| 1 | SITC of MGPS of medically grade as per BSEN-13348 with third party certification from Lloyds/TUV degreased (ie free from oil, grease and partivulate matters) seamless copper pipe confirming to ASTM B88 and all copper joining done by brazing with AWSA5.8, classification BCuP-5 or BS 1845 following procedure in accordance with ASTM B828 after purging with nitrogen. All pipe cutting shall be carried out with a radial pipecutter and copper pipe fitting\"s shal comply with B4 alloy designation. Adequate support shall be provided while laying pipeline testing shall be done at 17 bar and after testing pipe shall be painted with two coat of enamel paint as per colour codification as per ISO 7396-Part-1 2016. |
| 2 | SITC of non lubricated ball type GM Isolation Valve with adapter & PTFE Seat havng quarter turn handle opening of following sizes suitable for flow capacity 1500 LPM at 4.7 bar with maximum allowable pressure of 30 bar and suitable for working temperature ranging - 20\"C to 130\"C. Valve should be CE approved / CE certified. |
| 3 | For 12 MM OD pipe |
| 4 | For 15 MM OD pipe |
| 5 | For 22 MM OD pipe |
| 6 | For 28 MM OD pipe |
| 7 | SITC of Gas outlet points (AR-4), (AR-7) and vacumm (8.7 psig) for dispensing medical gases (oxygen/air/vaccum) at point of use confirming to BSEN ISO 9170-1: 2008. The Gas outlet are quick connect for different gas source and should accept only respective adapters as required. |
| 8 | SITC of BPC (back pressure compensated) flow meter with humidifer made of nickel plated body double jacketed with flow gradations marked on it. Desired flow will be setteled through roatary knob. Flow range should be between 0 to 15 Ipm & work should be executed as per direction of engineer n charge. |
| 9 | SITC of suction unit (suction controller and collection jar) with posibility to configure required capacity capacity collection jar and should meets the requirements as per BSEN ISO 10079-3:2009 the unit must designed to operate with the vacucum regulator suitable for 0-14.7 psig with flow rate 0-55 Lmp (min) for operating temperature - 18\"C to 50\"C with ON/OFF facility. The collection jar should be transparent, made of high quality polycarbonate that can be autoclaved at 121\"C for 20 minutes for reuse and provided with auto stop to avoid over spill and contamination of the suction source when the jar collection reached optimized level, the complete unit supplied with filter to protect the source and pipe line from bacterial contamination. |
| 10 | 600 ml Capacity collection Jar |
| 11 | SITC of Valve box made of CRCA sheet duly powder coated with transparent window which is installed in the MGPS for sxygen and vaccum line and should comply with ENISO5211:2001 complete with ball type valves and gauses as required for oxygen compressed air and vaccum line (three gas) |
| 12 | For Three Gas |
| 13 | For Four Gas |
| 14 | SITC of microprocessor based auto alarm system (digital type) suitable for medical gas service provided with audible and visual alarm for MGPS Zoning it should monitors the current status of oxygen/ compressed air pressure in distrubuton pipeline of central medical supply system and trigger the alarm to alert. The system should comply BSEN ISO:7396-1:2007 |
| 15 | For Two Gas Services |
| 16 | For Three Gas Services |
| 17 | For Four Gas Services |
| 18 | SITC of Bed Head Panel of 1200-1500 MM long made out from high strength extruded aluminum with powder coating with 4 nos 6/16 Amp switch socket and provision for four Nos gas outlet point work should be executed as per directions of engineer in charge and of CE certified makes. |
| 19 | Providing and Fixing of Rail clamp for mounting ward vaccum unit on bed head panel complete as required. |
| 20 | SITC of automatic gas control panel for oxygen/nitrous oxide control panel cover made for M.S duly powder coated. Compact and fully automatic manifold control system for oxygen services easy to maintain and use Designed with both safety and continuity of flow supply at a constant pressure via two banks of bottled gas cylinders with following status monitoring A- Bank in use (Green Indication) B- Empty bank (Red Indication) Control Panel should have built in LED display to indicate Normal, High & Low line pressure. It should have facility to test all above indicators working perfectly. The control Panel should include pressure gauge to indicate the gas pressure of each header and pipe line distribution pressure. Capable to provide a distribution flow rate in excess of 1200 LPM. The control panel should incorporate manual bypass system in case of failure of shifting mechanism. It should be of CE certified product. |
| 21 | SITC of Oxygen/Nitrous Oxide Manifold System (8,8)with tal pipes NRV-manifold system comprise of bank of 8+8 cylinders (Bulk cylinder of D type) capacity manifold high pressure copper pipe of size 1/2\"ID x14 swg (approx 2.0320 mm) & high pressure fitting made of high tensile strength brass be used to connect the cylinders to the header assemblies with 16 no\"s non return valves & 16 no\"s high pressure flexible tail pipe is made of copper pipe of 1/3\"x16 swg (approx. 1.6256 mm) the manifold is hydraulically tested at 225 kg/cm2 pressure it is also degreased and is to be offered duly wrapped in a polythene bag make CE Approved/CE. Note: Providing of Cylinders is in the scope of Hospital / End Client. |
| 22 | SITC of Oxygen/Nitruous Oxide Manifold System (4+4) with tail pipes NRV- manifold system comprise of bank of 4+4 cylinders (Blk cylinder of D type) capacity manifold high pressure fitting made of high tensile strength brass be used to connect the cylinders to the header assemblies with 8 no\"s non return valves & 8 no\"s high pressure flexible tail pipe is made of copper pipe of 1/3\"x16 swg (approx. 1.6256mm ) the manifold is hydraulically tested at 225 kg/cm2 pressure it is also degreased and is to be offerred duly wrapped in a polythene bag make CE Approved/CE certified. Note: Providing of Cylinders is in the scope of Hospital/Eng Client. |
| 23 | SITC of Oxygen/Nitrous Oxide emergency system Emergency manifold system comprise of bank of 1+1 cylinders (Bulk cylinder of D type) capacity manifold high pressure copper pipe of size 1/2\"IDx14 swg (approx. 2.0320 mm) & high pressure fitting made of high tensile strength brass be used to connect the cylinders to the header assemblies with 2 no\"s non return valves & 2 no\"s high pressure flexible tail pipe is made of copper pipe of 1/3\"x16 swg (approx. 1.6256 mm) the manifold is hydrauically tested at 225 kg/cm2 pressure it is also degreased and is to be offered duly wrapped in a polythene bag. One High pressure imported and approved make double gauge regulator with manual pressure setting option and showing cylinder and line pressure make CE approved/CE certified. Note: Providing of cylinders is in the scope of Hospital / End Client. |
| 24 | SITC of Dessicant Air Dryer Output Capacity - 60 cfm with UL certified Microprocessor Controller with dewpoint based changeover option, Pre-filter rating 0.3 microns, shuttle valve for low pressure drop, All Aluminium resist oxidation & scale fromation dewpoint better than - 4º C including fixing on wall with required T&P making connections etc complete in all respect. |
| 25 | SITC of compressed air syste should consist on 1 nos. air compressors with electric motors electrical switch gear and automatic control system of following.Specification:A) Air Compressor 1 (One) Nos: Type Non-lubricated /Oil-free capacity 57 cfm at 8.5 kg/cm2 cooling air cooledB) Drive electric motor 2 (Two) Nos. Capacity 15 HP Speed 1440 rpm drive belt drive Electricity supply 440 volt, 50 hz 3 Phase. C) Starter Star/Delta Control & Switchgear with overload protection including making PCC foundation and fixing withbolts anti vibration pad and making connections complete as required. |
| 26 | SITC of Vacuum pump of single stage capacity 4235 lpm/149 cfm (piston displacement) The pump should be suited for maximum working pressure of 29 inch mercury (730 mm mercury) The pump should be fitted with MS channel frame complete having vibration isolators with 1 Nos. silencers at vacuum pump discharge end. The pump should be air cooled 1 sets of isolation valve on return valve and filter should be provided with pumps. Drive Assembly The electrical drive for vacuum pump should consist of suitable TEFC induction motor operating at 1440 RPM and connected through a V-belt. The motor should be suited for 415 V+10% 50 HZ.3 Phase AC supply capacity : 10 HP of a reputed make vacuum switch vacuum switch of 0-760 mm range should be provided it should have both NO/NC contracts and suitable for 230 V 50 Hz . AC supply. The vacuum switch should be housed in weather proof casing with 3/8\"BSP gas service connection at the bottom of the assembly. Vacuum Filter 1 Nos vacuum filters with drain valve. This filter should be non-ferrous and in line. including making PCC foundaton and fixing with bolts, anti vibration pad and making connections complete as required. |
| 27 | SITC of compressed air filtration system: one set of 3- stage filter the filters should be made of die cast aluminums housing with epoxy power paint on the outside and anodized surface treatment inside to prevent corrosion and ensure extra long life. The filters should have maximum contaminant removal efficiency with minimum pressure drop. Total 3-stage of filters should be used as mentioned below:- Stage1:- coalescing filters for general purpose protection removind liquid water and oil aerosol to 0.1 mg/cum (0.1 pm) and and particles down to 5 micro.Stage :- 2 particular filter for dust protection removing particles down to 1 micron. Stage:- 3 high efficiency coalescing filters, removing liquid water and oil aerosol to 0.01 mg / cum (0.01 pip) and particles down to 0.01 micron. |
| 28 | SITC of hot dipped galvanized ( inside and outside) Air receiver tank (as per IS: 7938-1976 and upto date amendment ) for compressed air system to dampen out pulsatin and condense and trap the moisture in the compressed air and also to let oil and other impurities settle down before air passes into the piping with safety valve Drain Valve Pressure gauge and fusible plugs of 1000 litres capacity complete as required including making PCC foundation and fixing with bolts and making connections complete as required. |
| 29 | P&F recessed/ surface mounting heavy duty Vertical type 16 SWG sheet steel Distribution board with provision of incomer suitable for MCCB and SP / TP MCB as outgoing ,phophatised ,powder painted complete with insulated suitable ratingcopper bus bar , neutral link, earth link and din bar, masking sheet & conforming to IS13032 & IS8623 including making internal DB terminations with copper lugs , testing etc. as required. |
| 30 | Double door with Provision of Incomer MCCB 100 / 125 A Rating |
| 31 | 6 Way |
| 32 | P&F 240/415 V AC MCB with positive isolation of breaking capacity not less than 10 KA (B/ C/ D tripping characteristic) ISI marked IS 8828(1996)]/ conforming to IEC 60898 in existing board/sheets including making connections, testing etc. as required. |
| 33 | Triple pole MCB |
| 34 | 40 A 63 A rating |
| 35 | Single pole MCB 6A to 32A |
| 36 | SITC of quick make and quick break3 pole current limiting MCCB having following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings and conforming to IS 60947-2 / IEC 60947-2 with frontface and centralised adjustable, line load interchangeability, having positive isolation capability, provision for UVR , shunt trip , earth fault trip, push( test) to trip, including making connections with lugs & spreaders,etc. as required. |
| 37 | With Thermal Magnetic release |
| 38 | up to 100 Amp , 10 kA, fixed O/L & S/C setting |
| 39 | P/Laying P.V.C./ XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved makein ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick underlayer ofsand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required of size. |
| 40 | 10.0 Sq.mm ,4 core (Un Armoured) |
| 41 | 25 sq mm 3.5 core Ar |
| 42 | Maintenance free Gel EarthingwithPipe in pipe / Pipein striptechnologyfilled with anti corrosive conductive compound ( CPRI Tested )below the ground in 150 - 200 mm dia. earth pit & surrounding filled with required mineralfillingcompound ( MFC should have hygroscopic property to retain the moisture for long time to create low resistance zone) and C.C.finished chamber covered with hinged type with locking arrangement C.I. Cover,C.I. Frame of size 300mm x 300mm complete testing of earth resistance as required. of following sizes. |
| 43 | With Pipe in Pipe Technology (Inner pipe dia. / Outer pipe dia. ) 80 - 100 micron GI Coating |
| 44 | GI pipe 2000 mm long, 50 / 25mm, Terminal 12 mm GI Strip |
| 45 | S & Laying following size earth wire/stripin horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required. |
| 46 | 25mm x 3mm G.I. ( Hot Dipped) Strip |
| 47 | S&F following sizesof ISI marked ( IS:14927 P - II ) PVC casing capping along with accessorieslike coupler, inner, outer, elbow, square box, tee etc. on surfacewith screws, expansionfastenersas required. |
| 48 | E010401) 20 mm x 12 mm |
| 49 | P/Laying ISI marked P.V.C. insulated submersible cable confirming to IS:694 with flexible copper conductor including making connection etc. as required. |
| 50 | 2.5 Sq.mm 3 core flat / Round |
| 51 | P & F ISI marked 16 amp bakelite unbreakable 3 pin plug top including making connection testing etc. as required. |
| 52 | SITC of High pressure Rubber Tube for Oxygen/Vacuum work should be executed as per direction of Engineer in charge of CE certified. |