Repairs And Maint Of Internal Wiring And Summer Appliances Alongwith Connected Items At Af Stn Ferozepur Under Ge (Af) Bhisiana Repairs And Maint Of Internal Wiring And Summer Appliances Alongwith Connected Items At Af Stn Ferozepur Under Ge (Af) Bhisiana, GE (AF) Bhisiana-Punjab

Military Engineer Services-MES has published Repairs And Maint Of Internal Wiring And Summer Appliances Alongwith Connected Items At Af Stn Ferozepur Under Ge (Af) Bhisiana Repairs And Maint Of Internal Wiring And Summer Appliances Alongwith Connected Items At Af Stn Ferozepur Under Ge (Af) Bhisiana. Submission Date for this Tender is 30-08-2021. Electrification Work Tenders in GE (AF) Bhisiana Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

28726177
Corrigendum : Repairs And Maint Of Internal Wiring And Summer Appliances Alongwith Connected Items At Af Stn Ferozepur Under Ge (Af) Bhisiana Repairs And Maint Of Internal Wiring And Summer Appliances Alongwith Connected Items At Af Stn Ferozepur Under Ge (Af) Bhisiana
Open Tender
Indian
Punjab
GE (AF) Bhisiana
30-08-2021

Tender Details

Repairs And Maint Of Internal Wiring And Summer Appliances Alongwith Connected Items At Af Stn Ferozepur Under Ge (Af) Bhisiana Repairs And Maint Of Internal Wiring And Summer Appliances Alongwith Connected Items At Af Stn Ferozepur Under Ge (Af) Bhisiana

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 12-Aug-2021 CORRIGENDUM MAKE Other 23-08-2021
2 23-Aug-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 30-08-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 16000.0 /-
Tender Value
INR 8 Lakhs /-

BOQ Items

NAME OF WORK : REPAIR AND MAINT OF INTERNAL WIRING AND SUMMER APPLIANCES ALONGWITH CONNECTED ITEMS AT AF STN FEROZEPUR UNDER GE (AF) BHISIANA
Sl. No. Item Description
1SCH "A", PART-I
2S&F incl taking down 1X5 watt wall mounted, new generation LED batten for multipurpose application with LED Rod , made from exturded plastic housing, polycarbonate diffuser including all fixing accessories & connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed by Engr-in-Charge.
3S&F incl taking down1X18/20 wattwall mounted, new generationLEDbatten for multipurpose application with LED Rod , made from exturded Plastic housing, polycarbonate diffuser including all fixing accessories & connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed by Engr-in-Charge.
4Supply and fix incl taking down new generation energy saving 9/10 watt LED bulk head (porch light fitting) made of plasitic housing with opal diffuser complete all as specified and directed by Engr-in-Charge.
5Taking down carefully existing aluminum/copper point wiring including wooden batten or taking out from existing complete (light/fan/socket) including all fittings such as ceiling rose, switches, regulators, sockets etc and making good distrubed surface of wall, floor & ceiling etc complete all as specified and directed.
6M&L for concealed point wiring complete with 1.5 Sqmm single core multistranded copper conductor PVC insulated and unsheathedcable 1100 volts grade drawn through and including non metallic rigid PVC conduit, medium grade minimum 19/20/25mm dia ISI marked and conduit accessories fixed concealed in wall/ceiling/roof etc with sunken type pressed steel/welded MS terminal boxes made out of 1.6 mm MS sheet, 3mm thick laminated sheath top cover for mounting of fittings, switches, sockets outlets, regulators etc complete including provisining of 1.5 sqmm PVC insulatedunsheathedcable 1100 volt grade with multi stranded copper conductor to common earth and connected to earth dolly for the following :-
7One light point, ceiling fan & Exhaust fan controlled by one switch 5/6 amp one way.
8One bell point controlled by one switch 5/6 amp one way.
9One 3 pin socket5/6 amp on the same board.
10One 3 pinsocket5/6 amp on the independent board.
11All as Per Item No 6 here in before but point wiring with 2.5 sqmm single core multi stranded copper conductor PVC insulated & unsheathedcable 1100 volt grade and 1.5 sqmm PVC insulated and unsheathed cable 1100 volt grade with multi stranded copper conductor for earth wire for 15/16 amp multi purpose socket combination point on independent board.
12S&F switch piano flush type single pole 1 way 5/6 A, complete all as specified and directed.
13S&F switch piano flush type single pole 1 way 15/16 A,complete all as specified and directed.
14S&F bell push flush type single pole 1 way 5/6 A, complete all as specified and directed.
15S&F bell AC 230 Volts single pole ding dong type complete all as specified and directed.
16S&F socket outlet 2 in 1, 3 Pin 5 Amps, flush type complete all as specified and directed.
17S&F socket outlet 3 pin,15 Amps flush type complete all as specified and directed.
18S&F stepped type electronic fan regulator flush typecomplete all as specified and directed.
19S&F modular white cover plate with frame, 1 module.
20S&F modular white cover plate with frame, 3 module.
21S&F modular white cover plate with frame, 6 module.
22S&F modular white cover plate with frame, 8 module.
23M&L modular switch 1 way 6 A, 1 module.
24M&L modular bell push switch, 6 A, 1 module.
25M&L modular socket, 6A-2/3 pin combined, 2 module.
26M&L modular switch16 Amps, 1 module.
27M&L modular socket16 Amps, 6 pin, 2 module.
28S&F modular fan step regulator, 120W - 1.
29S&F ceiling rose Polycarbonate, Isolated body surface type bakelite 65x50 mm three terminal complete all as specified and directed.
30M&L for Submain wiring with two single core of 4 Sqmm and one single core of 2.5 sqmm as earth wire with multi stranded copper conductor cable PVC (FR) insulated unsheathed cable 1100 volts gradedrawn through in PVC Conduit (ISI Marked) of size 20/25 mm dia and the conduits accessories as in repairs complete including making good the distrubed surface to match the existing surface.
31M&L for Submain wiring with two single core of 6 Sqmm and one single core of 4.0 sqmm as earth wire with multi stranded copper conductor cable PVC (FR) insulated unsheathed cable 1100 volts gradedrawn through in PVC Conduit (ISI Marked) of size 20/25 mm dia and the conduits accessories as in repairs complete including making good the distrubed surface to match the existing surface.
32Disconnecting care fully old unserviceable main DB board etc. from site complete with wooden board and making good the disturbed surface complete all as specified and directed.
33S&F Tripple pole and neutral (TPN) 4 way MCB distribution box double door powder coated sheet metal encloser415 volts TPN including 200 Amps rated bus bar complete all as specified and directed.
34S&F Single pole and neutral (SPN) 8 way MCB distribution box double door powder coated sheet metal encloser240 volts including 200 Amps rated bus bar complete all as specified and directed.
35S&F of Isolator Three Pole & Neutral(TPN) 415 Volt 100 Amp, rupturing capacity 10 KA complete all as specified and directed.
36S&F of Isolator Three pole & Neutral(TPN) 415 Volt 63 Amp, rupturing capacity 10 KA complete all as specified and directed.
37S&F of MCB single pole (SP) B curve 240 Volt 6 to 32 Amp, rupturing capacity 10 KA complete all as specified and directed.
38S&F of MCB single pole & Neutral (SPN)B curve 240 Volt 40 Amp, rupturing capacity 10 KA complete all as specified and directed.
39S&F MCB DB TPN 4 Way vertical tupe factory made IP 43 protection class metal double doorwith Shrouded Neutral Bar & Pan assembly with connecting link complete including provision ofMCCB upto 125Aafter dismantling old one.
40Sypply and fix MCCB 125Amp 3 pole50 Hz 415 volt thermal magnetic release type with rupturing cap 16 KA complete all as specified and directed by Engr-in-Charge.
41Sypply and fix MCCB 63/100 Amp 3 pole50 Hz 415 volt thermal magnetic release type with rupturing cap 16 KA complete all as specified and directed by Engr-in-Charge.
42M&L for earthing complete with galvanized iron earth plate electrode 60 cm x 60 cm x 6.30 mm thick, buried directly in ground (earth pit not less than 2.25 meters deep below normal ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level connected to galvanized earth lead wire 4.00 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electric plate No 5 of SSR Part-I connected to continuous earth wire on main switch board all as specified or indicated and testing on completion including provision of earth wire protection by 15 mm dia medium grade GI pipe and watering pipe shall be 20 mm bore, medium grade including excavation & earth work,PCC pit with RCC cover, charcoal salt funnel, GI wire up to 7.5 mtrs length complete all as specified and directed.
43Supply and fix 36/40 watt recessed mounted LED luminaire suitable for armstrong/grid ceiling with super bright LED fittings with connector block etc with short circuit protection, open protection, reverse polarity protection, high voltage protection complete with all accessories pre wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size.
44S&F 7 watt LED Bulb with base cap B22 type along with angle holder complete all as specified and directed by Engr-in-Charge.
45Supply and fix 45 W IP 65 LED Security light for building luminaire comprising of die cast aluminium housing with weather proof gasket for lamp & driver compartment with system wattage of 45 W. The LED make must be of CREE/NICHIA/OSRAM with 120 degree view angle, > 120 lumen/watt, lumen maintenance > 70 % at 50,000 hrs, colour temperature of 5000-6500K,>70 color rendering and LM 80 test compliance . The driver must be integral APFC and constant current type having THD <15% and power factor > 0.95 with short circuit protection, open circuit protection, reverse polarity protection, high voltage protection, protection against 10 KV high surges and comply to IEC 60598-1 , IEC 61000-3-2, IEC 61547. The luminaire must have secondary optics with perfectly matched lens for better light control complete all as specified and directed by Engr-in-Charge.
46CollectingFans from Air Force Station Ferozepur, ceiling/exhaust/wall mounted fans of any size and any make/model, moving to reputed workshop as directed by GE/Engineer-in-Charge, dismantaling the same, cutting and removing the old defective/burnt out winding, cleaning the core of the fan motor, re-winding the fan motor by using machine with supper enemelled copper winding wire and using insulating materials, varnishing the assembly and re-assembling the fan including testing etc. complete all as specified and directed by Engineer-in-Charge. MAKE of winding wire : Devi Dayal/Chetak/HTP Thulax. Note : All defective/unserviceable parts/items other than winding wire, varnish and insulating material, shall be measured separately and paid for under respective item of this schedule.
47All as above item here-in-before but for ceiling fans any type/any size.
48All as above item here-in-before but for exhaust fans of 230/300 mm sweep any type complete all as specified and directed by Engineer-in-Charge.
49All as above item here-in-before but for exhaust fans of 400/450 mm sweep any type complete all as specified and directed by Engr-in-Charge.
50S&F in repair Capacitor 3.15 mfd fixed in replacement complete all as specified and directed by Engineer-in-Charge.
51S&F in repair Capacitor 4mfd fixed in replacement complete all as specified and directed by Engineer-in-Charge.
52M&L for painting with two coats of white synthetic enamel paint and marked MES No by black permanent marker all as directed by Engr-in-Charge.
53Taking down carefully Water Heater (Geyser) any capacity any Make after removing electric & water connections from existing system for carrying out repairs (Repairs will be measured and paid separately) and refixing the same after carrying out necessary repairs to original place all as directed by Engineer-in-Charge.
54Removing existing hot & cold water Copper/PVC flexible pipe connection from geyser and S&F new brass chromium plated water pipe with brass nut and washers of good quality about 45cm long in hot & cold water connections and connecting complete.
55Replacement of heating element 2 kW for 25/35 ltrs capacity geyser ISI marked.
56Replacement of thermo static switch of geyser.
57Detecting the leakage from geyser and arresting the same by brazing/soldering etc all as directed by Engr-in-Charge.
58SCH "A", PART-II
59Dismantling old defective/burnt sealed compressor of Refrigerator 165 to 310 Ltrs capacity replacement of the same with manufacture reconditioned compressor including soldering copper pipe with new compressor, charging of refrigerant gas R-134a in the system to its rated capacity, replacement of foundation rubber pad, nut and bolts, including testing on full load etc complete all as specified and as directed by Engineer-in-Charge.
60M&L for cleaning the gas system with anti corrosive solution and recharging the refrigerant gas R-134a with anti moisture substance and replacement of filter along with rectification of leakage system in the refrigerator of capacity 165 to 310 Ltrs including installation at site and testing on full load etc.
61S&F thermostat switch with defrosting system suitable for refrigerator of capacity 165 to 310 Ltrs fixed in repairs complete all as specified and as directed by Engineer-in-Charge.
62S&F starting relay assembly suitable for refrigerator of capacity 165 to 310 Ltr fixed in repairs complete all as specified and as directed by Engineer-in-Charge.
63S&F Plastic Ice tray suitable for refrigerator of capacity 165 to 310 Ltr fixed in replacement complete all as specified and as directed by Engineer-in-Charge.
64S&F Vegetable tray with suitable glass cover suitable for refrigerator of capacity165 to 310 Ltr fixed in replacement complete all as specified and as directed by Engineer-in-Charge.
65S&F Lamp assembly including lamp suitable for refrigerator of capacity165 to 310 Ltr fixed in replacement complete all as specified and as directed by Engineer-in-Charge.
66S&F Aluminum freezer suitable for refrigerator ofcapacity165 to 310 Ltr fixed in replacement complete all as specified and as directed by Engineer-in-Charge.
67S&F Plastic Chowki of superior quality suitable for refrigerator ofcapacity 165 to 310 Ltr fixed in replacement complete all as specified and as directed by Engineer-in-Charge.
68S&F in replacement fan blade for Water cooler of any capacity all as specified and directed by Engr-in-Charge.
69Repair to Voltage stabilizer of capacity 02-05 KVA Single phase including replacement of circuit plate, starting relay, voltmeter, fuse terminal box with fuse carrier, rewinding the main transformer with copper of existing size and repair / replacement time delay relay (1-2 Min) built-in type designed for low cut off 140/160 volt, high cut off 260/280 volt on single phase, 50 cycle AC supply etc complete all as specified and as directed by Engineer-in-Charge.
70Repair/replacement of condensing coil assembly complete suitable for Refrigerator of capacity 165 Ltrs to 310 Ltrs complete and recharging the refrigerant R-134 and testing all as specified and as directed by Engineer-in-Charge.
71Dismantling/taking down window type AC 1.5/2 Ton from site, opening, cleaning all dust with the help of air blower including cleaning of condenser and evaporator coil with Soap solution, removing the dust with the help of wire brush, repairing & proper fixing of wiring including thimbles and replacelment of Air filter Nylon and reinstalling AC in thesame Location and made air tight to opening with thermacol material all around the window type AC complete and testing on full load etc complete all as specified and as directed by Engineer-in-Charge.
72Dismantling/taking down Split type AC 1.5/2 Ton from site, opening, cleaning all dust with the help of air blower including cleaning of condenser and evaporator coil with Soap solution, removing the dust with the help of wire brush, repairing & proper fixing of wiring including thimbles and replacement of air filter Nylon and reinstalling AC in the same location both unit outdoor/indoor unit complete and testing on full load etc complete all as specified and as directed by Engineer-in- Charge.
73S&F starting relay assembly including cover and clips for air conditioner window type 1.5/2 Ton capacity fixed in replacement complete all as specified and as directed by Engineer-in-Charge.
74S&F running capacitor 36/45 mfd suitable for 1.5/2 Ton capacity of window type AC fixed in replacementcomplete all as specified and as directed by Engineer-in-charge.
75S&F capacitor 6 mfd suitable for blower motor, fixed in replacementcomplete all as specified and as directed by Engineer-in-charge.
76S&F selector switch rotary type suitable for window type AC of capacity 1.5 Ton, fixed in replacement complete all as specified and as directed by Engineer-in-Charge.
77S&F thermostat switch assembly suitable for window type AC of capacity 1.5/2 Ton, fixed in replacement complete all as specified and as directed by Engineer-in-Charge.
78Taking down dismantling of old unserviceable defective sealed compressor of Cap 1.5/2 TR of window type AC/split AC and replacement with manufactures reconditioned compressor company make hermatic sealed compressor of Cap 1.5/2 TR by soldering /brazing of copper Tubes and replacement offoundation pads including nut & bolt and washers as required and charging with Refrigerant R-22 to its rated capacityand testing of leakage in the system if any andmaking good, Testing on full load after reinstalling the same.
79S&F in replacement fan blade for window/split AC of 1.5/2.0 TR all as specified and directed by Engr-in-Charge.
80M&L for rewiring of complete window type AC of capacity 1.5 Ton with copper wire single core PVC cable of size 40/0.0076 with necessary sleeves, clip, thimble auto sweep switch etc.
81Supply & Fix cable of 3 core PVC sheathed copper flexible cable of size 70/0.0076 fixed in replacement complete all as specified and directed.
82S&F Blower motor single Phase 230 volts, 50 Hz, 1/5 HP, 900 RPM suitable for window type AC of capacity 1.5 Ton fixed in replacement complete all as specified and directed.
83S&F Filter pad nylon type suitable for window type AC of capacity 1.5 Ton fixed in replacement complete all as specified and directed.
84S&F Evaporator coil assembly complete suitable for window type AC of capacity 1.5 Ton etc complete and recharging the refrigerant R-22 and testing fixed in replacement complete all as specified and directed by Engineer-in-Charge.
85S&F Condensing coil assembly complete suitable for window type AC of capacity 1.5 Ton etc complete and recharging the refrigerant R-22 and testing fixed in replacement complete all as specified and directed by Engineer-in-Charge.
86S&F Front grill assembly complete suitable for window type AC of capacity 1.5 Ton fixed in replacement complete all as specified and as directed by Engineer-in-Charge.
87M&L for cleaning the gas system with anti corrosive solution and recharging the refrigerant Gas R-22 with anti moisture substance and replacement of filter along with rectification of leakage system in the window type AC of capacity 1.5 Ton including installation at site and testing on full load complete all as specified and as directed by Engineer-in-Charge.
88M&L for rewinding of blower motor of window type AC 1.5 Ton capacity single phase 1/5 HP, 900 RPM with super enameled copper wire of existing gauge including replacement of bush and nut and bolts, washer etc complete all as specified and as directed by Engineer-in-Charge.
89S&F Blower andblade assembly complete suitable for blower motor of window type AC of capacity 1.5 Ton fixed in replacement complete all as specified and as directed by Engineer-in-Charge.
90Preparation of old painted surface and applying two coats of Ducco paint by spray gun fully matched with its original colour outside of the window type AC of capacity 1.5/2 Tonincluding before painting removal ofall dust with the help of air blower, sand paper and rubbing with cleaning compound and polishing on painted surface etc complete all as specified and as directed by Engineer-in-Charge.
91M&L for cleaning the gas system with anti corrosive solution and recharging the refrigerant gas R-22 with anti moisture substance and replacement of filter along with rectification of leakage system in the split type AC of capacity 1.5/2 TR including installation at site and testing on full load etc complete all as specified and as directed by Engineer-in-Charge.
92S&F decorated frame of plywood/teak ply of size 70mm wide and 3mm thick duly varnished of good quality, all around the window type AC for air tight and fixing with screws on existing wooden frame complete all as specified and as directed by Engineer-in-charge.
93S&F Insulation to refrigerant pipes of split ACs any make and type complete with suitable size for suction and discharge refrigerant pipes including necessary clamps etc.
94S&F Remote Control complete with all components suitable for window/split type ACs of capacity 1.5/2.0 Ton as per existing make complete all as directed.
95M&L for Copper Pipe Line of size 1/2" for Split type AC of any capacity complete all as specified and directed by Engr-in-Charge.
96M&L for Copper Pipe Line of size 1/4" for Split type AC of any capacity complete all as specified and directed by Engr-in-Charge.
97M&L for Opeaning/Cutting holes in Brick wall suitable for window type AC 2/1.5 Ton and making good disturbed surface area complete with cement plaster and masonary work equired at site and made Air tight to Opeaning with the Thermocoal Material all round the window AC etccomplete all as specified and directed by Engr in Charge.
98S&F Starting relay assembly suitable for Water Cooler of capacity 40/40, 40/80, 60/120, 120/150Ltrs fixed in replacement, complete all as specified and as directed by Engineer-in-Charge.
99S&F Evaporator coil assembly complete suitable for Split type AC of capacity 1.5 Ton etc complete and recharging the refrigerant R-22 and testing fixed in replacement complete all as specified and directedby Engineer-in-Charge.
100S&F Condensing coil assembly complete suitable for window type AC of capacity 1.5 Ton etc complete and recharging the refrigerant R-22 and testing fixed in replacement complete all as specified and directed by Engineer-in-Charge.
101Taking down dismantling unserviceable/defective sealed compressor from water coolers of capacity40/40, 40/80, Ltrs and replacement with reconditioned compressor including soldering/Brazing of copper tubes and fitted with foundation rubber pakts, nuts, bolts, washers etc. cleaning the refrigerant system with gas pressure and charging the refrigerant F in the system to its rated capacity, to check the leakage if any and made good and testing andfull load after etc complete all as specified and as directed by Engineer-in-Charge.
102S&F Blower motor single phase 230 volts, 50 Hz, 1/16 HP, 1250 RPM suitable for water cooler of capacity 40/40/, 40/80, 120/150, & 150/180 Ltrs, fixed in replacement, complete all as specified and as directed by Engineer-in-Charge.
103S&F thermostat switch complete suitable for water cooler etc, fixed in replacement, complete all as specified and as directed by Engineer-in-Charge.
104S&F chromium plated water tap push type suitable for water cooler etc, fixed in replacement, complete all as specified and as directed by Engineer-in-Charge.
105M&L for cleaning the gas system with anti moisture solution and recharging the refrigerant gaswith anti moisture substance and replacement of filter and copper capillary along with rectification of leakage system in the water cooler of any capacity including installation at site and testing on full load etc complete all as specified and as directed by Engineer-in-Charge.
106M&L for writing/marking of SM No /MES No of size 25mm synthetic enamel white paint on the water cooler/desert cooler/Split/window AC of various capacity/Split type AC"s /Window type ACs etc complete all as specified and as directed by Engineer-in-Charge.
107M&L forFan motor single phase 230 volts, 50 Hz, 1/6 HP, 1250 RPM suitable for desert cooler of size 4000/5000 CFM, fixed in replacement ,complete all as specified and as directed by Engineer-in-Charge.
108Supply and fixing in replacement blower motor single Phase 230 volts, 50 Hz, 1/6 HP, 1250 RPM suitable for desert cooler of size 1800/3000 CFM complete all as specified and as directed by Engineer-in-Charge.
109S&F Submersible water pump for desert cooler 230 volts, 50 HZ, speed not less than 1300 RPM including replacement of mounting nut and bolts clamp etc, fixed in replacement, complete all as specified and as directed by Engineer-in-Charge.
110S&F PVC distributor suitable for desert cooler as per sample etc, fixed in replacement, complete all as specified and as directed by Engineer-in-Charge.
111S&F PVC Pipe Heavy duty polythene ISI marked suitable for desert cooler as per sample etc, fixed in replacement, complete all as specified and as directed by Engineer-in-Charge.
112S&F Wooden wool pad as per sample suitablefor desert cooler etc, fixed in replacement, complete all as specified and as directed by Engineer-in-Charge.
113Metal front grill with selector switch and indicator bulb suitable for 18"/ 24" desert cooler etc, fixed in replacement, complete all as specified and as directed by Engineer-in-Charge.
114M&L for Preparation of old painted surface after removal of all dust & foreign material with the help of sand paper and rubbing with cleaning compound and applying one coat ofblack Japan anticorrosion/black bituminous paint inside desert cooler body with paint brush and applying one coat aluminiumpaint of approved make out side the cooler body includingtulu pump, fan motor and body, withspray machine etc complete all as specified and as directed by Engineer-in-Charge.
115S&F Capacitor4 mfdsuitable fordesert cooler fan motor etc , fixed in replacement, complete all as specified anddirected.
116Supply and fixing complete body of Desert cooler of medium size made out of plain sheet of size 1.00 mm thickof good quality in lieu of worn out body of desert cooler as existing complete all as specified and as directed by Engineer-in-Charge.
117M&L for closing the opening all around the desert cooler in window with 6 mm thick plywood including cutting making to shape and fixing etc complete all as specified and directed.
118M&L for Submain wiring with two single core of 4 Sqmm and one single core of 2.5 sqmm as earth wire with multi stranded copper conductor cable PVC (FR) insulated unsheathed cable 1100 volts grade drawn through in PVC Conduit (ISI Marked) of size 20/25 mm dia and the conduits accessories as in repairs complete including making good the distrubed surface to match the existing surface.
119S&F single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB of 20 Amp 240 Volt all as specified and directed by Engr-in-Charge.
120Dismantling old defective/burnt sealed compressor of Deep Freezer 320/405 Ltrs capacity replacement of the same with manufacture reconditioned compressor including soldering copper pipe with new compressor, charging of refrigerant gas R-134a in the system to its rated capacity, replacement of foundation rubber pad, nut and bolts, including testing on full load etc complete all as specified and as directed by Engineer-in-Charge.
121M&L for cleaning the gas system with anti corrosive solution and recharging the refrigerant gas R-134a with anti moisture substance and replacement of filter along with rectification of leakage system in the Deep freezer of capacity 320/405 Ltrs including installation at site and testing on full load etc.
122Repair/replacement of condensing coil assembly complete suitable for deep freezer of capacity 320/405 Ltrs complete and recharging the refrigerant R-134a and testing all as specified and as directed by Engineer-in-Charge.
123M&L for replacement of PCB of Split AC Cap 1.5 TR of any make and all as directed by Engr-in-Charge.
124M&L for replacement of PCB ofWindow AC Cap 1.5/2 TR of any make and all as directed by Engr-in-Charge.
125M&L for replacement of PCB of Deep freezer of cap 320/405 ltrs of any make and all as directed by Engr-in-Charge.
126M&L for replacement of PCB of Refrigerator of cap 165 to 310 Ltrs of any make and all as directed by Engr-in-Charge.
127Supply and installed Window air conditioners electric driven single phase of capacity 1.5 TR of 5 star rating of latest model 2021 with Condensing coil of copper along with remote and batteries complete all as specified and directed.