| 1 | Supply , installation commissioning and testing of Factory assembled Silent DG set with AMF panel of capacity 82.5 KVA, 66 KW , 1500 RPM , Turbo Charged, water cooled comprising of 102 BHP Engine with microprocessor based Genset controller with silencer and canopy for sound less mode (sound level not exc level specified by pollution control board) and alternator both mounted on a common base frame conforming to ISO-3046/BS-5514 andIS-10002 rated for 415 volts 50 cycles , 0.8 Power factor (PF) complete withresidential silencer, AVM pads , battery with its leads, first fill of lub oil and all engine accessories such as self starter, alternator/dynomo with suitable coupling and base frame on foundation as recommended by the manufacturer and consisting of other electrical component and maintenance free battey including suitable size of copper cable lead with terminal, all mounting accessory and AVM pads all as specified comprising with the following. (Make : Engine : Cummins/ Kirloskar (KEOL) / Crompton Greaves, Alternator : Stamford/ Kirloskar |
| 2 | A. Engine : |
| 3 | (a) Vertical multicylinder, cold starting in accordance with BS-5514/IS-10002 at 1500 PM including the following accessories :-(i) Fuel tank(Suitable for capacity for minimum 10 Hrs run).(ii) Fuel filter(Ore & Micro).(iii) Fuel feed pump(Inline monoblock/PT type) with governor.(iv) Lub oil filter.(v) Lub oil cooler.(vi) Dry type/oil bath type air cleaner.(vii) Exhaust Silencer(Industrial type).(viii) Radiator, Radiator fan & mounting.(ix) Fly wheel with starting ring.(x) Expansion bellow.(xi)Exhaust gas turbocharger.(xii) 12 Volt electric starter with 01 Nos maintenance free battery 180 AH capacity.(xiii)Battery charging alternator(xiv)Engine control panel consisting with ON/OFF Start Key,Lub oil pressure guage, Battery charging ammeter,Coolant temp gauge, RPM Meter etc.(xv)Suitable flexible coupling(xvi) Front & Rear engine mounting supports (AVM pads) |
| 4 | B. ALTERNATOR |
| 5 | (i) Alternator, 3 phase, 415 Volts, 50 Hzs, 0.8 PF, 1500 RPM self excited, self regulated screen protected, drip proof alternator of capacity 82.5 KVA conforming to BSS 5000 (part 99) with insulation class \"H\", single bearing and automatic voltage regulator accessories |
| 6 | C. ACOUSTIC ENCLOSURE |
| 7 | (i) Specially design to meet stringent MOEF/CPCB norms of 75 dBA @ 1 mtr at 75% load under free field conditions.(ii) Air inlet louvers specially designed to operate at rated load even at 50 degree C air inlet temp.(iii) Powder coated for long lasting service life and superior finish. .(iv) Insulation material meets exacting IS 8183. |
| 8 | D.ACCESSORIES |
| 9 | (i) Suitable channel frame (ii) Storage battery of 1X12 Volts of suitable 180 AH capacity as per manufacturer instruction mounted on angle iron frame of suitable size as directed. |
| 10 | E. CONTROL PANEL |
| 11 | The control panel shall be made of CRCA sheet duly fabricated and powder coated and complete with internal wiring, bus bar etc and fitted with the following accessories :-(i) MCCB 4 Pole 200 Amps 36 KA Microprocessor release type – 01 No(ii) Digital Ammeter with CT of size 200/5A– 01 No(iii) Digital Voltmeter 3 Ph 415 volts– 01 No(iv) Microprocessor based DG set control unit with SIM enable - 01 No(v) Indicating lamps (LED type) (R-Y-B) – 01 set |
| 12 | F. AMF PANEL |
| 13 | The control panel shall be made of CRCA sheet duly fabricated and powder coated and complete with internal wiring, bus bar etc and fitted with the following accessories :-(i) MCCB 4 Pole 200 Amps 36 KA Microprocessor release type – 02 Nos(ii) Contactor 200 Amps -02 Nos(iii)Digital Ammeter with CT of size 200/5A– 02 Nos(iv) Digital Voltmeter 3 Ph 415 volts– 02 Nos(v) Indicating lamps (LED type) (R-Y-B) – 02 sets(vi) Relay, timmer and other acessories as per manufacturer. |
| 14 | NOTE |
| 15 | (i)Antivibraton mounting pads to be incorported during installation.(ii)Cost of PCC foundation as per manufacturer recommendation included in the cost of Gen Set.(iii) Silencer pipe of engine is to be extended out of the building with suitable dia of GI medium grade pipe duly heat insulated with suitable asbestos rope duly claded with plaster of paris, rate of which deemed to be included in the unit rate of Gen set.(iv) Lubricating oil shall be provided by the conractor Cost of which deemed to be included in the unit rate of DG Set.(v) Four Nos free servicing with complete material such as Lubricating oil, coolent, Lub oil filter, diesel filters, Air filter and fan belts etc as per manufacturer recommendation will be deemed to be included in the unit rate of DG set.(vi) Any other items which are not mentioned above but are essential for smooth functioning of DG set shall also deemed to be included in the quoted rates. |
| 16 | Supply, installation, commissioning and testing of Water Cooler fully stainless steel SS-304 material body, electric driven single phase 240 volts 50 Hz having approx storage capacity of 80 Litre and nominal cooling capacity of 40 litre per hour, R134a refrigerant gas filled, two Nos faucets, water over flow cnnection including all accessroies complete all as specified and as directed. Make: Voltas/Usha/Blue Star/LG. |
| 17 | Supply and fixing PVC connection pipe hot and cold, 15 mm dia, 450 mm long with PTMT nuts brass adopter & washer on both sides complete all as specified and directed.Make: Prayag/Sintex/Shakti |
| 18 | Supply, installation, commissioning and testing LT Panel Board factory made CPRI approved panel, weather, dust & vermin proof indoor cubical compartmental type, single door, front and back side openable, with providing rubber/PVC gasket of suitable size all sides of door, with copper busbar wrapped with PVC tape/sleeves with maintained the colour code and copper strip busbar of suitable rating to MCCB input and MCCB output of suitable length, made out of 2.00 mm thick mild steel CRCAsheet with 40 x 40 x 6mm size angle iron supporting frame including duly Powder coatedexposed external & internal surfaces suitable for 3 phase 4 wire system 415/440 volts grade including complete internal wiring with 1.5 sqmm copper wire and connections of all outgoing / incomming including PCC foundation complete all as directed and specified and comprising of the following fitment accessories :- |
| 19 | INCOMMING(a) Copper strip busbar of current carrying capacity 200 Amps wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends= 04 Nos.(b)MCCBIP 44 and IP 66/67 protection, 4 pole, 415 volts, Lcu=36 KA breaking capacity, rating 200 Amps, adjustable thermal magnetic type, thermal release range (64 to 100 %) with O/L, S/C protection including all fixing accessories with both ends spreader links -02 Nos (Make : Legrand/Schneider/L&T).(c) Supply and fixing changeover switch C-line type ,200 amps open execution type ,415 volt,50 cycles complete with operation handle.- 02 Nos Make :- L&T/Siemens/GE Power. . (d)LED Neon indicator lamp (RYB) with holder,230/250 volts,AC -03 sets (set of three) Make :- AE/L&T/Schneider.(e) Digital Ammeter of range (0-200) Amps, flush mounting type of size 100mm x 100mm (4”x4”) square dial with CT’s of ratio 100/5 and selector switch – 01 set (Make : Legrand/Schneider/L&T)(f) Digital voltmeter of range (0-500) volts, flush mounting type of size 100mm x 100mm (4”x4”) square dial with selector switch – 01 Nos (Make : Legrand/Schneider/L&T). |
| 20 | OUTGOING(a)MCCBIP 44 and IP 66/67 protection, 4 pole, 415 volts, Lcu=36 KA breaking capacity, rating 160 Amps, adjustable thermal magnetic setting type with O/L, S/C protection including all fixing accessories with both ends spreader links -02 Nos (Make : Legrand/Schneider/L&T). (Make : Legrand/Schneider/L&T).(b)MCCBIP 44 and IP 66/67 protection, 4 pole, 415 volts, Lcu=36 KA breaking capacity, rating 100 Amps, adjustable thermal magnetic setting type with O/L, S/C protection including all fixing accessories with both ends spreader links -02 Nos (Make : Legrand/Schneider/L&T).(b) Spare Pockets for MCCB - 01 No |
| 21 | Supply, laying, jointing & testing in trenches or passing through pipe, 1100 volts grade, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured LT electric power under ground cables, heavy duty with aluminium conductor with all fixing & connecting accessories such as Alluminium cable lugs, cable gland, nut, bolts, washer etc complete as specified and as directed.(NOTE: Earthwork & Excavation, GI pipe, brick protection etc shall be measured and paid separately under relevant items of this BoQ). |
| 22 | Size 120 Sqmm x 3.5core |
| 23 | Size 95 Sqmm X 3.5 core |
| 24 | Size 50 Sqmm X 3.5 core |
| 25 | Material and labour for earthing complete with galvanised steel plate electrodes of size 600x600x6mm thick burried directly in ground with earth pit not less than 2.25 meter deep below normal ground level with top edge of plate not less than 1.5 meter below normal ground level connected to galvanised32x 6 mm earth lead by means of nuts bolts check nuts GI washers earth wire protected by galvanised iron pipe 40 mm bore (light grade) for transformer/ LT panel including connection complete allas directed including concrete pit in PCC (1:3:6) type CI, precast RCC cover slab of size 45x45x10 cm with one handle for lifting made out of 8 mm diameter MS bar finnel wire mesh 20 mm bore galvanised iron pipe (light) for watering charcoal or coke and salt in alternate layers necessary earth work in soft/loose soil complete all as shown in electrical plate No 5 of SSR Part I including testing on completion all as specified and directed. |
| 26 | Supply, install, testing and commissioning of Servo controlled voltage stabilizer of capacity 30 KVA Confirming to BIS 9815:Part1 :1994 Three phase,50 Hz, Naturally Oil cooled , indoor, unbalanced type, copper wound, metallic body duly powder coated with lifting Hooks two Nos, digital display type, relay free smooth and silent operation with 1st filling of Transformer oil up to level having following specification:-(a) Input voltage 340V-480V,(b)Output voltage stabilized at any deigned/desired voltage 415V (+/-) 1%(c) Rated frequency 50 Hz(d) No distortion in wave form(e) Response time not to exceed 20 mille seconds(f) Sensitivity (+/-)1%(g) Rate of correction 8 Volt/second for single phase and 13 V/seconds for phase to phase(h) Efficiency more than 95%(i)Type of load : three phase , unbalanced type(j) Digital display Voltmeter/Ammeter(k) Over load/Short Circuit protections(l) High/Low voltage cut off protection(m) By pass arrangement in case of emergency (n) Single phase sequence change protection |
| 27 | Supply, installation and testing of swimming pool suction sweeper complete with SS trolley mounted wheel and handle, motor with pump set of capacity 2 HP 240 volts with DOL starter, three core multi stranded copper flexible cable 4.0 coreof approx 20 mtrs long, flexible PVC hose pipe of suitable dia of 15 mtr long, one feet long vacuum headed heavy duty brush, GI handle , fitting and nozzle etc complete all as specified and as directed. |
| 28 | Excavation in trenches in soft/loose soil not exc. 1.5 metre wide and not exc. 1.5 metre in depth and getting out for laying of under ground electric cable complete all as specified and as directed. |
| 29 | Returning, filling in excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and as directed |
| 30 | Removing excavated soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed |
| 31 | M & L dry sand cushioning to underground cables with 8cm thick before laying of cables and 15cm thick after laying and stretching of cable and gentally hand ramming and consolidation of thickness of sand 18 cm thick complete all as specified and as directed |
| 32 | Supply and laying sub class B bricks of size 25cmx15cmx7.5cm for protection of UG cable with width equal to length of bricks as mechanical protection laid dry and flat complete all as specified and as directed. |
| 33 | Supply and fixingof GI tubing, light grade, 50 mm bore with all fitting lais in trenches / pole / wall for protection of cables in repairs complete. |
| 34 | Supply and fixing Electrical GDR cheqeured rubber matting of size 2 mtr X 1 mtr X 25mm thick suitable for HT 11 KV indoor substation as per IS 5424:1969 complete all as specified and as directed. Make:- Joyti / Duratuf Product |
| 35 | M & Lfor Cement concrete 1:3:6 type C-2 using 40mm graded stone aggregate in foundations, filling and mass complete all as specified and directed. |
| 36 | Dismantling of OH ACSR conductor of any size and removing unserviceable conductor from site complete all as specified and directed. |
| 37 | Dismantling of LT insulators any type of size complete all as specified and directed. |
| 38 | Dismantling of cross arm of MS channels of angle, section etc complete and setting aside for reuse complete all as specified and directed. |
| 39 | Supply and fixing of GI tubing, light grade, 40 mm bore with all fitting lais in trenches / pole / wall for protection of cables in repair complete. Make- TATA /JINDAL / BANSAL |
| 40 | Supplying, transporting and erecting in position steel tubular swaged poles 410-SP-31 type, 9.00 Mtr long complete with mild steel base plate, CI finial taper, bolts, nuts and washers etc. including necessary excavation and earth work, PCC1:4:8 type D-2 in foundation below pole, PCC 1:3:6 type C-2 around poles and PCC 1:3:6 type C-1 as in plinth block asdirected, disposal of surplus soil to a distance not exceeding 50 m and depositing where directed, painting steel tubular poles exposed surface with Aluminium paint two coats over one coat of red oxide primer and providing 300 mm wide bands (3 bands /straps with synthetic enamel paint and 2 bands with black bituminouspaint) from plinth block and numbering of poles, painting embedded portion of poles with one coat of bituminous paints including disconnecting and taking out old damaged PCC pole complete all as specified and directed. |
| 41 | Supply, laying, jointing & testing in trenches or passing through pipe, 1100 volts grade, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured LT electric power under ground cables, heavy duty with aluminium conductor of cross sectional area 35 sqmm3.5 core with all fixing & connecting accessories such as aluminium cable lugs, cable gland, nut, bolts, washer etc complete as specified and as directed. (Make: HAVELLS/ POLYCAB/PLAZA/GRANDLAY) (NOTE: Earthwork & Excavation, GI pipe, brick protection etc shall be measured and paid separately under relevant items of this schedule \"A\" part). |
| 42 | ~Ditto~ all as per item 22.00 above but 16 Sqmm, 4 Core. |
| 43 | ~Ditto~ all as per item 22.00 above but 10 Sqmm, 4 Core. |
| 44 | ~Ditto~ all as per item 22.00 above but 10 Sqmm, 2 Core. |
| 45 | M & L forCross arms, bracing, supports, clamps and back plate, fabricated from structural steel sectionincluding nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed including two coats of synthetic enamel paint over a coat of red oxide primer, complete all as directed |
| 46 | S & F in repair street light bracket made out of GI pipe light grade 40mm dia 1.2 metre length bent to shape and reduced to required size at top upto 1.5 metre length by cutting, welding and well finishing including MS clamp of flat iron of size 40x6 suitable length 2 sets with nut- bolts of required size complete with drilling hole, fixing with nuts bolts and washers including painted with two coats of aluminium paints over a coat of red oxide primer including dismantling one complete all as specified and as directed. |
| 47 | Supply and fixing pole mounted SMC junction box/bus bar chamber for loop IN/OUT connection of street light cable of size 295x195x100 mm high heat distoration temperature, non-fusing , shockproof, rustproof, 100 % weatherproof, fire retardant- class FV-O as per IS 11731 Part-II and suitable locking arragement with three phase and neutral aluminium busbar of size 20X3 mm of length 170 mm wrapped with PVC sleeves with maintained the colour code and provision of making holes with GI nuts, bolts & washers for cable connections mounted on hydrograpic insulators with nuts & bolts at both ends of busbar and fixed on pole steel/PCC with suitable two flat iron clamp 25x4mm with nuts and bolts (duly painted with two coats of aluminium paint over a coat of red oxide primer) and dismantling of old unserviceable one complete all as specified and as directed.complete all as specified and directed.Make: Sintex , Cat No: GSJB3020 or equivalent model of Hensel/Rittel. |
| 48 | Supply and fixing PVC Sheathed multi stranded unarmoured copper conductor cable LT 1100 volt grade Conforming to IS 7098 FRLS (inner sheet) of size 1.5 Sqmm 3 Core (Nominal Area) from pole junction box to light fitting with suitable size copper cable lugs and connectorcomplete all as specified and directed. Make : Plaza/Havells/Polycab/Finolex. |
| 49 | Taking down old unserviceable convetional street light fittings/ post top lantren/ bollards etc of any type/modelincluding associated accessories from 8.5/9 mtr pole/Top of the building/ other similar situationcomplete all as specified and directed. |
| 50 | Supply and fixing LED light fitting for street/security lighting energy saving & environmental friendly long life versatile pressure die-cast housing with toughened glass and individual high power LED with secondary optics of capacity 60 Watt 240 volts AC 50 Hz , IP 66 protection suitable for 40 mm dia GI pipe bracket including three years on site warranty from manufacturer complete all as specified and directed. Make: Bajaj, Cat No: BRTFG 60W LED V3 / Crompton Greaves, Cat No: LSTP-60-CDL-M/ HPL , Cat No: HPLLEDSL6060S |
| 51 | Refixing old serviceable street light fitting obtained from item no of any type/model includingassociated accessories to 8.5/9 mtr pole / Top of the building / other similar situation complete all as specified and directed. |
| 52 | Supply ,fabrication, installation and testing of LT out door type factory made CPRI Approved ,feeder pillar box of size 700mmX500mmX400mm (over all dimension) made out of 3.00 mm thick CRCA sheet duly supported with mild steel angle iron of size 40X40X5mm vertical legs frame with front and back side openable ,single hinged door / shutter with locking arrengement and powder coated finish both internal and external steel surfaces after necessary preparation of steel surfaces including providing PCC (1:3:6) type C2 foundation of suitable size and connections of all outgoing / incomming existing cable of any size drawing / digging out cable from loops in trenches inclusive of necessary excavation and earthwork as required and relaying the cables including the following fitment accessories complete all as specified and as directed. |
| 53 | Incoming(a) Copper strip busbar of size 25 x 5 mm wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends= 04 Nos |
| 54 | (b)MCCB, adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity, rating 63 Amps including all fixing accessories with both ends spreader links-01 No.(Make :- L& T/ Legrand/ Schneider |
| 55 | (c)Digital voltmeter of range (0-500) volts, flush mounting type of size 96mm x 96mm (4”x4”) square dial with selector switch – 01 No (Make : Legrand/L&T/Schneider/AE). |
| 56 | (d)LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 Volts, AC - 01 Set (Set of three) (Make : Legrand/L&T/Schneider) |
| 57 | Outgoing(a) MCB Single Pole 32 Amps,240 volts, 10 KA breaking capacity C curve - 04 Nos Make :- Legrand/L&T/Schneider. |
| 58 | (b) Digital type time Switch 240 volts AC Single Phase, 01 No. Make :- L&T, Cat No AUTS02DIG00 or equivalent model of Legrand//Schneider. |
| 59 | (c) Power contactor 32 amps 3 Pole 415 Volts AC - 01 NoMake: L&T, Model: MNX40 Cat No:- CS94190 or equivalent model of Schneider/Siemens. |
| 60 | (d)Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm X 150mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of JB for LT -01 No. |
| 61 | Supply ,fabrication, installation and testing of LT out door type factory made CPRI Approved, water and vermin proof protection type junction box of size 900mmX600mmX400mm (over all dimension) made out of 3.00 mm thick CRCA sheet dully supported with mild steel angle iron of size 40X40X5mm vertical frame and legs with mild steel flat iron 25X5 mm in horizontal sides of the frame with front and back side openable ,single hinged door / shutter with locking arrengement and powder coated finish both internal and external steel surfaces after necessary preparation of steel surfaces including providing PCC (1:3:6) type C-2 foundation of size 0.80m x 0.60m x 0.90m depth (0.30m below ground lavel and 0.60m above ground level) and connections of all outgoing / incomming existing cable of any size drawing / digging out cable from loops in trenches inclusive of necessary excavation and earthwork as required and relaying the cables including the following fitment accessories all complete as specified and as directed. NOTE: Rate of earthwork and PCC work are deemed to be inclusive in this item. |
| 62 | (a)Alluminium bus bar of size 50 mm X 6 mm X 400mm long wrapped with PVC sleeves with maintained the colour code and provision of making holes as required with nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends= 04 nos. |
| 63 | (b)Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm X 150mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of JB for LT -01 No. |