| 1 | Part A: SITC OF UPS |
| 2 | Supply,Installation ,testing &commissioning of 30kVA UPS with following major specifications: [Make : APC / EMERSON / VERTIV / NUMERIC / SWITCHING AVO/ ABB/Powerone] |
| 3 | TECHNOLOGY :Should be digitally controlled, IGBT based double conversion On-line VFI according to IEC62040-3 specification, Inverter and Rectifier both should be IGBT based. Isolation Transformer (Delta to Star connected) should be provided on the Inverter output ,outside of the UPS for modular UPS system. Output Neutral with Ground voltage should be <1 VNominal power :30 KVAActive power : 28 KWIn/Out phase Configuration : Three/Three, Three/SingleNeutral : Neutral passing through Ouput wave form on mains run : Pure Sinusoidal Bypass type :Static and electro-mechanicalTransfer time: Zero |
| 4 | INPUT :Phase :3 Phase 4 Wires and GroundRated Voltage : 380/400/415Vac Working Voltage Range:320~478Vac Frequency Range : 45-55Hz at 50Hz/54-66Hz at 60Hz (auto sensing)Power Factor : =0.99Current THDi : =3%(100% linear load) Bypass Voltage Range : Max.voltage:220Vac: +25%(optional +10%,+15%,+20% )230Vac: +20%(optional +10%,+15%)240Vac: +15%(optional +10% ) Min. voltage: -45% (optional -20%, -30%) Frequency protection range: ±10% |
| 5 | OUTPUT : Phase : 3 Phase 4 Wires and GroundRated Voltage : 380/400/415Vac Power Factor : 0.9Voltage Regulation:±1%Frequency Utility Mode:±1%, ±2%, ±4%, ±5%, ±10% of the rated frequency(optional) Battery Mode : (50/60±0.2%)HzCrest Factor : 3:1THD :=2% with linear load=5% with non linear load Overload : 110% for 1 Hr., 125% for 10 mins., 150% for 1 min.Minimum efficiency : Should be > 90% at full load |
| 6 | BATTERY :Type & Voltage :SMF & 12VMinimum VAH required : 31200 VAH or, to satisfy the condition of 60 min run at full load whichever is higher. Minimum Backup time : 60 min at full load conditionMake :Exide Power Safe / Amaron QuantaCharging cycle : Automatic float cum boost charging capability with settable float & boost charging voltages & current levels and boots charger timer. |
| 7 | GENERAL FEATURES Noise level@1m :46 dBAWorking temperature range :from 0 deg.C to 40 deg.CStorage temperature range :from-20 deg.C to + 50 deg.C (Excluded batteries)Relative Humidity range : 20-95% with out condensationProtection Degree :IP 21 CONFIGURATION AND MANAGEMENT : Technology Rectifier/Booster : IGBTCommunication interface : 2 serial port RS 232, SNMP Enabled. Slots for communication interface for SNMP Input/Output connection : 3P+N+PE Connectors on omega bar |
| 8 | Normal Protection : Input, output, rectifier input, battery fuse, bypass fuse, short circuit etc. Thermal on system, rectifier, bypass and inverter. Protection against prolonged battery discharge |
| 9 | METERING,ALARM : Audio alarm : Mains fail, Battery low pre-alarm, inverter trip etc.Metering : (i) input & output (a) Current:-RMS Value,peak value crest factor (b) Voltage:- ph-N RMS Value,ph-ph RMS value,bypass line (c) voltage (for input) Power:- Nominal power (VA), Active power(W),power factor, frequency(ii) Battery :voltage, current , capacity, history data, residual capacity, charging status(iii)Bypass :Enabling, Forced, DIP Speed, ECo Mode(iv) Miscellaneous : internal Temperature, DC bus voltageINDICATION/DISPLAY : Mains:-on/Fail/High/Low/Single Phasing,DC:- on/high,battery:-low pre-alarm/low trip,inverter:-on/trip,by-pass,intervention, overheats overloads,battery intervention,total discharge etc. |
| 10 | Supply,Installation ,testing &commissioning of 10kVA UPS with following major specifications: [Make : APC / EMERSON / VERTIV / NUMERIC / SWITCHING AVO/ ABB/Powerone] |
| 11 | TECHNOLOGY :Should be digitally controlled, IGBT based double conversion On-line VFI according to IEC62040-3 specification, Inverter and Rectifier both should be IGBT based. Isolation Transformer (Delta to Star connected) should be provided on the Inverter output ,outside of the UPS for modular UPS system. Output Neutral with Ground voltage should be <1 VNominal power :10KVAActive power : 8KWIn/Out phase Configuration : Three/Three, Three/SingleNeutral : Neutral passing through Ouput wave form on mains run : Pure Sinusoidal Bypass type :Static and electro-mechanicalTransfer time: Zero |
| 12 | INPUT :Phase :3 Phase 4 Wires and GroundRated Voltage : 380/400/415Vac Working Voltage Range:320~478Vac Frequency Range : 45-55Hz at 50Hz/54-66Hz at 60Hz (auto sensing)Power Factor : =0.99Current THDi : =3%(100% linear load) Bypass Voltage Range : Max.voltage:220Vac: +25%(optional +10%,+15%,+20% )230Vac: +20%(optional +10%,+15%)240Vac: +15%(optional +10% ) Min. voltage: -45% (optional -20%, -30%) Frequency protection range: ±10% |
| 13 | OUTPUT : Phase : 3 Phase 4 Wires and GroundRated Voltage : 380/400/415Vac Power Factor : 0.9Voltage Regulation:±1%Frequency Utility Mode:±1%, ±2%, ±4%, ±5%, ±10% of the rated frequency(optional) Battery Mode : (50/60±0.2%)HzCrest Factor : 3:1THD :=2% with linear load=5% with non linear load Overload : 110% for 1 Hr., 125% for 10 mins., 150% for 1 min.Minimum efficiency : Should be > 90% at full load |
| 14 | BATTERY :Type & Voltage :SMF & 12VMinimum VAH required : 9500 VAH or, to satisfy the condition of 30 min run at full load whichever is higher. Minimum Backup time : 60 min at full load conditionMake :Exide Power Safe / Amaron QuantaCharging cycle : Automatic float cum boost charging capability with settable float & boost charging voltages & current levels and boots charger timer. |
| 15 | GENERAL FEATURES Noise level@1m :46 dBAWorking temperature range :from 0 deg.C to 40 deg.CStorage temperature range :from-20 deg.C to + 50 deg.C (Excluded batteries)Relative Humidity range : 20-95% with out condensationProtection Degree :IP 21 CONFIGURATION AND MANAGEMENT : Technology Rectifier/Booster : IGBTCommunication interface : 2 serial port RS 232, SNMP Enabled. Slots for communication interface for SNMP Input/Output connection : 3P+N+PE Connectors on omega bar |
| 16 | Normal Protection : Input, output, rectifier input, battery fuse, bypass fuse, short circuit etc. Thermal on system, rectifier, bypass and inverter. Protection against prolonged battery discharge |
| 17 | METERING,ALARM : Audio alarm : Mains fail, Battery low pre-alarm, inverter trip etc.Metering : (i) input & output (a) Current:-RMS Value,peak value crest factor (b) Voltage:- ph-N RMS Value,ph-ph RMS value,bypass line (c) voltage (for input) Power:- Nominal power (VA), Active power(W),power factor, frequency(ii) Battery :voltage, current , capacity, history data, residual capacity, charging status(iii)Bypass :Enabling, Forced, DIP Speed, ECo Mode(iv) Miscellaneous : internal Temperature, DC bus voltageINDICATION/DISPLAY : Mains:-on/Fail/High/Low/Single Phasing,DC:- on/high,battery:-low pre-alarm/low trip,inverter:-on/trip,by-pass,intervention, overheats overloads,battery intervention,total discharge etc. |
| 18 | N.B: 1. The OEM/Manufacturer should comply standard certification, it must be submitted during the uploading of tender documents or latest by prior to issuance of LOA failing which the bid may be cancelled and appropriate action leading to debbarment may be taken in due course. 2.The work shall be completed in all respect and shall be free from all kindsof defects/deficiencies/damages in equipment, materials, components and other auxiliaries and workmanship from any cause whatsoever for a period of Three years warrenty or, total replacement in case of major defects or fault for both the battery and UPS from the date of commisioning of the UPS. |
| 19 | Part B: Allied EI works for UPS System |
| 20 | EMERGENCY SUB PANEL : Design, Manufacture, testing, supply, installationand commissioningof floor mounted Indoor type extensible cubical MV switchboard,fabricated by CPRI approved panel maker having compartmentalized design, fabricated out of 14 SWG ( 2.0 mm ) nominal thickness CRCA sheet steel for framework and covers, and 3 mm nominal thickness for gland plates, including cleaning and finishing complete with 7 tank process, with short circuit withstand capacity of 31 MVA for one second, front and back openable, hinged, single shuttered, single door, with locking arrangement, good quality dust, damp and vermin proof rubber gaskets, solid connections from main busbars to switchgears with required size of copper busbars, connections and interconnections and control wiring using 2.5 sq. mm of RYB colour coded FRLS PVC Insulated Copper conductor single core cables and copper cable lugs |
| 21 | 1 no. of 25 mm x 5 mm GI earth strip for earthing, cable alleys, cable gland plates in two halves, dinrail for mounting switchgear, metering arrangements, drilling holes, detachable gland plates / knockout plates, providing 50 mm x 50 mm x 5 mm nominal thickness MS angle iron support for ACBs alongwith horizontal / vertical intermediate MS flat members for stiffening, mounting on MS channel iron framework 100 mm x 50 mm x 5 mm ( 9.2 kg / metre ) for floor mounting of MV panel, providing MS plate, suitable for bottom cable entry, grouting in ground, powder coating, providing and fixing the following switchgear and measuring instruments, earthing, cartage from fabricator\"s premises to site of work etc. as required.[ ACBs/MCCBs/SFUswill be Legrand/Simens/L&T/ABB Make, . All theother accessories will be Legrand /Simens/L&T/ABB Make and as per manufacurers standard ]. |
| 22 | INCOMER : A) 415V, 400A, TPN open execution type, onload change over switch--1set |
| 23 | BUSBAR : Extensible bus bar chamber 3 phase, 4 wire, 440 volts, 50 c/s consisting of high conductivity electrolytic grade tinned copper bus bars of capacity 600 Amps for incoming / outgoing feeder with PVC coloured sleeves with DMC / SMC busbar supports -1 Set |
| 24 | OUTGOING : A) S & F 415V 160Amp TPN SFU with DIN type HRC fuse Open Execution type ---6 Set B) S & F 415V 63 Amp TPN SFU withDIN type HRC fuse Open Execution type ---4Set [spare] |
| 25 | CONTROL & ACCESSORIES : A) Load Manager Class 1.0 accuracy Load Manager 3 Ph 4 W 240V 5A with RS 485 port( For measurement of V, A, F, kW, kWh ) with 3 nos. 400 / 5Amps bar primary type CTs 15 VA burden Class 1.0 accuracy, and 3 nos. back up 2 Amps HRC fuse or SPMCBs 10 kA breaking capacity - 1 SetsB) 3 nos. phase Indication lamps LED type in RYB colours with toggle switches and 3 nos. of 2 Amps back up HRC fuse or SPMCBs 10 kA breaking capacity, 1 no. breaker ON indication lamp, fuses, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required - 1 SetsC) Providing & fixing danger plates [Medium Voltage - size 200mm x 150mm ] made of mild steel at least 2mm thick & vitreous enameled white on both sides & with inscription in signal red colour on front side as required. -- 1 set |
| 26 | S & delivery of the4 core 300 sq. mm 1.1kv grade XLPE insulated Auminium conductor cable (As Per IS 7098 (Part 1) 1988) (Make - Polycab/ Havells/ RR Kabel / Gloster).(From Emergency Main DG Panel to Emergency Sub- panel interconnection) |
| 27 | Supplying and fixing 415 V, 16-32A per way, 4 wayTPN MCBDB with SS enclosure double-door with IP-42/43 protection with 63A Four Pole Isolators as incomer and 12non SPMCBs (\"C\" Curve, 10 kA) as outgoing, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment, 63A FP Isolator, 12 no. (16-32A)SPMCB. (Make - Siemens(8GB32202RC04) / Schneider / Legrand) |
| 28 | Supplying and fixing 415 V, 16-32A per way, 6 way TPN MCBDB with SS enclosure double-door with IP-42/43 protection with 63A Four Pole Isolators as incomer and 18 nos SPMCBs (\"C\" Curve, 10 kA) as outgoing, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment, 1no. 63A FP MCB type Isolator, 18 no. (16-32A)SPMCB, Make- Siemens (8GB32202RC06)/ Schneider/ Legrand. |
| 29 | Supplying & Fixing Industrial Plug & Socket board with 415 V, 63A, TPN & Earth Metal Industrial Plug socket & 63A Industrial top incl. S & F 63 A TPN/FP MCB breaking capcity 10kA (C- Curve) in SS enclosure fixed on wall and cecessary conection. (Make - Legrand/ L&T/Siemens). |
| 30 | Supplying & Fixing Industrial Plug & Socket board with 415 V, 32A, TPN & Earth Metal Industrial Plug socket & 32A Industrial top incl. S & F 32 A TPN/FP MCB breaking capcity 10kA (C- Curve) in SS enclosure fixed on wall and cecessary conection.(Make - Legrand/ L&T/Siemens). |
| 31 | Supply & Delivery of4 Core 35 sqmm 1.1 kv.gr. XLPE insulated 1100V Grade as per IS 7098 (part 1)1988 armoured sheathed Aluminium conductor cable |
| 32 | Laying of cable on wall/surface incl. S & FMS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting [4 Core 35 sqmm] |
| 33 | Laying of cable as below, on existing Cable Tray and binding with suitable size GI wire.[4 Core 35 sqmm] |
| 34 | S & F compression type brass cable gland complete with brass gland, brass ring & rubber ring for dust & moisture proof entryof XLPE/PVC armoured cableas & Finishing the end of the following XLPE/PVC armoured cableas by crimping method incl. S&F solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials: [4 core 35 Sqmm] |
| 35 | S&drawing 1.1 kv single core stranded FR PVC insulated &unsheated single core stranded cupper wire (approved make)of the following sizes through prelaid poly pipe. & by the Gifish wire & making necy connection as required. |
| 36 | a) 4 X 80/0.4 ( 10 sqmm) + 2 X 84/0.3 (6 sqmm) as ECC (For30 KVA UPS) |
| 37 | b) 4 x 84/0.3 (6 sqmm) + 2 x 56/0.3 (4 sqmm) as ECC( For 10 KVA UPS) |
| 38 | Distributionwiring in 1.1 KVsingle core stranded \"FR\"PVC insulated & unsheathed copper wire (Brand approved by EIC) in 25mm size PVC rigid conduit \"FR\" (Precision make) incl. necy. fittings as required. |
| 39 | a) 4 X 80/0.4 ( 10 sqmm) + 2 X 84/0.3 (6 sqmm) as ECC (New & old UPS) |
| 40 | b) 4x84/0.3 (6 sqmm) + 2x56/0.3 (4 sqmm) as ECC |
| 41 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. |
| 42 | a)10 sq.mm. |
| 43 | b)6 sqmm |
| 44 | c) 4 sqmm |
| 45 | Cutting Channel of size (43 mm x 43 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 25 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI \"U\" hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles 25 mm dia 3 mm thick polythene pipe without earth continuity wire |