Repair / Replacement Of Apfc Panel, Conventional And Chemical Earthings, Dbs And Allied Works At Af Stn Udhampur Repair / Replacement Of Apfc Panel, Conventional And Chemical Earthings, Dbs And Allied Works At Af Stn Udhampur, AF STATION UDHAMPUR-Jammu And Kashmir

Military Engineer Services-MES has published Repair / Replacement Of Apfc Panel, Conventional And Chemical Earthings, Dbs And Allied Works At Af Stn Udhampur Repair / Replacement Of Apfc Panel, Conventional And Chemical Earthings, Dbs And Allied Works At Af Stn Udhampur. Submission Date for this Tender is 04-09-2021. Electrification Work Tenders in AF STATION UDHAMPUR Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

28784799
Corrigendum : Repair / Replacement Of Apfc Panel, Conventional And Chemical Earthings, Dbs And Allied Works At Af Stn Udhampur Repair / Replacement Of Apfc Panel, Conventional And Chemical Earthings, Dbs And Allied Works At Af Stn Udhampur
Open Tender
Indian
Jammu And Kashmir
AF STATION UDHAMPUR
04-09-2021

Tender Details

Repair / Replacement Of Apfc Panel, Conventional And Chemical Earthings, Dbs And Allied Works At Af Stn Udhampur Repair / Replacement Of Apfc Panel, Conventional And Chemical Earthings, Dbs And Allied Works At Af Stn Udhampur

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 17-Aug-2021 CERTAIN AMENDMENT IN BOQ AND APPX A TO NIT Other 28-08-2021
2 28-Aug-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 04-09-2021
3 03-Sep-2021 CERTAIN AMENDMENT IN BOQ Other 04-09-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 70000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work :REPAIR/REPLACEMENT OF APFC PANEL, CONVENTIONAL AND CHEMICAL EARTHINGS, DBs AND ALLIED WORKS AT AF STATION UDHAMPUR
Sl. No. Item Description
1M&L for in replacement of Varlogic APFC relays- classic range RT6,6 step ,440 volts,5 Amps Make : Schneider -electric,cat part No. 51207 or equivalent approved model in Legrand/ C&S complete all as specified and directed.
2M&L for in replacement ofcapacitor duty contactor (AC coil),nominal reactive power 440 volts, 3 phase , 50 Hz of capacity 12.5 KVAR with auxilliary contacts (1 NO+2NC) Make : Schneider -electric,cat part No. LC1DFK* or equivalent approved model in Legrand/ ABB/ C&S complete all as specified and directed.
3M&L for in replacement ofcapacitor duty contactor (AC coil),nominal reactive power 440 volts, 3 phase , 50 Hz of capacity 25 KVAR with auxilliary contacts (1 NO+1NC) Make : Schneider -electric,cat part No. LC1DMK11*C or equivalent approved model in Legrand/ ABB/ C&S complete all as specified and directed.
4M&L for in replacement ofcapacitor duty contactor (AC coil),nominal reactive power 440 volts, 3 phase , 50 Hz of capacity 40 KVAR with auxilliary contacts (1 NO+2NC) including taking down old. Make : Schneider -electric,cat part No. LC1DTK*C or equivalent approved model in Legrand/ ABB/ C&S complete all as specified and directed.
5M&L for in replacement ofcapacitor duty contactor (AC coil),with damping resistors and block make poles ,nominal reactive power 440 volts, 3 phase , 50 Hz of capacity 60 KVAR with auxilliary contacts (1 NO+2NC) Make : Schneider -electric,cat part No. LC1DWK*C or equivalent approved model in Legrand/ ABB/ C&S complete all as specified and directed.
6M&L for in replacement of three phase voltmeter CI0.5as per IEC 61010-1,50 HzAC,LED indicators complete . Make: : Schneider -electric,cat part No. METSEDDM3210 or equivalent approved model in Legrand/ ABB/ C&S complete all as specified and directed.
7M&L for in replacement of three phase Ammeter CI0.5as per IEC 61010-1,50 HzAC,LED indicators complete . Make: : Schneider -electric,cat part No. METSEDDM3110 or equivalent approved model in Legrand/ ABB/ C&S complete all as specified and directed.
8M&L for in replacement of MPP heavy duty can type, power capacitors 3 phase 12.5 kVAr,440 volts ,50 Hz complete all as specified and directed.Make : Schneider -electric, /ABB/ Legrand/ C&S
9M&L for in replacement of MPP heavy duty can type , power capacitors 3 phase 5 kVAr,440 volts ,50 Hz complete all as specified and directed by Engineer-in Charge make : Schneider -electric,cat part no.MEHVCHDY050A44or equivalent approved model in Legrand/ ABB/ C&S complete all as specified and directed.
10M&L for in replacement of Alternating current miniature circuit breakers c curve type of capacity 10 amps, tripple pole complete all as specified and directed.
11M&L for in replacement of non illuminated pushbuttonturn to release of dia of head40 mm ,type of contact NC colour red complete all as specified and directed.
12M&L for in replacement of Alternating current miniature circuit breakers c curve type of capacity 25 amps, tripple pole complete all as specified and directed. Make : Schneider /ABB/ Legrand/ C&S
13M&L for in replacement of Alternating current miniature circuit breakers c curve type of capacity 32 amps, tripple pole complete all as specified and directed .Make : Schneider /ABB/ Legrand/ C&S
14M&L for in replacement of Alternating current miniature circuit breakers c curve type of capacity 50 amps, tripple pole complete all as specified and directed.Make : Schneider /ABB/ Legrand/ C&S
15M&L for in replacement of Alternating current miniature circuit breakers c curve type of capacity 63 amps, tripple pole complete all as specified and directed. Make : Schneider /ABB/ Legrand/ C&S
16M&L for in replacement of pilot lights direct integral LED of 230 volts ,colour redcomplete all as specified and directed.
17M&L for in replacement of pilot lights direct integral LED of 230 volts ,colour green complete all as specified and directed.
18M&L for standard extended rotary handle for 100/160/250 amper complete all as specified and directed.
19M&L for Compact type Moulded case circuit breakers with micrologic 2.3 of capacity 400 amps with protection, lcs = 100% Icu as per IEC60947-2 complete all as per specified and directed by Engineer including taking down old Make : Schneider - electrical Model No : NSX400N or equivalent approved model in Legrand /ABB/ C&S complete all as specified and directed.
20M&L for compact type Moulded case circuit breakers with micrologic 2.3 of capacity 250 amps with protection, lcs = 100% Icu as per IEC60947-2 including taking down old Make : Schneider - electric Model No : NSX250N or equivalent approved model in Legrand/ ABB/ C&S complete all as specified and directed.
21M&L for Compact type Moulded case circuit breakers with TMD of capacity 160 amps with protection, lcs = 100% as per IEC60947-2 including taking down old Make : Schneider - electric Model No NSX160N or equivalent approved model in Legrand/ ABB/ C&S complete all as specified and directed
22M&L for Easypact type Moulded case circuit breakers with TMD of capacity 100 amps with protection as per IEC60947-2 including taking down old Make : Schneider - electric Model No : CVS100B or equivalent approved model in Legrand/ ABB/ C&S complete all as specified and directed.
23Disconnecting and taking down old unserviceable and M&L for single core stranded copper conductor cable of size 150 sqmm FR type 1.1 KV complete all as specified and directed. Make : Polycab/ Finolex/ Havells
24Disconnecting and taking down old unserviceable and M&L for Lugs of size 150 sqmm of made copper complete all as specified and directed
25Disconnecting and taking down old unserviceable and M&L for wall mount sensors neo C-metro 200 degrees including all accessories fixed by board or wall and electrically connection complete all as specified and directed.
26M&L in replacement for 12 pin/ 14 pin power relay with insulator base for wall mounting sensors including wiring complete all as specified and directed
27M&L in replacement for Power contractor 4 pole 315 amps with AC/DC coil, 415 volts, 50 Hz including high electrical life conformity to international standards IES complete all as specified and directed
28M&L in replacement for Moulded case circuit breakers 4 pole, 415 volts, adjustable type 320/350 amps with breaking capacity 36KA, 50 Hz complete all as specified and directed
29M&L in replacement for Moulded case circuit breakers 4 pole, 415 volts, adjustable type 250 amps with breaking capacity 36 KA, 50 Hz complete all as specified and directed
30M&L in replacement for Moulded case circuit breakers 4 pole, 415 volts, adjustable type 160 amps with beaking capacity 25 KA, 50 Hz complete all as specified and directed
31M&L for earthing complete with copper plate of size 600x600x3.15mm thick as earth electrode burried directly in ground (earth pit not less than 2.25 Meter deep below ground level) with top edge of the earth plate not less than 1.5mtr below ground level using copper strip 20x3mm dia as earth continuity conductor connected to earth plate by means of GI thimbles nuts bolts washers incl jointing of earth electrode and earth wire by means of welding, all as directed including providing earth strip protection pipe GI light grade 32mm dia from earth plate to main switch board/ panel, watering pipe 20mm dia with wire mesh and funnel at top, earth pit and pit cover made of MS sheet 2mm thick duly fixed to angle iron frame with hinges of appropriate size by welding and having locking arrangement, adequate quantity of charcoal dust and salt all around the earth plate, earth work in any type of soil, removing surplus excavated material all as required at site and specified in EP No 5 of SSR Part 1 1991 complete all as specified and directed by Engineer-in-Charge including dismantling existing earthing. Notes: (a) Copper strip beyond test point shall be measured and paid for separately. (b) Earthing resistance result shall be less than 3 ? .If the result comes more than 3 ? the contractor shall carry out the earthing at separate location/site given by the Engr-in-Charge after taking out of earth electrode without any extra cost to the deptt. (c) Test point terminal block shall be measured and paid for separately. (d) The contractor"s quoted rates shall be deemed to include for dismantling/taking down of old unserviceable earthing of any type and making good the disturbed surfaces and nothing extra shall be admissible on this account. (e) Any other fittings/fixtures if technically required for achieving desired results (if not included above) shall be provided by the contractor without any extra cost to the Govt. (f) If mother soil is not available then mother soil wil be provided by contractor from outside source without any extra cost to the Govt.
32Test point terminal block made of gun metal or phosphorous bronze size 75 x 75 x 25mm drilled and screwed including 3 Nos. 8mm dia 25mm long hexagonal head screws complete all as specified and directed including taking down old unserviceable.
33Maintenance free safe earthing system (set of three electrodes to be used as grid for equipment earthing), each pit complete with 01 Number UL 467 approved/ CPRI tested copper bonded ( copper cladded earth rod with 250 microns of copper cladding) earth rod 17.2mm dia. 3000 mm long electrode buried in ground to bore holes 120 mm dia. vertically to a depthnot less than 3.50 Mtr deep below ground level with top edge of earth electrode at a depth not less than 500 mm below normal ground level, provision of copper bus bar of size 200mm x 25mm x 6mm for inter connection with copper earth lead strip 25mm x 3mm and further connected to test point terminal block all as directed. Each earth pit shall include minimum 50 Kg (two bags of 25 Kg each) NABL Lab Certified back fill and 06 kg (two containers of 03 kg each) NABL lab certified conductive gel(LOHM-EG-03) compound for fillingbore holes with mother soil mixed in 1:3 ratio (one part of back fill compound and three parts of mother soil), so as to achieve earth resistance below 1 Ohm including excavation of polypit chamber with polyplastic pit cover (cost of polypit chamber with polyplastic pit cover shall be deemed to be included in the rate quoted) complete all as specified and as directed by Engineer-in-Charge including dismantling old unserviceable. Makes : ASHLOK SAFE EARTHING/ PRAGATI/ DHRUVA TECHNOLOGIES PVT LTD/ASHOK SAFE EARTHING/PRAGATI Notes :(a) Copper strip beyond test point shall be measured and paid separately. (b) Earthing resistance result shall be less than 1 ? .If the result comes more than 1 ?, the contractor shall carry out the earthing at separate location /site given by the Engr-in-Charge after taking out of earth electrode without any extra cost to the deptt. (c) Contractor shall give guarantee of minimum 5 years for the earthing carried out by him. (d) Contractor shall submit the purchase vouchers of material purchased and undertaking obtained from the agency executing the earthing certifying that the earthings have been provided by them for the entire quantity of earthings on non-judicial stamped paper worth Rupees 100/-. (e) Test point terminal block shall be measured and paid separately. (f) The contractor"s quoted rates shall be deemed to include for dismantling/taking down of old unserviceable earthing of any type and making good the disturbed surfaces and nothing extra shall be admissible on this account. (g) Guarantee money :- An amount equal to 5% of the quoted amount against earthing catered under item No. 32 of BOQ will be retained till satisfactory completion of perfomance guarantee period of five years. Contractor can give BGB or interest bearing deposit receipt from any nationalized/scheduled bank for the amount failing which the said amount shall be deducted from final RAR/final bill of contractor. (h) Any other fittings/fixtures if technically required for acheiving desired results (if not included above) shall be provided by the contractor without any extra cost to the Govt. (j) The rates quoted by the contractor shall be deemed to include for three electrodes (in three pits separately) with three polypit chambers (minimum 3 metre apart) with polyplastic pit covers.
34Maintenance free safe earthing system (set of one electrodes to be used as grid for equipment earthing), each pit complete with 01 Number UL 467 approved/ CPRI tested copper bonded ( copper cladded earth rod with 250 microns of copper cladding) earth rod 17.2mm dia. 3000 mm long electrode buried in ground to bore holes 120 mm dia. vertically to a depthnot less than 3.50 Mtr deep below ground level with top edge of earth electrode at a depth not less than 500 mm below normal ground level, provision of copper bus bar of size 200mm x 25mm x 6mm for inter connection with copper earth lead strip 25mm x 3mm and further connected to test point terminal block all as directed. Each earth pit shall include minimum 50 Kg (two bags of 25 Kg each) NABL Lab Certified back fill and 06 kg (two containers of 03 kg each) NABL lab certified conductive gel(LOHM-EG-03) compound for fillingbore holes with mother soil mixed in 1:3 ratio (one part of back fill compound and three parts of mother soil), so as to achieve earth resistance below 1 Ohm including excavation of polypit chamber with polyplastic pit cover (cost of polypit chamber with polyplastic pit cover shall be deemed to be included in the rate quoted) complete all as specified and as directed by Engineer-in-Charge including dismantling old unserviceable. Makes : ASHLOK SAFE EARTHING/ PRAGATI/ DHRUVA TECHNOLOGIES PVT LTD Notes :(a) Copper strip beyond test point shall be measured and paid separately. (b) Earthing resistance result shall be less than 1 ? .If the result comes more than 1 ?, the contractor shall carry out the earthing at separate location /site given by the Engr-in-Charge after taking out of earth electrode without any extra cost to the deptt. (c) Contractor shall give guarantee of minimum 5 years for the earthing carried out by him. (d) Contractor shall submit the purchase vouchers of material purchased and undertaking obtained from the agency executing the earthing certifying that the earthings have been provided by them for the entire quantity of earthings on non-judicial stamped paper worth Rupees 100/-. (e) Test point terminal block shall be measured and paid separately. (f) The contractor"s quoted rates shall be deemed to include for dismantling/taking down of old unserviceable earthing of any type and making good the disturbed surfaces and nothing extra shall be admissible on this account. (g) Guarantee money :- An amount equal to 5% of the quoted amount against earthing catered under item No. 32 of BOQ will be retained till satisfactory completion of perfomance guarantee period of five years. Contractor can give BGB or interest bearing deposit receipt from any nationalized/scheduled bank for the amount failing which the said amount shall be deducted from final RAR/final bill of contractor. (h) Any other fittings/fixtures if technically required for acheiving desired results (if not included above) shall be provided by the contractor without any extra cost to the Govt. (j) The rates quoted by the contractor shall be deemed to include for three electrodes (in three pits separately) with three polypit chambers (minimum 3 metre apart) with polyplastic pit covers.
35Copper strip 20 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground
36M&L for removing ofscrap material in pipe of solar system by iron rod including brazing of copper or branze flanged withrubber flanged, nut ,boltscompletejob all as per Engineer-in Charge
37M&L in repair for Geyser element of solar water heater of capacity 1500 wattcomplete all as specified and directed.
38M&L in repair for Geyser element of solar water heater of capacity 2000 watt complete all as specified and directed.
39M&L in repair for Geyser element of solar water heater of capacity 3000 watt complete all as specified and directed.
40Disconnecting and taking down old unserviceable protection panel of any description and capacity and Supply, installation, testing and commissioning of Transformer protection control for 160 KVA transformer having di/do with user define input for emergency interrupts alongwith protections against Overload, earth fault protection, phase reversal, automatic phase correctgor, high voltage, under voltage, short circuit and capable sensing for Transformer oil temperature by mercury switch with optional machine interference for efficient maintenance.The Panel shall be feagtured with Phase indication, display, power factor, amperemeter, frequency, voltage, forward/reverse sequence indication, supply fault buzzer, transformer temperature trip indication, earth fault indication, on off trip indications of brfeaker and user selectable trips selector switches including suitable copper bus bar with enclouser completge all as specified and directed by Engineer-in-Charge.Make : DVEPL Cat Part No TCPFPDV160S or equivalent approved model in Legrand/ ABB/ C&S
41Disconnecting and taking down old unserviceable protection panel of any description and capacity and Supply, installation, testing and commissioning of Transformer protection control for 100 KVA transformer having di/do with user define input for emergency interrupts alongwith protections against Overload, earth fault protection, phase reversal, automatic phase correctgor, high voltage, under voltage, short circuit and capable sensing for Transformer oil temperature by mercury switch with optional machine interference for efficient maintenance.The Panel shall be feagtured with Phase indication, display, power factor, amperemeter, frequency, voltage, forward/reverse sequence indication, supply fault buzzer, transformer temperature trip indication, earth fault indication, on off trip indications of brfeaker and user selectable trips selector switches including suitable copper bus bar with enclouser completge all as specified and directed by Engineer-in-Charge.Make : DVEPL Cat Part No TCPFPDV160S or equivalent approved model in Legrand/ ABB/ C&S
42Disconnecting and taking down old unserviceable protection panel of any description and capacity and Supply, installation, testing and commissioning of Transformer protection control for 63 KVA transformer having di/do with user define input for emergency interrupts alongwith protections against Overload, earth fault protection, phase reversal, automatic phase correctgor, high voltage, under voltage, short circuit and capable sensing for Transformer oil temperature by mercury switch with optional machine interference for efficient maintenance.The Panel shall be feagtured with Phase indication, display, power factor, amperemeter, frequency, voltage, forward/reverse sequence indication, supply fault buzzer, transformer temperature trip indication, earth fault indication, on off trip indications of brfeaker and user selectable trips selector switches including suitable copper bus bar with enclouser completge all as specified and directed by Engineer-in-Charge.Make : DVEPL Cat Part No TCPFPDV160S or equivalent approved model in Legrand/ ABB/ C&S