| 1 | Motarable cartage of Material from Almora to road side dump store Including Loading & Un-loading both End.Dist 90 Km ST Pole SP-23 |
| 2 | Motarable cartage of Material from Almora to road side dump store Including Loading & Un-loading both End.Dist 90 Km Small materials |
| 3 | Head load cartage of following materials from Dump store to pit site ava. Lead distance 6 Km ST Pole SP-23 |
| 4 | Head load cartage of following materials from Dump store to pit site ava. Lead distance 6 Km Small materials |
| 5 | Excavation of earth for pole pit for errection of pole in all type of soil in size 0.9X0.6X1/6X8.5 Mtr Sp 23 pole |
| 6 | Excavation of earth for Stay pit for errection of Stay in all type of soil in size 0.6X0.6X1.2 CuMtr |
| 7 | Erection of Single Poles support in proper level and alignment alongwith Fixing all Accessories in the pole as per RESPO of SP-23. |
| 8 | Grouting of pole in CC ratio 1:4:8 including cost of Cement, sand, Stone ballast as per RESPO norms in size 0.45X0.45X1/9 of SP 23 Pole |
| 9 | Muffing of Pole With CC 1:3:6 Block 45cm Height from Ground level Including cost of Ballast,cement & sand Etc. |
| 10 | Fixing, tightening and nozzaling of stay with pole as per RESPO |
| 11 | Grouting of stay in CC ratio 1:4:8 including cost of Cement, sand, Stone ballast as per RESPO norms in size 0.6X0.6X0.3 CuM |
| 12 | Laying, Spreading, Stringing and Sagging of 11 KV line in Weasel Conductor Complete including Fixing of all accessories including Binding and Jumpering as per RESPO (1ph to 3 Ph) |
| 13 | Electrode Earthing of SP/DP of GI no 6 SWG with Pole & Earth Rod and nuts & Bolts.etc Complete as per specification. |
| 14 | Fabrication of Cross Arm with cutting of MS Channel/MS Angle making proper hole as per norms complete |
| 15 | Cartage of material by road transport from store Almora to dump store Upto distance 90 Km.including loading & un-loading both end. 25 KVA T/F |
| 16 | Cartage of material by road transport from store Almora to dump store Upto distance 90 Km.including loading & un-loading both end. Small material |
| 17 | Head load cartage from Dump Store to pit site ava. Lead dist.6 Km 25 KVA T/F |
| 18 | Head load cartage from Dump Store to pit site ava. Lead dist.6 Km Small material |
| 19 | dismentling of T/F from DP including opening of Connections, circuits & erathing Strip Etc |
| 20 | Installation/mounting of new T/F in DP structure with fixing of angle/channel and making all HT& LT connections and its complete comissioning 25 KVA T/F |
| 21 | Laying of LT cable of all Size |
| 22 | Fabrication of Cross Arm with cutting of MS Channel/MS Angle making proper hole as per norms complete |
| 23 | Earthing of T/F with MS earth Rod by hammering of Rod to proper depth and connecting of earth electrode with GI wire No 6 3 no of earth rod for delta earthing for neutral, 1 no for T/F body and 1 no for Structure earthing |
| 24 | Mounting & Fixing of fuse set on DP structure including making all connection complete work |
| 25 | Mounting & fixing of Lightening arrester set (3 no) on DP structure including making all connection complete work |
| 26 | Head load cartage of 16 KVA T/F from site to Dump Store ava. Lead dist.6 Km |
| 27 | Cartage of 16 KVA Transformer by road transport from Site to Almora store Upto distance 90 Km.including loading & un-loading both end. |
| 28 | Motarable cartage of Material from Almora to road side dump store Including Loading & Un-loading both End.Dist 90 Km ST Pole SP-21 |
| 29 | Motarable cartage of Material from Almora to road side dump store Including Loading & Un-loading both End.Dist 90 Km Small Material |
| 30 | Head load cartage of pole & material from road site to work site distance aprox 6 Km SP-21 |
| 31 | Head load cartage of pole & material from road site to work site distance aprox 6 Km Small Material |
| 32 | Excavation of earth for pole pit for errection of pole in all type of soil in size 0.9X0.6X1/6X8.5 Mtr Sp 21 pole |
| 33 | Excavation of earth for Stay pit for errection of Stay in all type of soil in size 0.6X0.6X1.2 CuMtr |
| 34 | Erection of Single Poles support in proper level and alignment alongwith Fixing all Accessories in the pole as per RESPO of SP-21. |
| 35 | Grouting of pole in CC ratio 1:4:8 including cost of Cement, sand, Stone ballast as per RESPO norms in size 0.45X0.45X1/9 of SP 21 Pole |
| 36 | Muffing of Pole With CC 1:3:6 Block 45cm Height from Ground level Including cost of Ballast,cement & sand Etc. |
| 37 | Fixing, tightening and nozzaling of stay with pole as per RESPO |
| 38 | Grouting of stay in CC ratio 1:4:8 including cost of Cement, sand, Stone ballast as per RESPO norms in size 0.6X0.6X0.3 |
| 39 | Laying, Sagging & Stringing of LTLine with ACSR Weasel conductor as Main and Neutralincludinglaying,sagging & stringing of continuous earth wire with Jumphering etc complete work up to energizingAB Cable 3 Phase LT line Complete |