Maintenance, Repair And Replacement Of Defective Items Lt Distribution System In Viman Nagar, 509 And 1020 Area At Airforce Station Pune- 1 Dismantling Cross-Arms Of M.S. Channel Or Angle Sections, Clamps, Nut Bolts Etc. Complete All As Specified , GE (AF) LOHEGAON, PUNE-Maharashtra

Military Engineer Services-MES has published Maintenance, Repair And Replacement Of Defective Items Lt Distribution System In Viman Nagar, 509 And 1020 Area At Airforce Station Pune- 1 Dismantling Cross-Arms Of M.S. Channel Or Angle Sections, Clamps, Nut Bolts Etc. Complete All As Specified . Submission Date for this Tender is 20-09-2021. Overhead Line Tenders in GE (AF) LOHEGAON, PUNE Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

28997247
Corrigendum : Maintenance, Repair And Replacement Of Defective Items Lt Distribution System In Viman Nagar, 509 And 1020 Area At Airforce Station Pune- 1 Dismantling Cross-Arms Of M.S. Channel Or Angle Sections, Clamps, Nut Bolts Etc. Complete All As Specified
Open Tender
Indian
Maharashtra
GE (AF) LOHEGAON, PUNE
20-09-2021

Tender Details

Maintenance, Repair And Replacement Of Defective Items Lt Distribution System In Viman Nagar, 509 And 1020 Area At Airforce Station Pune- 1 Dismantling Cross-Arms Of M.S. Channel Or Angle Sections, Clamps, Nut Bolts Etc. Complete All As Specified And Directed. 2 Dismantling / Taking Out Insulator Of Any Size / Type From Existing Electric Lt Lines Complete All As Specified And Directed. 3 Dismantling Of Existing Stay Assembly Any Type / Size From Its Stay Rod, Cutting Stay Rods ( Above Ground Portion ) Dismantling Ms Clamps, Nuts, Bolts, Stay Bow, Loop Insulators, Stay Wire Etc Complete All As Specified And Directed. 4 Dismantling / Taking Out Existing Acsr Conductor Any Size From Existing Over Head Lines Incl Disconnection Complete All As Specified And Directed. 5 Disconnecting Of Incoming / Outgoing Cables And Earthing Lead And Taking Out Existing Unserviceable Outdoor Feeder Pillar Box / Paneland Removing Unserviceable Pillar Box / Panel With Frame From The Pcc Foundation Complete All As Specified And Directed. 6 Taking Down Old Unserviceablelt Ug Cable Of Service Connection Or Distribution Systemof Any Size And Removing From Site Complete All As Specified And Directed. ( Excavation And Earth Work Will Be Measured Seperately ) 7 M&L For Scrapping Of Old Alum Paint Of Steel Tubular Pole 9 / 11 Mtr By Means Of Emery Paper For Preparation Of Smooth Surfaces Andpainting With Two Coats Of Alum Paint On Pole , Brackets Old Junction Boxes Channels Etc Inclalternate 30 Cm Wide White Andblue Strip Painting Up To 1.5 Mtr Height From Ground Levelinclfixing Of Red Brightlaminatedreverse Lights Reflection Strip 100 Mm Wide03round Complete All As Specified And Directed. 8 Material & Labour Forpainting To Feeder Pillar Box / Lt Panel & Duct Coveretc, Including Angle Iron Frame With Two Coat Of Grey Synthetic Enamel Paint Includingwelding Of Door With Proper Size New Hinges Of Suitable Size And Locking Arrangementswhere Required Complete All As Specified And Directed. 9 Supply & Fix Line Separator Suitable For Lt Oh Line Of 3 Phase And Neutral Conductor Complete All As Specified And Directed. 10 Ditto All As Per Ser Item No.9.00 Above But Single Phase And Neutral Conductor Complete All As Specified And Directed. 11 Felling / Trimming Of Trees Not Exc 30 Cm Girth Including Cutting Of Upper Portion Of Branches And Disposal Ofsame At A Distance Not Exc 50 Mtr And Clearing Of Site Complete All As Specified And Directed. ( Note:Tools / Ladder Required For Cutting / Trimming Of Trees Will Be Provided By The Contractor At No Extra Cost And Cost Of The Same Be Deemed To Be Included In The Quoted Rate. ) Note:Each Span Will Be Measured From One Pole To Another Pole 12 Removing Lt Over Head Conductor From Insulator Where Ever Required And Restretching The Same Without Any Kink / Bend Upto Premissible Sag, Binding It On Insulator By Means Of Binding Wire Including Fixing Line Seprator At 3 Places Where Required And Directed And Testing Lt Over Head Line On Completion And Complete All As Specified And Directed. ( Note:- 1.Three Runs Of Lt Over Head Conductor For Phase, One Run Of Lt Over Head Conductor For Neutral Shall Be Measured & Paid As One Length. 2.Line Seprator Shall Be Measured And Paid Seperately. ) 13 Provision Ofservices For Cable Fault Locationfor Lt Ug Cable, Xlpe Insulated 1100 Volts, Of Any Size With Fault Detector Machine Complete All As Specified And As Directed. 14 Material And Labour For Straight Through Jointing Kits Heat Shrinkable Type Lt Ug Xlpe Cable Heavy Duty Armoured Sheathed Including Excavation In Any Strata, Taking Out Cable, And Making Disturbed Surface After Relaying The Cable Making Joints Suitable For Aluminium Conductor Of Size Given Below Complete All As Specified And Directed. 15 25 To 50 Sqmm 3.5 Core 16 70 To 120 Sqmm 3.5 Core 17 150 To 185 Sqmm 3.5 Core 18 240 To 300 Sqmm 3.5 Core 19 Supply And Fix Gi Pipe Light Gradewith All Connected Accessoriesof Sizes100 Mm Complete All As Specified And Directed. 20 Supply And Fix Gi Pipe Light Gradewith All Connected Accessoriesof Sizes80 Mm Complete All As Specified And Directed. 21 Supplying And Erecting ( In True Vertical Position ) Steel Tubular Swaged Poles Complete With Cast Iron Base Plate Final Taper Plug, Bolts Nuts And Screws All As Specified Of Type 410-Sp-31 ( 9.0 Mtr Length ) Complete All As Specifed In Is 2713 ( Part-Ii ) 1980 Including One Coat Or Red Oxide Primer And Two Coats Of Aluminium Paint To Exposed Surfaces And With Blach Bituminous Paint For Embedded Portion Of Pole Complete All As Specified And Directed. 22 Material And Labour For Cross Arms, Bracing Supports, Clamps And Back Plates Fabricated From Structural Steel Sections, Including Nut Bolts, Washer Welding Bending Cold / Hot, Drilling Holes For Bolts In Any Shape Or Size As Indicated Or Directed And Inclusive Of One Premer Coat Of Red Oxide Primer, One Under Coat And One Finishing Coat Of Aluminium Paint Complete All As Specified And Directed. 23 Material And Labour For Replacement Of Old Broken Acsr With Aluminium Conductor Steel Reinforced Streching Without Kinks / Bends And Binding With Insulators On Street Poles Complete All As Specified And Directed. 24 M&L For Stay Assembly Complete With Accessories As Shown In Electrical Plate No.1 Of Ssr Part-I 1991 Using Stay Rod Of 20Mm Dia Stay Plate 6Mm Thick Complete All As Specified And Directed.Note :-Loop Type Insulator, Stay Clamps Excavation And Earthwork And Pcc Shall Be Measured And Paid Separately Respective Item Of This Schedule. 25 S&F Shackle Type Insulator Vitreous Procelain White / Brown / Greenwith And Including Galvanised Mild Steel Straps, Washer Insulator, Bolts And Nuts, Insulator Of Size 100Mm Height And 115 Mm Max Dia With Working Pressure 1100 Volt And Galvanised Steel Straps 3 To 5 Mm Size And Suitable Size Nut And Bolts Complete All As Specified And Directed. 26 M&L For Providing Pin Type Procelain White / Brown / Green / Insulator Including Galvanised Mild Steel Spindle, Two Galvanised Iron.Washer And One Galvanised Iron Nut, 100Mm Height 65 Mm Dia For 1100 Volts Grade Complete All As Specified And Directed. 27 M& L For Danger Notice Plate 1.6 Mm Thick Mild Steel Sheet Vitreous Enamelled White With Letter Figures And Conventional Skull And Tongue In Signal Red Colour And Fixed With Ms Clamps Bolts Nuts Of Approved Size Lt, 20X15cm Complete All As Specified And Directed. 28 M&L For Cement Concrete ( 1:4:8 ) Type D2 In Foundation Filling And Mass Concrete Using 40Mm Graded Stone Aggregate For Pole / Stay Foundation Or As Required On Siteetc Complete All As Specified And Directed. 29 M&L For Cement Concrete ( 1:3:6 ) Type C2 In Foundation Filling And Mass Concrete Using 40Mm Graded Stone Agg For Pole / Stay Foundation Or As Required On Siteetc Complete All As Specified And Directed. 30 M&L For Cement Concrete ( 1:2:4 ) Type B1 In Foundation Filling And Mass Concrete And Coping Of Poles Incl Necessary Form Work Using 20 Mm Graded Stone Aggregate Etcor As Required On Siteetc Complete All As Specified And Directed. 31 Supplying, Spreading & Leveling Stone Aggregate Size Of 40 Mm Grade To The Existing Sub Station Complete All As Specified And Directed. 32 Supplying , Laying, Jointing, Testing And Commissioning Of Lt Under Ground Cable 1100 Volts Grade Xlpe ( Cross Linked Polythene ) Armoured With Galvanised Round Steel Wire Or Steel Strip , Electric Power Cable Heavy Duty, With Multi Stranded Aluminium Conductor, Laid In Trenches, Ducts Fix On Walls / Poles With Proper Size Saddles And Clamp Laid Under Roads / Path / Drain / Colverts Or Enclosed In Gi Pipe / Fix Complete All As Specified And Directedfor Following Size:- 33 16 Sqmm 4 Core 34 25 Sqmm 3.5 Core 35 35 Sqmm 3.5 Core 36 50 Sqmm 3.5 Core 37 70 Sqmm 3.5 Core 38 95 Sqmm 3.5 Core 39 120 Sqmm 3.5 Core 40 150 Sqmm 3.5 Core 41 185 Sqmm 3.5 Core 42 240 Sqmm 3.5 Core 43 300 Sqmm 3.5 Core 44 Excavation In Trenches Not Exc 1.5 M Wide Andnot Exc 1.5 M In Depth And Getting It Out For Laying Of Cable / Pole Etc. Complete All As Specified And Directed. 45 Soft / Loose Soil 46 Hard / Dense Soil 47 Soft / Disintegrated Rock 48 Returning / Refilling Of Excavated Soil Including Spreading Levelling And Well Ramming In Layers For Any Type Of Soil Complete All As Specified And Directed. 49 Removing The Surplus Spoil To A Distance Not Exceeding 50 Mtrs From The Starting Point And Depositing At A Height Not Exceeding 1.5 M Above Ground Level Complete All As Specified And Directed. 50 Material And Labour For Stone Dust Sand Cushioning To Under Ground Cable, Provided With A Layer 8 Cm Before And 15 Cm After Laying And Stretching Jointing And Testing The Cable Complete All As Specified And Directed. [ Note : Measuremenet Will Be Done After Punning ] 51 M&L For Brick Protection Covers Laid Over Cables Of Sub ClassB Bricks Old Size ( 230X115x75 ) Mm Complete All As Specified And Directed. 52 Supply And Fix In Repair / Replacement Of Mccb Fp 630 Amps Adjustable Type With Breaking Capacity50 Kaincluding Connections And Testing For Proper Functioningincl Taking Out Unserviceablecomplete All As Specified And Directed. 53 Supply And Fix In Repair / Replacement Of Mccb Fp 400 Amps Adjustable Type With Breaking Capacity36 Kaincluding Connections And Testing For Proper Functioning Incl Taking Out Unserviceablecomplete All As Specified And Directed. 54 Supply And Fix In Repair / Replacement Of Mccb Fp 250 Ampsadjustable Type With Breaking Capacity36 Kaincluding Connections And Testing For Proper Functioning Incl Taking Out Unserviceable Complete All As Specified And Directed. 55 Supply And Fix In Repair / Replacement Of Mccb Fp 200 Ampsadjustable Type With Breaking Capacity36 Kaincluding Connections And Testing For Proper Functioning Incl Taking Out Unserviceablecomplete All As Specified And Directed. 56 Supply And Fix In Repair / Replacement Of Mccb Fp 160 Ampsadjustable Type With Breaking Capacity36 Ka Including Connections And Testing For Proper Functioning Incl Taking Out Unserviceable Complete All As Specified And Directed. 57 Supply And Fix In Repair / Replacement Of Mccb Tp 200 Amps Adjustable Type With Breaking Capacity36 Kaincluding Connections And Testing For Proper Functioning Incl Taking Out Unserviceable Complete All As Specified And Directed. 58 Supply And Fix In Repair / Replacement Of Mccb Tp 160 Amps Adjustable Type With Breaking Capacity36 Kaincluding Connections And Testing For Proper Functioningincl Taking Out Unserviceablecomplete All As Specified And Directed. 59 Supply And Fix In Repair / Replacement Of Mccb Tp 100 Amps Fixed Type With Breaking Capacity 16 Kaincluding Connections And Testing For Proper Functioning Incl Taking Out Unserviceablecomplete All As Specified And Directed. 60 Supply And Fix In Repair / Replacement Of Mccb Tp 63 Ampsfixed Type With Breaking Capacity16 Kaincluding Connections And Testing For Proper Functioningincl Taking Out Unserviceablecomplete All As Specified And Directed. 61 Supply And Fix In Repair / Replacement Of Digital Volt Meter ( 0-500 ) Including Connections And Testing For Proper Functioningincl Taking Out Unserviceablecomplete All As Specified And Directed. 62 Supply And Fix In Repair / Replacement Of Digital Ammeterincluding Connections And Testing For Proper Functioning Incl Taking Out Unserviceablecomplete All As Specified And Directed. 63 Supply And Fix In Repair / Replacement Of Indicating Lamp R. Y. B ( Led ) Type Including Connections And Testing For Proper Functioning Incl Taking Out Unserviceable Complete All As Specified And Directed. 64 Supply And Fix In Repair / Replacement Ofselector Switch For Voltmeter And Ammeter Including Connections And Testing For Proper Functioning Incl Taking Out Unserviceable Complete All As Specified And Directed. 65 Supply And Fix In Repair / Replacement Of Cts Of Ratio 100 / 5 Including Connections And Testing For Proper Functioning Incl Taking Out Unserviceablecomplete All As Specified And Directed. 66 Supply, Install, Test And Commissioning Of Lt Feeder Pillar Box Outdoor Type Fabricated Out Of 3.0 Mm Thick Crca Sheet Double Door ( Front & Back Opening ) , Cpriapproved Complete With Powder Coating With Seven Tank Process Mounted On M.Sangle Iron Frame Of Size 40X40x6mm, Duly Grouted With Pcc Reqd With The Following:- ( A ) Aluminium Bus Bar 400 Amp ( R Y B & N ) With Colouredheat Shrinkable Insulated Sleeve 415 Volts As Per Is Of Suitable Size Mounted On Dmc / Epoxy Insulator ( Not Less Than 50Mmx50mm Conicle Type At A Maximum Interval Of 500 Mm- 01 Set. ( B ) Mccb Fp 250 Amps35 Ka- 01 No For Main In Coming ( C ) Mccb160 Tp Amps 35 Ka- 01 Nos ( D ) Mccb 63 Amps 3P, 10 Ka- 08 Nos ( E ) Led Indicator For Ryb Of Size 22.5 Mm- Set Of 3 ( F ) 3 Phase Digital Voltmeter -01 Nos ( G ) 3 Phase Digital Ammeter-01 Nosnote: All Mccbs Must Conforms Fixed Thermal And Fixed Thermal Magnetic Setting And Ics= 100% Of Icu 67 Supply, Install, Test And Commissioning Of Lt Feeder Pillar Boxof Size 1200X1200x400 Mm Outdoor Type Fabricated Out Of 3.0 Mm Thick Crca Sheet Double Door ( Front & Back Opening ) , Cpriapproved Complete With Powder Coating With Seven Tank Process Mounted On M.Sangle Iron Frame Of Size 40X40x6mm, Duly Grouted With Pcc Reqd With The Following:- ( A ) Aluminium Bus Bar 400 Amp ( R Y B & N ) With Colouredheat Shrinkable Insulated Sleeve 415 Volts As Per Is Of Suitable Size Mounted On Dmc / Epoxy Insulator ( Not Less Than 50Mmx50mm Conicle Type At A Maximum Interval Of 500 Mm- 01 Set. ( A ) Mccb Fp 160 Amps35 Ka- 01 Nos For Main Incoming ( B ) Mccb 3P 100 Amps 25 Ka - 01 Nos ( Outgoings ) ( C ) Mmcb Tp 63 Amps 10 Ka- 08 Nos ( C ) Led Indicator For Ryb Of Size 22.5 Mm- Set Of 3 ( D ) 3 Phase Digital Voltmeter -01 Nos ( E ) 3 Phase Digital Ammeter-01 Nosnote: All Mccbs Must Conforms Fixed Thermal And Fixed Thermal Magnetic Setting And Ics= 100% Of Icujunction Panel 68 Supply, Install, Test And Commissioning Of Lt Bus Bar Panel Of Size 600X600x300 Mm Outdoor Type Fabricated Out Of 3.0 Mm Thick Crca Sheet Double Door ( Front & Back Opening ) , Cpriapproved Complete With Powder Coating With Seven Tank Process Mounted On M.Sangle Iron Frame Of Size 40X40x6mm, Duly Grouted With Pcc Reqd With The Following:- ( A ) Incomming - Aluminium Bus Bar 400 Amp ( Ryb& N ) With Colouredheat Shrinkable Insulated Sleeve 415 Volts As Per Is Of Suitable Size Mounted On Dmc / Epoxy Insulator ( Not Less Than 50Mmx50mm Conicle Type At A Maximum Interval Of 500 Mm- 01 Set. Out Going ( B ) Mccb Tp100 Amps 35 Ka -01 ( C ) Mccbtp63 Amps 10 Ka - 01 Nos 69 S & F Vtpndb 4 Waysheet Metal Enclosure Double Door Suitable For Mccb Incommer Andmcbs Outgoing Including Mccb 4P 100 Amps 10 Kacomplete All As Specified And Directed 70 Supply And Fixing Sp 5 To 32 Amps Rating 240V, 10Ka C Curve Miniature Circuit Breaker ( Mcb ) Of Following Poles And Current Carrying Capacity In The Mcb Db Complete With Connection Testing Andcommissioning Complete All As Specified And Directed. 71 Ditto All As Per Ser Item No 52.00 Above Butspn 32 Amps Complete All As Specified And Directed. 72 Ditto All As Per Ser Item No 52.00 Above Buttp 25 To 63Amps 415 Volts Complete All As Specified And Directed. 73 S & F Sub Main Wiringwith Pvc Insulatedmultistranded Copper Conductorwires Ofsize2x6.0 Sq. Mm + 1X4.0 Sq. Mm Earth Wireincluding Pvc Cassing And Capping Complete All As Specified And Directed 74 Earthing Complete With Galvanised Iron Earth Plate Electrode 600 Mm X 600 Mm X 6Mm As Earthing Lead Buried Directly In Ground Vertically To A Depth Not Less Than 2.25 Mtr Deep Below Ground Level With Top Edge Of The Plate Not Less Than 1.5 Mtr Below Normal Ground Level Connected To And Including Galvanised Iron Strip 25 X 4 Mm As Earthing Lead By Means Of Bolts, Nuts, Check Nuts & Washers Etc Made Of Gi And Connected To Earthing Test Point All As Shown In Electrical Plateno. 5 Of Ssr Part I Of 2009 & As Specified Or Indicated And Testing On Completion Including Excavation / Earth Work In Any Type Of Strata Pcc ( 1:3:6 ) Type C1 Earthing Chamber, Pre Cast Slab Cover 50 Mm Thick In Cement Concrete ( 1: 2 : 4 ) Type B 1 ( Reinforced With Welded Steel Wire Fabric ( Xpm ) Weight Not Less Than 4 Kg / Sqm ) , Funnel With Wire Mesh, Watering Pipe Of 20 Mm Bore Medium Grade, Including Galvanised Iron Strip 25X4 Mm With Gi Protection Pipe Of 40 Mm Medium Grade Up To 7.5 Meter Length, Etc Complete All As Specified And Directed. 75 S & F Gi Earth Continuity Conductor Or Main Earthing Lead Of Size 25X4 Mm Fixed To Wall On Batten Or Recess Or Chases Or Buried In Ground Or Drawn In Conduit / Pipe Or Fixed To Poles Or Any Other Indicated Situation For Earthing Etc. As Required Complete All As Specified And Directed. 76 Material And Labour For Surface Excavation N.Exc ( Not Exceeding ) 30 Cm Deep And Averaging 15Cm Deep And Getting Out Removing Of Grass And Vegetation Grown Around The Electrical Installations Like Transformers, Lt Panels, 2 Pole Structure, Ht Panels And Complete Area Inside The Fencing Complete All As Specified And Directed.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 07-Sep-2021 BOQCORRIGENDUM BOQ 13-09-2021
2 13-Sep-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 20-09-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 70000.0 /-
Tender Value
INR 35 Lakhs /-

BOQ Items

Name of Work: MAINTENANCE, REPAIR AND REPLACEMENT OF DEFECTIVE ITEMS LT DISTRIBUTION SYSTEM IN VIMAN NAGAR, 509 AND 1020 AREA ATAIRFORCE STATION PUNE
Sl. No. Item Description
1Dismantling cross-arms of M.S. channel or angle sections, clamps, nut bolts etc. complete all as specified and directed.
2Dismantling / taking out insulator of any size / type from existing electric LT lines complete all as specified and directed.
3Dismantling of existing stay assembly any type / size from its stay rod, cutting stay rods (above ground portion) dismantling MS clamps, nuts, bolts, stay bow, loop insulators, stay wire etc complete all as specified and directed.
4Dismantling / taking out existing ACSR conductor any size from existing over head lines incl disconnection complete all as specified and directed.
5Disconnecting of incoming / outgoing cables and earthing lead and taking out existing unserviceable outdoor feeder pillar box / Paneland removing unserviceable pillar box / Panel with frame from the PCC foundation complete all as specified and directed.
6Taking down Old unserviceableLT UG cable of service connection or distribution systemof any size and removing from site complete all as specified and directed. ( Excavation and earth work will be measured seperately)
7M&L for scrapping of old alum paint of steel tubular pole 9/11 mtr by means of emery paper for preparation of smooth surfaces andpainting with two coats of alum paint on pole , brackets old junction boxes channels etc inclalternate 30 cm wide white andblue strip painting up to 1.5 Mtr height from ground levelinclfixing of red brightlaminatedreverse lights reflection strip 100 mm wide03round complete all as specified and directed.
8Material & Labour forpainting to feeder pillar box / LT panel & duct coveretc, including angle iron frame with two coat of grey synthetic enamel paint includingwelding of door with proper size new hinges of suitable size and locking arrangementswhere required complete all as specified and directed.
9Supply & fix line separator suitable for LT OH line of 3 phase and neutral conductor complete all as specified and directed.
10Ditto all as per Ser Item No.9.00 above but single phase and neutral conductor complete all as specified and directed.
11Felling/trimming of trees not exc 30 cm girth including cutting of upper portion of branches and disposal ofsame at a distance not exc 50 mtr and clearing of site complete all as specified and directed. (Note:Tools/ladder required for cutting/trimming of trees will be provided by the contractor at no extra cost and cost of the same be deemed to be included in the quoted rate.) Note:Each Span will be measured from one pole to another pole
12Removing LT over head conductor from insulator where ever required and restretching the same without any kink / bend upto premissible sag, binding it on insulator by means of binding wire including fixing line seprator at 3 places where required and directed and testing LT over head line on completion and complete all as specified and directed. (Note:- 1.Three runs of LT over head conductor for phase, one run of LT over head conductor for neutral shall be measured & paid as one length. 2.Line seprator shall be measured and paid seperately.)
13Provision ofservices for cable fault locationfor LT UG cable, XLPE insulated 1100 Volts, of any size with fault detector machine complete all as specified and as directed.
14Material and labour for straight through jointing kits heat shrinkable type LT UG XLPE cable heavy duty armoured sheathed including excavation in any strata, taking out cable, and making disturbed surface after relaying the cable making joints suitable for aluminium conductor of size given below complete all as specified and directed.
1525 to 50 sqmm 3.5 core
1670 to 120 sqmm 3.5 core
17150 to 185 sqmm 3.5 core
18240 to 300 sqmm 3.5 core
19Supply and fix GI Pipe Light gradewith all connected accessoriesof sizes100 mm complete all as specified and directed.
20Supply and fix GI Pipe Light gradewith all connected accessoriesof sizes80 mm complete all as specified and directed.
21Supplying and erecting ( in true vertical position) steel tubular swaged poles complete with cast iron base plate final taper plug, bolts nuts and screws all as specified of type 410-SP-31 (9.0 mtr length) complete all as specifed in IS 2713 (part-II) 1980 including one coat or red oxide primer and two coats of aluminium paint to exposed surfaces and with blach bituminous paint for embedded portion of pole complete all as specified and directed.
22Material and labour for cross arms, bracing supports, clamps and back plates fabricated from structural steel sections, including nut bolts, washer welding bending cold/ hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one premer coat of red oxide primer, one under coat and one finishing coat of aluminium paint complete all as specified and directed.
23Material and labour for replacement of old broken ACSR with aluminium conductor steel reinforced streching without kinks / bends and binding with insulators on street poles complete all as specified and directed.
24M&L for stay assembly complete with accessories as shown in electrical plate No.1 of SSR part-I 1991 using stay rod of 20mm dia stay plate 6mm thick complete all as specified and directed. Note :-Loop type insulator, stay clamps excavation and earthwork and PCC shall be measured and paid separately respective item of this schedule.
25S&F shackle type insulator vitreous procelain white / brown / greenwith and including galvanised mild steel straps, washer insulator, bolts and nuts, insulator of size 100mm height and 115 mm max dia with working pressure 1100 volt and galvanised steel straps 3 to 5 mm size and suitable size nut and bolts complete all as specified and directed.
26M&L for providing pin type procelain white / brown / green / insulator including galvanised mild steel spindle, two galvanised iron.Washer and one galvanised iron nut, 100mm height 65 mm dia for 1100 volts grade complete all as specified and directed.
27M& L for danger notice plate 1.6 mm thick mild steel sheet vitreous enamelled white with letter figures and conventional skull and tongue in signal red colour and fixed with MS clamps bolts nuts of approved size LT, 20x15cm complete all as specified and directed.
28M&L for cement concrete (1:4:8) type D2 in foundation filling and mass concrete using 40mm graded stone aggregate for pole/stay foundation or as required on siteetc complete all as specified and directed.
29M&L for cement concrete (1:3:6) type C2 in foundation filling and mass concrete using 40mm graded stone agg for pole/stay foundation or as required on siteetc complete all as specified and directed.
30M&L for cement concrete (1:2:4) type B1 in foundation filling and mass concrete and coping of poles incl necessary form work using 20 mm graded stone aggregate etcor as required on siteetc complete all as specified and directed.
31Supplying, spreading & leveling stone aggregate size of 40 mm grade to the existing sub station complete all as specified and directed.
32Supplying ,Laying, jointing, testing and commissioning of LT under ground cable 1100 volts grade XLPE(cross linked polythene ) armoured with galvanised round steel wire or steel strip , electric power cable heavy duty, with multi stranded aluminium conductor, laid in trenches, ducts fix on walls/poles with proper size saddles and clamp laid under roads/path/ drain /colverts or enclosed in GI pipe/ fix complete all as specified and directedfor following size:-
3316 sqmm 4 core
3425 sqmm 3.5 core
3535 sqmm 3.5 core
3650 sqmm 3.5 core
3770 sqmm 3.5 core
3895 sqmm 3.5 core
39120 sqmm 3.5 core
40150 sqmm 3.5 core
41185 sqmm 3.5 core
42240 sqmm 3.5 core
43300 sqmm 3.5 core
44Excavation in trenches not exc 1.5 m wide andnot exc 1.5 m in depth and getting it out for laying of cable / pole etc. complete all as specified and directed.
45Soft/loose soil
46Hard/dense soil
47Soft/disintegrated rock
48Returning/ Refilling of excavated soil including spreading levelling and well ramming in layers for any type of soil complete all as specified and directed.
49Removing the surplus spoil to a distance not exceeding 50 mtrs from the starting point and depositing at a height not exceeding 1.5 m above ground level complete all as specified and directed.
50Material and labour for stone dust sand cushioning to under ground cable, provided with a layer 8 cm before and 15 cm after laying and stretching jointing and testing the cable complete all as specified and directed. [Note : Measuremenet will be done after punning]
51M&L for brick protection covers laid over cables of sub class"B" bricks old size (230X115X75) mm complete all as specified and directed.
52Supply and fix in repair / replacement of MCCB FP 630 Amps Adjustable type with breaking capacity50 KAincluding connections and testing for proper functioningincl taking out unserviceablecomplete all as specified and directed.
53Supply and fix in repair / replacement of MCCB FP 400 Amps Adjustable type with breaking capacity36 KAincluding connections and testing for proper functioning incl taking out unserviceablecomplete all as specified and directed.
54Supply and fix in repair / replacement of MCCB FP 250 AmpsAdjustable type with breaking capacity36 KAincluding connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
55Supply and fix in repair / replacement of MCCB FP 200 AmpsAdjustable type with breaking capacity36 KAincluding connections and testing for proper functioning incl taking out unserviceablecomplete all as specified and directed.
56Supply and fix in repair / replacement of MCCB FP 160 AmpsAdjustable type with breaking capacity36 KA including connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
57Supply and fix in repair / replacement of MCCB TP 200 Amps Adjustable type with breaking capacity36 KAincluding connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
58Supply and fix in repair / replacement of MCCB TP 160 Amps Adjustable type with breaking capacity36 KAincluding connections and testing for proper functioningincl taking out unserviceablecomplete all as specified and directed.
59Supply and fix in repair / replacement of MCCB TP 100 Amps Fixed type with breaking capacity 16 KAincluding connections and testing for proper functioning incl taking out unserviceablecomplete all as specified and directed.
60Supply and fix in repair / replacement of MCCB TP 63 AmpsFixed type with breaking capacity16 KAincluding connections and testing for proper functioningincl taking out unserviceablecomplete all as specified and directed.
61Supply and fix in repair / replacement of digital Volt meter (0-500) including connections and testing for proper functioningincl taking out unserviceablecomplete all as specified and directed.
62Supply and fix in repair / replacement of digital ammeterincluding connections and testing for proper functioning incl taking out unserviceablecomplete all as specified and directed.
63Supply and fix in repair / replacement of Indicating Lamp R. Y. B (LED) Type including connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
64Supply and fix in repair / replacement ofselector switch for voltmeter and ammeter including connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed.
65Supply and fix in repair / replacement of CTs of ratio 100/5 including connections and testing for proper functioning incl taking out unserviceablecomplete all as specified and directed.
66Supply, Install, Test and Commissioning of LT feeder pillar box outdoor type fabricated out of 3.0 mm thick CRCA sheet double door(front & back opening),CPRIapproved complete with powder coating with seven tank process mounted on M.Sangle Iron frame of size 40x40x6mm, duly grouted with PCC reqd with the following:- (a) Aluminium bus bar 400 Amp (R Y B & N) with colouredheat shrinkable insulated sleeve 415 Volts as per IS of suitable size mounted on DMC/epoxy insulator (not less than 50mmx50mm conicle type at a maximum interval of 500 mm- 01 Set. (b) MCCB FP 250 Amps35 KA- 01 No for main in coming(c) MCCB160 TP Amps 35 Ka- 01 Nos (d) MCCB 63 Amps 3P, 10 KA- 08 Nos (e) LED indicator for RYB of size 22.5 mm- Set of 3 (f) 3 Phase Digital voltmeter -01 nos (g) 3 Phase Digital ammeter-01 Nos Note: All MCCBs must conforms Fixed thermal and fixed thermal magnetic setting and Ics= 100% of Icu
67Supply, Install, Test and Commissioning of LT feeder pillar boxof size 1200x1200x400 mm outdoor type fabricated out of 3.0 mm thick CRCA sheet double door(front & back opening),CPRIapproved complete with powder coating with seven tank process mounted on M.Sangle Iron frame of size 40x40x6mm, duly grouted with PCC reqd with the following:- (a) Aluminium bus bar 400 Amp (R Y B & N) with colouredheat shrinkable insulated sleeve 415 Volts as per IS of suitable size mounted on DMC/epoxy insulator (not less than 50mmx50mm conicle type at a maximum interval of 500 mm- 01 Set. (a) MCCB FP 160 Amps35 KA- 01 Nos for Main incoming (b) MCCB 3P 100 Amps 25 KA - 01 Nos (outgoings) (c) MMCB TP 63 Amps 10 Ka- 08 Nos (c) LED indicator for RYB of size 22.5 mm- Set of 3 (d) 3 Phase Digital voltmeter -01 nos (e) 3 Phase Digital ammeter-01 Nos Note: All MCCBs must conforms Fixed thermal and fixed thermal magnetic setting and Ics= 100% of Icu JUNCTION PANEL
68Supply, Install, Test and Commissioning of LT bus bar panel of size 600x600x300 mm outdoor type fabricated out of 3.0 mm thick CRCA sheet double door(front & back opening),CPRIapproved complete with powder coating with seven tank process mounted on M.Sangle Iron frame of size 40x40x6mm, duly grouted with PCC reqd with the following:- (a) Incomming - Aluminium bus bar 400 Amp (RYB& N )with colouredheat shrinkable insulated sleeve 415 Volts as per IS of suitable size mounted on DMC/epoxy insulator (not less than 50mmx50mm conicle type at a maximum interval of 500 mm- 01 Set. Out Going(b)MCCB TP100 Amps 35 kA -01 (c) MCCBTP63 Amps 10 kA - 01 Nos
69S & F VTPNDB 4 Waysheet metal enclosure double door suitable for MCCB incommer andMCBs outgoing including MCCB 4P 100 Amps 10 KAcomplete all as specified and directed
70Supply and fixing SP 5 To 32 Amps rating 240V, 10KA "C" curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing andcommissioning complete all as specified and directed.
71Ditto all as per Ser Item No 52.00 above butSPN 32 Amps complete all as specified and directed.
72Ditto all as per Ser Item No 52.00 above butTP 25 to 63Amps 415 Volts complete all as specified and directed.
73S & F Sub Main Wiringwith PVC Insulatedmultistranded copper conductorwires ofsize2x6.0 sq. mm + 1x4.0 sq. mm earth wireincluding PVC cassing and capping complete all as specified and directed
74Earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6mm as earthing lead buried directly in ground vertically to a depth not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to and including galvanised iron strip 25 X 4 mm as earthing lead by means of bolts, nuts, check nuts & washers etc made of GI and connected to earthing test point all as shown in electrical plateNo. 5 of SSR Part I of 2009 & as specified or indicated and testing on completion including excavation/earth work in any type of strata PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab cover 50 mm thick in cement concrete ( 1: 2 : 4 ) type B 1 ( reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg / Sqm),funnel with wire mesh, watering pipe of 20 mm bore medium grade, including galvanised iron strip 25X4 mm with GI protection pipe of 40 mm medium grade up to 7.5 meter length, etc complete all as specified and directed.
75S & F GI earth continuity conductor or main earthing lead of size 25x4 mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for earthing etc. as required complete all as specified and directed.
76Material and labour for Surface excavation n.exc (not exceeding) 30 cm deep and averaging 15cm deep and getting out removing of grass and vegetation grown around the electrical installations like transformers, LT panels, 2 pole structure, HT panels and complete area inside the fencing complete all as specified and directed.