Augmentation Of Existing Electric Supply Infra And Upgradation Of Perimeter Led Security Lights At Pallanwala Under Ge South Akhnoor Augmentation Of Existing Electric Supply Infra And Upgradation Of Perimeter Led Security Lights At Pallanwala Under Ge , Akhnoor-Jammu And Kashmir

Military Engineer Services-MES has published Augmentation Of Existing Electric Supply Infra And Upgradation Of Perimeter Led Security Lights At Pallanwala Under Ge South Akhnoor Augmentation Of Existing Electric Supply Infra And Upgradation Of Perimeter Led Security Lights At Pallanwala Under Ge . Submission Date for this Tender is 10-09-2021. Electrification Work Tenders in Akhnoor Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

28861735
Corrigendum : Augmentation Of Existing Electric Supply Infra And Upgradation Of Perimeter Led Security Lights At Pallanwala Under Ge South Akhnoor Augmentation Of Existing Electric Supply Infra And Upgradation Of Perimeter Led Security Lights At Pallanwala Under Ge
Open Tender
Indian
Jammu And Kashmir
Akhnoor
10-09-2021

Tender Details

Augmentation Of Existing Electric Supply Infra And Upgradation Of Perimeter Led Security Lights At Pallanwala Under Ge South Akhnoor Augmentation Of Existing Electric Supply Infra And Upgradation Of Perimeter Led Security Lights At Pallanwala Under Ge South Akhnoor

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 24-Aug-2021 Amendment to BOQ and List of Makes BOQ 03-09-2021
2 03-Sep-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 10-09-2021

Key Value

Document Fees
INR 1000 /-
EMD
Refer document
Tender Value
INR 1.36 Crore /-

BOQ Items

Name of Work :AUGMENTATION OF EXISTING ELECTRIC SUPPLY INFRA AND UPGRADATION OF PERIMETER LED SECURITY LIGHTS AT PALLANWALA UNDERGE (SOUTH) AKHNOOR
Sl. No. Item Description
1Taking out concrete poles/struts, any size, complete all as specified and as directed.
2Taking down existing rusted/worn out MS cross arm, angle, clamps, nuts, bolts, washers and GI Bracket from existing pole, complete all as specified and as directed.
3Taking down existing unserviceableinsulators, shackle type, Pin type, including nuts, bolts and washers, complete all as specified and as directed.
4Taking down existing unserviceable worn out XLPE under ground cable of any size and length at any position from, complete all as specified and as directed.
5Taking down existing unserviceableACSR Conductor from pole including nuts, bolts and washers, complete all as specified and as directed. (From HT Pole)
6Supply and erecting, in truly vertical position Steel tubular swaged pole with cast iron base plate finial tapper plug, bolts nuts and screws and specified type 410 SP-55 (11 mtr long) in truly vertical position 1.83m length of pole above ground level shall be painted with two coats of synthetic enamel paint in strips of 30 cm width, black and yellow alternatively and painting with two coats of aluminum paint over a coat of red oxide primer on rest part of pole and its connected parts, complete all as specified and as directed. (Note:- Excavation and PCC shall be measured and paid separately)
7Supply and erecting, in truly vertical position Steel tubular swaged pole with cast iron base plate finial tapper plug, bolts nuts and screws and specified type 410 SP-31 (9 mtr long) in truly vertical position 1.5 m length of pole above ground level shall be painted with two coats of synthetic enamel paint in strips of 30 cm width, black and yellow alternatively and painting with two coats of aluminum paint over a coat of red oxide primer on rest part of pole and its connected parts, complete all as specified and as directed. (Note:- Excavation and PCC shall be measured and paid separately)
8S&F Arial bunched cable, 1.10 KV, nominal cross sectional area 16.0 Sqmm, consisting 4 single core (three Phase and one neutral), sizes 4x16 Sqmm+ 16 Sqmm (Insulated messenger) constitute of three single core of screend cable twisted around an Al alloy messenger conducter enabling it to carry the full load of the cable with screend by an extuded semi conducting layer and a coppar tape with XLPE insulation over all sheathed with PVC/Polythelene incl anchor clamp,suspension clamp, inline connecter, service clamp, insulation peircing connecter, insulation peircing connecter for Tap from bare lines mounted on PCC pole, complete all as specified and directed.
9Aerial bunch cable of 11 KV, nominal cross sectional area 95.0 Sqmm, consisting 3 single core, sizes 3x95 Sqmm + 70 Sqmm (Insulated messenger)constitute of three single core of screend cable twisted around an Al alloy messenger conducter enabling it to carry the full load of the cable with screend by an extuded semi conducting layer and a coppar tape with XLPE insulation over all sheathed with PVC/Polythelene incl anchor clamp,suspension clamp, inline connecter,service clamp,insulation peircing connecter, Insulation peircing connecter for Tap from bare lines mounted on PCC pole, complete all as specified and directed.
10M&L for SMC FRP Junction Box, Sliding – Door fixed to base by means of sliding, Pole mounting arrangement, maint free,fire retardent, pilferage proof for entry the cable from side and bottom of size 300x200x105 mm with aluminium bus bar and terminal for street lighting of 3 phase/4 core complete all as specified and directed. Make:- Sintex GS-JB-3020 or any other Equivelent in volume.
11Supply and fixing LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum housing inverter backup and heat resistant complete with electronic driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete. Make:- Havells, Philips, Hellonix.
12M&L GIbracket for mounting light fittings, any type complete with 1.50mtr long galvanised iron pipe 40mm dia medium grade, bent to required shape including mild steel clamps of flat iron 40x6mm, hook, stay, nut, bolt and washer including painting with two coats of synthetic enamel paint over one coat of red oxide primer, complete all as specified and as directed.
13S & F Lightning arrestor expulsion type complete with all fittings, station class, discharge capacity 65 KA 11 KV grade, complete all as specified and directed.
14S & F Switch air break gang operated (Swing out expulsion ruse insulators), tripple pole mechnical operated from ground level mounted on insulator and Mild steel frame (15 insulators type) out door type suitable for vertical installation single break provided with locking arrangement consisting of MS channel HT post top insulator with drop out fuses operating rod 20mm dia GI medium grade pipe worked from ground level confirming of IS 1818 of 1972 and contineous current rating upto 200 amp and volt 11 KV, complete all as specified and as directed.
15M&L Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint, complete all as specified and as directed.
16Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm, complete all as specified and as directed.
17Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground vertically to a depth not less than 2.25 meter below ground level with top edge of the earth plate at a depth not less than 2.25 mtr below ground level earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers, all around top and bottom and electrode connection by using GI Wire4 Sqmm(upto the body of equipment) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles. GI pipe 20mm bore light grade for watering with funnel and wire mesh including medium grade GI Pipe 40mm bore protection and 40 mm GI pipe light grade for protection of strip. PCC chamber in cement concrete 1:3:6 type C-2 and RCC pit cover in M20 (design mix) complete all as shown in Electrical Plate No.3 of MES Standard Schedule of Rates (Part-I) of 2009, complete all as specified and testing on completioni)The unit rate shall include for protection pipe, GI water pipe, wire mesh, funnel, excavation.RCC pit cover, test point, 32mm GI strip from top of earth plate upto 7.5 above ground level and if GI protection is less than 7.5 meter, no price adjustment shall be made.iii)If the testing result of earthing work is not been found satisfactorily then the contractor shall do other earthing work at his own cost and nothing shall be permissible on this account.iv)Earthing work will be carried out in presence of MES representative.
18Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground vertically to a depth not less than 2.25 meter below ground level with top edge of the earth plate at a depth not less than 2.25 mtr below ground level earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers, all around top and bottom and electrode connection by using GI Strip 32x6 mm(upto the body of equipment) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles. GI pipe 20mm bore light grade for watering with funnel and wire mesh including medium grade GI Pipe 40mm bore protection and 40 mm GI pipe light grade for protection of strip. PCC chamber in cement concrete 1:3:6 type C-2 and RCC pit cover in M20 (design mix) complete all as shown in Electrical Plate No.3 of MES Standard Schedule of Rates (Part-I) of 2009, complete all as specified and testing on completion i)The unit rate shall include for protection pipe, GI water pipe, wire mesh, funnel, excavation.RCC pit cover, test point, 32mm GI strip from top of earth plate upto 7.5 above ground level and if GI protection is less than 7.5 meter, no price adjustment shall be made.iii)If the testing result of earthing work is not been found satisfactorily then the contractor shall do other earthing work at his own cost and nothing shall be permissible on this account.iv)Earthing work will be carried out in presence of MES representative.
19Construction of brick masonry platform 3x2.5x1.2 mtr with XPM fencing with weight not less than 4Kgs/Sqm and angle iron 50x50x6mm for support gate with locking arrangement. PCC floor type B-1 (1:2:4) 100mm thick including excavation and earth work, platform white washing, painting of fencing and frame work, complete all as specified and directed. Note: Rate inclusive of taking down transformer from foundation, fixing on suitable trolley making all connections and re-storing electrical supply and refixing the transformer after civil works all as directed.
20Supply and fixing new stay assembly complete with accessories as shown in electrical plate No-01 using GI stay rod 20mm dia. Stay wire 7/4 mm stranded galvanised including mild steel stay plate 300mm x 300mm x 6mm, galvanised steel 14mm dia 400mm long stay bow and GI nuts, washers, loop type insulator vitreous porcelain white, brown or green of small size with overall dimensions 90mm x 140mm clearance of hole 20mm, complete all as specified and directed. Note:- Excavation, stay clamps and conrete work etc will be measured and paid separately
21M&L Broken stone aggregate for loose filling in the area sarroundings of transformer, of gauge 20 mm to 40 mm graded, laying in layers thickness not exceeding 150mm, complete all as specified and directed.
22Design, Supply, Install, Commissioning and testing of Automatic Voltage Regulation (HT Stabilizer) operation on three phase, naturally oil cooled (ONAN) copper wound , outdoor type and designed for input variation between 6 KV to 12 KV with output voltage stabilizer at 11 KV with accuracy +/- 1% and of capacity 600 KVA, 50 Hz, suitable for balanced supply , unbalanced load & efficiency more than 99%.Make- Andrew Yule, Automatic Electric, ABB & AREVA, Indian Transformer and Electricals pvt ltd Gurgaon.The unit consists of : (a) Copper wound Step down Transformer double wound Star/Delta connected. (b) On Load stepless rolling contact type regulator Auto wound Delta connected . (c) Booster Transformer double copper wound open connected. (d) Automatic control gear consists of (i) one electronic voltage relay (ii) One reversing geared motor unit. (iii) Two limit switches in order to avoid over running highest and lowest position chain drive coupling devices and all electrical connections.(Regular part ) Item (b) & (d) above- shall be housed in a separate tank and shall have the following fitting - (a) Lifiting lugs (b) Earthing termainls (c) Rating plate (d) Filter value top & bottom (e) Oil fitting hole (f) Thermometer pocket (g) Silcagel dehydrating breather (h) Oil level gauge (j) Voltmeter with selector switch for measuring output voltage.
23Terminals : (i) Bare Bushing for both input & outpur(ii) Aux connection suitable for 1.1KV grade PVC cable.Central Consturctional Features : The unit shall have three distinct features as uner :- 1.Hand Control.2. Motor contral3. Automatic control.Hand Control : Hand Wheel will be located on the front of the regulator tank at convenient oprative height. Motor Control : Raise/Lower push button control by means of small single phase reversible geared motor of the permanent capacitor type shall be provided. The limit switches shall be provided to restrict the travel at extreme position. With this arragement it wound also be possible to privide remote control of the Regulating Unit. The reversible geared motor wound of STEP-SYN type. Automatic Control : For automatic correction of fluctuating supply voltage, provide Electronic relay which will sense the output voltage and provide signal to the driving motor for necessary corrections. Fittings & Accessories :- As per annexure attached.
24Note : (a) Commissioning /first time energizating of the products in the presence of supplied by manufacture (OEM). The cost per man/day to & fro fare local converyance, lodging & boarding expenses will be charged by Contractor. (b) Both the tank shall be supplied with first filling of transformer oil conforming to IS-335 (latest addition) and other std fittings. (c) The pre-inspection of equipment at factory by the rep of accepting officer.The fare of to & fro, local conveyance, lodging & boarding expenses will be borne by Contractor.(Transformer Parts) Items (a) & (c) above shall be housed in a sheet steel tank fitted with radiators and mounted on unidirectional rollers and shall have the following fittings :- (a) Lifting lugs (b) Earthing terminals (c) Rataing plate (d) Filter value top & bottom (e) Oil fitting hole (f) Thermometer pocket (j) Dial type oil temprature indicator with alarm and contacts(k) Explosion vent (l) Bochhoz relay with alarm and trip contracts (m) Air release plug.
25Supply, installation, commissioning and testing of powder coated factory made panel board outdoor type double door confirming to IP 52 or better protection, of suitable size made of Robust steel sheet construction made from min 3.15 mm steel sheet with countersunk holes at bottom for base mounting brackets and sheet steel gland plates for cable entry, formed gasket around doors, with provision of lock inserts, earthing straps, wiring plan pockets, door stay, fan and filter units, heaters and grouted in ground by using angle iron frame of size 50x50x6mm, PCC (1:2:4) type C-1 with 20mm graded stone aggregate. Al bus bar system of size 25 x 4 mm, duly colour coded. The panel will be prewired with suitable size PVC insulated copper conductor cable, multistranded housed, complete all as directed by Engineer-in-Charge with the following accessories :- (i)MCCB 4 pole 415 Volts of capacity 100 amps thermal magnetic release adjustable type of breaking capacity 16 KA-01 No (incoming). (ii)MCCB 4 pole 415 Volts of capacity 63 amps thermal magnetic release adjustable type of breaking capacity 16 KA-02 Nos (outgoing). (iii)Onload change over switch 4 pole 100 amps -01 No for outgoing. (iv)MCB SPN 40 amps rating 10 KA-02 Nos (outgoing). (v)Voltmeter digital type, three phase 0-500 volts with inbuilt selector switch-01 No. (vi)Amp meter digital type, 0-200 amps with selector switch and CTs of sutable ratio-01 No. (vii)Indicator lamps LED type (RYB) : 01 Set. (viii)Masonary work for installation of panel as required. (X)Analog time switch With battery backup and suitable Contactor and connected accessories Make:- ITE Gurgoan, ABB, Seimnens
26Supply, install, testing and commissioning of 11KV 630 Amps 21KA for 3 Sec. SF6 insulated, One side extensible, outdoor duty 4 way Ring main unit with Bus metering Module fully motorized in combination of 4 nos. VCB module, consisting of copper busbar in SF6 insulated 304 (Non-Ferrite Non-Magnetic Grade) stainless steel enclosure of thickness3.15 mm with manometer fixed, with series trip, self-powered microprocessor based numerical over current relay (IDMTL + Inst.)in each VCB feeder. Suitable CT for Protection to be provided with each VCB Feeder.The Breaker shall have mechanical ON /OFF indicator with hand trip device and spring charging, spring release coil, auxiliary switch of 2 NO +2NC. The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFLR classification for gas tank & cable box and gas to be released from the rear top from operator. The complete RMU along cable chamber to put to an outdoor enclosure to have ingress protection of minimum IP55. The RMU design should support site replaceable HT cable bushing and VI of VCB should be RMU Manufacturer’s own make.Each feeder of should have voltage presence indicator. All the type test certificated as per IEC from Third party lab to be submitted.
27RMU Should have followings :- - 1 No. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder. The relay should be of ABB / SIEMENS / SCHNEIDER/ASHIDA/C&S make only. - 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 40-20/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB for each VCB module. - 3 Nos. Metering CT shall be of Burden 2.5VA, ratio 40-20/1A, Class of Accuracy class 0.5 for Metering purpose for each VCB Module. - 1 No. Manometer for each tank. - 1 No. Voltage passage indicator for each feeder. - 3 Nos. Single phase cast resin potential transformer ratio 11kV/110V, 50VA, accuracy class 0.5. - 1 No. Trivectormeter of Class 0.5 Accuracy (Make: Schnieder / L&T/Conzerv / Secure / ABB / Siemens) with each VCB. - 1 No. Auxiliary Transformer of 250 VA, 11KV/230V for local power supply for battery charging, lights etc. - 1 Set of Battery and Charger set (2X12V DC) for motorized operation. -Right angle boots for all the feeder Modules. Make of VCB RMUl:- ABB/SIEMENS/ SCHNEIDER (System house & Franchise is not approved)
28Excavating in trenches not exc 1.5 m wide and not exc 1.5 m in depth formanholes, sewage line etc not exc 10 sqm on plan and getting out in soft/loose soil, complete all as specified and as directed.
29Excavating in post holes (or similar holes) each n exc 0.5 cum, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25cm, watering, and removing surplus soil to a distance n exc 50 m and making good surface in any type of soil, complete all as specified and as directed.
30Returning, filling in soil, including spreading, levelling, watering and well ramming in layers not exc 25 cm, complete all as specified and as directed.
31Removing excavated material (soils) not exc 50 m and depositing where directed at a level not exc 1.5 m above the starting point, complete all as specified and as directed.
32Plain cement concrete 1:4:8 type D-2 using 40mm graded stone aggregate as in foundation, filling and mass concrete, complete all as specified and as directed.
33Form work rough finished surface to sides of pillars, post, struts, piers, columns and stanchions, complete all as specified and as directed.
34Reinforced cement concretetype A1 1:1.5:3Nominal Mix (20mm graded aggregate)in columns, pillars and the like, complete all as specified and as directed.
35TMT bars 6 mm to 8 mm dia, cut to length, bent to shape required, including cranking, bending spirally hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia, complete all as specified and as directed.
36TMT steel bars 10mm dia and over, cut to length, bent to shaperequired, including cranking, bending spirally for hopping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9m dia or securing with clips, complete all as specified and as directed.
37Brick work with sub class `B" bricks, straight or curved on plan exc 6 m mean radius, built in CM 1:4, complete all as specified and as directed.
38Rendering 15 mm thick in CM 1:4 on fair faces of brick work or concrete surfaces, finished even & smooth without using extra cement, complete all as specified and as directed.
39Preparing newly plastered or unplastered surfaces of walls and applyingtwo coats of cement based paint over a coat of primer, complete all as specified and as directed.
40Framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering. Doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging; also fastening and fixing, complete all as specified and as directed.
41M & L for preparation of new steel surfaces and applying two coats of synthetic enamel paint over a coat of red oxide primer over 10cm width or girth, complete all as specified and as directed.
42Excavating in post holes (or similar holes) each n exc 0.5 cum, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25cm, watering, and removing surplus soil to a distance n exc 50 m and making good surface in any type of soil, complete all as specified and as directed.
43Providing cement concrete type C2 (1:3:6) as in foundations, filling and mass concrete, complete all as specified and as directed.
44S&F MS works as in fencing posts and struts including cutting tops to shape as directed, drilling holes notching for wire etc flat iron fillets for securing wire mesh etc incl all drilling bolting riveting etc and similar works conforming to FE 290 gde E-165, complete all as specified and as directed.
45S&F Galvanised 2 strand steel barbed wire 2.24mm dia barbed with 2mm dia barbs at 75mm spacing and straining and fixing to any typoe of standard rails includng securing or tying with ms steel wire staples ar steel pins etc, complete all as specified and as directed. Note :- Wt of the barbed wire at site of work will be ascertain by the BOO convened by GE.
46Fixing only chain link fencing including line wires any mesh size and type including straining bolts etcand provision of binding wire, complete all as specified and as directed.
47S&F chain link MS galvanised fencing any size or type, complete all as specified and as directed. Note :- Wt of the barbed wire at site of work will be ascertain by the BOO convened by GE.
48Excavation in trenches n.exc. 1.5 mtr wide and n.exc 1.5 mtr deep for foundations of poles/stays/cable etc not exc 10 Sqm area on plan and getting out in soft/loose soil, complete all as specified and as directed.
49All as per Srl item No. 45 here-in before but depth exceeding 1.5 mtr and not exceeding 3 mtr, complete all as specified and as directed.
50Removing surplus soil to a distance not exc. 50 mtr and depositing where directed at a level n.exc. 1.5 mtr above the starting point, complete all as specified and as directed.
51Insulation Rubber Mat CLASS 4 INSULATING MATTING - WORKING VOLTAGE UP TO 36KV,Working voltage: 36kV Withstand voltage: 50kV, Colour: grey, Width: 1000x2000 mm, Hardness: 65 ShA, Surface: smooth, Thickness: 3 mm, Strength: 6 Mpa, complete all as specified and as directed.
52Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4 mm dia galvanised iron or steel wire, complete all as specified and as directed.
Disclaimer :