Military Engineer Services-MES has published Gek-50 / 2021-22 Repair Maint Of Lt Cables And Other Connected Services At Mil Station Solan Under Ge Kasauli. Submission Date for this Tender is 04-09-2021. LT Cable Tenders in SOLAN Himachal Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

28800119
Corrigendum : Gek-50 / 2021-22 Repair Maint Of Lt Cables And Other Connected Services At Mil Station Solan Under Ge Kasauli
Open Tender
Indian
Himachal Pradesh
SOLAN
04-09-2021

Tender Details

Gek-50 / 2021-22 Repair Maint Of Lt Cables And Other Connected Services At Mil Station Solan Under Ge Kasauli

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 28-Aug-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 04-09-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 12000.0 /-
Tender Value
INR 6 Lakhs /-

BOQ Items

Name of Work:REPAIR/ MAINT OF LT CABLESAND OTHER CONNECTED SERVICES AT MIL STATION SOLANUNDER GE KASAULI.
Sl. No. Item Description
1Schedule "A" Section - I
2Taking down old UNSV ACSR conductor, any type and size from the poles and supply and fixingnew ACSR conductorincluding stringing on LT poles complete including aluminium binding wires, jumpering, bindings at insulators etc, complete, all as specified and directed by Engr-in-Charge.
3S&F Stay assembly complete with accessories as shown in electrical plate No-1 (loop type insulator, stay clamps, excavation and concrete measured separately) with stay rod 16mm dia, MS plate 6mm thick size 230x230mm, complete, all as specified and directed by Engr-in-Charge.
4Supplying & fixing in replacementof Cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drillingholes for bolts in any shape or size as indicated & directed and including one primer coat, one under coat and one finishing coat of paint, fixed in replacement including taking down existing one, complete, all as specified and directed by Engr-in-Charge.
5Supplying & fixing in replacementof pin insulator porcelain vitreous, white, brown & green incl. One galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100mm height 65mm dia for 1100 volts grade, complete, all as specified and directed by Engr-in-Charge.
6Supplying & fixing in replacementof shackle type porcelain, vitreous , white, brown or green insulator including galvanised mild steel straps washers insulator bolts, washer and nuts of size 100 mm height, 115mm dia for working pressure 1100 volts, complete, all as specified and directed by Engr-in-Charge.
7S&F Loop type insulator, vitreous porcelain white , brown, green small size with overall dimensions 65mm x 90mm clearance of hole 16mm, complete, all as specified and directed by Engr-in-Charge.
8S&F in replacement of Galvanized stay strand, size 7/2.24 mm, incl taking down the old unserviceable stay wire, complete, all as specified and directed by Engr-in-Charge.
9Taking down street/security/Gate light fittings LED/HPSV/CFL light fittings of any capacity or type from pole/wall after disconnection and connecting wires, carrying out to store yard for necessary repair/replacement of spares and fittings etc.,complete, all as specified and directed by Engr-in-Charge.
10Refixing only street light fittings any type or capacity including making connections with cables and testing, complete, all as specified and directed by Engr-in-Charge. Cable required for replacement shall be measured and paid for separately.
11Supply and fix in replacement to existing 1x18 Watt CFL post top light fitting withDecorative LED Post Top Lantern with transparent difuser of cap 30 Watt complete all as specified and directed by Engr-in-Charge.
12Supply and fixing inreplacement of street/security light with"CUB" LED light 45 watt presure die cast housing with epoxy power coated dark graphite grey colour finish. polycarbonate cover with individual LED lenses , inbuilt electronic driver and providing necessary connections with 2 core 2.5 Sqmm stranded PVC insulated and PVC sheathed copper conductor upto 3 metre length.
13Supplying & fixing in replacementof street light fitting GI bracket made out of 40mm bore GI pipe, light grade, tubing bend to shape, 1.2 metre long, fixed to pole/wall with and including two sets of clamps made out of flat iron of size 50 x 6 mm with bolts, nuts and washers, complete, all as specified and directed by Engr-in-Charge.
14Supplying & fixing in replacement of clamps made out of 40x6 mm bending to shape, drilling holes for bolts suitable for fixing GI pipe bracket to steel pole, made in two halves, including nuts, bolts, washers and painting with two coats of aluminium paint over a coat of red oxide primer, complete, all as specified and directed by Engr-in-Charge.
15S&F Steel water tubing,light grade, galvanised (ISI marked),40 mm bore with all fittings, laid in trenches/ under roads or fixed to poles for passing cables for protection of cables,complete, all as specified and directed by Engr-in-Charge.
16Taking down carefully under ground cable of any size and making good to disturbed surface as per existing complete all as specified and directed by Engr-in-Charge.
17Supply, laying, jointing and testing ofXLPE insulated, armoured, heavy duty LT cable 1100 Volts gradewith aluminium conductor laid in trenches, on poles, through pipes, fixed to walls etc cross sectional area 25 Sqmm 3.5 core,complete, all as specified and directed by Engr-in-Charge.
18Supply, laying, jointing and testing ofXLPE insulated, armoured, heavy duty LT cable 1100 Volts gradewith aluminium conductor laid in trenches, on poles, through pipes, fixed to walls etc cross sectional area 25 Sqmm 4 core,complete, all as specified and directed by Engr-in-Charge.
19Supply, laying, jointing and testing ofXLPE insulated, armoured, heavy duty LT cable 1100 Volts gradewith aluminium conductor laid in trenches, on poles, through pipes, fixed to walls etc cross sectional area 16 Sqmm 4 core,complete, all as specified and directed by Engr-in-Charge.
20Supply, laying, jointing and testing ofXLPE insulated, armoured, heavy duty LT cable 1100 Volts gradewith aluminium conductor laid in trenches, on poles, through pipes, fixed to walls etc cross sectional area 10 Sqmm 2 core,complete, all as specified and directed by Engr-in-Charge.
21Streching of loose ACSR conductor includingjumpering, binding,etc all as required in LT OH line, complete, all as directed by Engr-in-Charge. Note:- Disconnecting the existing security light or cable connection before stringing and reconnecting after stringing is included in the rates quoted.
22Supplying & fixing in replacementof GI wire as earth wire of size 4mm dia as required at site complete all specified and directed by Engr-in-Charge.
23Supplying & fixing in replacementofconnection/Junction box made out of 1.6mm thick MS sheet front openable, weather & vermin proof including painting two coats ofsynthetic enamel paint over a coat of red primer. Connection box shall be suitable for housing & including aluminium bus bar 25 Amps cap - 2 Nos, MCB SP 6 Amps- 01 No and having provision of cable hole in bottom for two to three cables of size 16 Sqmm 4 core armoured cable connection box shall be fitted on street light pole and fixing arrangements i.e. MS clamps etc deemed to be provided by the contractor, size of box - 200 x 150 x 100mm, complete, all as directed by Engr-in-Charge.
24Supplying & fixing in replacementof double walled corrugated HDPE duct pipe of 63 mm outer dia confirming to IS-14930 (Part-II) of approved colour with fittinggs for cable protection complete all as specified and directed by Engr-in-Charge.
25Supplying & fixing in replacementof non metallic rigid PVC conduit medium grade 20 mm dia ISI marked to be fixed on pole with all fittings including mouth pieces for passing of sub main wiring, complete, all as directed by Engr-in-Charge.
26M&L Cable PVC insulated PVC unsheathed un-armoured copper conductor (multi stranded) of cross sectional area 2.5 sqmm 2 core all as required for connections to light fittings, complete, all as directed by Engr-in-Charge.
27Supply and fixingin replacement of Steel tubular swaged poles complete with cast iron base plate, finial, taper plug, bolts, nuts and screws as specified type 410 SP-31 9.0 mtr long duly painted with two coats of aluminium pait over a coat of red oxide primercomplete, all as specified and directed by Engr-in-Charge.Note- Excavation, earth work and PCC shall be measured and paid separately.
28M&L for Painting of steel tubular pole 9.0 metre long, by applying two coat of aluminium paint after scraping / brushing and cleaning the rust on pole and cross arms. Aluminium painting will be done on pole above 1.5 metre height from ground level and balance 1.5 mtr from groundlevel will be painted by alternate layer of black and white enameled paint (30 Cms each). Pole Nos will be written on pole by black paint in yellow circle of 150mm dia, complete, all as specified and directed by Engr-in-Charge. Note:- Only one coat will be applied at one time and payment at 50% of coated rate to be applied at the firsttime of first coat. Second coat is to be done more than 30 days after first coat.
29Excavationin trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth, for foundations, laying of pipes etc and notexceeding 10Sqm on plan for manholes etcand not exceeding 1.5 metre in depth and getting out in any type of soil, complete, all as specified and directed by Engr-in-Charge.
30Returning filling in with approved excavated soil including spreading levelling watering and well ramming in layers not exceeding 25cm thick, complete, all as specified and directed by Engr-in-Charge.
31Removing excavated material (soils) to a distance not exceeding 50metre and depositing where directed at a level not exceeding 1.5 metre above the starting point, complete, all as specified and directed by Engr-in-Charge.
32Supply and laying Sub Class "B" common burnt bricks, old size, designated 75, laid dry, flat with width equal to length of brick & with gaps between the adjucent bricks not exceeding 10mm as cover laid over the cable to give mechanical protection to under ground cable, complete, all as specified and directed by Engr-in-Charge.
33Supply and lay Dry sand cushioning to under ground electric cable on layer of8cm thick before laying the cable and second layer of 15cm thick after laying the cable, complete, all as specified in clause 19.75 of M.E.S Schedule Part-I (2009)and directed by Engr-in-Charge.
34Earthing with Galvanised iron earth plate electrode 600mm x 600 mm & 6 mm thick burried directly in ground (earth pit not less than 2.25 metre deep below normal GL) with top of earth plate not less than 1.5 metre below GL, connected to GI earth lead wire 4 mm dia connected to earth plate electrode by means of GI nuts, bolts & washers earth wire protected with & including 15 mm bore medium grade ISI marked GI pipenot less than 7.5 metre long all as shown in electrical plate No 3 of MES Schedule Part I, with & including; PCC 1:3:6 type C1 pit with cover of RCC 1:2:4 typeB1 reinforced with welded steel wire fabric not less than 4 Kg per Sq M, watering arrangements with 20 mm bore GI medium grade pipe ISI marked , GI funnel with GI mesh, filling with mixture of common salt & charcoal, necessary excavation and earth works in any type of soil, including test point, testing & commissioning, complete
35Supply and fix in replacement of Sheet metal enclosure including fiiting on wall including and making the connection with MCCB 4 Pole 100 Amps 25 KA, 415 volts , 50 Hz ,thimble/lugs, aslo including all nuts bolts required for fixing all as specified and directed by Engr-in-Charge by Engineer - in - Charge.
36Supply and fix in replacement of sheet metal enclosure, Triple pole and neutral AC, 415 volts, 04 way, with 200 Amps rated copper bus bar and IP - 43 & IK 09 protection including provision of four pole 100 Amp isolator and MCBs of cap 20 to 40 Amps as incomer with metal double door and flush to wall including all cutting etc on wall and making good including two coats of white / colour washing / distempering etc to match the existing disturbed surfaces complete all as directed by Engr-in-Charge.
37Supply & fix in replacement of Isolator 4 Pole "C" series 100 amps capacity AC 415 V,10kA complete all as specified and directed by Engr-in-Charge.
38Supply and fix in replacement of MCCB 4 pole 630 Amps 50 KA capacity AC 415 v complete all as specified and directed by Engr-in-Charge.
39Supply and fix in replacement of MCCB 4 pole 400 Amps 36 KA capacity AC 415 v complete all as specified and directed by Engr-in-Charge.
40Supply and fix in replacement of MCCB 4 pole 350 Amps 36 KA capacity AC 415 v complete all as specified and directed by Engr-in-Charge.
41Supply and fix in replacement of MCCB 4 pole 250 Amps 36 KA capacity AC 415 v complete all as specified and directed by Engr-in-Charge.
42Supply and fix in replacement of MCCB 4 pole 200 Amps 36 KA capacity AC 415 v complete all as specified and directed by Engr-in-Charge.
43Supply and fix in replacement of MCCB 4 pole 160 Amps 36 KA capacity AC 415 v complete all as specified and directed by Engr-in-Charge.
44Supply and fix in replacement of MCCB 4 pole 100 Amps 16 KA capacity AC 415 v complete all as specified and directed by Engr-in-Charge.
45M&L PVC spacer suitable for 3 wire LTOH lineincluding taking down of old one complete all as specified and directed by Engr-in-Charge.
46M&L PVC spacer suitable for 4 wire LTOH lineincluding taking down of old onecomplete all as specified and directed by Engr-in-Charge.
47M&L PVC spacer suitable for 5 wire LTOH lineincluding taking down of old one complete all as specified and directed by Engr-in-Charge.
48M&L PVC spacer suitable for 6 wire LTOH lineincluding taking down of old one complete all as specified and directed by Engr-in-Charge.
49Material and labour of danger notice plate of 1.6 mm thick as per IS : 2551 of 1982 mild steel sheets vitreous enamelled whitewith lettersfiguresand conventional skull and bones in signal red colour and fixed with MS clamps , bolts , and nuts of approved size for HT 25 cms x 20 cms including taking down of old one complete all as specified and directed by Engr-in-Charge.
50Material and labour straight through cable jointing kit cold shrinkable 1100 volts grade cable for out door suitable for 3.5 core 95 to 120 sqmmXLPE armoured aluminium conductor including taking down of old one complete all as specified and directed by Engr-in-Charge.
51Material and labour straight through cable jointing kit cold shrinkable 1100 volts grade cable for out door suitable for 3.5 core 50-70 sqmmXLPE armoured aluminium conductorincluding taking down of old one complete all as specified and directed by Engr-in-Charge.
52Pruning of tree branches and making clear LT/HT line to the minimum distace of 1.8 mtrs all arround complete all as specified and directed by Engr-in-Charge.
53(a) For 3/4 conductors
54(b) For 5/6 conductors
55Amount of credit of Rs. 32305.00 for retrived old material as mentioned in Schedule "A" section-II of tender document in pdf form, will be deducted offline while acceptence of tender.