| 1 | P & Laying XLPE insulated IS:7098/II/85 of Group 1 and approved make H.T. cable for working voltage 11 K.V. Earthed direct in ground including excavation of 30 cm x100 cm size trench, 25 cm layer of rivers and, IInd class bricks covering, refilling earth, compaction of earth, making necessary connection testing etc. as required of size. 3 core 185.0 Sq.mm |
| 2 | Providing & making heat shrinkable typeindoor/outdoor/straight through terminations/joint kitof Group1 and approved make suitable for XLPEinsulated 11 KV / 33 KV cable, with requiredcomponents, prepration of cable ends,testing etc. asrequired of following sizes. 11 KV Straight Through Joint Kit. 3 core 120/150/185/225 Sq.mm |
| 3 | Providing & making heat shrinkable typeindoor/outdoor/straight through terminations/joint kitof Group1 and approved make suitable for XLPEinsulated 11 KV / 33 KV cable, with requiredcomponents, prepration of cable ends,testing etc. asrequired of following sizes. 33 KV Straight Through Joint Kit. 3 core 240/400 Sq.mm |
| 4 | S & F of IP - 65 protected impact resistantpolycarbonate / Polysterene enclosures of followingsizes. 300 x 450 x 132 mm |
| 5 | S & F of IP - 65 protected impact resistantpolycarbonate / Polysterene enclosures of followingsizes. 320 x 440 x 179 mm |
| 6 | S & F of IP - 65 protected impact resistantpolycarbonate / Polysterene enclosures of followingsizes. 320 x 640 x 179 mm |
| 7 | Supply and erection of P.C.C./R.C.C. pole as per REC manual no 15/1979 conforming to IS: 2905/1966 as per requirement of sec3 in alignment, including excavation of pit and back filling with stone aggregate/boulders and soil in 0.45m consolidating each deposited layer of 0.45m by ramming and watering etc complete in all respect. 8.0 Mtr long (200 Kg ) as per Discom specification |
| 8 | P / L of Double wall corrugated HDPE pipe confirming toIS : 14930 P - 1 & 2 with HDPE Coupler at 1 mtr. Depthbelow the ground for laying cable including making thetrench and back filling , compaction of earth as requiredof Gemini or IS:14930 marked make.Outer Dia. / Inner dia. 90 / 76 mm |
| 9 | Supplying and making one end termination with heavyduty single compression brass gland SIBG type, heavyduty aluminium lugs duly crimped with crimping tool,PVC tape etc for following size of Armoured PVCinsulated & PVC sheathed/ XLPE aluminium conductorcable of 1100 volt grade as required of size. 3 x 185.0 sq.mm |
| 10 | P&F following size aluminium bus bar on insulators atapproved spacing in existing bus bar chamber includingmaking holes etc. as required. 50 x 5 mm |
| 11 | S & Laying following size earth wire/strip in horizontalor vertical run in ground/surface/recess includingriveting, soldering, saddles, making connection etc. asrequired. 8 SWG G.I. ( Hot Dipped ) Wire |
| 12 | S & Making Heat shrinkable type outdoor straightthrough joint for following size of PVC/ XLPE insulatedaluminium conductor cable of 1.1 KV grade includingcost of compound, sleeves etc. as required. 3.5 x 185.0 sq.mm |
| 13 | S & Making Heat shrinkable type outdoor straightthrough joint for following size of PVC/ XLPE insulatedaluminium conductor cable of 1.1 KV grade includingcost of compound, sleeves etc. as required. 4 x 16.0 sq.mm |
| 14 | P/Laying P.V.C./XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor of IS:1554 P-I/IS:7098 P-I of Group 1of approved make in ground as per IS:1255 including excavation of 30 cmx75 cm size trench, 25 cm thick underlayer of sand, IInd class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size 185 sq. mm. 3.5 core |
| 15 | free standing floor mounted dust and vermin proof compartmentalised cubical panel made out of CRCA sheet , required hardware , duly treated for derusting in 7 tank process with dephosphating and with powder coating on both side of panel in desired shade The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness , separate detachable gland plate M.S. base channel , hinged door with locking arrangement for equipment / switchgear. Thickness of sheet shall not be less than 1.6 mm upto 600 mm length/width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required. Sidewalls and cable alley compartments having bolted type doors with / without detachable extension type structure.(only outer area on all sides shall be measured & panel to be fabricated from CPRI approved fabricator) |