Providing Multi Villages Piped Water Supply Scheme ( Balance Work ) For Gagret Constituency In Gagret Block And Amb Block In Distt Una ( Hp ) ( Under Jal Jeevan Mission ) In Single Package On Turn Key Job Basis Including Trial And Testi
Tender Overview
Project Description
Providing Multi Villages Piped Water Supply Scheme ( Balance Work ) For Gagret Constituency In Gagret Block And Amb Block In Distt Una ( Hp ) ( Under Jal Jeevan Mission ) In Single Package On Turn Key Job Basis Including Trial And Testing Run, Period Of 3 ( I ) Supply And Errection Of Submersible, Centrifugal Pumping Machinery Including All Accessories ( Ii ) Construction Of Pump House, Boundary Wall Around The Pump House, Underground Reservoirs And Ohsr Of Various Capacity, ( Iii ) Laying, Jointing And Tes
BOQ
| Sl. No. | Item Description |
| 1 | Schedule -B1S/E of Pumping Machinery(Submersible & Centrifugal ) |
| 2 | S/E of Submersible Pumping Machinery for T/Well at GugleharSupply ofsubmersiblepumping set of reputed make such as KSB/ Calama / BS/ Worthigton / Sabar/ Seerex /Johnston / Amrut/ lubi/ Hindustan,Groundfosconfirming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ; 5659-1978 with upto date amendments, suitable for raw / clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to submersible motor of same as that of offered submersible pump make confirming to BIS ;9283-1979 with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with doublemechanicalseal in oil chamber and grease packed, lubricated bearing and provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum weartear.It should also be fitted with a device to make up expantion of water with heating of motor. The pumpset should include water level guard i/c cable ,errection clamps, cable clips and depth gauge etc. and suitable for opertion on data given below. a Pumps :- Specifications i) Makeii) Modeliii)No. of stages iv) Manufacter\"s certificate to be attached Performancei) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speedv) Insulation |
| 3 | Discharge=( Q) 3.51 LPS |
| 4 | Total Head=( H)33.82 Mts. |
| 5 | a) SWL in Tubewell= 10.00Mtr. bgl. |
| 6 | c) R.L. point of discharge = 405.00 Mtr. |
| 7 | d) Seasonal fluctuation + draught condition + bowl assembly. 9.00 Mtrs. |
| 8 | e) Drawdown in Tubewell=8.00 Mtrs. |
| 9 | f) R.L of lowest point of pumpset installation = 378.00 Mtrs. |
| 10 | g) Static Column lift = 37.00 Mtrs. |
| 11 | Rising main. Column Pipe. |
| 12 | Length 50 Mtrs.Length 37.00 mtr. |
| 13 | Dia meter. 80mmDia 125 mm |
| 14 | Class GMSClass GMS. (M) |
| 15 | Pumping hours hours |
| 16 | Altitude of installations above M.S.L.__________mtr. |
| 17 | Characteristic of water. |
| 18 | a) Temperature _______ Deg Cel. |
| 19 | b) Turbidity________JTU. |
| 20 | c) Allkanity. ___________mg/ l Ca Co3 |
| 21 | d) Size of solids____________mm |
| 22 | e) others |
| 23 | Depth of T/wellmtr. |
| 24 | Dia of T/ well assembly 300/200mm. |
| 25 | Length of assembly pipe. |
| 26 | Dia of housing pipe300 mm. |
| 27 | Length of housing pipe |
| 28 | OPERATINGCONDITIONS. |
| 29 | Type of Current :-A.C.Three Phase. |
| 30 | Frequency:- 50 Cycles /Sec. |
| 31 | Rated Voltage 415 +/- 15 % Volts. |
| 32 | System of earthing: Double Loop earthing as per BIS 3843-1987 Latest. |
| 33 | Speed of Revolution____________ RPM 2900 |
| 34 | MOTOR. |
| 35 | Ref. to BIS code BIS 9283-1979 with upto date amendments. |
| 36 | Type of enclosure of motor: As per BIS ; 4691-1985 ( latest ) |
| 37 | Mechanical out put in H.P. |
| 38 | Class of insulation:Class B |
| 39 | The motor should be able to withstand initial current of 2.50 times the rated current for two minutes without suffering damages of permanent deformations. |
| 40 | PUMP |
| 41 | Ref. to BIS code ;BIS ; 5659-1978 with upto date amendments. |
| 42 | Drive Type: Electric driven. |
| 43 | Operating Range:-15 % to+10 % of Total head at duty point. |
| 44 | Deliver size of Pump :________( To be quoted by tenderer.) |
| 45 | Providing ICTP Main Switch with HRC fuses ofL&T/ Havells make and having capacity 30%extra of the operational rating as per IS : 13947-P I & II with upto date amendments. ICTP Switch:i) Make :ii) Type :iii) Capacity : 32.00 Amp. |
| 46 | ProvidingMSSheetsteel fabricated floor mounted closed ( Almirah type ) switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections..Panel /Switch Board. i) Drawing.ii) layout Plan. |
| 47 | MCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder with or withoutintial oil filling asthe case may be with neutral linked under voltagereleases as per IS ; 2516-1985 with upto date amendments. MCB 1) Make. ii) Typeiii) Range. 32 Amp. iv) Capacity. |
| 48 | ii) ELCB of recommendedmakeL&T / Havellsas per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off springcondition of the circuit breaker for over current protection.The circuit should be equiped with magnet thermal releasewith metallic tape CTS. It shouldalso be fitted with earth fault for tripping of breakeron occurence of Earth fault. ELCB 1) Make. ii) Type iii) Range. 32 Amp.iv) Capacity. |
| 49 | iii) The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage,reverse phasing,overloading and phase voltage difference as per IS; 3842 ( Latest Edition ) Volatage Monitor Relayi) Makeii ) Type iii) Range 0-500 |
| 50 | b) A.C. supply,voltmeter of recommended make A.E / L&T of suitable range with selector switches as per IS ;1248-1983 with latest amendments.Voltmeter i) Make ii ) Typeiii) Range 0-500 |
| 51 | c) AC supply ammeter of A.E/ L&T make of suitable range with selector switches and CIS operated as per IS :1248 ( P-I&II ) -1983 with upto date amendments. Ammeter i) Makeii) Type 15 Amp |
| 52 | d) Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS ;8084-1976 and IS :11353-1985 read with BIS ; 5578 -1985 with upto date amendments including. Bus Bar Chamber i) Type ii) Makeiii) Rating |
| 53 | Three phase indicator lamps complete with toggle switches for indivual motors as per IS 3452 ( P- I&II ) withupto date amendments. 3 phase indicators |
| 54 | e) Capacitor ofBHEL / GEC / L&T / Mecheilmake asperIS ; 2834-1968with upto date amendments,to raise the power factor at site to 0.95 for directconnections to induction motor individually of requiredKVA ratingaccordingto H.P. offered including cables as per releventISI code ( ofSeimens / Glocter / IEC make ) frombus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments . Rating of capacitor will be approved by HPSEB. Capacitori) Type ii) Makeiii) Range 2 KVAR |
| 55 | Providing suitablestarter ofL&T /BHEL make as per IS : 13947-IIwith upto date \"amendments for Squirrel cage / Slipringmotor mounted on panel board with magnetic type over load release and dashpot, time lag, under voltage release, with or without initial oil filling as the case may be with single phase preventor as perIS ;1248 ( P-V ) 1983with up to date amendments.Starteri) Type ii) MakeSingle phase preventor i) Typeii) Make |
| 56 | Providing and fixing double flanged Cast IronSliuce valve of Leader / Kirloskar/Kartar/LP brand approvedmakefor the Column pipe of pump and capable of withstanding thenormal seat pressure and asperIS 780-1992with latest ammendments Class PN 1.00 For Column Pipe 125 mm diaSluice valve i) Makeii) Class PN 1.00iii) Material Cast iron |
| 57 | Providing and fixing digital pressure gauge of Prega / Precision / Fiebig make complete with all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendementsPressure Gauge i) Make |
| 58 | Supply of PVC jointless,flat water proof cable with copper conductoras per BIS 694-1998 latest with upto date ammendments of Havelles/Finolex makesuitablefor the pumpsets offeredfrom MCBtomotorincluding allother electrical equipments / accessories such as thimble, flexible pipe,solder, nuts and bolts, cable glands, clips etc, laid in pipes or trenches under floor.The type, size and make shall be subject to approval of HPSEB authorities. Submersible cablei) Finolex/ Havells make ii) Size 2.50 mm2 (iii) Core=3 |
| 59 | Providing and Lowering ofGMSColumn pipe for assembly 100 mm dia including MS flanges\" of Table 17 as per IS : 6392-1971 with upto date amendments, rubber / asbestos gasket of min.3 mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 .The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated under item No.5 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction ofRising main .The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2 Nos.) at the top of T/well assembly, and as per the direction of Engineer - in - Charge. Column pipei) Size 125 mm dia ii) Class (M)iii) Length |
| 60 | Installation of all items appearing as aboveas per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge. |
| 61 | Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 ( P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay Finolex/ Havellsmakeincludingallother accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A) Supply side from meter of HPSEB to Bus Bar and Switchi) Size 2.50 mm2 ii) Makeiii) Typeiv) Capacity v) core |
| 62 | Providingand fixing double loop earthingwith GI plate of 600x600x6.3 mm thick electrodecomplete with material such as thimble, nuts and bolts, charcoal, saltas per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) GI wire 8SWG |
| 63 | Providing and installation of sensor based auto cut off system for dry run condition of submersible pump as per approved specification and as directed by Engineer-in-Charge |
| 64 | S/E of Submersible Pumping Machinery for T/Well at Andora |
| 65 | Supply ofsubmersiblepumping set of reputed make such as KSB/ Calama / BS/ Worthigton / Sabar/ Seerex /Johnston / Amrut/ lubi/ Hindustan,Groundfosconfirming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ; 5659-1978 with upto date amendments, suitable for raw / clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to submersible motor of same as that of offered submersible pump make confirming to BIS ;9283-1979 with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with doublemechanicalseal in oil chamber and grease packed, lubricated bearing and provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum weartear.It should also be fitted with a device to make up expantion of water with heating of motor. The pumpset should include water level guard i/c cable ,errection clamps, cable clips and depth gauge etc. and suitable for opertion on data given below. a Pumps :- Specifications i) Makeii) Modeliii)No. of stages iv) Manufacter\"s certificate to be attached Performancei) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speedv) Insulation. |
| 66 | Discharge=( Q) 9.43 LPS |
| 67 | Total Head=( H)61.53 Mts. |
| 68 | a) SWL in Tubewell= 16.77Mtr. bgl. |
| 69 | c) R.L. point of discharge = 510.00 Mtr. |
| 70 | d) Seasonal fluctuation + draught condition + bowl assembly. 9.00 Mtrs. |
| 71 | e) Drawdown in Tubewell =24.39 Mtrs. |
| 72 | f) R.L of lowest point of pumpset installation = 456.84 Mtrs. |
| 73 | g) Static Column lift = 53.16 Mtrs. |
| 74 | Rising main. Column Pipe. |
| 75 | Length 50 Mtrs.Length 60.16 mtr. |
| 76 | Dia meter. 80mmDia 100 mm |
| 77 | Class GMSClass GMS. (M) |
| 78 | Pumping hours hours |
| 79 | Altitude of installations above M.S.L.__________mtr. |
| 80 | Characteristic of water. |
| 81 | a) Temperature _______ Deg Cel. |
| 82 | b) Turbidity________JTU. |
| 83 | c) Allkanity. ___________mg/ l Ca Co3 |
| 84 | d) Size of solids____________mm |
| 85 | e) others |
| 86 | Depth of T/wellmtr. |
| 87 | Dia of T/ well assembly 200mm. |
| 88 | Length of assembly pipe. |
| 89 | Dia of housing pipe300 mm. |
| 90 | Length of housing pipe |
| 91 | OPERATINGCONDITIONS. |
| 92 | Type of Current :-A.C.Three Phase. |
| 93 | Frequency:- 50 Cycles /Sec. |
| 94 | Rated Voltage 415 +/- 15 % Volts. |
| 95 | System of earthing: Double Loop earthing as per BIS 3843-1987 Latest. |
| 96 | Speed of Revolution____________ RPM 2900 |
| 97 | MOTOR. |
| 98 | Ref. to BIS code BIS 9283-1979 with upto date amendments. |
| 99 | Type of enclosure of motor: As per BIS ; 4691-1985 ( latest ) |
| 100 | Mechanical out put in H.P. |
| 101 | Class of insulation:Class B |
| 102 | The motor should be able to withstand initial current of 2.50 times the rated current for two minutes without suffering damages of permanent deformations. |
| 103 | PUMP |
| 104 | Ref. to BIS code ;BIS ; 5659-1978 with upto date amendments. |
| 105 | Drive Type: Electric driven. |
| 106 | Operating Range:-15 % to+10 % of Total head at duty point. |
| 107 | Deliver size of Pump :________( To be quoted by tenderer.) |
| 108 | Providing ICTP Main Switch with HRC fuses ofL&T/ Havells make and having capacity 30%extra of the operational rating as per IS : 13947-P I & II with upto date amendments. ICTP Switch:i) Make :ii) Type :iii) Capacity : 63 Amp. |
| 109 | ProvidingMSSheetsteel fabricated floor mounted closed ( Almirah type ) switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections.Panel /Switch Board. i) Drawing.ii) layout Plan. |
| 110 | MCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder with or withoutintial oil filling asthe case may be with neutral linked under voltagereleases as per IS ; 2516-1985 with upto date amendments. MCB 1) Make. ii) Typeiii) Range. 63 Amp. iv) Capacity. |
| 111 | ii) ELCB of recommendedmakeL&T / Havellsas per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off springcondition of the circuit breaker for over current protection.The circuit should be equiped with magnet thermal releasewith metallic tape CTS. It shouldalso be fitted with earth fault for tripping of breakeron occurence of Earth fault. ELCB 1) Make. ii) Type iii) Range. 63 Amp.iv) Capacity. |
| 112 | iii) The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage,reverse phasing,overloading and phase voltage difference as per IS; 3842 ( Latest Edition ) Volatage Monitor Relayi) Makeii ) Type iii) Range 0-500 |
| 113 | b) A.C. supply,voltmeter of recommended make A.E / L&T of suitable range with selector switches as per IS ;1248-1983 with latest amendments.Voltmeter i) Make ii ) Typeiii) Range 0-500 |
| 114 | c) AC supply ammeter of A.E/ L&T make of suitable range with selector switches and CIS operated as per IS :1248 ( P-I&II ) -1983 with upto date amendments. Ammeter i) Makeii) Type 60 Amp |
| 115 | d) Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS ;8084-1976 and IS :11353-1985 read with BIS ; 5578 -1985 with upto date amendments including. Bus Bar Chamber i) Type ii) Makeiii) Rating |
| 116 | Three phase indicator lamps complete with toggle switches for indivual motors as per IS 3452 ( P- I&II ) withupto date amendments. 3 phase indicators |
| 117 | e) Capacitor ofBHEL / GEC / L&T / Mecheilmake asperIS ; 2834-1968with upto date amendments,to raise the power factor at site to 0.95 for directconnections to induction motor individually of requiredKVA ratingaccordingto H.P. offered including cables as per releventISI code ( ofSeimens / Glocter / IEC make ) frombus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments . Rating of capacitor will be approved by HPSEB. Capacitori) Type ii) Makeiii) Range 4 KVAR |
| 118 | Providing suitablestarter ofL&T /BHEL make as per IS : 13947-IIwith upto date \"amendments for Squirrel cage / Slipringmotor mounted on panel board with magnetic type over load release and dashpot, time lag, under voltage release, with or without initial oil filling as the case may be with single phase preventor as perIS ;1248 ( P-V ) 1983with up to date amendments.Starter i) Type ii) Make Single phase preventor i) Typeii) Make |
| 119 | Providing and fixing double flanged Cast IronSliuce valve of Leader / Kirloskar/Kartar/LP brand approved makefor the Column pipe of pump and capable of withstanding thenormal seat pressure and asperIS 780-1992with latest ammendments Class PN 1.00 For Column Pipe 125 mm diaSluice valve i) Makeii) Class PN 1.00iii) Material cast iron |
| 120 | Providing and fixing digital pressure gauge of Prega / Precision / Fiebig make complete with all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendementsPressure Gauge i) Make |
| 121 | Supply of PVC jointless,flat water proof cable with copper conductoras per BIS 694-1998 latest with upto date ammendments of Havelles/Finolex makesuitablefor the pumpsets offeredfrom MCBtomotorincluding allother electrical equipments / accessories such as thimble, flexible pipe,solder, nuts and bolts, cable glands, clips etc, laid in pipes or trenches under floor.The type, size and make shall be subject to approval of HPSEB authorities. Submersible cablei) Finolex/ Havells make ii) Size 6.00 mm2 (iii) Core=3 |
| 122 | Providing and Lowering ofGMSColumn pipe for assembly 100 mm dia including MS flanges\" of Table 17 as per IS : 6392-1971 with upto date amendments, rubber / asbestos gasket of min.3 mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 .The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated under item No.5 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction ofRising main .The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2 Nos.) at the top of T/well assembly, and as per the direction of Engineer - in - Charge. Column pipei) Size 100 mm dia ii) Class (M)iii) Length |
| 123 | Installation of all items appearing as aboveas per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge. |
| 124 | Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 ( P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay Finolex/ Havellsmakeincludingallother accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A) Supply side from meter of HPSEB to Bus Bar and Switchi) Size 10.00 mm2 ii) Makeiii) Type iv) Capacityv) core |
| 125 | Providingand fixing double loop earthingwith GI plate of 600x600x6.3 mm thick electrodecomplete with material such as thimble, nuts and bolts, charcoal, saltas per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) GI wire 25x3mm 15HP to 50HP |
| 126 | Providing and installation of sensor based auto cut off system for dry run condition of submersible pump as per approved specification and as directed by Engineer-in-Charge |
| 127 | S/E of Submersible Pumping Machinery for T/Well at Shiv Bari |
| 128 | Supply ofsubmersiblepumping set of reputed make such as KSB/ Calama / BS/ Worthigton / Sabar/ Seerex /Johnston / Amrut/ lubi/ Hindustan,Groundfosconfirming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ; 5659-1978 with upto date amendments, suitable for raw / clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to submersible motor of same as that of offered submersible pump make confirming to BIS ;9283-1979 with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with doublemechanicalseal in oil chamber and grease packed, lubricated bearing and provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum weartear.It should also be fitted with a device to make up expantion of water with heating of motor. The pumpset should include water level guard i/c cable ,errection clamps, cable clips and depth gauge etc. and suitable for opertion on data given below. a Pumps :- Specifications i) Makeii) Modeliii)No. of stages iv) Manufacter\"s certificate to be attached Performancei) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speedv) Insulation. |
| 129 | Discharge =( Q) 4.37 LPS |
| 130 | Total Head =( H)68.60 Mts. |
| 131 | a) SWL in Tubewell= 10.00 Mtr. bgl. |
| 132 | c) R.L. point of discharge = 491.50 Mtr. |
| 133 | d) Seasonal fluctuation + draught condition + bowl assembly. 9.00 Mtrs. |
| 134 | e) Drawdown in Tubewell=10.00 Mtrs. |
| 135 | f) R.L of lowest point of pumpset installation = 430.40 Mtrs. |
| 136 | g) Static Column lift= 37.00 Mtrs. |
| 137 | Rising main. Column Pipe. |
| 138 | Length 200 Mtrs.Length 37.00 mtr. |
| 139 | Dia meter. 80mmDia 125 mm |
| 140 | Class GMS Class GMS. (M) |
| 141 | Pumping hours hours |
| 142 | Altitude of installations above M.S.L.__________mtr. |
| 143 | Characteristic of water. |
| 144 | a) Temperature _______ Deg Cel. |
| 145 | b) Turbidity________JTU. |
| 146 | c) Allkanity. ___________mg/ l Ca Co3 |
| 147 | d) Size of solids____________mm |
| 148 | e) others |
| 149 | Depth of T/wellmtr. |
| 150 | Dia of T/ well assembly 200mm. |
| 151 | Length of assembly pipe. |
| 152 | Dia of housing pipe300 mm. |
| 153 | Length of housing pipe |
| 154 | OPERATINGCONDITIONS. |
| 155 | Type of Current :-A.C.Three Phase. |
| 156 | Frequency:- 50 Cycles /Sec. |
| 157 | Rated Voltage 415 +/- 15 % Volts. |
| 158 | System of earthing: Double Loop earthing as per BIS 3843-1987 Latest. |
| 159 | Speed of Revolution____________ RPM 2900 |
| 160 | MOTOR. |
| 161 | Ref. to BIS code BIS 9283-1979 with upto date amendments. |
| 162 | Type of enclosure of motor: As per BIS ; 4691-1985 ( latest ) |
| 163 | Mechanical out put in H.P. |
| 164 | Class of insulation:Class B |
| 165 | The motor should be able to withstand initial current of 2.50 times the rated current for two minutes without suffering damages of permanent deformations. |
| 166 | PUMP |
| 167 | Ref. to BIS code ;BIS ; 5659-1978 with upto date amendments. |
| 168 | Drive Type: Electric driven. |
| 169 | Operating Range:-15 % to+10 % of Total head at duty point. |
| 170 | Deliver size of Pump :________( To be quoted by tenderer.) |
| 171 | Providing ICTP Main Switch with HRC fuses ofL&T/ Havells make and having capacity 30%extra of the operational rating as per IS : 13947-P I & II with upto date amendments. ICTP Switch:i) Make :ii) Type :iii) Capacity : 32 Amp. |
| 172 | ProvidingMSSheetsteel fabricated floor mounted closed ( Almirah type ) switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections.Panel /Switch Board. i) Drawing.ii) layout Plan. |
| 173 | MCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder with or withoutintial oil filling asthe case may be with neutral linked under voltagereleases as per IS ; 2516-1985 with upto date amendments. MCB 1) Make. ii) Typeiii) Range. 32 Amp. iv) Capacity. |
| 174 | ii) ELCB of recommendedmakeL&T / Havellsas per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off springcondition of the circuit breaker for over current protection.The circuit should be equiped with magnet thermal releasewith metallic tape CTS. It shouldalso be fitted with earth fault for tripping of breakeron occurence of Earth fault. ELCB 1) Make. ii) Type iii) Range. 32 Amp.iv) Capacity. |
| 175 | iii) The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage,reverse phasing,overloading and phase voltage difference as per IS; 3842 ( Latest Edition ) Volatage Monitor Relayi) Makeii ) Type iii) Range 0-500 |
| 176 | b) A.C. supply,voltmeter of recommended make A.E / L&T of suitable range with selector switches as per IS ;1248-1983 with latest amendments.Voltmeter i) Make ii ) Typeiii) Range 0-500 |
| 177 | c) AC supply ammeter of A.E/ L&T make of suitable range with selector switches and CIS operated as per IS :1248 ( P-I&II ) -1983 with upto date amendments. Ammeter i) Makeii) Type 30 Amp |
| 178 | d) Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS ;8084-1976 and IS :11353-1985 read with BIS ; 5578 -1985 with upto date amendments including. Bus Bar Chamber i) Type ii) Makeiii) Rating |
| 179 | Three phase indicator lamps complete with toggle switches for indivual motors as per IS 3452 ( P- I&II ) withupto date amendments. 3 phase indicators |
| 180 | e) Capacitor ofBHEL / GEC / L&T / Mecheilmake asperIS ; 2834-1968with upto date amendments,to raise the power factor at site to 0.95 for directconnections to induction motor individually of requiredKVA ratingaccordingto H.P. offered including cables as per releventISI code ( ofSeimens / Glocter / IEC make ) frombus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments . Rating of capacitor will be approved by HPSEB. Capacitori) Type ii) Makeiii) Range 3 KVAR |
| 181 | Providing suitablestarter ofL&T /BHEL make as per IS : 13947-IIwith upto date \"amendments for Squirrel cage / Slipringmotor mounted on panel board with magnetic type over load release and dashpot, time lag, under voltage release, with or without initial oil filling as the case may be with single phase preventor as perIS ;1248 ( P-V ) 1983with up to date amendments.Starter i) Type ii) Make Single phase preventor i) Typeii) Make |
| 182 | Providing and fixing double flanged Cast IronSliuce valve of Leader / Kirloskar/Kartar/LP brand approved makefor the Column pipe of pump and capable of withstanding thenormal seat pressure and asperIS 780-1992with latest ammendments Class PN 1.00 For Column Pipe 80 mm diaSluice valve i) Makeii) Class PN 1.00iii) Material cast iron |
| 183 | Providing and fixing digital pressure gauge of Prega / Precision / Fiebig make complete with all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendementsPressure Gauge i) Make |
| 184 | Supply of PVC jointless,flat water proof cable with copper conductoras per BIS 694-1998 latest with upto date ammendments of Havelles/Finolex makesuitablefor the pumpsets offeredfrom MCBtomotorincluding allother electrical equipments / accessories such as thimble, flexible pipe,solder, nuts and bolts, cable glands, clips etc, laid in pipes or trenches under floor.The type, size and make shall be subject to approval of HPSEB authorities. Submersible cablei) Finolex/ Havells make ii) Size 2.50 mm2 (iii) Core=3 |
| 185 | Providing and Lowering ofGMSColumn pipe for assembly 80 mm dia including MS flanges\" of Table 17 as per IS : 6392-1971 with upto date amendments, rubber / asbestos gasket of min.3 mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 .The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated under item No.5 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction ofRising main .The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2 Nos.) at the top of T/well assembly, and as per the direction of Engineer - in - Charge. Column pipei) Size 80 mm dia ii) Class (M)iii) Length |
| 186 | Installation of all items appearing as aboveas per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge. |
| 187 | Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 ( P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay Finolex/ Havellsmakeincludingallother accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A) Supply side from meter of HPSEB to Bus Bar and Switchi) Size 2.50 mm2 ii) Makeiii) Type iv) Capacityv) core |
| 188 | Providingand fixing double loop earthingwith GI plate of 600x600x6.3 mm thick electrodecomplete with material such as thimble, nuts and bolts, charcoal, saltas per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) GI wire 25x3mm |
| 189 | Providing and installation of sensor based auto cut off system for dry run condition of submersible pump as per approved specification and as directed by Engineer-in-Charge |
| 190 | S/E of Submersible Pumping Machinery for T/Well at Amboa |
| 191 | Supply ofsubmersiblepumping set of reputed make such as KSB/ Calama / BS/ Worthigton / Sabar/ Seerex /Johnston / Amrut/ lubi/ Hindustan,Groundfosconfirming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ; 5659-1978 with upto date amendments, suitable for raw / clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to submersible motor of same as that of offered submersible pump make confirming to BIS ;9283-1979 with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with doublemechanicalseal in oil chamber and grease packed, lubricated bearing and provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum weartear.It should also be fitted with a device to make up expantion of water with heating of motor. The pumpset should include water level guard i/c cable ,errection clamps, cable clips and depth gauge etc. and suitable for opertion on data given below. a Pumps :- Specifications i) Makeii) Modeliii)No. of stages iv) Manufacter\"s certificate to be attached Performancei) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speedv) Insulation. |
| 192 | Discharge =( Q) 14.80 LPS |
| 193 | Total Head=( H)78.14 Mts. |
| 194 | a) SWL in Tubewell = 29.88Mtr. bgl. |
| 195 | c) R.L. point of discharge = 511.00 Mtr. |
| 196 | d) Seasonal fluctuation + draught condition + bowl assembly. 9.00 Mtrs. |
| 197 | e) Drawdown in Tubewell=10.67 Mtrs. |
| 198 | f) R.L of lowest point of pumpset installation = 458.45Mtrs. |
| 199 | g) Static Column lift = 59.55 Mtrs. |
| 200 | Rising main. Column Pipe. |
| 201 | Length 35 Mtrs.Length 59.55 mtr. |
| 202 | Dia meter. 80mm Dia 80 mm |
| 203 | Class GMSClass GMS. (M) |
| 204 | Pumping hours hours |
| 205 | Altitude of installations above M.S.L.__________mtr. |
| 206 | Characteristic of water. |
| 207 | a) Temperature _______ Deg Cel. |
| 208 | b) Turbidity________JTU. |
| 209 | c) Allkanity. ___________mg/ l Ca Co3 |
| 210 | d) Size of solids____________mm |
| 211 | e) others |
| 212 | Depth of T/wellmtr. |
| 213 | Dia of T/ well assembly 300/200mm. |
| 214 | Length of assembly pipe. |
| 215 | Dia of housing pipe300 mm. |
| 216 | Length of housing pipe |
| 217 | OPERATINGCONDITIONS. |
| 218 | Type of Current :-A.C.Three Phase. |
| 219 | Frequency:- 50 Cycles /Sec. |
| 220 | Rated Voltage 415 +/- 15 % Volts. |
| 221 | System of earthing: Double Loop earthing as per BIS 3843-1987 Latest. |
| 222 | Speed of Revolution____________ RPM 2900 |
| 223 | MOTOR. |
| 224 | Ref. to BIS code BIS 9283-1979 with upto date amendments. |
| 225 | Type of enclosure of motor: As per BIS ; 4691-1985 ( latest ) |
| 226 | Mechanical out put in H.P. |
| 227 | Class of insulation:Class B |
| 228 | The motor should be able to withstand initial current of 2.50 times the rated current for two minutes without suffering damages of permanent deformations. |
| 229 | PUMP |
| 230 | Ref. to BIS code ;BIS ; 5659-1978 with upto date amendments. |
| 231 | Drive Type: Electric driven. |
| 232 | Operating Range:-15 % to+10 % of Total head at duty point. |
| 233 | Deliver size of Pump :________( To be quoted by tenderer.) |
| 234 | Providing ICTP Main Switch with HRC fuses ofL&T/ Havells make and having capacity 30%extra of the operational rating as per IS : 13947-P I & II with upto date amendments. ICTP Switch:i) Make :ii) Type :iii) Capacity : 63 Amp. |
| 235 | ProvidingMSSheetsteel fabricated floor mounted closed ( Almirah type ) switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections.Panel /Switch Board. i) Drawing.ii) layout Plan. |
| 236 | MCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder with or withoutintial oil filling asthe case may be with neutral linked under voltagereleases as per IS ; 2516-1985 with upto date amendments. MCB 1) Make. ii) Typeiii) Range. 40 Amp. iv) Capacity. |
| 237 | ii) ELCB of recommendedmakeL&T / Havellsas per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off springcondition of the circuit breaker for over current protection.The circuit should be equiped with magnet thermal releasewith metallic tape CTS. It shouldalso be fitted with earth fault for tripping of breakeron occurence of Earth fault. ELCB 1) Make. ii) Type iii) Range. 40 Amp.iv) Capacity. |
| 238 | iii) The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage,reverse phasing,overloading and phase voltage difference as per IS; 3842 ( Latest Edition ) Volatage Monitor Relayi) Makeii ) Type iii) Range 0-500 |
| 239 | b) A.C. supply,voltmeter of recommended make A.E / L&T of suitable range with selector switches as per IS ;1248-1983 with latest amendments.Voltmeter i) Make ii ) Typeiii) Range 0-500 |
| 240 | c) AC supply ammeter of A.E/ L&T make of suitable range with selector switches and CIS operated as per IS :1248 ( P-I&II ) -1983 with upto date amendments. Ammeter i) Makeii) Type 60 Amp |
| 241 | d) Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS ;8084-1976 and IS :11353-1985 read with BIS ; 5578 -1985 with upto date amendments including. Bus Bar Chamber i) Type ii) Makeiii) Rating |
| 242 | Three phase indicator lamps complete with toggle switches for indivual motors as per IS 3452 ( P- I&II ) withupto date amendments. 3 phase indicators |
| 243 | e) Capacitor ofBHEL / GEC / L&T / Mecheilmake asperIS ; 2834-1968with upto date amendments,to raise the power factor at site to 0.95 for directconnections to induction motor individually of requiredKVA ratingaccordingto H.P. offered including cables as per releventISI code ( ofSeimens / Glocter / IEC make ) frombus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments . Rating of capacitor will be approved by HPSEB. Capacitori) Type ii) Makeiii) Range 4 KVAR |
| 244 | Providing suitablestarter ofL&T /BHEL make as per IS : 13947-IIwith upto date \"amendments for Squirrel cage / Slipringmotor mounted on panel board with magnetic type over load release and dashpot, time lag, under voltage release, with or without initial oil filling as the case may be with single phase preventor as perIS ;1248 ( P-V ) 1983with up to date amendments.Starter i) Type ii) Make Single phase preventor i) Typeii) Make |
| 245 | Providing and fixing double flanged Cast IronSliuce valve of Leader / Kirloskar/Kartar/LP brand approved makefor the Column pipe of pump and capable of withstanding thenormal seat pressure and asperIS 780-1992with latest ammendments Class PN 1.00 For Column Pipe 100 mm diaSluice valve i) Makeii) Class PN 1.00iii) Material cast iron |
| 246 | Providing and fixing digital pressure gauge of Prega / Precision / Fiebig make complete with all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendementsPressure Gauge i) Make |
| 247 | Supply of PVC jointless,flat water proof cable with copper conductoras per BIS 694-1998 latest with upto date ammendments of Havelles/Finolex makesuitablefor the pumpsets offeredfrom MCBtomotorincluding allother electrical equipments / accessories such as thimble, flexible pipe,solder, nuts and bolts, cable glands, clips etc, laid in pipes or trenches under floor.The type, size and make shall be subject to approval of HPSEB authorities. Submersible cablei) Finolex/ Havells make ii) Size 4.00 mm2 (iii) Core=3 |
| 248 | Providing and Lowering ofGMSColumn pipe for assembly 100 mm dia including MS flanges\" of Table 17 as per IS : 6392-1971 with upto date amendments, rubber / asbestos gasket of min.3 mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 .The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated under item No.5 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction ofRising main .The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2 Nos.) at the top of T/well assembly, and as per the direction of Engineer - in - Charge. Column pipei) Size 100 mm dia ii) Class (M)iii) Length |
| 249 | Installation of all items appearing as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge. |
| 250 | Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 ( P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay Finolex/ Havellsmakeincludingallother accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A) Supply side from meter of HPSEB to Bus Bar and Switchi) Size 600 mm2 ii) Makeiii) Type iv) Capacityv) core |
| 251 | Providingand fixing double loop earthingwith GI plate of 600x600x6.3 mm thick electrodecomplete with material such as thimble, nuts and bolts, charcoal, saltas per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) GI wire 25x3mm 15HP to 50HP |
| 252 | Providing and installation of sensor based auto cut off system for dry run condition of submersible pump as per approved specification and as directed by Engineer-in-Charge |
| 253 | Centrifugal Pumping Machinery alongwith allied accessories for GUGLEHAR) (Rising Main) |
| 254 | Providinghorizontal spindle, horizontal / radialsplit casing /end suction ( backpullout arrangement ) Single /double /multi stage ofKirloskar / KSB/ Hindustan/ lubbi/ Groundfos Crupton KSB/Calama/BS/ makeas per BIS IS 1520-1980 with upto date ammendments read with IS: 9137-1978 or latest edition suitable for lifting water for under mentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible couplingon a common castiron / cast steelbase plate (base plate to be framed from the manufacturers of the pumpingunit only)to slipring / Squirrel cage screen protected drip proof induction motor / motors of standard make such as Crompton / NGEF / GEC / Seimens /Jyoti/ Kirloskar BHEL / ABB suitablefor operation on 415 (+/-15%) volts. 50 Cycles /Sec. 3 phase AC electric supply of 2900RPM.The power of electric motor/ motors shouldbe at least +10% in excess of the maximum power required by the pump / pumpsin the Operation range of (+10%) and (-15%) of the duty point head. The motor / motors as per IS 325IS -1978 with upto date amendments read with IS 900 -1972. It should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements. |
| 255 | Discharge=( Q) 5.26 LPS |
| 256 | Total Head=( H) 196.74 Mts. |
| 257 | a)LWL In clear water Tank =406.50 mtr |
| 258 | b) R.L. of shaft = 405.00 Mtrs. |
| 259 | c) R.L. of discharge Point. = 511.00 mtrs. |
| 260 | d) Suction lift. +tivemtrs. |
| 261 | e)Discharge Head = 0.0 mtrs. |
| 262 | f) Static Head = 104.50 mtrs. |
| 263 | Rising main. |
| 264 | Length =3000.00 mtrs. |
| 265 | Diameter =80mm. dia |
| 266 | ClassGMS Tube (MG) |
| 267 | Pumping hours. 16.00hours. |
| 268 | Altitude of installations above M.S.L425 mtrs. |
| 269 | Characteristic of Water |
| 270 | a)Temperature________Deg.Col. |
| 271 | b)Turbidity ________ JTU |
| 272 | c) Alloanity _________ mg/1 ca Co3 |
| 273 | d)Size of solids__________ mm |
| 274 | e) Others. |
| 275 | (a) Pumps: Specifications: |
| 276 | i)Make |
| 277 | ii)Model. |
| 278 | iii)No.of stages:- |
| 279 | iv)Manufacturers |
| 280 | certificate to be attached. |
| 281 | Performance |
| 282 | i)Discharge:- |
| 283 | ii)Total Head:- |
| 284 | iii)B.H.P. |
| 285 | iv)Efficiency: |
| 286 | vi)Performance Curve to be attached. |
| 287 | b)Motors: Specifications. |
| 288 | i)Make |
| 289 | ii)Model |
| 290 | iii)Rating |
| 291 | iv)Speed. |
| 292 | v)Insulation. |
| 293 | (C) Coupling: |
| 294 | (d) Base Plate. |
| 295 | Providing ICTP Main Switch with HRC fuses ofL&T/ Havells make and having capacity 30%extra of the operational rating as per IS : 13947-P I & II with upto date amendments. ICTP Switch:i) Make :ii) Type :iii) Capacity : 63 Amp. |
| 296 | ProvidingMSSheetsteel fabricated floor mounted closed ( Almirah type ) switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections..Panel /Switch Board. i) Drawing.ii) layout Plan. |
| 297 | MCB ofL&T/ Havellsmake of suitable capacity on incoming feeder with or withoutintial oil filling asthe case may be with neutral linked under voltagereleases as per IS ; 2516-1985 with upto date amendments. MCB1) Make. ii) Typeiii) Range. 63 Amp. iv) Capacity |
| 298 | ii) ELCB of recommendedmakeL&T / Havells as per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off springcondition of the circuit breaker for over current protection.The circuit should be equiped with magnet thermal releasewith metallic tape CTS. It shouldalso be fitted with earth fault for tripping of breakeron occurence of Earth fault. ELCB 1) Make. ii) Type iii) Range. 63 Amp.iv) Capacity. |
| 299 | iii) The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage,reverse phasing,overloading and phase voltage difference as per IS; 3842 ( Latest Edition ) Volatage Monitor Relayi) Makeii ) Type iii) Range 0-500 |
| 300 | 100 mm diameter circular, A.C. supply, voltmeter ofrecommended make Havells / AE / L&T of suitable range with selector switches as per IS: 4064-1978 with latest up to ammendments.Voltmeteri) Make ii ) Typeiii) Range 0-500 |
| 301 | Power factor meter of standard make as per relevent IS code with upto date ammendments. Power factor meteri) Make ii ) Typeiii) Range 0-500 |
| 302 | Frequency meter of standard make as per relevent IS code with upto date ammendments. Frequency meteri) Make ii ) Typeiii) Range 0-500 |
| 303 | c) AC supply ammeter of A.E/ L&T make of suitable range with selector switches and CIS operated as per IS :1248 ( P-I&II ) -1983 with upto date amendments. Ammeter i) Makeii) Type 60 Amp |
| 304 | d) Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS ;8084-1976 and IS :11353-1985 read with BIS ; 5578 -1985 with upto date amendments including. Bus Bar Chamber i) Type ii) Makeiii) Rating |
| 305 | Three phase indicator lamps complete with toggle switches for indivual motors as per IS 3452 ( P- I&II ) withupto date amendments. 3 phase indicators |
| 306 | e) Capacitor ofBHEL / GEC / L&T / Mecheilmake asperIS ; 2834-1968with upto date amendments,to raise the power factor at site to 0.95 for directconnections to induction motor individually of requiredKVA ratingaccordingto H.P. offered including cables as per releventISI code ( ofSeimens / Glocter / IEC make ) frombus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments . Rating of capacitor will be approved by HPSEB. Capacitori) Type ii) Makeiii) Range 6 KVAR |
| 307 | Providing suitablestarter ofL&T /BHEL make as per IS : 13947-IIwith upto date \"amendments for Squirrel cage / Slipringmotor mounted on panel board with magnetic type over load release and dashpot, time lag, under voltage release, with or without initial oil filling as the case may be with single phase preventor as perIS ;1248 ( P-V ) 1983with up to date amendments.Starteri) Typeii) Make Single phase preventor i) Typeii) Make |
| 308 | Providing and fixing double flanged cast steel Sluice valve as per BIS 1414/API 600with upto date ammendmnentofKirloskar / Leader/ Kartar/ LP brand approved make for the suction pipe of50 mm dia ClassASA 150 forthe suctionline of pump .SluiceValvei)Make ii) ClassASA 150iii)Test working head.iv) Material: Cast Steel |
| 309 | Providing and fixingdouble flanged Cast steel Sluice valve ofLeader / Kirloskar/ Kartar/LP brandapproved make of 50 mm dia forthe delivery line of pumpand capable of with standing normal Seat Pressure as per BIS 1414/API 600 with upto dateammendments.For delivery pipe of pump. 65 mm SluiceValve i)Make ii) ClassASA 150 iii)Test working head iv) Material:-Cast Steel |
| 310 | Providingand fixing double flanged swing typecast steel Reflux valves of Leader/Kirloskar/ Kartar/LP brand make of 65 mm dia ClassASA 150 for delivery line of pump and capable of with standing the normal seat pressure and as per IS: 1868/API 6Dwith upto date ammendments. 65 mm dia Reflux Valve i)Make ii) ClassASA 150iii)Test working head. iv) Material:-Cast Steel |
| 311 | Providing and fixingdouble flanged swing typecast steel Refluxvalves of Leader /Kirloskar/ Kartar/ LP brandapproved make of80 mm dia ClassASA 150 having by pass arrangement for the Rising main of the Pumpand capable of with standing the normal seat pressure and as perIS: 1868/API 6D with upto date ammendments.Reflux Valve i)Makeii) ClassASA 150 iii)Test working head. iv) Material:-Cast Steel |
| 312 | Providing & fixing pressure gauge of Prega / Precision / Fiebig make complete with all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendementsPressure Gauge i) Make |
| 313 | Installation of all items appearing as aboveas per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge. |
| 314 | Providing and Fixing double flangedGMS pipingwork ( Layout to be approved by Engineer-in-Charge). for suction and delivery pipes suitable to pumps offeredand common header as per the risingmain respectively complete with all specials such as bends,Tees, Reducers / Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing including rubber / asbestos gasket of 3 mm thickness as per IS : 2712-1972 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.50 times total head stipulated under item No.30.The size of various components to be as under:- |
| 315 | i) Suction Pipe 50 mm dia. |
| 316 | ii)Delivery Pipe 65 mm dia. |
| 317 | iii) Common Header 65 mm dia. and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of80 mm dia to be joined. |
| 318 | Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 ( P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay Finolex/ Havellsmakeincludingallother accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A) Supply side from meter of HPSEB to Bus Bar and Switchi) Size 6mm2ii) Makeiii) Typeiv) Capacity v) coreB) Motor side (i) Size: 10.00 mm2 ii) Make: iii) Type: |
| 319 | Providingand fixing double loop earthingwith Copper plate of 600x600x6.3mm thick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,25x5mm stripas per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge.. i) GI wire 6 SWG |
| 320 | Providing and installation of sensor based auto cut off system for dry run condition of submersible pump as per approved specification and as directed by Engineer-in-Charge |
| 321 | Centrifugal Pumping Machinery alongwith allied accessories for Amboa) |
| 322 | Providinghorizontal spindle, horizontal / radialsplit casing /end suction ( backpullout arrangement ) Single /double /multi stage ofKirloskar / KSB/ Hindustan/ lubbi/ Groundfos Crupton KSB/Calama/BS/ makeas per BIS IS 1520-1980 with upto date ammendments read with IS: 9137-1978 or latest edition suitable for lifting water for under mentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible couplingon a common castiron / cast steelbase plate (base plate to be framed from the manufacturers of the pumpingunit only)to slipring / Squirrel cage screen protected drip proof induction motor / motors of standard make such as Crompton / NGEF / GEC / Seimens /Jyoti/ Kirloskar BHEL / ABB suitablefor operation on 415 (+/-15%) volts. 50 Cycles /Sec. 3 phase AC electric supply of 2900RPM.The power of electric motor/ motors shouldbe at least +10% in excess of the maximum power required by the pump / pumpsin the Operation range of (+10%) and (-15%) of the duty point head. The motor / motors as per IS 325IS -1978 with upto date amendments read with IS 900 -1972. It should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements. |
| 323 | Discharge =( Q) 4.57 LPS |
| 324 | Total Head =( H) 264.77 Mts. |
| 325 | a)LWL In clear water Tank=509.50 mtr |
| 326 | b) R.L. of shaft= 508.00 Mtrs. |
| 327 | c) R.L. of discharge Point. = 638.00 mtrs. |
| 328 | d) Suction lift. +tivemtrs. |
| 329 | e)Discharge Head = 0.0 mtrs. |
| 330 | f) Static Head = 130.00 mtrs. |
| 331 | Rising main. |
| 332 | Length =5850.00 mtrs. |
| 333 | Diameter =80 mm. dia |
| 334 | ClassGMS Tube (MG) |
| 335 | Pumping hours. 16.00hours. |
| 336 | Altitude of installations above M.S.L425 mtrs. |
| 337 | Characteristic of Water |
| 338 | a)Temperature________Deg.Col. |
| 339 | b)Turbidity ________ JTU |
| 340 | c) Alloanity _________ mg/1 ca Co3 |
| 341 | d)Size of solids__________ mm |
| 342 | e) Others. |
| 343 | (a) Pumps: Specifications: |
| 344 | i)Make |
| 345 | ii)Model. |
| 346 | iii)No.of stages:- |
| 347 | iv)Manufacturers |
| 348 | certificate to be attached. |
| 349 | Performance |
| 350 | i)Discharge:- |
| 351 | ii)Total Head:- |
| 352 | iii)B.H.P. |
| 353 | iv)Efficiency: |
| 354 | vi)Performance Curve to be attached. |
| 355 | b)Motors: Specifications. |
| 356 | i)Make |
| 357 | ii)Model |
| 358 | iii)Rating |
| 359 | iv)Speed. |
| 360 | v)Insulation. |
| 361 | (C) Coupling: |
| 362 | (d) Base Plate. |
| 363 | Providing ICTP Main Switch with HRC fuses ofL&T/ Havells make and having capacity 30%extra of the operational rating as per IS : 13947-P I & II with upto date amendments. ICTP Switch:i) Make :ii) Type :iii) Capacity : 63 Amp. |
| 364 | ProvidingMSSheetsteel fabricated floor mounted closed ( Almirah type ) switch board including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections..Panel /Switch Board. i) Drawing.ii) layout Plan. |
| 365 | MCB ofL&T/ Havellsmake of suitable capacity on incoming feeder with or withoutintial oil filling asthe case may be with neutral linked under voltagereleases as per IS ; 2516-1985 with upto date amendments. MCB1) Make. ii) Typeiii) Range. 63.00 Amp. iv) Capacity |
| 366 | ii) ELCB of recommendedmakeL&T / Havells as per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off springcondition of the circuit breaker for over current protection.The circuit should be equiped with magnet thermal releasewith metallic tape CTS. It shouldalso be fitted with earth fault for tripping of breakeron occurence of Earth fault. ELCB 1) Make. ii) Type iii) Range. 63.00 Amp.iv) Capacity. |
| 367 | iii) The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage,reverse phasing,overloading and phase voltage difference as per IS; 3842 ( Latest Edition ) Volatage Monitor Relayi) Makeii ) Type iii) Range 0-500 |
| 368 | 100 mm diameter circular, A.C. supply, voltmeter ofrecommended make Havells / AE / L&T of suitable range with selector switches as per IS: 4064-1978 with latest up to ammendments.Voltmeteri) Make ii ) Typeiii) Range 0-500 |
| 369 | Power factor meter of standard make as per relevent IS code with upto date ammendments. Power factor meteri) Make ii ) Typeiii) Range 0-500 |
| 370 | Frequency meter of standard make as per relevent IS code with upto date ammendments. Frequency meteri) Make ii ) Typeiii) Range 0-500 |
| 371 | c) AC supply ammeter of A.E/ L&T make of suitable range with selector switches and CIS operated as per IS :1248 ( P-I&II ) -1983 with upto date amendments. Ammeter i) Makeii) Type 30 Amp. |
| 372 | d) Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS ;8084-1976 and IS :11353-1985 read with BIS ; 5578 -1985 with upto date amendments including. Bus Bar Chamber i) Type ii) Makeiii) Rating |
| 373 | Three phase indicator lamps complete with toggle switches for indivual motors as per IS 3452 ( P- I&II ) withupto date amendments. 3 phase indicators |
| 374 | e) Capacitor ofBHEL / GEC / L&T / Mecheilmake asperIS ; 2834-1968with upto date amendments,to raise the power factor at site to 0.95 for directconnections to induction motor individually of requiredKVA ratingaccordingto H.P. offered including cables as per releventISI code ( ofSeimens / Glocter / IEC make ) frombus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments . Rating of capacitor will be approved by HPSEB. Capacitori) Type ii) Makeiii) Range 7.00 KVAR |
| 375 | Providing suitablestarter ofL&T /BHEL make as per IS : 13947-IIwith upto date \"amendments for Squirrel cage / Slipringmotor mounted on panel board with magnetic type over load release and dashpot, time lag, under voltage release, with or without initial oil filling as the case may be with single phase preventor as perIS ;1248 ( P-V ) 1983with up to date amendments.Starteri) Typeii) Make Single phase preventor i) Typeii) Make |
| 376 | Providing and fixing double flanged cast steel Sluice valve as per BIS 1414/API 600with upto date ammendmnentofKirloskar / Leader/ Kartar/ LP brand approved make for the suction pipe of80 mm dia ClassASA 150 forthe suctionline of pump .SluiceValvei)Make ii) ClassASA 150iii)Test working head.iv) Material: Cast Steel |
| 377 | Providing and fixingdouble flanged Cast steel Sluice valve ofLeader / Kirloskar/ Kartar/LP brandapproved make of 80 mm dia forthe delivery line of pumpand capable of with standing normal Seat Pressure as per BIS 1414/API 600 with upto dateammendments.For delivery pipe of pump. 65 mm SluiceValve i)Make ii) ClassASA 150 iii)Test working head iv) Material:-Cast Steel |
| 378 | Providingand fixing double flanged swing typecast steel Reflux valves of Leader/Kirloskar/ Kartar/LP brand approved make of 80 mm dia ClassASA 150 for delivery line of pump and capable of with standing the normal seat pressure and as per IS: 1868/API 6Dwith upto date ammendments. 65 mm dia Reflux Valve i)Make ii) ClassASA 150iii)Test working head. iv) Material:-Cast Steel |
| 379 | Providing and fixingdouble flanged swing typecast steel Refluxvalves of Leader /Kirloskar/ Kartar/ LP brandapproved make of80 mm dia ClassASA 150 having by pass arrangement for the Rising main of the Pumpand capable of with standing the normal seat pressure and as perIS: 1868/API 6D with upto date ammendments. Reflux Valve i)Makeii)ClassASA 150 iii)Test working head. iv) Material:-Cast Steel |
| 380 | Providing & fixing pressure gauge of Prega / Precision / Fiebig make complete with all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendementsPressure Gauge i) Make |
| 381 | Installation of all items appearing as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge. |
| 382 | Providing and Fixing double flangedGMS pipingwork ( Layout to be approved by Engineer-in-Charge). for suction and delivery pipes suitable to pumps offeredand common header as per the risingmain respectively complete with all specials such as bends,Tees, Reducers / Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing including rubber / asbestos gasket of 3 mm thickness as per IS : 2712-1972 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.50 times total head stipulated under item No.30.The size of various components to be as under:- |
| 383 | i) Suction Pipe 50 mm dia. |
| 384 | ii)Delivery Pipe 65 mm dia. |
| 385 | iii) Common Header 65 mm dia. and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of80 mm dia to be joined. |
| 386 | Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554 ( P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay Finolex/ Havellsmakeincludingallother accessories such as thimble, flexible pipes, solder nuts and bolts,cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A) Supply side from meter of HPSEB to Bus Bar and Switchi) Size 4mm2ii) Makeiii) Typeiv) Capacity v) coreB) Motor side (i) Size: 10.00 mm2 ii) Make: iii) Type: |
| 387 | Providingand fixing double loop earthingwith Copper plate of 600x600x6.3mm thick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,25x5mm stripas per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge.. i) GI wire 6 SWG |
| 388 | Providing and installation of sensor based auto cut off system for dry run condition of submersible pump as per approved specification and as directed by Engineer-in-Charge |
| 389 | Schedele B2- Civil Work |
| 390 | (Pump house, boundary wall, Toilet & Septic Tank)Excavationinfoundation trenchesupto alldepthsin all classification ofearth work such as pick work, jumper work, saturated soil including bailing or pumping out water, blasting soft/hard rock or chieselling soft/ hard rock where blasting is prohibited, in all lifts includingtrimming and dressing of sides,levelling of beds to correct grade including,shoring,strutting, planking, timbering and dewateringwherever required,stacking the useable and unuseable material/soil separately and afterlaying, jointingandtestingofpipesreturningtheuseablesoilintrenchesin 15cm(fiften centimeter ) layersincluding consolidating of such deposited layer by rammingandwatering and then disposing of all surplus excavated soil /un-useable materials as directed within allleads andlifts including restoration of un-metalledsurface to its original condition andincluding cost of diversion for traffic, night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respect within all leads and lifts as per the directions of Engineer-in-Charge. |
| 391 | Providing and laying cement concrete 1:6:12 ( 1 cement : 6 sand : 12 graded stone aggregate 40 mm nominal size) and curing complete excluding the cost of form work in foundation and plinth comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 392 | Providing and laying cement concrete (M-10) 1:3:6 (1 cement: 3 sand : 6 crushed stone aggregate 40mm nominal size) and curing complete excluding the cost of form work in foundation and plinth including carriage ofmaterials withinall leadsand lifts complete in all respect to the entire satisfactionof Engineer-in-Charge. |
| 393 | Randam rubble Masonary / Polygonal rubble masonary( (un coursed/ brought to courses) with hard stoneof approved quality i/c levellingup at PL with cement conc.1:6:12 in cement motor 1:6 ( 1cemet :6 Sand )in foundation and plinth comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 394 | 1st. class brick work using common burnt clay building bricks in foundation and plinth in cement mortor 1:6 (1 cement: 6 sand ) comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 395 | Ist class brick work using common burnt clay building bricks in superstructure in cement mortor 1:6 (1 cement :6 sand) comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 396 | Providing and fixing pressed steel doors frames manufactured from commercial mild steel sheet of 1.25 mm thickness including hinges, jump lock jamb, beed and if required angle threshold of mild steel angle of section 50X25 mm or base ties of 1.25 mm pressed mild steel welded or regidly fixed together by mechanical means, adjustable lugs with split and tails to each jamb including steel but things 2.5 mm thick with gaurds, lock strike plate and shock as specified and applying a coat of approved steel primer after pretreatment of the surfacecomlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge.a) Profile A |
| 397 | Providing and fixing panneled glazed or panelled and glazed shutters for doors, windows and clerestory windows,including black enamelled iron butt hinges with necessary screws. 45 mm thick.2nd class deodar wood comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 398 | Providing form work with steel plates 3.15mm thick welded with angle iron in frame 30x30x5mm, so as to give a fair finish including centring shuttering ,strutting and propping etc.with wooden battens and ballies,height of propping and centring below supporting floor to ceilingnot exceeding 4 mtrs. andremoval of the same for in situ reinforced concrete and plain concrete work in comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. :- |
| 399 | Foundation footing bases of columns etc and mass concrete. |
| 400 | Flat surfacessuch as soffits of suspended floors, roofs, landing and the like floors etc. upto 200 mm thickness within all leads and lifts complete in all respect to the entire satisfactionand asper the direction of the Engineer-in-Charge. |
| 401 | Edges of slab and breaking in floor and walls under 20 cm wide in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 402 | Beams,cantilivers,girders and lintels sides and soffits of beams,beam haunchings, cantilivers , girders, bressumers and lintels not exceeding 1 metre in depth. |
| 403 | Providing and laying cement concrete work DESIGN MIX M20 not less than1:2:4 ( 1cement:2 sand: 4graded stone aggregate 20 mm nominal size )and curing complete excluding the cost of form work and reinforcementfor reinforced concrete work in:- |
| 404 | Foundation footings bases of columns and the like and mass concrete. |
| 405 | Suspended floors, roofs,landings and shelves and their supports, balconies, beams, girders, bressumers and cantilivers up to floor two level. |
| 406 | Providing tor steel reinforcement for RCC work including bending, binding and placing in positioncomplete up to floor two levelcomlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 407 | Half brick work using common burnt clay building bricks in super structure above plinth levelupto floor two level in cementmortor 1:4 ( 1 cement:4 sand ) 1st. classBrick work. comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 408 | Pointing on brick work with cement mortor 1:3 ( 1 cement: : 3 sand ) comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge.Raised and cut |
| 409 | Providing and laying brick tiles over mumty roofs grouted with cement motor 1:3 (1 cement : 3 Sand) over a 12 mm layer of Cement Motor 1:3 (1 cement : 3 Sand)and finished neat with in all leads and liftcomplete. |
| 410 | 6mm cement plaster to ceiling in CM 1:3 ( 1Cement :3 Sand) comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 411 | 15 mm cement plaster in single coat on rough side of brick/concrete stone walls for interior plastering up to floor two levels including arrises, internal rounded angles, chamfers and/or rounded angles not exceeding 80 mm in girth and finished even and smooth in cement mortar 1:6 (1 cement:6 sand)comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 412 | 20 mm cement plaster in single coat on rough side of brick/concrete stone walls for interior plastering up to floor two levels including arrises, internal rounded angles, chamfers and/or rounded angles not exceeding 80 mm in girth and finished even and smooth in cement mortar 1:6 (1 cement:6 sand)comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 413 | Providing & fixing M.S. grills of required pattern in wooden frame of window etc.with M.S. flats, square or round barswith round headedbolts and nuts by screws plain grills comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 414 | Providingand fixing wire gaugeshutters using galvanizedMS wire gauge of I.S.gauge designation 85G(eighty five ) with wire of dia 0.56 mm(zero point five six millimetre) for doors windows and clerestory windows including bright finished black enameled iron butt hinges with necessary screws 40mm(forty millimetre )thickofsecond class deodar woodwith in all leadsand lifts and as per the direction of the Engineer - in- Charge. |
| 415 | Boulder filling under floor dry hand packed tightly comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 416 | Providing plinth protection 50 mm thick in cement concrete 1:3:6 (1cement:3sand:6 graded stone aggregate 20 mm nominal size comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 417 | Constructing brick masonary \"U\" shape open surface drain with side wall. 15 x 22 cm in cement mortar 1:6 ( 1 cement : 6 sand) and inside plastering with cement plaster 1:3 ( 1 cement : 3 sand) including earth work and laying 10 cm cement concretein 1:5:10(1 cement : 5 sand :10 graded stone aggregate of40 mm nominal size) and 7.5 cm.cement concrete 1: 2:4 ( 1cement : 2 sand : 4 graded stone aggregate 20 mm nominal size ) and finished with a floating coat of neat cement complete as per standard design. |
| 418 | Providing 40x3mm flat iron hold fast 40 cms long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embedding in cement concrete block 30x10x15 cms 1:3:6 ( 1 cement :3 sand : 6 graded stone aggregate 20 mm nominal size ) complete in all respect as per the direction of the Engineer -in- Charge. |
| 419 | P/F MS fan clamps type 1 of 16 mm dia bar bent to shape with hooked ends in RCC slab during laying includingpainting the exposed portion of roof as per standard design complete in respect . |
| 420 | White washing with lime on undecorated wall surfaces two coats to give an even shade including thoroughly brooming the surface to remove all dirt , dust and other foreign matters comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 421 | Distempering with dry distemper of approved brand and manufacture (two coats) and of required shade on undecorated wall surfaces to give an even shade sand papered smooth comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 422 | Finishing wall with water proofing cement paint of approved brand and manufacture and of requiredshade on undecorated wall surface (two coats) to give an even shade after thoroughly brushing the surface to remove alldirt & remains of loose powdered materials complete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 423 | Providing and fixing sliding door bolts anodized transparent or dyed to required shade and colour with screws etc. complete in all respect300 x16 mm |
| 424 | Providing and fixing tower bolts barrel type anodized transport or dyed to required shade and colour with screws com lete in all respect.200 x 10 mm |
| 425 | Providing and fixing aluminium handle anodized transparent or dyed to required shade and colour with screws etc.complete in all respect 100 mm |
| 426 | Painting two coats (excluding priming coat) on new steel and other metal surfaces with enamel paint to give an even shade including cleaning the surface of dirt ,dust and other foreign matter with enamel with enamel paint other than white complete in all respect as per the direction of the Engineer-in-Charge. |
| 427 | Terrazzo tiles flooring with precast terrazzo tiles 20 mm thick with marble chips of specified sizes laid in floors,treads of steps and landings on a bed of 25 mm average thickness of cement mortar 1:6 (1 cement :6 sand) jointed with neat cement slurry mixed with pigment to match the shade of tiles(wherever required) including rubbing and polishing complete with tiles grey and yellow shades mediumin all leads and lifts complete in all respect to the entire satisfaction and as per the direction of the Engineer-in-Charge. |
| 428 | Steel work welded in built up sections,trusses and framed work including cutting hoisting fixing in position and applying a priming coat of red lead paint comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge.In gratings framed gaurd bar, ladderrailing brackets etc. |
| 429 | Providing and fixing toilet seat (Orissa Pattern) Cera make. complete in all respect as per the direction of the Engineer-in-Charge. |
| 430 | Providing and fixing of PVC water tank ( 500 litres) including all fittings complete in all respect as per the direction of the Engineer-in-Charge. |
| 431 | Providing and fixing of flushing cistern ( 5 litres)including all fittings complete in all respect as per the direction of the Engineer-in-Charge. |
| 432 | Providing and fixing Cast iron Manhole cover with frame having frames size of 500 mm dia with frame (Medium grade duty) weight of cover and frame to be not less than 116 Kg. |
| 433 | Providing and fixing sand cast/ cast iron spun spigot & socket soil waste and vent pipe 100 mm dia.complete in all respect as per the direction of the Engineer-in-Charge. |
| 434 | Wiringfor light/Fan point /Exhaust fan point/call bell point with 1.5 .mm Sq. PVC insulated copper conductor cable in surface /recessed PVC conduit as required including carriage of materials within all leads and lifts. Group \"C\" |
| 435 | Wiring for light/power plug with 2 x 4 Sq.mmPVC insulated copper conductor or single core cable in surface/recessed steel conduit alongwith 1 No.2.24 mm dia bar copper wire for loop earthing as required including carriage of materials within all leads and lifts. |
| 436 | Wiring for circuit wiring with 2 x 1.5 Sq.mm PVC insulated copper conductor single core cable in surface/recessed steel conduitas required including carriage of materials within all leads and lifts. |
| 437 | Wiring for sub-main wiring with the following size of PVC insulated copper conductor single core cable in surface/recessed steel conduit as required including carriage of materials within all leads and lifts.2x 6mm |
| 438 | Supplying and fixing metal box of 180 x 100 x 60 mm deep (Nominal size) on surface/ recess with suitable size phenolic leminated sheet cover fixing 3 pin 5/6 amps socket tumber/piano type switch connective painting etc. as required (for power plug) including carriage of materials within all leads and lifts. |
| 439 | Supplying and fixing 32 Amps rating 240 volts, L series miniature circuit breaker of following pole in the connections testing and connections etc. including carriage of materials existing MCB DB complete within all leads and lifts. Category \"A\",single pole. |
| 440 | Supplying and fixing 40 Amps to 63 Amps rating 240 Volts \"L\" series miniature circuit breaker of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as requiredincluding carriage of materials within all leads and lifts. |
| 441 | Supplying and fixing of following way single pole and neutral sheet steel MCB distribution board 240 volts on surface/recessedcomplete with tinned copper bar neutral link earth din bar detachable gland plate interconnection including painting earthing as required including carriage of materials within all leads and lifts. |
| 442 | Wiring for threepin 5/6 amp. Plug point with 1.5 mm sq. PVC including copper conductor cable i/c. providing and fixing three pin 5/6 amp. Socket outlet on switch board (in surface) recessed steel conduit wiring system and 5/6 amp. Tumble /piano type switch earthing as rerquiredincluding carriage of materials within all leads and lifts. . |
| 443 | Providing, installation, testing and commissioning of prewired flouroscent tube fitting complete with ballast, starter and capactors but excluding flouroscent tube rod, suitable to operate on 230 volts single phase A.C.supply directly on surface with copper wiring as required including carriage of materials within all leads and lifts tube fixture 1 x 40 watt box type category \"A\" |
| 444 | Providing / installing testing tube rods 40 watt4\" long complete in all respect.. |
| 445 | Providing, installing, testing and commissioning of ceiling fan and regulator including wiring the rod of standard length (upto 30cm) with 1.5 Sqmm PVC insulated copper conductor single core cabe etc. as required sweep type.Cat. A (1200 mm sweep) including carriage of material complete in all respect to the entire satisfaction as per the direction of the Engineer -in- Charge. |
| 446 | Earthing withG.I. pipe earth, pipe 4.5 mtrs length, 40mm dia including accessories and providing masonry enclousres with cover plate having locking arrangement and watering pipe etc.( but without charcal coke and salt) complete as required including carriage of materials within all leads and liftscomplete in all respect to the entire satisfaction and as per the direction of the Engineer -in- Charge. |
| 447 | Extra usingsalt and charcoal for pipe earthelectrode asrequired, including carriageofmaterials within all leads and liftscomplete in all respect to the entire satisfaction and as per the direction of the Engineer -in- Charge. |
| 448 | Supplying and laying 6 SWG G.I.wire at 0.50 mtr. below ground level for conductor earth electrode, including soldering etc. as required including carriage of materials within all leads and lifts complete in all respect to the entire satisfaction and as per the direction of the Engineer -in- Charge. |
| 449 | Supplying and fixing backellite batten/angle holder including connection as requiredincludingcarriage of materials within all leads and lifts complete in all respect to the entire satisfaction and as per the direction of the Engineer -in- Charge. |
| 450 | Supplying / fixing MVL light cast aluminium control gear housing complete with accessories 125 watts BPMV lamp deep drain aluminium housing acletic cover with toggle catches with best satisfaction of the Engineer-in-Charge including connection with 40 mm G.I. Pipe 1.5 mtrs Bend (1.00 and 0.50) mtrs. including nut & screw grouted with cement in the existing MCB including carriage of materials within all leads and lifts complete in all respect to the entire satisfaction and as per the direction of the Engineer -in- Charge. |
| 451 | Providing and connection of bulk head fitting of all size and shape containing one No. GLS lamp holder steel wire guard and lock complete with all accessories excluding GLS lamp including connection etc. required bull head fittingsCategory -A- |
| 452 | C/ORCC Collection tank MBR and S Retc)Excavationinfoundation trenchesupto alldepthsin all classification ofearth work such as pick work, jumper work, saturated soil including bailing or pumping out water, blasting soft/hard rock or chieselling soft/ hard rock where blasting is prohibited, in all lifts includingtrimming and dressing of sides,levelling of beds to correct grade including,shoring,strutting,planking,timbering and dewateringwherever required,stacking the useable and unuseable material/soil separately and afterlaying, jointingandtestingofpipesreturningtheuseablesoilintrenchesin 15cm(fiften centimeter ) layersincluding consolidating of such deposited layer by rammingandwatering and then disposing of all surplus excavated soil /un-useable materials as directed within allleads andlifts including restoration of un-metalledsurface to its original condition andincluding cost of diversion for traffic, night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respect within all leads and lifts as per the directions of Engineer-in-Charge. |
| 453 | Providing and laying cement concrete (M-10) 1:3:6 (1 cement: 3 sand : 6 crushed stone aggregate 40mm nominal size) and curing complete excluding the cost of form work in foundation and plinth including carriage ofmaterials withinall leadsand lifts complete in all respect to the entire satisfactionof Engineer-in-Charge. |
| 454 | Providing and laying cement concrete workDESIGN MIX M30 not less than 1:1.5:3(1 cement: 1.5 sand :3 crushed stone aggregate 20mm nominal size)and curing complete excluding cost of form work and reinforcement for reinforced concrete work in :- |
| 455 | Foundations, footings bases of columns and the like and mass concrete withinall leadsand liftscomplete in all respect to the entire satisfaction and as per the directions of Engineer-in-Charge. |
| 456 | Walls (any thickness but not less than 0.10 mtrs. thickness) including attached pilasters, buttersses, plinth and string courses etc. from top of foundation level upto floor two level. |
| 457 | Providing form work with steel plates 3.15mm.thick welded with angle iron in frame 30x30x5mm. so as to give a fair finish including centring, shuttering, strutting and propping etc. with wooden battens and ballies, height of propping and centring below supporting floor to ceiling not exceeding 4 Mtrs. and removal of the same for insitu-reinforced concrete & plain concrete work in :- |
| 458 | Vertical surfaces such as walls (any thickness) partitions and the like including attached pillasters, buttresses, plinth and string courses and the like within all leads and liftscomplete in all respect to the entire satisfaction and as per the directions ofEngineer-in-Charge. |
| 459 | Providing form work of ordinary timber plankings so as to give a rough finish including centring, shuttering, strutting and propping etc. height of propping and centring below supporting floor to ceililng not exceeding 4 metres and removal of the same for insitu reinforced concrete and plain concrete work in Arches upto 6 metres span completein all respect to the entire satisfaction and as per the directions ofEngineer-in-Charge. |
| 460 | Providing in RCC work smooth finishing of the exposed surface with cement mortar 1:3 (1 cement : 3 sand) complete in all respect to the entire satisfaction and as per the directions ofEngineer-in-Charge. |
| 461 | Providing and laying cement concrete workDESIGN MIX M 25 not linear than 1:1.5:3 (1 cement: 1.5 sand :3 crushed stone aggregate 20mm nominal size)and curing complete excluding cost of form work and reinforcement for reinforced concrete work in :- |
| 462 | Suspended Floor roofs, landing and shelves and their support balconies, beams, girders, bressumers and contilever upto floor two level completein all respect to the entire satisfaction and as per the directions ofEngineer-in-Charge. |
| 463 | Arches upto floor two level. |
| 464 | Providing Tor steel reinforcement for R.C.C. work including bending, binding and placing in position complete upto floor two levelwithin all leads and liftscompletein all respect to the entire satisfaction and as per the directions ofEngineer-in-Charge. |
| 465 | Steel work welded in built up sections, trusses and framed work, including cutting, hoisting ,fixing in position and applying a priming coat of red lead paintIn gratings, framed guard bars, ladders, railling, brackets and similar works within all leads and liftscompletein all respect to the entire satisfaction and as per the directions ofEngineer-in-Charge. . |
| 466 | Fixing inlet, outlet, over flow and scour pipe of GMS pipe of following internal dia (medium grade) including extra carriage within all leads and lifts and as per directions of the Engineer-in-charge. |
| 467 | Inlet , Outlet and Over flowpipe 100 mm dia.(M) |
| 468 | Scour pipe 100 mm dia. |
| 469 | Providing and fixing C.I. Sluice valve (With hand wheel) as per IS -780-1984class-I upto 300 mm dia (including brass spindle and as per IS; 2906-1984class -II dia >300 mm) complete with nuts, rubber insertion etc. complete ( The tail piece if required shall be measured and paid fior seperately ) PN 1.0 |
| 470 | Over flow pipe 100 mm dia |
| 471 | Over flow & Scour pipe 100 mm dia. |
| 472 | Constructing chamber for sluice valve, with CI surface box 100 mm top dia.,160 mm bottom dia and 180 mm deep (inside) with chained lidRCC top 1:2:4 mix (1 cement : 2 sand :4 graded stone aggregate 20 mm nominal size) 100 mm thick foundation concrete 1:5:10 mix (1cement : 5 sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortor 1 :3 (1 cement : 3 sand) finished with a floating coat of neat cement including curing complete. 600 x 600 x 750 mm inside size with 150 mm thick walls of RCC 1:2 :4 (1 cement :2 sand :4 graded stone aggregate 20 mm nominal size) complete with form work and reinforcement with 6 mm bars at not exceeding 150 mm centres both wayswithin all leads and liftscompletein all respect to the entire satisfaction and as per the directions ofEngineer-in-Charge. . |
| 473 | Providing and fixing Cast iron Manhole cover with frame having frames size of 500 mm dia with frame (Medium grade duty) weight of cover and frame to be not less than 116 Kg. |
| 474 | C/O OHSR tank 20 Mtrs. Staging heightMBR )Excavationinfoundation trenchesupto alldepthsin all classification ofearth work such as pick work, jumper work, saturated soil including bailing or pumping out water, blasting soft/hard rock or chieselling soft/ hard rock where blasting is prohibited, in all lifts includingtrimming and dressing of sides,levelling of beds to correct grade including,shoring,strutting,planking,timbering and dewateringwherever required,stacking the useable and unuseable material/soil separately and afterlaying, jointingandtestingofpipesreturningtheuseablesoilintrenchesin 15cm(fiften centimeter ) layersincluding consolidating of such deposited layer by rammingandwatering and then disposing of all surplus excavated soil /un-useable materials as directed within allleads andlifts including restoration of un-metalledsurface to its original condition andincluding cost of diversion for traffic, night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respect within all leads and lifts as per the directions of Engineer-in-Charge. |
| 475 | Providing and laying cement concrete (M-10) 1:3:6 (1 cement: 3 sand : 6 crushed stone aggregate 40mm nominal size) and curing complete excluding the cost of form work in foundation and plinth including carriage ofmaterials withinall leadsand lifts complete in all respect to the entire satisfactionof Engineer-in-Charge. |
| 476 | Providing and laying cement concrete workDESIGN MIX M30 not linear than 1:1.5:3 (1 cement: 1.5 sand :3 crushed stone aggregate 20mm nominal size)and curing complete excluding cost of form work and reinforcement for reinforced concrete work in :- |
| 477 | Foundations, footings bases of columns and the like and mass concrete withinall leadsand liftscomplete in all respect to the entire satisfaction and as per the directions of Engineer-in-Charge. |
| 478 | Columns, pillars posts and struts upto all heights. |
| 479 | Lintels, beams, girders, bressumers and cantilevers upto all heights. |
| 480 | Stair cases (except spiral stair cases) excluding landing but including preparing of the surface and finishing of nosing upto all heights. |
| 481 | Arches upto floor two level. |
| 482 | Suspended Floor, roofs, landing and shelves and theirsupport balconies, beams, girders, bressumers and contilever upto floor two levelwithinall leadsand lifts complete in all respect to the entire satisfactionas per the directions of Engineer-in-Charge . |
| 483 | Walls (any thickness but not less than 0.10 mtrs. thickness) including attached pilasters, buttersses, plinth and string courses etc. from top of foundation level. |
| 484 | Providing form work with steel plates 3.15mm.thick welded with angle iron in frame 30x30x5mm. so as to give a fair finish including centring, shuttering, strutting and propping etc. with wooden battens and ballies, height of propping and centring below supporting floor to ceiling not exceeding 4 Mtrs. and removal of the same for insitu-reinforced concrete & plain concrete work inall leadsand lifts complete in all respect to the entire satisfactionas per the directions of Engineer in -Charge :- |
| 485 | Foundation, footingsand basis of columns etc. and mass concrete within alllead and lifts complete in all respect to the entire satisfaction as per the directions of the Engineer-in-Charge.. |
| 486 | Columns, pillars, posts and struts Circular or curved in plan upto all heights. |
| 487 | Sides and soffits of beams, beam haunchings, cantilevers, bressumers and lintels not exceeding 1 Mtr. in depth in all heights from floors. |
| 488 | Vertical surfaces such as walls (any thickness) partitions and the like including attached pillasters, buttresses, plinth and string courses and the like. |
| 489 | Flat surfacessuch as soffits of suspended floors, roofs, landing and the like floors etc. upto 200 mm thickness within all leads and lifts complete in all respect to the entire satisfactionand asper the direction of the Engineer-in-Charge. |
| 490 | Stair cases with sloping or stepped soffits excluding landing upto all heights.. |
| 491 | Providing form work of ordinary timber plankings so as to give a rough finish including centring, shuttering, strutting and propping etc. height of propping and centring below supporting floor to ceililng not exceeding 4 metres and removal of the same for insitu reinforced concrete and plain concrete work inArches upto 6 metres span complete in all respect to the entire satisfactionand asper the direction of the Engineer-in-Charge. |
| 492 | Steel work welded in built up sections, trusses and framed work, including cutting, hoisting ,fixing in position and applying a priming coat of red lead paintIn gratings, framed guard bars, ladders, railling, brackets and similar works within all leads and lifts complete in all respect to the entire satisfactionand asper the direction of the Engineer-in-Charge. |
| 493 | Providing tor steel reinforcement for RCC work including bending, binding and placing in position complete in all respectincluding carriage of materials within all leads and liftscomplete in all respect to the entire satisfactionand asper the direction of the Engineer-in-Charge. |
| 494 | Providing plinth protection 50mm thick in cement concrete 1:3:6 (1 Cement : 3 Sand : 6 graded stone aggregated 20mm nominal size)including carriage of materials complete in all respect to the entire satisfactionand asper the direction of the Engineer-in-Charge. |
| 495 | Providing under layer for plinth protection of 75mm thick (unconsolidated) bed dry brick/stone aggregated 40mm nominal size with rammed and consolidated and grouted with fine sand including preparation of ground complete in all respect to the entire satisfactionand asper the direction of the Engineer-in-Charge.. |
| 496 | Providing and fixing MS manhole cover of 500 mm dia with frame (Medium grade duty) weight of cover and frame to be not less than 116 Kg. |
| 497 | Fixinginlet, outlet, over flow and scour pipe of GMS flanged pipe of following internal dia (medium grade) including extra carriage within all leads and liftscomplete in all respect to the entire satisfactionand asper the direction of the Engineer-in-Charge.. |
| 498 | Inlet Rising Main 100 mm dia. |
| 499 | Outlet pipe 100 mm dia (Distribution) |
| 500 | Over flow & Scour pipe 100 mm dia. |
| 501 | Providing, fixing and welding of MS flanges confirming to BIS code 6392-1971 table -5 below noted diameter (Latest with upto date ammendments) Welding of M.S. flanges on G.I. Pipe on both ends according to relevant BIS standard and detailed technical specifications) and provided with nuts and bolts of required size complete. within all leads and liftscomplete in all respect to the entire satisfactionand asper the direction of the Engineer-in-Charge.. |
| 502 | Inlet Rising Main 100 mm dia. |
| 503 | Outlet pipe 100 mm dia (Distribution) |
| 504 | Over flow & Scour pipe 100 mm dia. |
| 505 | Providing and fixing full way wheel valve (With hand wheel) as per IS -780 class for following dia (including brass spindle and as per IS; 2906 class -II including M.S. Flanges, bolts, nuts, rubber insertion etc. complete in all respects including carriage of material within all leads and lifts. |
| 506 | Outlet pipe 100 mm dia (Distribution) |
| 507 | Scour pipe 100 mm dia. |
| 508 | Providing and fixing of water measuring gauge of standards design complete in all respect to the entire satisfactionand asper the direction of the Engineer-in-Charge.. |
| 509 | Providing and fixing of sky lightening arrestorcomplete in all respect in all leads and lifts complete in all respect to the entire satisfactionand asper the direction of the Engineer-in-Charge.. |
| 510 | Providing and fixing of vent opening including cowl with mesh in the top of the tankcomplete in all respect complete in all respect to the entire satisfactionand asper the direction of the Engineer-in-Charge.. |
| 511 | Finishing wall with water proofing cement paint of approved brand and manufacture and of requiredshade on undecorated wall surface (two coats) to give an even shade after thoroughly brushing the surface to remove alldirt & remains of loose powdered materials complete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 512 | Construction of cholorination Room for installation of gaseous plant at MBRs. |
| 513 | Excavationinfoundation trenchesupto alldepthsin all classification ofearth work such as pick work, jumper work, saturated soil including bailing or pumping out water, blasting soft/hard rock or chieselling soft/ hard rock where blasting is prohibited, in all lifts includingtrimming and dressing of sides,levelling of beds to correct grade including,shoring,strutting,planking,timbering and dewateringwherever required,stacking the useable and unuseable material/soil separately and afterlaying, jointingandtestingofpipesreturningtheuseablesoilintrenchesin 15cm(fiften centimeter ) layersincluding consolidating of such deposited layer by rammingandwatering and then disposing of all surplus excavated soil /un-useable materials as directed within allleads andlifts including restoration of un-metalledsurface to its original condition andincluding cost of diversion for traffic, night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respect within all leads and lifts as per the directions of Engineer-in-Charge. |
| 514 | Providing and laying cement concrete 1:6:12 ( 1 cement : 6 sand : 12 graded stone aggregate 40 mm nominal size) and curing complete excluding the cost of form work in foundation and plinth comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge.. |
| 515 | Squarredrubble stone masonary coursed with hard stone of approved quality in foundation and plinth in retaining walls/breast wall includingracking out joint in cement mortar 1:6(1cement:6sand) as per direction and to the entire satisfaction of Engineer-in-charge. |
| 516 | Providing and laying damp proof course 38mm thick with cement concrete 1:2:4 (1cement:2sand:4 graded stone aggregate 20 mm nominal size and curing complete in all leads and lifts. |
| 517 | Ist class brick work using common burnt clay building bricks in superstructure in cement mortor 1:6 (1 cement :6 sand) comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 518 | Providing and fixing pressed steel doors frames manufactured from commercial mild steel sheet of 1.25 mm thickness including hinges, jump lock jamb, beed and if required angle threshold of mild steel angle of section 50X25 mm or base ties of 1.25 mm pressed mild steel welded or regidly fixed together by mechanical means, adjustable lugs with split and tails to each jamb including steel but things 2.5 mm thick with gaurds, lock strike plate and shock as specified and applying a coat of approved steel primer after pretreatment of the surfacecomlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge.a) Profile A |
| 519 | Providing and fixing panneled glazed or panelled and glazed shutters for doors, windows and clerestory windows,including black enamelled iron butt hinges with necessary screws. 45 mm thick.2nd class deodar wood comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 520 | Providing and laying cement concrete work DESIGN MIX M20 not less than 1:2:4 ( 1cement:2 sand: 4graded stone aggregate 20 mm nominal size )and curing complete excluding the cost of form work and reinforcementfor reinforced concrete work in:- |
| 521 | Suspended floors, roofs,landings and shelves and their supports, balconies, beams, girders, bressumers and cantilivers up to floor two level. in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 522 | Providing & laying cement concreteM- 30 (not leaner than 1:1.5:3) mix concrete using aggregate 20 mm nominal size) & curing complete excluding the cost of form work & reinforcement for reinforced concrete work in wall |
| 523 | Providing form work with steel plates 3.15 mm thick welded with angle iron in frame 30x30x5mm,so as to give a fair finish i/c centring shuttering,strutting & propping etc. with wooden battens & ballies,ht. of propping & centring below supporting floor to ceiling not exceeding 4.00 mts. & removal of the same for in situ-reinforced concrete & plain concrete work :- |
| 524 | Flat surface such as soffits of suspended floors,roofs,landing and the likefloor etc.upto 200mm I thickness asper the direction of the Engineer-in-Charge. |
| 525 | Edges of slab and breaking in floor and walls under 20 cm wide in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 526 | 15 mm cement plaster in single coat on rough side of brick/concrete stone walls for interior plastering up to floor two levels including arrises, internal rounded angles, chamfers and/or rounded angles not exceeding 80 mm in girth and finished even and smooth in cement mortar 1:6 (1 cement:6 sand)comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 527 | Cement concrete flooring 1:2:4 (1 cement : 2 sand :4 graded stone aggregate 20 mm nominal size) laid in one layer finished with a floating of neat cement comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge.40 mm thick |
| 528 | Providing plinth protection 50 mm thick in cement concrete 1:3:6 (1cement:3sand:6 graded stone aggregate 20 mm nominal size comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 529 | 6mm cement plaster to ceiling in CM 1:3 ( 1Cement :3 Sand) comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 530 | Providing plinth protection 50 mm thick in cement concrete 1:3:6 (1cement:3sand:6 graded stone aggregate 20 mm nominal size comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 531 | Providing tor steel reinforcement for RCC work including bending, binding and placing in positioncomplete up to floor two levelcomlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 532 | Boulder filling under floor dry hand packed tightly comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 533 | Applying two coat of wood preservative coat on new wood and wood based surface after and including preparing the surface by thoroughly cleaning oil, grease, dirt and other foreign sand papering and knotting in all lead and lift |
| 534 | Applying priming coat on new wood and wood based surfaces after and including preparing the surface by thoroughly cleaning oil,greese,dirt and other foreign matters,sand papering and knotting.Ready mixed paint brushing wood primer pink comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 535 | Painting two coats (excluding priming coat) on new wood and wood based surfaces,with enamel paintto give an even shade including cleaningthe surface of dirt ,dust and other foreign matters sand papering and stopping with enamel paint other than white comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 536 | White washing with lime on undecorated wall surfaces two coats to give an even shade including thoroughly brooming the surface to remove all dirt , dust and other foreign matters comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 537 | Providing 40x3mm flat iron hold fast 40 cms long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embedding in cement concrete block 30x10x15 cms 1:3:6 ( 1 cement :3 sand : 6 graded stone aggregate 20 mm nominal size ) complete in all respect as per the direction of the Engineer -in- Charge. |
| 538 | Providing and fixing sliding door bolts anodized transparent or dyed to required shade and colour with screws etc. complete in all respect 250x16mm |
| 539 | Providing and fixing tower bolts barrel type anodized transport or dyed to required shade and colour with screws com lete in all respect. 200x10mm |
| 540 | Prvoviding Fixing M.S handle with necessary screwsetc.completein all respect 100mm |
| 541 | Providing and fixing M.S fan clamp (Type-1) of 16mm dia.M.S including end upto shape with broken end in RCC .Slab door painting the exposed position of trapall as per standard designcomplete in all lead and lifts. |
| 542 | Providing & fixing M.S. grills of required pattern in wooden frame of window etc.with M.S. flats, square or round barswith round headedbolts and nuts by screws plain grills comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 543 | Providing /fixing wiring forCholorination Room. |
| 544 | Wiring for light / Fan point / Exhaust fan point / call bell point with 1.5 Sq.mm PVC insulated copper conductor cable in surface/recessed PVc conduct at required including of all material within all leads and lifts. |
| 545 | Wiring for light / power plug with 2 x 4 Sq.mm PVC insulated copper conductor or single core cable in surface/ recessed steel conduit alongwith 1 No.2.24 mm dia bare copper wire for loop earthing as required including carriage of materials within all leads and lifts. |
| 546 | Wiring for Circuit wiring with 2 x 1.5 Sqm.mm PVC insulated copper conductor single core cable in surface/rcessed steel conduit as required including carrige of material upto all leads and lifts. 2 x 6 Sq.mm |
| 547 | Wiring for sub-main wiring with the following size of copper conductor single core cable in surface/ recessed steel conduit as required including carriage of materials upto all leads and lifts. |
| 548 | Supplying and fixing metal box of 150 x 100 x 60mm deep (Nominal size) on surface/ recess with suitable size phonolic laminated sheet cover fixing 3 pim 15/16 amps socket tumber/piano type switch connections painting etc. inculding carriage of materials within all leads and lifts. |
| 549 | Supplying and fixing 32 Amps rating 240 volts, L series miniature circuit breaker of following pole in the connections testing and connections etc. including carriage of materials existing MCB DB complete within all leads and lifts. Category \"A\",single pole. |
| 550 | Supplying and fixing 40 Amps to 63 Amps rating 240 Volts \"L\" series miniature circuit breaker of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as requiredincluding carriage of materials within all leads and lifts. |
| 551 | Supplying and fixing of following way single pole and neutral sheet steel MCB distribution board 240 volts on surface/recessedcomplete with tinned copper bar neutral link earth din bar detachable gland plate interconnection including painting earthing as required including carriage of materials within all leads and lifts. |
| 552 | Wiring for threepin 5/6 amp. Plug point with 1.5 mm sq. PVC including copper conductor cable i/c. providing and fixing three pin 5/6 amp. Socket outlet on switch board (in surface) recessed steel conduit wiring system and 5/6 amp. Tumble /piano type switch earthing as rerquiredincluding carriage of materials within all leads and lifts. . |
| 553 | Providing, installation, testing and commissioning of prewired flouroscent tube fitting complete with ballast, starter and capactors but excluding flouroscent tube rod, suitable to operate on 230 volts single phase A.C.supply directly on surface with copper wiring as required including carriage of materials within all leads and lifts tube fixture 1 x 40 watt box type category \"A\" |
| 554 | Providing / installing testing tube rods 40 watt4\" long complete in all respect.. |
| 555 | Providing, installing, testing and commissioning of ceiling fan and regulator including wiring the rod of standard length (upto 30cm) with 1.5 Sqmm PVC insulated copper conductor single core cabe etc. as required sweep type.Cat. A (1200 mm sweep) including carriage of material complete in all respect to the entire satisfaction as per the direction of the Engineer -in- Charge. |
| 556 | Earthing withG.I. pipe earth, pipe 4.5 mtrs length, 40mm dia including accessories and providing masonry enclousres with cover plate having locking arrangement and watering pipe etc.( but without charcal coke and salt) complete as required including carriage of materials within all leads and liftscomplete in all respect to the entire satisfaction and as per the direction of the Engineer -in- Charge. |
| 557 | Extra usingsalt and charcoal for pipe earthelectrode asrequired, including carriageofmaterials within all leads and liftscomplete in all respect to the entire satisfaction and as per the direction of the Engineer -in- Charge. |
| 558 | Supplying and laying 6 SWG G.I.wire at 0.50 mtr. below ground level for conductor earth electrode, including soldering etc. as required including carriage of materials within all leads and lifts complete in all respect to the entire satisfaction and as per the direction of the Engineer -in- Charge. |
| 559 | Supplying and fixing backellite batten/angle holder including connection as requiredincludingcarriage of materials within all leads and lifts complete in all respect to the entire satisfaction and as per the direction of the Engineer -in- Charge. |
| 560 | Supplying / fixing MVL light cast aluminium control gear housing complete with accessories 125 watts BPMV lamp deep drain aluminium housing acletic cover with toggle catches with best satisfaction of the Engineer-in-Charge including connection with 40 mm G.I. Pipe 1.5 mtrs Bend (1.00 and 0.50) mtrs. including nut & screw grouted with cement in the existing MCB including carriage of materials within all leads and lifts complete in all respect to the entire satisfaction and as per the direction of the Engineer -in- Charge. |
| 561 | Providing and connection of bulk head fitting of all size and shape containing one No. GLS lamp holder steel wire guard and lock complete with all accessories excluding GLS lamp including connection etc. required bull head fittingsCategory -A- |
| 562 | Supply and errection of chlorine gas plant |
| 563 | Supply, installation commissioning and testing of vacuum operated, pressure feed gaseous chlorinator/ Jasco/ Capital for chlorinator of water by direct feeding to existing water main consisting of the following and all as specified. |
| 564 | Cholrinator capable to deliver 0-2500 gm/hour of chlorine gas comprising of spring opposed inlet valve, rate valve, flow meter remote ejector assembly with build in check valve, vaccum tubing, vent tubing and injection assembly. Set of 2 No. : 1W+ IS |
| 565 | Booster pump set BE/NF with electirc motor CROMPTON/ KIRLOSKAR/ ABB operated on 400/440 volts, 3 phase 50 HP electric supply to suit ejector assembly of chlorinator, mounted on common base frame and starter and making foundation in PCC 1:3:6 for booster pump. Set of 2 No. : 1W+ IS |
| 566 | Water piping from water main to booster pump and delivery of water to elector through 25mm dia G.I pipe medium grade complete with all fittings such as 25mm inlet gate valve, 25mm delivery valve, Y type stainer 25mm heavy duty PVC Plumbing pipe Sch. 80 upto injection point before ejector assy/piping upto delivery mains. |
| 567 | Assessories / spares:- Multi purpose cylinder Key-1 No. lead washers -6 Nos. Ejector gasket-2 sets. Hose clips- 4 Nos. Ammomia Bottle - 50 ml -1 No. |
| 568 | Chlorine Gas cylinder 100 kg capaciaty duly approved by CCE Nagpur and filled with Chlorine gas. |
| 569 | Chlorine analyzer to indicate chlorine content level in the chlorinated water to supply. |
| 570 | Safety item covering Chlorine leak emergency kit 1 No. self contained breathing apparatus 1 No. and eye shower - 1 No. |
| 571 | Erection and commissioning charge. |
| 572 | Schedule B3-Gravity mains and Distribution system:- |
| 573 | Excavationinfoundation trenchesupto alldepthsin all classification ofearth work such as pick work, jumper work, saturated soil including bailing or pumping out water, blasting soft/hard rock or chieselling soft/ hard rock where blasting is prohibited, in all lifts includingtrimming and dressing of sides,levelling of beds to correct grade including,shoring,strutting,planking,timbering and dewateringwherever required,stacking the useable and unuseable material/soil separately and afterlaying, jointingandtestingofpipesreturningtheuseablesoilintrenchesin 15cm(fiften centimeter ) layersincluding consolidating of such deposited layer by rammingandwatering and then disposing of all surplus excavated soil /un-useable materials as directed within allleads andlifts including restoration of un-metalledsurface to its original condition andincluding cost of diversion for traffic, night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respect within all leads and lifts as per the directions of Engineer-in-Charge. |
| 574 | Laying, jointing and testing in trenches GMS pipes (light grade/Medium grade) confirming to ISIspecification including commissioning andcost of all fittings in respect of following diametersin gravity mains/distribution system(earth work in trenches to be measured and paid for separately) including entire carriage of material comlete in all respect including all leads and lifts asper the direction of the Engineer-in-Charge. |
| 575 | 32 mm dia (L). |
| 576 | 40 mm dia (L). |
| 577 | 50 mm dia (L). |
| 578 | 65 mm dia (L). |
| 579 | 80 mm dia (L). |
| 580 | 100 mm dia (L). |
| 581 | Dismentling of old GMS pipe in existing distribution system where changing is required of following diameters including staking of material at site in all leads & lift and as per the direction of Engineer-in-Charge. |
| 582 | 15mm dia (L). |
| 583 | 20mm dia (L). |
| 584 | 25mm dia. (L). |
| 585 | 32 mm dia (L). |
| 586 | 40mm dia (L). |
| 587 | 50mm dia (L). |
| 588 | 65 mm dia. (L). |
| 589 | 100 mm dia. (L). |
| 590 | Relaying of old serviceable GMS pipe of following diameters in all leads & lift and as per the direction of Engineer-in-Charge. |
| 591 | 32 mm dia (L). |
| 592 | 40mm dia(L). |
| 593 | 50mm dia(L). |
| 594 | 65 mm dia. (L). |
| 595 | 100 mm dia. (L). |
| 596 | Providingandfixingofbrass full way valves for water works purpose as per 778-1984 (reaffirmed-2010) of the following diametersin distribution systemincluding entire carriage of material in all leads and lifts as per the direction ofthe Engineer- in-Charge. |
| 597 | 32 mm dia |
| 598 | 40 mm dia |
| 599 | ProvidingandfixingC.I sluice valve of approved (withhandwheel ) asperIS 780class upto300 mmdiaincludingbrassspindle andasper IS- 2906class IIfor diametermorethan300 mmcomplete with bolts,nuts,insertion etc.( The tail pieces if required shall be measured and paid for separately.) within all leads & lifts. PN 1.0 LEADER / KIRLOSKAR MAKE |
| 600 | 50 mm dia. |
| 601 | 65 mm dia. |
| 602 | 80 mm dia |
| 603 | 100 mm dia |
| 604 | 125 mm dia |
| 605 | SCHEDULE B4Providing and FixingPLC based Automation System& Solar Plant |
| 606 | Providing and FixingPLC based Automation System &MCC panels for pumps |
| 607 | Providing and Fixing Automation Systemconsidering the micrologix 1400 basd PLC system having following instruments |
| 608 | Ultrasonic Level Transmitter . Measuring Range :4 Mtrs. Make :SBEM/Emerson / Mobery =2Nos. |
| 609 | Pressure Transmeter Make: Emerson/Yokogawa =2Nos |
| 610 | Insertion Magnetic Flow Meter Make: George Fisher/Emerson/SBEM. =2Nos |
| 611 | Butterfly ValveLine Size: 80 mm& 65 mmMake: Belimo/Mascon/Geroge Fisher =2Nos |
| 612 | Pressure SwitchMake: Switzer/Indfos =2Nos |
| 613 | GPRS Facilities installation & Activation. =2Nos |
| 614 | UPS & Distribution boxes =2Nos |
| 615 | Earthing =2Nos |
| 616 | Suitable cables in required length =2Nos |
| 617 | Providing and Fixing Solar Plant |
| 618 | Providing and installation of solar track stand dusk to dawn automatic opertation with 1 KM Panel Completereputed make System with1500VASolar Inverter, 2x150 AH Solar Battery, 4x270 wattsSolar Panels, GI Structure including complete Accessories as per standard . Inculding ,Tax ,Transporttation, Installation complete in all respects. |
| 619 | SCHEDULE B5Operation and Maintenance of Scheme for 3 years:- |
| 620 | Operation and maintenance of Scheme from sourceto main/ sector storage tank gravity main, distribution mains, rising mains etc. and to keep all structure/ machinery/ facility to proper working O&M includes the regular i.e daily supplying of designed/ required quantity of potable water having water quality as per of water Supplyto the beneficiaries of the schemeup to main storage /delivery tank from above mentioned source to main/ sector storage tanks at different location as per plan and repair and maintenanceof main lines, gravity linesand entire distribution mains of scheme, regular maintenance of all the facilities i/c cleaning washing oil and greasing repair, replacement of worn out / damaged parts of pumping Machinery, pipe lines valves and electrical mechanical requirements regular cleaning of all structurelike collection tank, storage tank, pump houseetc. and disposal of same as per the direction of Engineer-in-Charge. Fixing / repairing leakage in civil structure, pipe line, pumping machinery etc proper distribution of treated water and regular testing of water samples. Maintaining log book of runningof pumping machineryregister for sample reports and consumption of chemicals keeping regularand proper record of water quantity and quality, repair and maintenancework chemical dosing and time andhours of run of pumping machinery removed of all kind of slips, slush, up-rooting of unwanted grass, shrub, weeds etc growing near the structureand keeping the area neat and cleanto the entire satisfactionofEngineer-in-Charge. Planting and maintenance of plants, flowers, tree around the pump House and storage tank etc to the entire satisfactionofEngineer-in-Charge, i/c the cost of procurement of adequate and proper tools and plants, Skilled and unskilled manpower spare parts, oil/ grease/ lubricants, chemicals for water treatment and all kinds of regents required for water samples testing and making standby arrangement all time . Instruments, equipments, stationery and any other material etc. required for O&M excluding the cost of energy charges. All the operation shall be carried out as per the CPHEEO manual of water Supply and treatment (latest addition) HPPWD/ JSV specification Hp & JSV norms direction issued by the Engineer-in-Charge from time to time and sound engineering practice. |
| 621 | The O&M part will commence from date of completion of successful trial&test run 3 month period after physical completion of all components. |
| 622 | Operation &maintenance for Ist year |
| 623 | Operation &maintenance for 2nd year |
| 624 | Operation&maintenance for 3rd year |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender