| 1 | M & L for repair of Single pointed air termination aluminium rod 12 mm dia 300mm long complete to walls/roof/pipes with suitable clamps of MS bolts and nuts etc required at site complete all as specified and as directed by Engineer-in-Charge. (MS work will be measured and paid separately). |
| 2 | M& L for taking down existing aluminum strip 25mmx3.00mm / 32x6mm Gl Strip from the top of bldg /ground (roof down conductor) and keeping serviceable strips in safe custody for reuse completeall as specified and directed by Engineer-in-Charge. |
| 3 | M & L for making old serviceable strips refined obtained against item no-2 by making them straight and re-fixing the same in position by wiring screw/ gattas/ insulators/ PCC Block complete all as specified and directed by Engineer-in-charge. |
| 4 | M & L foraluminum strip 25x3.15 mm earth continuity conductor or Main earthing lead fixed to wall on batten or recess or chasesor buried in ground or drawn in conduit/pipe or fixed to poles in roof of bldg or any other indicated situation for loop earthing etc as required including 2mm dia galvanized iron or steel wire complete all as specified and directed by the Engineer-in-Charge. |
| 5 | M & L forcopper strip 25x3.15 mm earth continuity conductor or Main earthing lead fixed to wall on batten or recess or chasesor buried in ground or drawn in conduit/pipe or fixed to poles in roof of Bldg or any other indicated situation for loop earthing etc as required including 2mm dia galvanized iron or steel wire.complete all as specified and directed by the Engineer-in-Charge. |
| 6 | M & L forgalvanised iron strip 32x6mm earth continuity conductor or main earthing lead fixed to wall on batten or recess or chasesor buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required including 2mm dia galvanized iron or steel wire complete all as specified and directed by the Engineer-in-Charge. |
| 7 | S & F in repair Gl tubing 40mm bore light grade in trenches/floor/fixed along pole for cable/earth strip protection with proper sizeof clamps nuts and bolts for fixing lighting conductor etc. complete all as specified and directed by the Engineer-in-Charge. |
| 8 | All as per item No 7 above but of size 50mm bore complete all as specified and directed by the Engineer-in-Charge. |
| 9 | M&L for Raw salt with mixing in water complete all as specified and directed by the Engineer-in-Charge. |
| 10 | M&L funnel suitable for each pit complete all as specified and directed by the Engineer-in-Charge. |
| 11 | M&L for repair insulator for each strip and fixed arrangement in roof/wall of building for run of strips on it with nuts and bolts.Complete all as specified and directed by the Engineer-in-Charge |
| 12 | M & Lfor Test Point terminal block made of gunmetal or phosphorus bronze size 75X75X25mm drilled and screwed including 03 Nos 8 mm dia long hex head screw complete all as specified and directed by Engineer-in-Charge. |
| 13 | M&L for making PCC chamber of size as per electrical plate No 3 of SSR 2009 Part I with PCC (1:2:4) type B1 including RCC cover with suitable handle including dismantling of old PCC earth pit chamber complete all as specified and directed by the Engineer-in-Charge |
| 14 | M&L in replacement of Pit cover, Cl 10mm thick hinged to Cl frame 40x40mmduly painted with anti corrosive paint internally and externally Complete all as specified and directed by the Engineer-in-Charge. |
| 15 | S&F cross arms bracing supports clamps and back plates fabricated from structural steel section including nut, bolts, washers, welded, binding, cold as hot drilling holes for bolts in any shape or size as required painted with two coats of aluminium paint over a coat of red oxide primer after preparation of surface complete all as specified and directed by the Engineer-in-Charge. |
| 16 | S&F plug & socket board TPN enclosure with 3pole and earth metal plug & socket for incorporating TP including MCB TPN 32 Ampscomplete all as specified and directed by the Engineer-in-Charge.Make :- Havells/ Standard/Legrand. |
| 17 | S&F metal plug clad & socket including MCB SPN 20 Amps complete all as specified and directed by the Engineer-in-Charge.Make :- Havells/ Standard/Legrand. |
| 18 | S & F in repair of Aviation obstruction light with twin 100w GLS in over head tanks / Bldg / high mast/Saft pans with following specification and accessories.(a)Luminaries body :Aviation yellow colored die-cast aluminum alloy housing for one nos 100watt GLS Lamps, (b) Enclosure :Red colored poly carbonate done secured to housing by 3 Nos screw, (c)Mounting arrangement : 38 mm dia threaded item with lock nets for mounting on pipe above structure , (d)Degree of protection : IP43Make : Bajaj/ Havells / CG |
| 19 | S & F in repairt of serviceable 2 core aluminum conductor of Size 2.5 Sqmm for obstruction light in over head tank/Blast pans all as specified and directed by Engineer-in-Charge. |
| 20 | M&L for maintenance free chemical earthing comprising of 17.2 mm dia molecularly copper bounded 250 mm micron on steel electrode 2.5 meter long each 03 nos per set, earth enhancing soil treatment compound TEREC + having essential chemical ingredients such as ionic chemical to provide stable low resistance for earth terminal to make it maintenance free ( TEREC + comes in 25 kg per bag required per set of chemical earthing ) HDPE earth pit cover medium duty to withstand 2000 kg load U clamp bolt for connecting copper strip ( minimum size of copper strip 25 x 3 mm -20 meter ) to earth rod. Note:- The subject item shall be executed at site by the authorised person or its agent. Approval of the same shall be obtained from Accepting Officer before execution. |
| 21 | M & L sheet metal enclosure 2 way with MCB SPN 16 Amps fixed in Blast Pans , all as specified and directed by Engineer-in-Charge. |
| 22 | Excavation in trenches n exc 1.5 mtr wide and depth n exc 1.5 mtr deep for foundation, laying GI pipes and UG cables etc n exc 10 sqmtr on plan, in soft/loose soil and getting out complete all as specified and directed. |
| 23 | Returning filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified and directed. |
| 24 | M&L for Sand cushioning with dry cleanriver sand for protection/covering of under ground cable in trenches complete all as specified and directed by Engr-in-Charge.Note:- Punned thickness only shall be measured for payment. |
| 25 | Removing excavated material not exc 50 mtr and depositing where directed at a level not exc 1.5m above the starting point complete all as specified and directed. |
| 26 | M & L Sub class\"B\" old size well burnt brick laid flat in trenches as protection to LT cable complete all as specified and as directed. |
| 27 | M&L PCC, type C1, (1:3:6, using 20mm graded stone aggregates) as in coping of poles including formwork complete all as specified and as directed including demolition of old damaged concrete from pole. |
| 28 | M&L PCC, type D2, (1:4:8, using 40mm graded stone aggregates) as in PCC/Road cutting /installation area and foundation of pole etccomplete all as specified and as directed by Engr-in-Charge. |
| 29 | Supply and fixing GI Tubing light grade under road, on pole floor and on wall for cable protection complete all as directed for sizes 50 MM dia bore complete as directed by Engr-in-charge. |
| 30 | Supply, laying XLPE insulated PVC inner sheathed, armoured with galvanized steel strip or wire heavy duty underground cable withstranded aluminumconductor 1100 volt grade of size 185 Sqmm 3.5 Core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing complete all as specified and directed including taking down old unserviceable XLPE cable with brick protection andcomplete all as specified and as directed. |
| 31 | All as per Item No.30 above but size of XLPE cables 70 Sqmm 4 Core. |
| 32 | All as per Item No.30 above but size of XLPE cables 50 Sqmm 4 Core. |
| 33 | All as per Item No.30 above but size of XLPE cables 25 Sqmm 4 Core. |
| 34 | All as per Item No.30 above but size of XLPE cables 16 Sqmm 4 Core. |
| 35 | Relaying XLPE insulated PVC inner sheathed, armoured with galvanized steel strip or wire heavy duty underground cable withstranded aluminiumconductor 1100 volt grade of size 180 Sqmmto 95 Sqmm, 3.5 Core complete after clearing fault relaying of same cablelaid in trenches / duct passing through pipe / duct or fixed on pole including Lux, ferrul, nut, blots tapping etc., and connecting and testing complete all as specified and directed including taking down old unserviceable XLPE cablecomplete all as specified and as directed.Note:- LT Joint will be measured separately and unserviceable cable shall be taken on charge. |
| 36 | All as per Item No.35 above but size of XLPE cables 70 to 35Sqmm Sqmm 3.5 Core. |
| 37 | All as per Item No.35 above but size of XLPE cables 25 to 10 Sqmm 4/3.5 Core. |
| 38 | Supply and fixing in repair PVC Insulated and sheathed twin core Flat cables 1100 volts each core having single stranded aluminium conductor service cable size 10 sqmm complete all as specified and directed. |
| 39 | Supply and fixing in repairPVC Insulated and sheathed twin core Flat cables 1100 volts each core having single stranded aluminium conductor service cable size 4 sqmm complete all as specified and directed.Make- Havells/ Polycabe/KEI |
| 40 | Supply and fixing in repairPVC Insulated and sheathed twin core Flat cables 1100 volts each core having single stranded aluminium conductor service cable size 2.5 sqmm complete all as specified and directed. |
| 41 | Supply and erecting steel tubular swaged pole 9.00 m long type 410 SP-31 complete with cast iron base plate and final taper plug duly painted with anti corrosive paint internally and externally and upto 1.5 m length of pole above ground level (externally) shall be painted with two coats of synthetic enamel paint in strips of 30 Cm length, black and yellow alternatively and balance of pole with two coats of aluminium paint including dismantling of old unserviceable steel tubular pole of any size with necessary disconnection of electric wire, fitting and fixtures etcas required complete all as specified and as directed byEngr-in-Charge. Make:- Bansal / M/s Calcutta poles ltd or equivalent and approved. |
| 42 | Supply and fix in repairLT cable jointing kit 1100 volt grade cable for straight through joint , cold shrink type complete with jointing material and accessories suitable for 4 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm etc complete all as specified and as directed byEngr-in-Charge. |
| 43 | All as per item No 42 above but LT XLPE jointing kit for 4 core XLPEarmoured aluminium conductor cable of size 120 to 185 sqmm |
| 44 | Supply and fix in repairLT cable jointing kit 1100 volt grade cable for indoor / outdoor termination joint, heat shrink type complete with jointing material and accessories suitable for 4.0 core XLPE armoured aluminium conductor cable of size 70 to 150 sqmm etc complete all as specified and as directed byEngr-in-Charge. |
| 45 | Cutting and trimming of tree branches to clear OH lines in the area of LT OH lines feeders for a span of 30m each(including repairing and jointing of ACSR conductor if damaged during cutting of tree) and removal of the trimmed branches of trees and depositing the same in MCD waste bins inside the campus complete all as specified and directed by Engr-in-charge. |
| 46 | S&F in repair Indicator lamp (AC/DC), LED, type for as per existing fitting. Make: Legrand /Semens/L&T/Havells. |
| 47 | S&F in repair 3 Phase LED AmmeterCat Part No WL131020OOO Make - L&T or equivalent in AE/SCHNEIDER/BCH |
| 48 | S&F in repair, 3 phase LED Voltmeter Cat Part No WL132020OOOO Make:- L& T or equivalent in AE/SCHNEIDER/BCH |
| 49 | S&F MCCB, 100-125 Amps, 4P, 25 kA, 415 Volts, with thermal and magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed. Make:- L&T Cat part No. CM90642OOLO or equivalent model fromLegrand / Siemens. |
| 50 | S&F MCCB, 250 Amps, 4P, 25 kA, 415 Volts, with thermal and magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed. Make:- L&T Cat part No. CM90642OOPO or equivalent model fromLegrand / Siemens. |
| 51 | S&F MCCB, 125-160 Amps, 4P, 25 kA, 415 Volts, with thermal and magnetic release with sheet metal enclosure type complete including taking down old unserviceable MCCB complete all as specified and as directed. Make:- L&T Cat part No. CM90642OOMO or equivalent model from Legrand / Siemens. |
| 52 | S&F ACB 800Amps, 4P, 50 kA, 415 Volts, with thermal and magnetic release complete including taking down old unserviceable ACB complete all as specified and as directed. Make:- L&Tor equivalent model fromLegrand / Siemens. |
| 53 | S&F MCCB, 400 Amps, 4P, 36 kA, 415 Volts, with thermal and magnetic release complete including taking down old unserviceable MCCB complete all as specified and as directed. Make:- L&T Cat part No. CM94106OOS1OG or equivalent model from Legrand / Siemens. |
| 54 | S&F MCB, TPN, 415 Volts, 63 Amps, 10kA, \"C\" series including taking down old unserviceable MCB complete all as specified and as directed. Make:- L&T Cat Part No.BB40630C or equivalent model fromLegrand / Siemens. |
| 55 | S&F MCB, SPN, 415 Volts, 40Amps, 10kA, \"C\" series including taking down old unserviceable MCB complete all as specified and as directed. Make:- L&T Cat Part No.BB20630C or equivalent model from Legrand / Siemens. |
| 56 | M&L Earthing with galvanized steel earth plate electrode of size 600 mm x 600 mm x 6.00 mm buried directly in ground connected to galvanized earth lead strip of size 25 x 3.15 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel including 40mm dia medium grade GI tubing for protection of earth lead, MS sheet metal funnel with wire mesh, watering pipe light grade 20mm dia, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC type C1 (1:3:6, using 20mm graded crushed stone aggregates) 50mm thick precast RCC type B1, (1:2:4, using 20mm graded crushed stone aggregates) pit cover reinforced with 8mm dia deformed bar and suitablehandle made of 10mm dia round bar including galvanised strip of size 32mm x 6mm for extension of earth lead and necessary excavation, earth work, in soft/loose soil and disposal of spoils to a distance n.exc 50m and necessary connection and testing complete all as shown in electrical plate No 3 of SSR Part-I, 2009 and all as specified and directed including taking down old unserviceable earth pit.Note:- GI strip upto 7.5 m length shall be deemed to be included in the quoted rate against ibid item. The quantity required over 7.50 m shall be measured andpaid under relevant items seperately. |
| 57 | M&L Earthing with galvanized steel earth plate electrode of size 600 mm x 600 mm x 6.00 mm buried directly in ground connected to galvanized earth lead strip of size 32 mm x 6 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel including 40mm dia medium grade GI tubing for protection of earth lead, MS sheet metal funnel with wire mesh, watering pipe light grade 20mm dia, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC type C1 (1:3:6, using 20mm graded crushed stone aggregates) 50mm thick precast RCC type B1, (1:2:4, using 20mm graded crushed stone aggregates) pit cover reinforced with 8mm dia deformed bar and suitablehandle made of 10mm dia round bar including galvanised strip of size 32mm x 6mm for extension of earth lead and necessary excavation, earth work, in soft/loose soil and disposal of spoils to a distance n.exc 50m and necessary connection and testing complete all as shown in electrical plate No 3 of SSR Part-I, 2009 and all as specified and directed including taking down old unserviceable earth pit.Note:- GI strip upto 7.5 m length shall be deemed to be included in the quoted rate against ibid item. The quantity required over 7.50 m shall be measured andpaid under relevant items seperately. |
| 58 | M & L for painting LT Panel/feeder pillar by one coat of synthetic enamel paint after preparation of surfaces complete all as specified and as directed. |
| 59 | Servicing of LT Panel after shut downand removing all dust particles and proper layout of LT panel wlth gland packing including 2.5 sqmm single core copper cable including repairing/replacing door hinges/door lock etc including all necessary connections complete all as specified and directed. |
| 60 | Supply andfixing in repair onload changeover 400 Amps, 415 Volts , 50 HZ complete all as specified and directed.Make:- L&T/ Havells/ Schneider/ Siemens/ ABB |
| 61 | Supply andfixing in repaironload changeover 125 Amps 415 Volts , 50 HZ complete all as specified and directed.Make:- L&T/ Havells/ Schneider/ Siemens/ ABB |
| 62 | Supply and fixingonload changeover 63 Amps 415 Volts , 50 HZ complete all as specified and directed.Make:- L&T/ Havells/ Schneider/ Siemens/ ABB |
| 63 | M&L for preparation of old painted (outer exposed surface) of electric steel tubular poles 8.5/9.0 metres long with painting starting from ground level with black bituminious paint up to one metre andthereafterapplying one coat of aluminium paint including painting of MS channel / angle iron andclamps with bolts, nutsof street light fittingandwriting Pole No.with black colour synthetic enamel paint of letters size as existing complete all as specified and as directed. |
| 64 | S&F in repair LED Street light fitting 1x 45W LED street light including LED lamp in aluminium PDC housing, toughened glass cover with IP-66 protection including suitable size bracket complete all as directed by Engr-in-chargeMake: Havells /Crompton/Philips |
| 65 | S&F in repair LED Street light fitting 1x 60W LED street light including LED lampin aluminium PDC housing, toughened glass cover with IP-66 protection complete including suitable size bracketall as directed by Engr-in-chargeMake: Havells /Crompton/Philips |
| 66 | S&F repair LED Street light fitting 1x 70W LED street light including LED lamp in aluminium PDC housing, toughened glass cover with IP-66 protection complete including suitable size bracket all as directed by Engr-in-chargeMake: Havells /Crompton/Philips |
| 67 | Material and labour Street light bracket, made out of 40 mm dia GI pipe (medium grade) 1.5m long bend to shape as required and welded and fixing in position including dismantling and taking down old unserviceable bracket complete all as specified and directed. |
| 68 | Material and labour Street light bracket, made out of 25 mm dia GI pipe, (medium grade) 1.5m long bend to shape as required and welded and fixing in position including dismantling and taking down old unserviceable bracket complete all as specified and directed. |
| 69 | S&F Three Phase street light time switch distribution board consisting with 65 Amps 3 pole power contactor andAnalogue time switch includingtaking down old unserviceable time switchcomplete all as specified and as directed. Make : Indo Asian cat. No. TL065ABO or equivalent model fromLegrand /BCH. |
| 70 | S&F Three Phase street light time switch distribution board consisting with 40 Amps 3 pole power contactor andAnalogue time switch includingtaking down old unserviceable time switchcomplete all as specified and as directed. Make: Indo Asian cat. No. TL040ABO or equivalent model from Legrand /BCH. |
| 71 | S&F Three Phase street light time switch distribution board consisting with 32 Amps 3 pole power contactor andAnalogue time switch includingtaking down old unserviceable time switchcomplete all as specified and as directed. Make : Indo Asian cat. No. TL032ABO or equivalent model from Legrand /BCH. |
| 72 | S&F Three Phase street light time switch distribution board consisting with 16 Amps 3 pole power contactor andAnalogue time switch includingtaking down old unserviceable time switchcomplete all as specified and as directed. Make: Indo Asian cat. No. TL016ABO or equivalent model from Legrand /BCH. |
| 73 | Supply and fix in repair of 3 pole power contractor 40 Amps 415 volts complete all as specified and directed. Make: Indo Asian /Siemens / Legrand/L&T |
| 74 | Supply and fix in repair of analogue time switch 3module 24 hours progaramme, Programmable every 20 Min with battery backup of 100 Hrs. Make : Indo Asian cat Part No. TA912472 or equivalent model from Make :Siemens/ Legrand/ L&T |
| 75 | S&F in repairs LED driver for 25 Watt LED street light complete all as specified and as directed. Make:- Crompton Greaves /Phillips/ Bajaj. |
| 76 | S&F in repairs LED driver for 45 Watt LED street light complete all as specified and as directed. Make:- Crompton Greaves /Phillips/ Bajaj. |
| 77 | Supply and fix testing and commissioning of LED flood light fitting 100 W new generation energy saving and enviromental friendly, long life, versatile pressure die cast aluminium IP 65 PDC flood light aesthetically designed with better thermal management with electronic driver complete all as directed by Engr-in-Charge Make: CG/Havells/Phillips /Bajaj |
| 78 | Supply and fix testing and commissioning of LED flood light fitting 50 W new generation energy saving and enviromental friendly, long life, versatile pressure die cast aluminium IP 66 PDC flood light aesthetically designed with better thermal management with electronic driver complete all as directed by Engr-in-ChargeMake: CG/Havells/Phillips /Bajaj |
| 79 | Supply and fix LED post top lantern suitable for 1 X 25 Watt LED post top Made in cast aluminium spigot housing with decorative opal polycarbonate diffuser and IP66 protection includingall accessories and taking down old unserviceable one.MakeHavells/ Philips/ CG |
| 80 | S&F in repairs integral decorative LED bollard 8 watt with lamp and all accessories including taking down old unserviceable one MakeHavells /Bajaj/Philips / CG. |
| 81 | Supply and fixing factory made IP-65 (Dust and power jet Proof according to IEC 60529) opaque street light junction box of size 260 mm x 210 mmx116mm made of high quality polycarbonate (shock proof, rust free, corrosion free acid and chemical resistant, fire retardant having high impact(IK 08) totally insulatedmade of halogen and silica free recyclable material, UV resistant having high grade gasket made of polyurethane with copper terminal , MCB SP 6 Amps rating 10 KA with locking arrangement and 2 Nos M40 size cable glandand one M32 size gland suitable up to 35 Sqmm cable etc complete all as specified and directed. Make: HENSEL Cat No K-8350 or equivalent in Sintex. |
| 82 | M&L for PVC Cable of Three core2.5 Sq.mm sizePVC insulated , un sheathed , multi stranded aluminum conductor cables in 20 mm PVC conduit including clampand connecting up to streetlight fitting. Make- Havells/ Polycab/ KEI |