University Of Jammu-UOJ has published Annual Electric Repair Of Academic Administrative Buildings Staff Quarters Etc At New University Upper Campus. Submission Date for this Tender is 28-07-2021. Electrical Maintenance Tenders in University of Jammu Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Wiring for light point/fan point/ceiling fan point/exhaust fan point/call bell point with 1.5 Sq. mm FRLS PVC insulated, copper conductor cable in surface/recessed medium class PVC conduit, with piano type switch, phenolic, laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq mm. FRLS PVC insulated copper conductor single core cable etc. as required. (WireMake ISI Marked Havells/ Anchor/ HPL/Shalimar/KEI/Polycab) (Conduit Make -ISI Marked Anchor/High Power /Finlox/National Gold/Shalimar /Ravindra) Group ‘A’ |
2 | -------------do------------ ---------do-------- Group "B" |
3 | -------------do-----------------------do--------Group "C" |
4 | Wiring for circuit/sub-main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required. (WireMake ISI Marked Havells/ Bonton/ Anchor/Grandley/L&T/HPL/ Shalimar/KEI/polycab) 2x1.5 +1x1.5 Sq mm earthwire |
5 | ------------do------------- 2 x 2.5 + 1 x 2.5 Sqmm earthwire |
6 | ------------do------------- 2 x 4 + 1 x 4 Sqmm earthwire |
7 | ------------do------------- 2 x 6 +1 x 6 Sqmm earthwire |
8 | Supplying and fixing of following sizes of medium class PVC conduit along with the accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required-ISI Marked Anchor/High Power /Finlox/National Gold/Shalimar /Ravindra) 25 mm dia |
9 | Supplying and fixing 5 amp to 32 amps rating, 240/415 volts, 10 KA "C" curve miniature circuit breaker of Single pole in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Make Havells /Legrand /Anchor/ C&S/L&T/Siemen/IA/HPL/Standard/Wipro) Single pole |
10 | Earthing with Copper earth plate 600mm x 600mm x 3mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/coke and salt as required. |
11 | Providing and fixing 4mm dia copper wire on surface or in recess for loop earthing as required. |
12 | Supply and fixing of metal Box of following size on the surface/recess with suitable size of phenolic laminated sheet cover in front including painting etc as required. 100mm x 100mm x 60mm deep |
13 | -----------do-----------200mm x 125mm x 60mm deep |
14 | Supply & fixing 15/16 amp piano type switch on the existing switch box or cover including connection as required. (Make:Anchor /Havells/SSK/HPL/Sanchi Major) |
15 | Supply & fixing 6 pin 15/16 amp socket outlet on the existing switch box or cover including connection as required (Make: Anchor/Havells/SSK/HPL/Sanchi Major) |
16 | Supply & fixing 5/6 amp piano type switch on the existing switch box or cover including connection as required (Make :Havells/ HPL/Anchor/SSK/Sanchi Major) |
17 | Supply & fixing 3 pin 5/6 amp socket outlet on the existing switch box or cover including connection as required (Make: Havells/ HPL /Anchor /SSK/Sanchi Major) |
18 | Supplying and fixing following ways and poles, plain/horizontal sheet steel MCB Distribution Board on surface/in recess complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections including powder painted earthing etc. as required (But without MCB/RCCB/Isolators) (Indokapp/Havells /Anchor /I.A /Legrand/Standard) 8 way 240 volts, single pole and neutral Double door |
19 | --------do-----------8 way (4+24), 415 volts, three pole & neutral Double door |
20 | Supply & fixing DP Sheet enclosure on the surface/recess alongwith 25/32A, 240Volts "C" Curve DP MCCB complete with connection, testing and commissioning etc. as required (Make Havells/HPL/Anchor) |
21 | Supply & fixing piano type Telephone socket outlet on the existing Switch Box or cover including connection as required (Make Havells/HPL/Anchor/SSK/C&S) |
22 | Supplying & drawing 2 pair (0.50)sqmm FR PVC insulated annealed copper conductor un armoured telephone cables in the existing surface/recessed steel or PVC Conduit as required (Make ISI Marked Havells/ ECKO /Anchor /Grandley /L&T/ Helicab /KEI/HPL) |
23 | Supply & fixing two module stepped type electronic fan regulator on the existing modular plate/switch box including connections but excluding modular plate etc. as required. (Make Havells/ HPL /Anchor /SSK/ C&S/Great White/Sanchi Major) |
24 | Supplying and fixing brass batten/Angle holder including connection etc. as required. (Make Havells/ HPL/Anchor/SSK/C&S/Great White/Sanchi Major) |
25 | Supplying and fixing 3 pin, 5 A Ceiling Rose on the existing junction box/wooden block including connection etc. as required. (Make Havells/ HPL /Anchor /SSK/ C&S/Great White/Sanchi Major) |
26 | Providing and fixing following rating and breaking capacity MCCB with Thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. (Make Siemens /Schreinder /L&T/Hager/Havells/I.A/HPL/Standard/Crompton) 125 AMP 16K FP MCCB |
27 | ----------do------------200 AMP 36KA FP MCCB |
28 | ----------do------------400 Amp 50 KA FP MCCB |
29 | Laying of one number PVC Insulated and PVC sheathed/XLPE power cable 1.1 KV grade of following size cables direct in ground including excavation, refilling the trench etc as required but excluding sand cushioning and protective covering. UPTO 35 sq mm |
30 | Supply and fixing of Piano type TV Antenna Socket outlet on the existing switch box/cover including connection as reqd. (Make ANCHOR/ HPL/ HAVELLS/LEGRAND) |
31 | Supply and drawing co-axial TV cable RG-6 grade,0.7mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/Recessed steel/PVC conduit as Reqd. (Make ANCHOR/ HPL/ HAVELLS/LEGRAND) |
32 | Supply and drawing UTP 4 Pair Cat 6 LAN Cable in the existing surface/recessed steel/PVC conduit as required (Make Legrand /Havells / Anchor/D Link /HPL/L&T) 1 run of cable |
33 | Re-wiring for light point/fan point/call bell point exhaust fan point with 1.5 Sqm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/ PVC conduit including dismantling as required. (WireMake ISI Marked Havells/Anchor/HPL/Shalimar/KEI/Polycab) (Conduit Make -ISI Marked Anchor/High Power /Finlox/National Gold/Shalimar /Ravindra) Group ‘A’ |
34 | ------------do---------------- Group "B" |
35 | ------------do---------------- Group "C" |
36 | Supplying and fixing of following ratings and poles 240/415 volts SPN/Isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required (Make Havells /Legrand /Anchor/ C&S/L&T/ Siemen/IA/HPL/Standard) 63 Amp240 volt Double Pole isolator |
37 | -------------do----------- 63 Amp415 volt Four Pole isolator |
38 | Supplying and drawing of following sizes of FR PVC insulated copper conductor, single core cable in the existing surface/recessed steel/PVC conduit as required (WireMake ISI Marked Havells/ Bonton /Anchor /Grandley/L&T/HPL/Shalimar/KEI/Polycab) 1 x 1.5 sqmm |
39 | ------------do----------- 2 x 1.5 sqmm |
40 | ------------do------------2 x 2.5 sqmm |
41 | ------------do------------2 x 6 sqmm |
42 | ------------do------------- 4 x 4 sqmm |
43 | ------------do--------------4 x 6 sqmm |
44 | P/F M.V danger plate of (200x150) mm made of mild steel at least 2mm thick and vitreous enameled white on both side and with inscription in single red colour on front side as reqd. |
45 | Supply/Installation testing and commissioning of following type of surface mounted/recessed mounted decorative Indoor Linearwith extruded Al. heat sink, environmental friendly energy efficient LED tube Light decorative energy efficient square moulded LED energy saving type. Make (Halonix/ Havells/ Syska/ Bajaj/ Eon/ Greatwhite/ Philips/ HPL/Crompton/Wipro/Compact/Anchor/C&S) 4 feet 18 to 22 watt ,230 volts LED batten type tube light fitting complete |
46 | --------do-------12 To 18 Watt LED recessed/surface mounting down, 6500 K, 240 Volts as per cat : GARNET Slim Panel Light square./ Round fittings/Luminaries square or round (225 x 225 mm) to 300 x 300 mm |
47 | Supply/installation of the following type of outdoor decorative faced light, bollard light, flood light/gate lights and Street lights luminaries complete with all accessories connection testing and commissioning as required including making the PCC foundation with nut and bolts where required as per following.Make (Bajaj/Legrand /Surya /Havells/Hager/ C&S/ HPL/ wipro/ compact) 45 to 60 watt, 230 volts IP 66 LED |
48 | Design, manufacture, testing at works & supply, installation, testing & commissioning cubicle panel floor mounted (on base frame) totally enclosed and extensible type . The general construction shall comprise to IS 8623-93. The design shall include all provisions for safety of operating and maintenance personal. IP 42 for indoor and IP54 for outdoor, shall be compartmentalized type having space and arrangements for I/C. cable/bus ducting/incoming switch gears, bus couplers, insulated and properly supported compartmentalized switch gear, outgoing compartmentalized switch gear, bus bar support and terminations, interconnection between bus bars & switch gear with auxiliary bus bars/insulated conductors/strips etc. The panel shall be fabricated out of CRCA not less than 2.00 mm thick for the load bearing members and 1.6mm for doors of L.T Panels. The frame work may be Agle Iron/Channel/Bolted type construction should be arrangement for I/C/O/G. Cable termination with 2 Each. 20x5mm cu. Strip fixed all around the panel connected to 2 Each. earth bars cu-strips connected to incoming earth conductor.(Make Electric Field/ Bharti Engineers/Gupta & Friends/ Semon/ Jai maa/U.S.Electrical works) MAIN OUTDOOR /BUILDING CONTROL PANEL a. INCOMING Space for 1 No. 100 to 630 Amp TPN Al. Bus bar of equal cross section for Main Power connection to Main MCCB. Space for 1 No. 100 to 630 Amp 4 pole MCCB of 35 KA Space for 1 no. 3-phase 5-wire Progdy type electronicmeter. b. INDICATING PANEL The indicating panel of the incomer shall be provided with the following: i. Ammeter of required range with ASS, CT"s. ii.Voltmeter of required range with VSS. c.OUTGOING Space for1 No. 100 to 630 Amp TPN Al. Bus bar of equal cross section for power load/light load. Dimensions = 2’x 2’ x 1’6” |
49 | -------------do-----------MAIN NORMAL CUM EMERGENCY a. INCOMING Space for 1 No. 100-630 Amp MCCB 25-50 KA b. INDICATING PANEL The indicating panel of the incomer shall be providedwith the following: i. Ammeter of required range with ASS, CT"s. ii.Voltmeter of required range with VSS. c.BUS BAR Space for 1 No. 100-630 Amp TPN Al. Bus bar of equal cross section for power load. d.OUTGOING Space for minimum 2 to 4No. 100 to 315Amp4 pole MCCB of 16 KA to 35 KA. Dimensions = 3’ x2 x 1’6” |
50 | Supply, testing and commissioning of PVC sheathed Aluminum conductor 1100 volts graded PVC AA Armoured/unarmoured XLPECable including end termination, crimping, cost of thimbles, nuts bolts, glands, connection, testing and commissioning complete job. (Make Havells /CCI/ Grandley /Finlox /Plaza / General/Polycab/Gloster) 2 core 16 sq mm armoured cable |
51 | ---------do---------- 3 ½ core 35 sq mm armoured cable |
52 | ---------do--------- 3 ½ core 120 sq mm armoured cable |
53 | ---------do----------3 ½ core 185 sq mm armoured cable |
54 | Supply, installation, testing, commissioningof 1200 mm sweep ceiling fans complete with bladesBEE 4 to 5 star rated energy efficient .(Make: Havells /Cromton/Anchor/Bajaj /Compact) |
55 | Supply /Installation testing and commissioning of 450 mm sweep wall mounted fan including the electronic regulators and connection with testing and commissioning etc complete JobBEE 4 to 5 star rated energy efficient. Make: (Anchor /Bajaj /Havells ) |
56 | Supply, installation, testing, commissioning of heavy duty 300 mmsweepBEE 4 to 5 star rated energy efficient exhaust fan. Make: ( Usha / Orient /Anchor) |
57 | Supply & installation of CAT 6 2 module toll lessinformation outlets complying fully or exceeding with category 6 connecting hardware specifications for all pair combinations upto 250 MHz. Outlets shall use lead frame technology, non PCB pyramid type complete as required. (Make Legrand/Delton/Systemax /Penuit/ Havells/HPL/Anchor) |
58 | Supply and installation of Singlex Face Plates along with clearly printed labels and holders complete as required (Make Legrand /Havells / Anchor/D Link /HPL/L&T/G.E) |
59 | Supply & fixing of 32mm dia G.I pipe for flood light bracket including bending to shape, (40x3)mm flat iron clamp and wiring with 1.5 sqmm PVC insulated wire complete wire complete as reqd. |
60 | P/F following rating 230 volts energy saver LED Lamps and LED Tubes 4’ long (Make :Philip /Havells/Bajaj/ Surya/ Crompton/ Wipro/Compact/Halonix) 8 to12 watt LED bulbs |
61 | -------------------do--------------------18 to 25 Watt LED bulbs |
62 | -------------------do--------------------18 to 22 Watt LED 4’ long tube |
63 | --------------------do------------------- 11 to 18 Watt 2pin/4pin type LED tube |
64 | Supplying and fixing bus bar chamber with 4 strips bus bar of following size, made of the copper, suitable for following capacity complete with all accessories including connections, earthing the body as required. 450mm 100 Amp |
65 | -------------------do-------------------450mm 200 Amp |
66 | Providing/fixing following way PVC gang box suitable for following socket and switches. (Havells/Anchor/SSK make) 3 pin 5 Amp socket with switch |
67 | -------------------do--------------- 6 pin 15 amp socket with switch |
68 | Providing/fixing 40 amp rating , 230 volts SPN MCB in the existing MCB DB or enclose complete with connection testing and commissing complete Job. (Havells/Anchor/SSK make) |
69 | Providing/fixing Ding Dong wall bell including connection as required (Anchor/SSK/Klick) |
70 | Providing/fixing following rating plug tops (Anchor/Sanchi major/SSK make) 3 pin 5 Amp |
71 | ---------------do----------------3 pin 15 Amp |
72 | P/F of 3mm thick phenolic laminated sheets of following size. Crown /Hylam. 5" x 5" |
73 | --------------do-----------------9" x 6" |
74 | ---------------do----------------- 11" x 13" |
75 | --------------do------------------- 3" Round |
76 | -------------do------------------- 5" Round |
77 | Providing and fixing of PVC/Wooden boards of following size. Crown/Hylam. 4" x 4" |
78 | ----------------do------------------ 8" x 5" |
79 | ----------------do------------------ 8" x 10" |
80 | -----------------do---------------- 11" x 13" |
81 | Supplying and fixing Post Lantern fittings as per CAT No: BMGSCFL Retrofit with globe cover mounted on Aluminum capsule suitable for 20 watt energy saver CFG including cost of 2.5" x 2" size G.I reducer for fixing on existing pole wherever required (Make Bajaj /Glomac /Havells/Wipro). |
82 | P/laying of 100 mm dia heavy duty PVC pipe in ground including digging the pit and refilling complete job. (prince/supreme/Astral/Uniplas) |
83 | Supply and fixing of following rating onload I-O-II Four pole with advanced neutral on load change over switch confirms to IS 13947 (Part-3) IEC:609473) (Make Legrand/ I.A/Havells /Siemen/HPL) 200 Amp |
84 | -----------------do-------------- 315/400 Amp |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy