| 1 | Supply & fixingtesting and commissioning of CPRI approved Factory made; outdoor type LT panel board with Copper busbar of suitable for 950 Amp for 3 Ph &500 Amp for N, platform mounted, cubical, self supported, front & rear openable, double door, hinged type with locking arrangement & sloping top canopy, suitable ventilation on both side, with wire mesh, IP54 protection with Dust & Vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with 7 Tank chemical process, size of the panel should be accommodated the following accesories mention below, mounted/fixed on MS Angle iron stand /frame 40cm height from FFL. Fabricated out of50 x 50 x 6 mm thick MS Angle duly painted with black enamel synthetic paint over coat of red oxide zink chrome primer, duly grouted in PCC 1:2:4type B1 using 20 mm graded stone aggregate in foundation, control wiring copper strandedPVC insulated FRLS cable connected from main bus bar, earth bus strip of32 x 6 mm size for entire length of panel, suitable size of MS Gland with gland plates and aluminum lugs/thimbles for allincoming and outgoing cables including disconnecting and dismanling carefully old LT panel complete all as specified and directed with & including accomodating the following:- Location:- 33 KV MRS Incomer:- (i) MCCB, 4 pole, 630A, 36kA at 415 Volt with thermal magnetic release type- 1 No,(ii) Phase indicating lamp, RYB neon type (set of three) - 1 Set(iii) VAF + PF Multifunction digital Meter - 1 No , Contd/... |
| 2 | Item No 1.00 Contd...Out going:- (i) MCCB, 4 pole, 250A,36kA at 415 volt with thermal magnetic release type - 5 No,(ii) MCCB, 4 pole, 100A, 25kA at 415 volts with thermal magnetic release type-1 Nos, (iii) MCCB, 4 pole, 80A, 25kA at 415 volts with thermal magnetic release type -1 Nos, (iv) one cabinet for accomodating one MCCB 63 Amps, 25kA (future eaxpansion) (v) Four pole extended ROM for spreader terminals each MCCBs.Notes:1.The LT Panel shall be fabricated by CPRI approved factory from the attached list of make. The necessary certification shall be furnished by the contractor.The constructional drawing make of switchgear and hardware, size of panel board technical specification shall be submitted by the contractor for approval of Accepting Officer. 2.Contractor shall arrange inspection of all panel at factory premises before dispatch .The inspection shall be carried out by the nominatedrepresentative of Accepting officer.3. Any civil work involved in installation of panel shall be deemed to be included in the quoted unit rate. |
| 3 | Supply & fixingtesting and commissioning of CPRI approved Factory made; outdoor type LT panel board with Copper busbar of suitable for 600 Amp for 3 Ph &300 Amp for N, platform mounted, cubical, self supported, front & rear openable, double door, hinged type with locking arrangement & sloping top canopy, suitable ventilation on both side, with wire mesh, IP54 protection with Dust & Vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with 7 Tank chemical process, size of the panel should be accommodated the following accesories mention below, mounted/fixed on MS Angle iron stand /frame 40cm height from FFL. Fabricated out of50 x 50 x 6 mm thick MS Angle duly painted with black enamel synthetic paint over coat of red oxide zink chrome primer, duly grouted in PCC 1:2:4type B1 using 20 mm graded stone aggregate in foundation, control wiring copper strandedPVC insulated FRLS cable connected from main bus bar, earth bus strip of32 x 6 mm size for entire length of panel, suitable size of MS Gland with gland plates and aluminum lugs/thimbles for allincoming and outgoing cablesincluding disconnecting and dismanling carefully old LT panel complete all as specified and directed with & including accomodating the following:- Location:- 33 KV MRSSF Qtr, Out side 33 KV MRS Incomer:- (i) MCCB, 4 pole, 400A, 36kA at 415 Volt with thermal magnetic release type - 1 No,(ii) Phase indicating lamp, RYB neon type (set of three) - 1 Set(iii) VAF + PF Multifunction digital Meter - 1 No , Out going:- (i) MCCB, 4 pole, 250A,36kA at 415 volt with thermal magnetic release type- 3 No,(ii) MCCB, 4 pole, 125A, 25kA at 415 volts with thermal magnetic release type -2 Nos, (iii) MCCB, 4 pole, 80A, 25kA at 415 volts with thermal magnetic release type -1 Nos, (iv) one cabinet for accomodating one MCCB 63 Amps, 25kA (future eaxpansion) (v) Four pole extended ROM for spreader terminals each MCCBs.Notes:1.The LT Panel shall be fabricated by CPRI approved factory from the attached list of make. The necessary certification shall be furnished by the contractor.The constructional drawing make of switchgear and hardware, size of panel board technical specification shall be submitted by the contractor for approval of Accepting Officer. 2.Contractor shall arrange inspection of all panel at factory premises before dispatch .The inspection shall be carried out by the nominatedrepresentative of Accepting officer.3. Any civil work involved in installation of panel shall be deemed to be included in the quoted unit rate. |
| 4 | Supply & fixingtesting and commissioning of CPRI approved Factory made; outdoor type LT panel board with Copper busbar of suitable for 600 Amp for 3 Ph &300 Amp for N, platform mounted, cubical, self supported, front & rear openable, double door, hinged type with locking arrangement & sloping top canopy, suitable ventilation on both side, with wire mesh, IP54 protection with Dust & Vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with 7 Tank chemical process, size of the panel should be accommodated the following accesories mention below, mounted/fixed on MS Angle iron stand /frame 40cm height from FFL. Fabricated out of50 x 50 x 6 mm thick MS Angle duly painted with black enamel synthetic paint over coat of red oxide zink chrome primer, duly grouted in PCC 1:2:4type B1 using 20 mm graded stone aggregate in foundation, control wiring copper strandedPVC insulated FRLS cable connected from main bus bar, earth bus strip of32 x 6 mm size for entire length of panel, suitable size of MS Gland with gland plates and aluminum lugs/thimbles for allincoming and outgoing cablesincluding disconnecting and dismanling carefully old LT panel complete all as specified and directed with & including accomodating the following:- Location:- 1 TB Cook House, 1 TB RO Plant Incomer:- (i) MCCB, 4 pole, 400A, 36kA at 415 Volt with thermal magnetic release type- 1 No,(ii) Phase indicating lamp, RYB neon type (set of three) - 1 Set(iii) VAF + PF Multifunction digital Meter - 1 No , Out going:- (i) MCCB, 4 pole, 250A,36kA at 415 volt with thermal magnetic release type- 3 No,(ii) MCCB, 4 pole, 200A, 25kA at 415 volts with thermal magnetic release type-2 Nos, (ii) MCCB, 4 pole, 125A, 25kA at 415 volts with thermal magnetic release type -2 Nos, (iii) MCCB, 4 pole, 80A, 25kA at 415 volts with thermal magnetic release type -1 Nos, (iv) one cabinet for accomodating one MCCB 63 Amps, 25kA (future eaxpansion) (v) Four pole extended ROM for spreader terminals each MCCBs. Notes:1.The LT Panel shall be fabricated by CPRI approved factory from the attached list of make. The necessary certification shall be furnished by the contractor.The constructional drawing make of switchgear and hardware, size of panel board technical specification shall be submitted by the contractor for approval of Accepting Officer. 2.Contractor shall arrange inspection of all panel at factory premises before dispatch .The inspection shall be carried out by the nominatedrepresentative of Accepting officer.3Any civil work involved in installation of panel shall be deemed to be included in the quoted unit rate. |
| 5 | Supply & fixingtesting and commissioning of CPRI approved Factory made; outdoor type LT panel board with Copper busbar of suitable for 950 Amp for 3 Ph &500 Amp for N, platform mounted, cubical, self supported, front & rear openable, double door, hinged type with locking arrangement & sloping top canopy, suitable ventilation on both side, with wire mesh, IP54 protection with Dust & Vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with 7 Tank chemical process, size of the panel should be accommodated the following accesories mention below, mounted/fixed on MS Angle iron stand /frame 40cm height from FFL. Fabricated out of50 x 50 x 6 mm thick MS Angle duly painted with black enamel synthetic paint over coat of red oxide zink chrome primer, duly grouted in PCC 1:2:4type B1 using 20 mm graded stone aggregate in foundation, control wiring copper strandedPVC insulated FRLS cable connected from main bus bar, earth bus strip of32 x 6 mm size for entire length of panel, suitable size of MS Gland with gland plates and aluminum lugs/thimbles for allincoming and outgoing cablesincluding disconnecting and dismanling carefully old LT panel complete all as specified and directed with & including accomodating the following:-Location:- Filter Pump House-02 Nos Incomer:- (i) MCCB, 4 pole, 630A, 36kA at 415 Volt with thermal magnetic release type - 1 No,(ii) Phase indicating lamp, RYB neon type (set of three) - 1 Set(iii) VAF + PF Multifunction digital Meter - 1 No , Out going:- ((i) MCCB, 4 pole, 630A, 36kA at 415 Volt with thermal magnetic release type - 2 No, (ii) Four pole extended ROM for spreader terminals each MCCBs. Notes:1.The LT Panel shall be fabricated by CPRI approved factory from the attached list of make. The necessary certification shall be furnished by the contractor.The constructional drawing make of switchgear and hardware, size of panel board technical specification shall be submitted by the contractor for approval of Accepting Officer. 2.Contractor shall arrange inspection of all panel at factory premises before dispatch .The inspection shall be carried out by the nominatedrepresentative of Accepting officer.3Any civil work involved in installation of panel shall be deemed to be included in the quoted unit rate. |
| 6 | Supply & fixingtesting and commissioning of CPRI approved Factory made; outdoor type LT panel board with Copper busbar of suitable for 950 Amp for 3 Ph &500 Amp for N, platform mounted, cubical, self supported, front & rear openable, double door, hinged type with locking arrangement & sloping top canopy, suitable ventilation on both side, with wire mesh, IP54 protection with Dust & Vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with 7 Tank chemical process, size of the panel should be accommodated the following accesories mention below, mounted/fixed on MS Angle iron stand /frame 40cm height from FFL. Fabricated out of50 x 50 x 6 mm thick MS Angle duly painted with black enamel synthetic paint over coat of red oxide zink chrome primer, duly grouted in PCC 1:2:4type B1 using 20 mm graded stone aggregate in foundation, control wiring copper strandedPVC insulated FRLS cable connected from main bus bar, earth bus strip of32 x 6 mm size for entire length of panel, suitable size of MS Gland with gland plates and aluminum lugs/thimbles for allincoming and outgoing cablesincluding disconnecting and dismanling carefully old LT panel complete all as specified and directed with & including accomodating the following:-Location:- CHQ Incomer:- (i) MCCB, 4 pole, 630A, 36kA at 415 Volt with thermal magnetic release type - 1 No,(ii) Phase indicating lamp, RYB neon type (set of three) - 1 Set(iii) VAF + PF Multifunction digital Meter - 1 No , Out going:- (i) MCCB, 4 pole, 315/400A,36kA at 415 volt with thermal magnetic release type- 3 No,(ii) MCCB, 4 pole, 250A, 25kA at 415 volts with thermal magnetic release type-1 Nos, (ii) MCCB, 4 pole, 160A, 25kA at 415 volts with thermal magnetic release type -1 Nos, (iii) MCCB, 4 pole, 80A, 25kA at 415 volts with thermal magnetic release type -1 Nos, (iv) one cabinet for accomodating one MCCB 63 Amps, 25kA (future eaxpansion) (v) Four pole extended ROM for spreader terminals each MCCBs. Notes:1.The LT Panel shall be fabricated by CPRI approved factory from the attached list of make. The necessary certification shall be furnished by the contractor.The constructional drawing make of switchgear and hardware, size of panel board technical specification shall be submitted by the contractor for approval of Accepting Officer. 2.Contractor shall arrange inspection of all panel at factory premises before dispatch .The inspection shall be carried out by the nominatedrepresentative of Accepting officer.3Any civil work involved in installation of panel shall be deemed to be included in the quoted unit rate. |
| 7 | Supply & fixingtesting and commissioning of CPRI approved Factory made; outdoor type LT panel board with Copper busbar of suitable for 600 Amp for 3 Ph &400 Amp for N, platform mounted, cubical, self supported, front & rear openable, double door, hinged type with locking arrangement & sloping top canopy, suitable ventilation on both side, with wire mesh, IP54 protection with Dust & Vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with 7 Tank chemical process, size of the panel should be accommodated the following accesories mention below, mounted/fixed on MS Angle iron stand /frame 40cm height from FFL. Fabricated out of50 x 50 x 6 mm thick MS Angle duly painted with black enamel synthetic paint over coat of red oxide zink chrome primer, duly grouted in PCC 1:2:4type B1 using 20 mm graded stone aggregate in foundation, control wiring copper strandedPVC insulated FRLS cable connected from main bus bar, earth bus strip of32 x 6 mm size for entire length of panel, suitable size of MS Gland with gland plates and aluminum lugs/thimbles for allincoming and outgoing cablesincluding disconnecting and dismanling carefully old LT panel complete all as specified and directed with & including accomodating the following:-Location:- 3 EME Offrs Mess Incomer:- (i) MCCB, 4 pole, 400A, 36kA at 415 Volt with thermal magnetic release type - 1 No,(ii) Phase indicating lamp, RYB neon type (set of three) - 1 Set(iii) VAF + PF Multifunction digital Meter - 1 No , Out going:- (i) MCCB, 4 pole, 250A,36kA at 415 volt with thermal magnetic release type- 3 No,(ii) MCCB, 4 pole, 200A, 25kA at 415 volts with thermal magnetic release type -1 Nos, (iii) MCCB, 4 pole, 125A, 25kA at 415 volts with thermal magnetic release type -1 Nos, (iii) MCCB, 4 pole, 80A, 25kA at 415 volts with thermal magnetic release type -1 Nos, (iv) one cabinet for accomodating one MCCB 63 Amps, 25kA (future eaxpansion) (v) Four pole extended ROM for spreader terminals each MCCBs. Notes:1.The LT Panel shall be fabricated by CPRI approved factory from the attached list of make. The necessary certification shall be furnished by the contractor.The constructional drawing make of switchgear and hardware, size of panel board technical specification shall be submitted by the contractor for approval of Accepting Officer. 2.Contractor shall arrange inspection of all panel at factory premises before dispatch .The inspection shall be carried out by the nominatedrepresentative of Accepting officer.3Any civil work involved in installation of panel shall be deemed to be included in the quoted unit rate. |
| 8 | Supply & fixingtesting and commissioning of CPRI approved Factory made; outdoor type LT panel board with Copper busbar of suitable for 400 Amp for 3 Ph &200 Amp for N, platform mounted, cubical, self supported, front & rear openable, double door, hinged type with locking arrangement & sloping top canopy, suitable ventilation on both side, with wire mesh, IP54 protection with Dust & Vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with 7 Tank chemical process, size of the panel should be accommodated the following accesories mention below, mounted/fixed on MS Angle iron stand /frame 40cm height from FFL. Fabricated out of50 x 50 x 6 mm thick MS Angle duly painted with black enamel synthetic paint over coat of red oxide zink chrome primer, duly grouted in PCC 1:2:4type B1 using 20 mm graded stone aggregate in foundation, control wiring copper strandedPVC insulated FRLS cable connected from main bus bar, earth bus strip of32 x 6 mm size for entire length of panel, suitable size of MS Gland with gland plates and aluminum lugs/thimbles for allincoming and outgoing cablesincluding disconnecting and dismanling carefully old LT panel complete all as specified and directed with & including accomodating the following:-Location:- Camp Area Incomer:- (i) MCCB, 4 pole, 250A, 36kA at 415 Volt with thermal magnetic release type - 1 No,(ii) Phase indicating lamp, RYB neon type (set of three) - 1 Set(iii) VAF + PF Multifunction digital Meter - 1 No , Out going:- (i) MCCB, 4 pole, 200A,36kA at 415 volt with thermal magnetic release type- 2 No,(ii) MCCB, 4 pole, 160A, 25kA at 415 volts with thermal magnetic release type -1 Nos, (iii) MCCB, 4 pole, 125A, 25kA at 415 volts with thermal magnetic release type -1 Nos,(iv) one cabinet for accomodating one MCCB 63 Amps, 25kA (future eaxpansion) (v) Four pole extended ROM for spreader terminals each MCCBs. Notes:1.The LT Panel shall be fabricated by CPRI approved factory from the attached list of make. The necessary certification shall be furnished by the contractor.The constructional drawing make of switchgear and hardware, size of panel board technical specification shall be submitted by the contractor for approval of Accepting Officer. 2.Contractor shall arrange inspection of all panel at factory premises before dispatch .The inspection shall be carried out by the nominatedrepresentative of Accepting officer.3Any civil work involved in installation of panel shall be deemed to be included in the quoted unit rate. |
| 9 | Supply & fixingtesting and commissioning of CPRI approved Factory made; outdoor type LT panel board with Copper busbar of suitable for 400 Amp for 3 Ph &200 Amp for N, platform mounted, cubical, self supported, front & rear openable, double door, hinged type with locking arrangement & sloping top canopy, suitable ventilation on both side, with wire mesh, IP54 protection with Dust & Vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with 7 Tank chemical process, size of the panel should be accommodated the following accesories mention below, mounted/fixed on MS Angle iron stand /frame 40cm height from FFL. Fabricated out of50 x 50 x 6 mm thick MS Angle duly painted with black enamel synthetic paint over coat of red oxide zink chrome primer, duly grouted in PCC 1:2:4type B1 using 20 mm graded stone aggregate in foundation, control wiring copper strandedPVC insulated FRLS cable connected from main bus bar, earth bus strip of32 x 6 mm size for entire length of panel, suitable size of MS Gland with gland plates and aluminum lugs/thimbles for allincoming and outgoing cablesincluding disconnecting and dismanling carefully old LT panel complete all as specified and directed with & including accomodating the following:-Location:- 68 Engr Regt Incomer:- (i) MCCB, 4 pole, 400A, 36kA at 415 Volt with thermal magnetic release type - 1 No,(ii) Phase indicating lamp, RYB neon type (set of three) - 1 Set(iii) VAF + PF Multifunction digital Meter - 1 No , Out going:- (i) MCCB, 4 pole, 250A,36kA at 415 volt with thermal magnetic release type- 5 No,(ii) MCCB, 4 pole, 160A, 25kA at 415 volts with thermal magnetic release type -1 Nos, (iii) MCCB, 4 pole, 125A, 25kA at 415 volts with thermal magnetic release type -1 Nos,(iv) one cabinet for accomodating one MCCB 63 Amps, 25kA (future eaxpansion) (v) Four pole extended ROM for spreader terminals each MCCBs. Notes:1.The LT Panel shall be fabricated by CPRI approved factory from the attached list of make. The necessary certification shall be furnished by the contractor.The constructional drawing make of switchgear and hardware, size of panel board technical specification shall be submitted by the contractor for approval of Accepting Officer. 2.Contractor shall arrange inspection of all panel at factory premises before dispatch .The inspection shall be carried out by the nominatedrepresentative of Accepting officer.3 The minimum clearance of 10 cm between bus bar to bus bar & 20 cm between bus bar to earth/ body shall be maintained4. Any civil work involved in installation of panel shall be deemed to be included in the quoted unit rate. |
| 10 | Supply & fixingtesting and commissioning of CPRI approved Factory made; outdoor type LT panel board with Copper busbar of suitable for 400 Amp for 3 Ph &200 Amp for N, platform mounted, cubical, self supported, front & rear openable, double door, hinged type with locking arrangement & sloping top canopy, suitable ventilation on both side, with wire mesh, IP54 protection with Dust & Vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with 7 Tank chemical process, size of the panel should be accommodated the following accesories mention below, mounted/fixed on MS Angle iron stand /frame 40cm height from FFL. Fabricated out of50 x 50 x 6 mm thick MS Angle duly painted with black enamel synthetic paint over coat of red oxide zink chrome primer, duly grouted in PCC 1:2:4type B1 using 20 mm graded stone aggregate in foundation, control wiring copper strandedPVC insulated FRLS cable connected from main bus bar, earth bus strip of32 x 6 mm size for entire length of panel, suitable size of MS Gland with gland plates and aluminum lugs/thimbles for allincoming and outgoing cablesincluding disconnecting and dismanling carefully old LT panel complete all as specified and directed with & including accomodating the following:-Location:- 1 TB OTM Area Incomer:- (i) MCCB, 4 pole, 250A, 36kA at 415 Volt with thermal magnetic release type - 1 No,(ii) Phase indicating lamp, RYB neon type (set of three) - 1 Set(iii) VAF + PF Multifunction digital Meter - 1 No , Out going:- (i) MCCB, 4 pole, 80A, 25kA at 415 volts with thermal magnetic release type -9 Nos,(v) Four pole extended ROM for spreader terminals each MCCBs. Notes:1.The LT Panel shall be fabricated by CPRI approved factory from the attached list of make. The necessary certification shall be furnished by the contractor.The constructional drawing make of switchgear and hardware, size of panel board technical specification shall be submitted by the contractor for approval of Accepting Officer. 2.Contractor shall arrange inspection of all panel at factory premises before dispatch .The inspection shall be carried out by the nominatedrepresentative of Accepting officer.3Any civil work involved in installation of panel shall be deemed to be included in the quoted unit rate. |
| 11 | Supply & fixingtesting and commissioning of CPRI approved Factory made; outdoor type LT panel board with Copper busbar of suitable for 600 Amp for 3 Ph &300 Amp for N, platform mounted, cubical, self supported, front & rear openable, double door, hinged type with locking arrangement & sloping top canopy, suitable ventilation on both side, with wire mesh, IP54 protection with Dust & Vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with 7 Tank chemical process, size of the panel should be accommodated the following accesories mention below, mounted/fixed on MS Angle iron stand /frame 40cm height from FFL. Fabricated out of50 x 50 x 6 mm thick MS Angle duly painted with black enamel synthetic paint over coat of red oxide zink chrome primer, duly grouted in PCC 1:2:4type B1 using 20 mm graded stone aggregate in foundation, control wiring copper strandedPVC insulated FRLS cable connected from main bus bar, earth bus strip of32 x 6 mm size for entire length of panel, suitable size of MS Gland with gland plates and aluminum lugs/thimbles for allincoming and outgoing cablesincluding disconnecting and dismanling carefully old LT panel complete all as specified and directed with & including accomodating the following:- Location:- SF Qtr Incomer:- (i) MCCB, 4 pole, 400A, 36kA at 415 Volt with thermal magnetic release type - 1 No,(ii) Phase indicating lamp, RYB neon type (set of three) - 1 Set(iii) VAF + PF Multifunction digital Meter - 1 No , Out going:- (i) MCCB, 4 pole, 250A,36kA at 415 volt with thermal magnetic release type- 2 No,(ii) MCCB, 4 pole, 125A, 25kA at 415 volts with thermal magnetic release type -1 Nos, (iii) MCCB, 4 pole, 80A, 25kA at 415 volts with thermal magnetic release type -2 Nos,(iv) one cabinet for accomodating one MCCB 63 Amps, 25kA (future eaxpansion) (v) Four pole extended ROM for spreader terminals each MCCBs. Notes:1.The LT Panel shall be fabricated by CPRI approved factory from the attached list of make. The necessary certification shall be furnished by the contractor.The constructional drawing make of switchgear and hardware, size of panel board technical specification shall be submitted by the contractor for approval of Accepting Officer. 2.Contractor shall arrange inspection of all panel at factory premises before dispatch .The inspection shall be carried out by the nominatedrepresentative of Accepting officer.3 Any civil work involved in installation of panel shall be deemed to be included in the quoted unit rate. |
| 12 | Supply & fixingtesting and commissioning of CPRI approved Factory made; outdoor type LT panel board with Copper busbar of suitable for 240 Amp for 3 Ph &150 Amp for N, platform mounted, cubical, self supported, front & rear openable, double door, hinged type with locking arrangement & sloping top canopy, suitable ventilation on both side, with wire mesh, IP54 protection with Dust & Vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with 7 Tank chemical process, size of the panel should be accommodated the following accesories mention below, mounted/fixed on MS Angle iron stand /frame 40cm height from FFL. Fabricated out of50 x 50 x 6 mm thick MS Angle duly painted with black enamel synthetic paint over coat of red oxide zink chrome primer, duly grouted in PCC 1:2:4type B1 using 20 mm graded stone aggregate in foundation, control wiring copper strandedPVC insulated FRLS cable connected from main bus bar, earth bus strip of32 x 6 mm size for entire length of panel, suitable size of MS Gland with gland plates and aluminum lugs/thimbles for allincoming and outgoing cablesincluding disconnecting and dismanling carefully old LT panel complete all as specified and directed with & including accomodating the following:-Location:- P-213, P-207, P-220 Incomer:- (i) MCCB, 4 pole, 160A, 25kA at 415 Volt with thermal magnetic release type - 1 No,(ii) Phase indicating lamp, RYB neon type (set of three) - 1 Set(iii) VAF + PF Multifunction digital Meter - 1 No , Out going:- (i) MCCB, 4 pole, 80A, 25kA at 415 volts with thermal magnetic release type -5 Nos,(ii) one cabinet for accomodating one MCCB 63 Amps, 25kA (future eaxpansion) (v) Four pole extended ROM for spreader terminals each MCCBs. Notes:1.The LT Panel shall be fabricated by CPRI approved factory from the attached list of make. The necessary certification shall be furnished by the contractor.The constructional drawing make of switchgear and hardware, size of panel board technical specification shall be submitted by the contractor for approval of Accepting Officer. 2.Contractor shall arrange inspection of all panel at factory premises before dispatch .The inspection shall be carried out by the nominatedrepresentative of Accepting officer.3 Any civil work involved in installation of panel shall be deemed to be included in the quoted unit rate. |
| 13 | Supply & fixingtesting and commissioning of CPRI approved Factory made; outdoor type LT panel board with Copper busbar of suitable for 300 Amp for 3 Ph &150 Amp for N, platform mounted, cubical, self supported, front & rear openable, double door, hinged type with locking arrangement & sloping top canopy, suitable ventilation on both side, with wire mesh, IP54 protection with Dust & Vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with 7 Tank chemical process, size of the panel should be accommodated the following accesories mention below, mounted/fixed on MS Angle iron stand /frame 40cm height from FFL. Fabricated out of50 x 50 x 6 mm thick MS Angle duly painted with black enamel synthetic paint over coat of red oxide zink chrome primer, duly grouted in PCC 1:2:4type B1 using 20 mm graded stone aggregate in foundation, control wiring copper strandedPVC insulated FRLS cable connected from main bus bar, earth bus strip of32 x 6 mm size for entire length of panel, suitable size of MS Gland with gland plates and aluminum lugs/thimbles for allincoming and outgoing cablesincluding disconnecting and dismanling carefully old LT panel complete all as specified and directed with & including accomodating the following:-Location:- P-208 BM Ors/Jcos Incomer:- (i) MCCB, 4 pole, 200A, 25kA at 415 Volt with thermal magnetic release type - 1 No,(ii) Phase indicating lamp, RYB neon type (set of three) - 1 Set(iii) VAF + PF Multifunction digital Meter - 1 No , Out going:- (i) MCCB, 4 pole, 80A, 25kA at 415 volts with thermal magnetic release type -7 Nos,(ii) one cabinet for accomodating one MCCB 63 Amps, 25kA (future eaxpansion) (v) Four pole extended ROM for spreader terminals each MCCBs. Notes:1.The LT Panel shall be fabricated by CPRI approved factory from the attached list of make. The necessary certification shall be furnished by the contractor.The constructional drawing make of switchgear and hardware, size of panel board technical specification shall be submitted by the contractor for approval of Accepting Officer. 2.Contractor shall arrange inspection of all panel at factory premises before dispatch .The inspection shall be carried out by the nominatedrepresentative of Accepting officer.3 Any civil work involved in installation of panel shall be deemed to be included in the quoted unit rate. |
| 14 | Supply & fixingtesting and commissioning of CPRI approved Factory made; outdoor type LT panel board with Copper busbar of suitable for 600 Amp for 3 Ph &300 Amp for N, platform mounted, cubical, self supported, front & rear openable, double door, hinged type with locking arrangement & sloping top canopy, suitable ventilation on both side, with wire mesh, IP54 protection with Dust & Vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with 7 Tank chemical process, size of the panel should be accommodated the following accesories mention below, mounted/fixed on MS Angle iron stand /frame 40cm height from FFL. Fabricated out of50 x 50 x 6 mm thick MS Angle duly painted with black enamel synthetic paint over coat of red oxide zink chrome primer, duly grouted in PCC 1:2:4type B1 using 20 mm graded stone aggregate in foundation, control wiring copper strandedPVC insulated FRLS cable connected from main bus bar, earth bus strip of32 x 6 mm size for entire length of panel, suitable size of MS Gland with gland plates and aluminum lugs/thimbles for allincoming and outgoing cablesincluding disconnecting and dismanling carefully old LT panel complete all as specified and directed with & including accomodating the following:- Location:- P-258 BM Ors/Jcos Incomer:- (i) MCCB, 4 pole, 400A, 36kA at 415 Volt with thermal magnetic release type - 1 No,(ii) Phase indicating lamp, RYB neon type (set of three) - 1 Set(iii) VAF + PF Multifunction digital Meter - 1 No , Out going:- (i) MCCB, 4 pole, 250A,36kA at 415 volt with thermal magnetic release type- 4 No,(ii) Four pole extended ROM for spreader terminals each MCCBs.Notes:1.The LT Panel shall be fabricated by CPRI approved factory from the attached list of make. The necessary certification shall be furnished by the contractor.The constructional drawing make of switchgear and hardware, size of panel board technical specification shall be submitted by the contractor for approval of Accepting Officer. 2.Contractor shall arrange inspection of all panel at factory premises before dispatch .The inspection shall be carried out by the nominatedrepresentative of Accepting officer.3Any civil work involved in installation of panel shall be deemed to be included in the quoted unit rate. |
| 15 | Supply & fixingtesting and commissioning of CPRI approved Factory made; outdoor type LT panel board with Copper busbar of suitable for 400 Amp for 3 Ph &200 Amp for N, platform mounted, cubical, self supported, front & rear openable, double door, hinged type with locking arrangement & sloping top canopy, suitable ventilation on both side, with wire mesh, IP54 protection with Dust & Vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with 7 Tank chemical process, size of the panel should be accommodated the following accesories mention below, mounted/fixed on MS Angle iron stand /frame 40cm height from FFL. Fabricated out of50 x 50 x 6 mm thick MS Angle duly painted with black enamel synthetic paint over coat of red oxide zink chrome primer, duly grouted in PCC 1:2:4type B1 using 20 mm graded stone aggregate in foundation, control wiring copper strandedPVC insulated FRLS cable connected from main bus bar, earth bus strip of32 x 6 mm size for entire length of panel, suitable size of MS Gland with gland plates and aluminum lugs/thimbles for allincoming and outgoing cablesincluding disconnecting and dismanling carefully old LT panel complete all as specified and directed with & including accomodating the following:-Location:- P-218 BM Ors/JCOs Qtr Incomer:- (i) MCCB, 4 pole, 250A, 36kA at 415 Volt with thermal magnetic release type - 1 No,(ii) Phase indicating lamp, RYB neon type (set of three) - 1 Set(iii) VAF + PF Multifunction digital Meter - 1 No , Out going:- (i) MCCB, 4 pole, 80A, 25kA at 415 volts with thermal magnetic release type -5 Nos,(v) Four pole extended ROM for spreader terminals each MCCBs. Notes:1.The LT Panel shall be fabricated by CPRI approved factory from the attached list of make. The necessary certification shall be furnished by the contractor.The constructional drawing make of switchgear and hardware, size of panel board technical specification shall be submitted by the contractor for approval of Accepting Officer. 2.Contractor shall arrange inspection of all panel at factory premises before dispatch .The inspection shall be carried out by the nominatedrepresentative of Accepting officer.3Any civil work involved in installation of panel shall be deemed to be included in the quoted unit rate. |
| 16 | Supply & fixingtesting and commissioning of CPRI approved Factory made; outdoor type LT panel board with Copper busbar of suitable for 950 Amp for 3 Ph &500 Amp for N, platform mounted, cubical, self supported, front & rear openable, double door, hinged type with locking arrangement & sloping top canopy, suitable ventilation on both side, with wire mesh, IP54 protection with Dust & Vermin proof, fabricated out of 3.15 mm CRCA sheet duly powder coated with 7 Tank chemical process, size of the panel should be accommodated the following accesories mention below, mounted/fixed on MS Angle iron stand /frame 40cm height from FFL. Fabricated out of50 x 50 x 6 mm thick MS Angle duly painted with black enamel synthetic paint over coat of red oxide zink chrome primer, duly grouted in PCC 1:2:4type B1 using 20 mm graded stone aggregate in foundation, control wiring copper strandedPVC insulated FRLS cable connected from main bus bar, earth bus strip of32 x 6 mm size for entire length of panel, suitable size of MS Gland with gland plates and aluminum lugs/thimbles for allincoming and outgoing cables including disconnecting and dismanling carefully old LT panel complete all as specified and directed with & including accomodating the following:-Location:- MES Colony Incomer:- (i) MCCB, 4 pole, 630A, 36kA at 415 Volt with thermal magnetic release type- 1 No,(ii) Phase indicating lamp, RYB neon type (set of three) - 1 Set(iii) VAF + PF Multifunction digital Meter - 1 No , Out going:- (i) MCCB, 4 pole, 315/400A,36kA at 415 volt with thermal magnetic release type - 1 No,(ii) MCCB, 4 pole, 250A, 36kA at 415 volts with thermal magnetic release type-3 Nos, (iii) MCCB, 4 pole, 160A, 25kA at 415 volts with thermal magnetic release type-1 Nos, (iii) MCCB, 4 pole, 80A, 25kA at 415 volts with thermal magnetic release type -1 Nos, (iv) one cabinet for accomodating one MCCB 63 Amps, 25kA (future eaxpansion) (v) Four pole extended ROM for spreader terminals each MCCBs.Notes:1.The LT Panel shall be fabricated by CPRI approved factory from the attached list of make. The necessary certification shall be furnished by the contractor.The constructional drawing make of switchgear and hardware, size of panel board technical specification shall be submitted by the contractor for approval of Accepting Officer. 2.Contractor shall arrange inspection of all panel at factory premises before dispatch .The inspection shall be carried out by the nominatedrepresentative of Accepting officer.3Any civil work involved in installation of panel shall be deemed to be included in the quoted unit rate. |
| 17 | M&L Earthing complete with GI strip as earth lead and MS galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate is not less than 1.5 mtr below normal ground level connected to galvanized iron strips 32 x 6 mm with GI pipe, nuts, bolts and washers complete upto and including test point made out of 40 x 3mm GI flat, PCC pit of required size in PCC 1:2:4 type B1 and RCC cover with frame including plastering and white wash, charcoal, common salt 15cm at round the earth plate, watering pipe 20mm med grade/galvanized and 40mm dia GI pipe medium grade for GI strip protectionwith GI funnel including dismantling old earthing complete all as specified and directed as shown in electrical plate No 3 of SSR Part-I 2009. Notes: (i) The unit rate includes for 40mm diam medium grade protection pipe and earth lead upto 7.50 meter.(ii) Any variation in length of earth lead and protection pipe beyond 7.5 m shall be measured & paid seperately separately.(iii)PCC pit shall be provided at least 500mm away from the pit and not on the earth pit itself and the extra cost of additional height of watering pipe, bends, elbow etc shall be deemed to be included in the unit rate. |
| 18 | Supply and replace 32mm x 6 mm GI strip as in earth continuity conductor fixed to wall or pole or recess or chases or burried in ground or drawn in conduit pipe or any other indicated situation for loop earthing etc as required complete all as specified and directed. |
| 19 | Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth for pole foundation, cable trench, etc and getting out inany type ofsoil complete all as specified and directed. |
| 20 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm each complete all as specified and directed. |
| 21 | Removing excavated materials (soil) to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed. |
| 22 | M&L for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection (8 cm below cable & 15 cm above cable) complete all as specified and directed. Note:- Compacted/punned thickness shall be measured & paid. |
| 23 | Supplying and laying sub class \"B\" bricks (modular) for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable complete all as specified and directed |
| 24 | Taking out old unservicible cable and Supply, laying & testingXLPEinsulated, armoured, heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointingwith suitable size aluminium lugs complete ofSize 35 Sqmm X 3.5 core, complete all as specified and directed. |
| 25 | All as per item No. 23.00 but Size 50 Sqmm X 3.5 core complete all as specified and directed. |
| 26 | All as per item No. 23.00 but Size 70 Sqmm X 3.5 core complete all as specified and directed. |
| 27 | All as per item No. 23.00 but Size 95 Sqmm X 3.5 core complete all as specified and directed. |
| 28 | All as per item No. 23.00 but Size 120 Sqmm X 3.5 core complete all as specified and directed. |
| 29 | All as per item No. 23.00 but Size 150 Sqmm X 3.5 core complete all as specified and directed. |
| 30 | All as per item No. 23.00 but Size 185 Sqmm X 3.5 core complete all as specified and directed. |
| 31 | All as per item No. 23.00 but Size 240 Sqmm X 3.5 core complete all as specified and directed. |
| 32 | Schedule of credit (calculation will be done off line)Rs. 64900.00 |