| 1 | Safe Loading carriage including unloading & proper stacking of following store materials from Electricity Store Centre, Gonda /JE store to site of work.(50.00 km Approx). |
| 2 | 33/0.4 KV 400 KVA T/F |
| 3 | 33 KV 3 Core Cable 3x185 mm. XLPE |
| 4 | M.S. Flat |
| 5 | 11 Mt. LongST Pole |
| 6 | M.S. Plate 50x50x6mm |
| 7 | 33 KV Polymer Pin Insulator |
| 8 | 33 KV Bus Isolator |
| 9 | 33 KV Post Insulator |
| 10 | 33 KV Lightening Arrestor |
| 11 | ACSR Dog Conductor |
| 12 | Disc Insulator B & S Type 70 KN |
| 13 | 33 KV Cable S/T Jointing kit 3x185 sq.mm XLPE |
| 14 | 33 KV Cable O/D Jointing kit 3x185 sq.mm XLPE |
| 15 | M.S. Channel 125 x 65 mm |
| 16 | M.S. Channel 100 x 50 mm |
| 17 | M.S. Angle 75x75x8 mm |
| 18 | R.S. Joist 150x150mm/Rail |
| 19 | Fabrication & erection of double pole structure for33 KVline on 11 Mtr. long ST pole with fixing of necessary clamps & other accessories like 1 No.top channel 125x65 mm its grounting, Painting of pole with one coat of red oxide & two coats of enamel paint ISI mark.(Contractor shall be provided 33 KV G.I. Pin, necessary clamp, F-bracket etc.) |
| 20 | Stringing and Sagging of 3 phase Bus Bar on ACSR Dog Conductor as per RESSPO Norms. |
| 21 | Laying of 33 KV 3 x 185 sq.mm. XLPE Cable in single circuit in normal soil by digging of trence 1050 mm deep, 750 mm wide including supply of required material as fine a sand, Ist class bricks (All the material will be supplied by the contractor except 33 KV XLPE cable) |
| 22 | Sealing by Heat Shrinkable Type cable Jointing kits O/D end Termination suitable for 33 KV 3 x 185 sq.mm. XLPE Cable confirming to IS ESI-09-13IS-13573 of 1992 amendment I & II VDE-0278 of latest version there of if any. (Jointing Kit supplied by Dept.) |
| 23 | Sealing by Heat Shrinkable Type cable Jointing kits S/T end Termination suitable for 33 KV 3 x 185 sq.mm. XLPE Cable confirming to IS ESI-09-13IS-13573 of 1992 amendment I & II VDE-0278 of latest version there of if any. (Jointing Kit supplied by Dept.) |
| 24 | Hosting of 33 KV Cable on existing/erected support with provision of MS Pipe 250 mm dia 3 mtr. Long suitable for 33 KV 3 x 185 sq.mm. XLPE Cable fixing of proper support and its clamping. Jumpering properly as per RESSPO Norms. (All material will be supplied by the contractor.) |
| 25 | High Pressure testing with D.C. Test Voltage to which cable shall able to be stand for duration of 5 minutes after completion of laying, Joints & termination upto 60 KV (Tesing equipment will be arranged by the contractor.) |
| 26 | LIGHTENING ARRESTORSTRUCTURE:- Fabrication of lightening arrestor as per drawing No. Res-39 Digging of two Nos. pits of size 1.075x0.3x0.3Mtr providing stone pad at the bottom of the pit and grouting of two legs of the above structures in CC (Cement, coarse sand and stone grit of 20mm gauge) of ratio 1:4:8 in block of 1.075Mtr X0.3Mtr including supply of all civil material complete in all respect. The work includes dragging, shifting up to 40Mtrs. raising and erecting the two legs with runner of isolator in proper alignment, level and plumb. Both plinths of the structures shall be properly finished with chambering of edges etc. |
| 27 | INSTALLATION OF LIGHTENING ARRESTORS:-Assembling and installation Mounting of 3Nos (1 set) lightening arrestors on the L.A. Structure complete with making earth connections (separate) and line connections the work includes fabrication for proper fixing if required. |
| 28 | BUS ISOLATOR STRUCTURE:- Fabrication of isolator structures 3.5 Mtr. In height as per drawing No. RES 39.Digging of two Nos. pits of size 1.075x0.9x0.3 Mtr. providing stone pad at the bottom of the pit and grouting pad at the bottom of the pit and grouting of two legs of the isolator structure in CC (cement coarse sand and stone grit of 20m.m gauge)of the ratio 1:4:8 in block of 1.075Mtrx0.3 mm including supply of all T&P complete in all respect. The work includes dragging, shifting upto 40 mtrs. Raising and erecting the two legs with runner in proper alignment, and level and plumb .Both plinths of the isolator structure shall be properly finished with smoothening of edges. |
| 29 | INSTALLATION OF BUS ISOLATOR:- Assembling and installation of Bus isolator on the isolator structure adjusting of opening mechanism in proper alignment so as to ensure smooth operation of the same in case of line isolator proper operation of earth links shall also be Insured. The work includes fabrication for proper fixing if required. |
| 30 | POST INSULATOR STRUCTURE:- Fabrication of isolator structures 3.5 Mtr. In height as per drawing No. RES 39.Digging of two Nos. pits of size 1.075x0.9x0.3 Mtr. providing stone pad at the bottom of the pit and grouting pad at the bottom of the pit and grouting of two legs of the isolator structure in CC (cement coarse sand and stone grit of 20m.m gauge)of the ratio 1:4:8 in block of 1.075Mtrx0.3 mm including supply of all T&P complete in all respect. The work includes dragging, shifting upto 40 mtrs. Raising and erecting the two legs with runner in proper alignment, and level and plumb .Both plinths of the isolator structure shall be properly finished with smoothening of edges. |
| 31 | INSTALLATION OF 33 KV POST INSULATORS:-Installation of 6 Nos.(3 set) Post Insulators on the post insulators structure. The work includes fabrication for proper fixing if required |
| 32 | Boring type earthing 20 mm dia upto water level depth (All material will be supplied by the contractor.) |
| 33 | Make proper connection at all structure in switchyard(Connector for L.I./B.I./L.A.) (All material supplied by Contractor Except dog Conductor) |
| 34 | Erectiion all Toe wall boundary of switchyard (600 mm below ground level & 400 mm above ground level 9 inch width of wall). All material will be supplied by the contractor) |
| 35 | Erection of welded mesh fencing with gate as per RESSPO Norms. (All material will be supplied by the contractor.) |
| 36 | Construction of masonry plinth of size 1.5x1.5x1.5 mtr. suitable for 400 KVA capacity of T/F including fixing of rail/joist on plinth. All required materials provided by the contractor at his own cost. |
| 37 | Commissionlng of 400 KVA T/F (33/0.4KV) |
| 38 | Commissionlng of 400 KVA T/F (11/0.4KV) |
| 39 | Painting of Sub-Structure:- Painting of sub-structure with one coat of ready mixed primer and 2 coats of AL.Paint of good quality including cost of material, Labour and T&P complete in all respect. The work includes cost of all the material. |
| 40 | Dismentalling of Old Plinth. |
| 41 | Cartage of old 250 KVA T/F (33/0.4KV) site to store center Gonda. |