) incl. necy. fittings as required [equivalet to PWD/GS Page: E-14 Item: E/1/a] |
| 8 | 2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC |
| 9 | 2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC |
| 10 | 2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) as ECC |
| 11 | Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.[PWD/GS Page: F-5 Item: 9] |
| 12 | 2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) |
| 13 | 2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) |
| 14 | S&F EPC make 9\" Sweep A.C Exhaust fan incl. making hole on wall with nuts & bolts of required with S&F of louver shutter. [PWD/GS Page: C-4, Item: 28, 30] |
| 15 | Supply & Fixing of Philips MAS LED Tube 1200mm 18W865 T8 l- 2100lm or Equivelent of Havells. |
| 16 | S&F single 4ft LED commercial tube light fitting incl. 4ft 20W LED tube, complete with all accessories suspended from ceiling/beem with L-clamp/ beem clamp as per schedule [Philips:or Equivalent of Havells, Crompton approved by EIC) [PWD/GS Page: C-2 Item: 17] |
| 17 | S&F double 4ft LED commercial tube light fitting incl. 2 nos. 4ft 20W LED tube lamp, complete with all accessories suspended from ceiling/beem with L-clamp/ beem clamp as per schedule [Philips:or Equivalent of Havells, Crompton approved by EIC)[PWD/GS Page: C-2 Item: 17] |
| 18 | Extra for suspension for florescent light fitting exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. [PWD/GS Page: C-2 Item: 16] |
| 19 | Supply & Fixing of 10W LED Lamp. Havells or Equivalent ofPhilips or Crompton) |
| 20 | Supplying and fixing 415V, TPN200A on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc (Make: L&T or equivalent) |
| 21 | Supplying and fixing 200A 415V, TPN SFU with sheet steel enclosure on flat iron/angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. (Make: L&T or equivalent)[PWD/GS Page: D-3 Item: 4/a] |
| 22 | S&F double door 6Way Vertical TPN MCB Distribution board for 160A MCCB incomer with IP-42/43 protection, on angle iron frame on wall incl. Inter connection & provision for earthing attachment (L&T/Siemense /Havells Metalica /ABB Elegance - as per direction of EIC)[PWD/GS Page: D-11Item: 15] |
| 23 | S&F double door Horizontal 6-Way TPN MCB Distribution board with IP-42/43 protection, concealed in wall (Legrand: (607716 /Siemense /Havells Metalica /ABB Elegance - as per direction of EIC) [PWD/GS Page: D-10 Item: 14 ] |
| 24 | S&F 415 V L&T 125A 4- Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection[PWD/GS Page: D-8 Item:10] |
| 25 | Supply & fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection (Legrand /Siemense /Havells Metalica /ABB Elegance - as per direction of EIC)[PWD/GS Page: D-6 Item: 7] |
| 26 | 63A FP MCB |
| 27 | 63A TP MCB |
| 28 | 6-32A SP MCB |
| 29 | Supply & delivery of 1.1 KV Gr. XLPE/ PVC Armoured Aluminium Cable (KEI/ Gloster / Havells / Approved by EIC) |
| 30 | 4 core 50 sq. mm. |
| 31 | 4 core 95 sq. mm. |
| 32 | 4 core 35 sq. mm. |
| 33 | Laying of cable on wall/surface incl. S & F MS saddles with earthing attachment in 2X10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting [PWD/GS Page: F-1 Item: 2/b] |
| 34 | Laying of cable 3/3.5/4 core 35 sqmm to 50 sqmm[PWD/GS Page: F-1 Item: 2/c] |
| 35 | Laying of cable 3/3.5/4 core 70 sqmm to 95 sqmm[PWD/GS Page: F-1 Item: 2/d] |
| 36 | S & F compression type brass cable glandcomplete with brass gland, brass ring & rubber ring for dust & moisture proof entry of XLPE/PVC armoured cable. [PWD/GS Page No.: F-4Item No.: 7/c] |
| 37 | 4 core 35 sq. mm. |
| 38 | 4 core 95 sq. mm. |
| 39 | 4 core 50 sq. mm. |
| 40 | Finishing the end of the XLPE/PVC armoured cableas by crimping method incl. S&F solderless socket (Dowels make), tapes, anticorrosive paste & joiting materials.[PWD/GS Page No.: F-5Item No.: 8/b] |
| 41 | 4 core 35 sq. mm. |
| 42 | 4 core 95 sq. mm. |
| 43 | 4 core 50 sq. mm. |
| 44 | Supply & Fixing 48\" (1200mm) AC ceiling fan make: (Orient PSPO NEWBREEZE or SUMMERCOOL / equivalent of UHSAapproved by EIC) complete with down rod, canopy fork, bladeswith all other accessories etc. but without regulator. [PWD/GS Page: C-3 Item: 21/a] Supply & fixing additional safety arrangement of ceiling fan by stranded GI strain wire of suitable gauge with one end fixed at RC clamp with special type of socket, nut-bolts, thimbles which throughly crimped with the strain wire and the wire passing through down rod (for upto 8 ft) and also other end connected with armature spindle by its existing jam nut hole with special arrangement (sample approved by EIC). The length of the strain wire up to 9ft also considering any type of work required i.e. enlarging the existing hole by file etc. to complete the job including installation as per direction of EIC (Static & Dynamic Load Test (in rotation of 1:20) certificate must be provided with final bill jointly with concerned Junior Engineer & authorised Electrical Supervisor of Agency). |
| 45 | S&F 18\" (450mm) 3-blades, AC Wall Bracket type, 1420rpm, 85W Sweep Air Circulator (make: EPC)by S&F rag bolts, nuts & washers (6mm dia x 62mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. Length. (Make: Orient-Wall-II Tornado/ USHA/Havells) |
| 46 | Supply & Fixing 240V single phase 18\" 3-blades, Metal BodyACpedestal fan (Make - Orient: Pedestal-II Tornado/Crompton: STROM-2-18\" /USHA: FARRATTA -18\"/ Similar type) complete with all accessories incl. connection as per direction of EIC. |
| 47 | S&F Electronic Socket type fan regulator on existing switch board with backelight top cover after making housing for regulator knob by cutting backelight top cover including making necessary connections. [Make: Anchor] [PWD/GS Page: E-6 Item: 18/a ] |
| 48 | Suppply & installation of Water Heater including suitable steel pipe & all other accessories. (Havells: ANODIA-GHWCAMTWH015- 15L- White/ V Guard-IRISH 15 L) |
| 49 | Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. [PWD/GS Page No.: D-14Item No.: 34/a/i] |
| 50 | 150x50x1.25mm (18SWG) Cable Tray |
| 51 | Supply & Fixing angular batten holder (Anchor) on 75mm dia PVC round block / round bakelite on wall/ceiling. |
| 52 | Dismantling of whole old existing wiring ceiling fan , exhaust fan etc. carefully with skill labour. |
| 53 | Supplying & Fixing 240 V AC/DC superior type Ding-Dong Call Bell (Anchor) on HW board incl. S&F HW board |