Supply Installation Testing And Commissioning Of Microprocessor Based Fire Alarm Control Panel With Allied Works Of Main Building Annex Building At Uttarkanya Kamrangaguri In The District Of Jalpaiguri ., JALPAIGURI-West Bengal

North Bengal Development Department has published Supply Installation Testing And Commissioning Of Microprocessor Based Fire Alarm Control Panel With Allied Works Of Main Building Annex Building At Uttarkanya Kamrangaguri In The District Of Jalpaiguri .. Submission Date for this Tender is 02-08-2021. Chemical Supply Tenders in JALPAIGURI West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

28520993
Supply Installation Testing And Commissioning Of Microprocessor Based Fire Alarm Control Panel With Allied Works Of Main Building Annex Building At Uttarkanya Kamrangaguri In The District Of Jalpaiguri .
Open Tender
Indian
West Bengal
JALPAIGURI
02-08-2021

Tender Details

supply installation testing and commissioning Of Microprocessor Based Fire Alarm Control Panel With Allied Works Of Main Building Annex Building At Uttarkanya Kamrangaguri In The District Of Jalpaiguri . , supply , installation , testing & commissioning of en/ul standard , fm/vds approved microprocessor based fire alarm control 4 loop ( up to 8 loop expandable ) panel fully networkable ( vender should consider network card for panel to panel networking ) with each loop capable of taking at least 250 devices and each loop should be connected to a dedicated loop card ( even if a loop card supports multiple loop the panel should be provided with 4 nos loop cards and should have provision for accommodating total 8 nos loop card ) , 114 vga display character alpha-numeric liquid crystal display . the panel shall be soft addressable type . the panel shall be able to give pin point location of all fire/fault conditions . further , the panel must be able to automatically switch off respective control switches whenever any alarm is triggered . the panel shall have in built rectifier , provision for external & internal printer ( if required ) , loop cards , l c d unit to indicate fire/fault signal with address and analogue output , complete in all respects , having minimum 1000 event memory , integral smf lead acid batteries with sealed cells of 24 v 112 v with integral battery charger complete as required and as per specification . ( approved make- honeywell by moreley or notifier/siemens ) , supply , drawing , designing , installation , testing & commissioning of analogue addressable intelligent multisensory detector with two in built optical smoke sensor with backward & forward scattering light angles as well as additional heat detector sensors with decentralise intelligence , soft addressable photo thermal type with inbuilt fault isolator as per nfpa style wiring complete with base as required ( approved make-honeywell by moreley or notifier/siemens ) . , supply , drawing , designing , installation , testing & commissioning of analogue addressable intelligent heat detector with fixed & rate of rise temperature function with decentralise intelligence , soft addressable type with inbuilt fault isolator as per nfpa style wiring complete with base as required . ( approved make-honeywell by moreley or notifier/siemens ) . , supply , drawing , designing installation , testing & commissioning of addressable manual call point soft addressable type with inbuilt fault isolator as per nfpa style 7 wiring complete as required . ( ( approved make-honeywell by moreley or notifier/siemens ) . , supply , drawing , designing installation , testing & commissioning of addressable loop powered hooter ( sound output of minimum 90 db ) cum strobe ( strength of light 10cd ) complete with inbuilt isolater & ip65 base and as required . ( approved make:honeywell-esser/siemens/securiton ) manual call point soft addressable type with inbuilt fault isolator as per nfpa style 7 wiring complete as required . ( approved make-honeywell by moreley or notifier/siemens ) . , supply drawing designing and laying of 2 core 1 . 5 sqmm frls shield copper cable ( for loop ) make-filolex/techno flex/mem with 20mm nb pvc rigid conduit pipe on the surface of the wall , or cable tray on ceiling . , servicing and repairing of existing fire panel ( addressable ) and reinstallation the same and have to be functioning all fire alarming system in all buildings as per e-i-c . , operation and maintenance the whole fire detecting systemm of all buildings at uttarkanya including sufficient tools & tackles and expert technician of similar nature of works . attend any type of breakdown and restore that in same day or as per direction of e-i-c . [log book to be maintained and submitted to the e-i-c] .

Key Value

Document Fees
Refer document
EMD
INR 10000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: S I T & C of Microprocessor based fire alarm control panel with allied works of Main building, Annex building at Uttarkanya, Kamrangaguri in the district of Jalpaiguri.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply, Installation, Testing & Commissioning of EN/UL standard, FM/VDS Approved Microprocessor based fire alarm control 4 Loop (Up to 8 Loop Expandable) panel fully networkable (Vender should consider Network card for panel to panel networking) with each loop capable of taking at least 250 devices and each loop should be connected to a dedicated loop card (even if a loop card supports multiple loop the panel should be provided with 4 nos loop cards and should have provision for accommodating total 8 nos loop card), 114 VGA display character alpha-numeric liquid crystal display. The panel shall be soft addressable type. The panel shall be able to give pin point location of all fire/fault conditions. Further, the panel must be able to automatically switch off respective control switches whenever any alarm is triggered. The panel shall have in built rectifier, provision for external & internal printer (if required), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analogue output, complete in all respects, having minimum 1000 event memory, integral SMF lead acid batteries with sealed cells of 24 V 112 V with integral battery charger complete as required and as per specification. (Approved Make- Honeywell by Moreley or Notifier/SIEMENS) 1 1 Each
2 2 Supply, Drawing, designing, Installation, Testing & commissioning of Analogue Addressable intelligent multisensory detector with two in built Optical smoke sensor with backward & Forward scattering light angles as well as additional heat detector sensors with decentralise intelligence, soft addressable Photo thermal type with inbuilt fault isolator as per NFPA style wiring complete with base as required (Approved Make-Honeywell by Moreley or Notifier/Siemens). 2 100 Nos
3 3 Supply, Drawing, designing, Installation, Testing & Commissioning of analogue Addressable Intelligent Heat Detector with fixed & rate of rise temperature function with decentralise intelligence, soft addressable type with inbuilt fault isolator as per NFPA style wiring complete with base as required. (Approved Make-Honeywell by Moreley or Notifier/Siemens). 3 10 Nos
4 4 Supply, Drawing, designing Installation, Testing & commissioning of Addressable Manual Call Point soft addressable type with inbuilt fault isolator as per NFPA style 7 wiring complete as required. ((Approved Make-Honeywell by Moreley or Notifier/Siemens). 4 8 Nos
5 5 Supply, Drawing, designing Installation, Testing & commissioning of Addressable loop powered hooter(sound output of minimum 90 db) cum strobe ( Strength of light 10cd) complete with inbuilt isolater & IP65 base and as required.(Approved make:Honeywell-Esser/Siemens/Securiton)Manual Call Point soft addressable type with inbuilt fault isolator as per NFPA style 7 wiring complete as required. (Approved Make-Honeywell by Moreley or Notifier/Siemens). 5 8 Nos
6 6 Supply drawing designing and laying of 2 core 1.5 sqmm FRLS shield copper cable(for loop) Make-Filolex/Techno flex/MEM with 20mm NB PVC rigid conduit pipe on the surface of the wall, or cable tray on ceiling. 6 1500 Mtr.
7 7 Servicing and Repairing of existing fire panel (addressable) and reinstallation the same and have to be functioning all fire alarming system in all buildings as per E-I-C. 7 2 job
8 8 Operation and maintenance the whole fire detecting systemm of all buildings at Uttarkanya including sufficient tools & tackles and expert technician of similar nature of works. Attend any type of breakdown and restore that in same day or as per direction of E-I-C.[Log book to be maintained and submitted to the E-I-C]. 8 36 Months