| 1 | 1 | Excavation in trenches for foundations, laying / taking out of cables, erecting of poles etc, in any type of soil, not exceeding 1.5 mtr in depth and not exceeding 1.5 mtr in width and getting out, complete all as specified and as directed. | 1 | 220 | CuM |
|---|
| 2 | 2 | All as per the description of Srl item No 1 herein above but depth exceeding 1.50 metre but not exceeding 3.00 metre | 2 | 1.6 | CuM |
|---|
| 3 | 3 | Returning, filling in soils, in trenches including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and as directed | 3 | 215 | CuM |
|---|
| 4 | 4 | Removing excavated soils to a distance exceeding 50 metres and not exceeding 100 metre and depositing where directed at a level not exceeding 1.50 metre above the starting point. | 4 | 6.6 | CuM |
|---|
| 5 | 5 | Cement concrete (1:4:8) type D-2 (using 40mm graded crushed stone aggregates) as in foundation and mass concrete etc complete all as specified and as directed. | 5 | 1.6 | CuM |
|---|
| 6 | 6 | Cement concrete (1:3:6) type C-2 (using 40mm graded crushed stone aggregates), in foundation and mass concrete etc complete all as specified and as directed. | 6 | 6.4 | CuM |
|---|
| 7 | 7 | Cement concrete (1:2:4) type B-1 (using 20mm graded crushed stone aggregates) as in coping, blocks, bed plates, kerbs etc including weathering, slightly rounded or chamfered angles and throating as directed including necessary formwork as required complete all as specified and directed. | 7 | 2.7 | CuM |
|---|
| 8 | 8 | Supply, erection and fixing in position 9.00 metre long, steel tubular swaged poles complete with mild steel base plate, flat top welded type 410, SP-31 IS:2713 marked, drilling of necessary holes including bolts, nuts and washers as required and pointed with two coats of Aluminium paint over a coat of red oxide primer on exposed, surfaces of poles and two coats of black bituminous paint throughout internally and externally upto the planting depth including providing reflective strips of width 10cm (03 Nos) at a height of 1.20 metre from ground level in alternate colour (green, white, green) alround the pole and marking pole number at appropriate height with shade and colour as approved by Engineer-in-Charge complete all as specified and as directed, with and including dismantling and taking up old existing damaged steel tubular pole and removing from site of work complete all as directed. \nNote : Excavation earthwork and concrete work shall be measured and paid for separately. | 8 | 15 | Each |
|---|
| 9 | 9 | 80mm bore (internal dia) steel water tubing, galvanized light grade, laid in trenches /fixed to wall/ along pole or laid in trenches or under roads etc as protection to cable, with all fittings and fixtures like mild steel flat iron clamps of appropriate size and shape, nuts, bolts and washers as approved by Engineer-in-Charge complete all as specified and as directed, with and including taking up/down old damaged steel pipe and removing from site of work complete all as directed. | 9 | 9 | RM |
|---|
| 10 | 10 | Double wall corrugated HDPE duct pipe of 100mm outer dia conforming to IS:14930 Pt-II with antirodant and non flame propergating properties of make and colour as approved by Engineer-in-Charge with fittings as protection to cable, laid in trenches or fixed to poles/walls complete all as specified and as directed. | 10 | 600 | RM |
|---|
| 11 | 11 | All as per the description of serial item-10 here-in-above but 50mm outer dia | 11 | 250 | RM |
|---|
| 12 | 12 | Disconnecting and taking out old damaged/defective LT cable from trenches or taking down from poles or taking out from pipes below or above ground level, or for rerouting of cable aluminium conductor 1100 volts grade, size 50.00 sqmm, 3.5 core and removing from site of work including taking out cable cover and pipe complete all as specified and as directed. | 12 | 200 | RM |
|---|
| 13 | 13 | All as per the description of serial item-12 here-in-above but of size 70.00 sqmm 3.5 core | 13 | 200 | RM |
|---|
| 14 | 14 | All as per the description of serial item-12 here-in-above but for of size 95.00 sqmm 3.5 core | 14 | 200 | RM |
|---|
| 15 | 15 | All as per the description of serial item-12 here-in-above but of size 120.00 sqmm 3.50 core | 15 | 200 | RM |
|---|
| 16 | 16 | All as per the description of serial item-12 here-in-above but for of size 185.00 sqmm 3.50 core | 16 | 400 | RM |
|---|
| 17 | 17 | All as per the description of serial item-12 here-in-above but for of size 240.00 sqmm 3.5 core | 17 | 250 | RM |
|---|
| 18 | 18 | All as per the description of serial item-12 here-in-above but of size 300.00 sqmm 3.50 core | 18 | 250 | RM |
|---|
| 19 | 19 | All as per the description of serial item-12 here-in-above but for of size 400.00 sqmm 3.50 core | 19 | 300 | RM |
|---|
| 20 | 20 | Supply, laying , jointing and testing LT underground electric cable XLPE insulated, PVC sheathed armoured heavy duty 1100 volts grade heavy duty multystranded aluminium conductor laid in trenches / ducts or passing through under road or fixed to poles or walls complete all as specifed and as directed of following size :-\nNote : Excavation and earth work shall be measured and paid for seperately. | 20 | | |
|---|
| 21 | 20.01 | Cross sectional area 50.00 Sqmm sqmm 3.50 core | 21 | 200 | RM |
|---|
| 22 | 20.02 | Cross sectional area 70.00 sqmm 3.50 core | 22 | 200 | RM |
|---|
| 23 | 20.03 | Cross sectional area 95.00 sqmm 3.50 core | 23 | 200 | RM |
|---|
| 24 | 20.04 | Cross sectional area 120.00 sqmm 3.50 core | 24 | 200 | RM |
|---|
| 25 | 20.05 | Cross sectional area 185.00 sqmm 3.50 core | 25 | 400 | RM |
|---|
| 26 | 20.06 | Cross sectional area 240.00 sqmm 3.50 core | 26 | 250 | RM |
|---|
| 27 | 20.07 | Cross sectional area 300.00 sqmm 3.50 core | 27 | 250 | RM |
|---|
| 28 | 20.08 | Cross sectional area 400.00 sqmm 3.50 core | 28 | 300 | RM |
|---|
| 29 | 21 | Material and labour for cutting existing bituminous/cement concrete road/hard standing/pavement of size 30 cm x 30cm for passing through the cables/pipes and surrounding /filling the entire cut space with cement concrete 1:3:6 type C-I after laying of pipe/cable and finishing the top surface fair and even complete all as specified and as directed. | 29 | 6 | RM |
|---|
| 30 | 22 | MCCB four pole 400Amps, 415 volts, 50HZ breaking capacity not less than 36 KA with thermal magnetic release, adjustable thermal and adjustable magnetic setting with spreader links 1cs = 100% of 1 cu, in replacement (taking down old damaged MCCB) complete all as specified and as directed. \nMake : L&T/ABB/Schnieder/Siemens | 30 | 6 | Each |
|---|
| 31 | 23 | All as per the description of serial item-22 here-in-above but of 320 Amps. \nMake : L&T/ABB/Schnieder/Siemens | 31 | 3 | Each |
|---|
| 32 | 24 | All as per the description of serial item-22 here-in-above but of 250 Amps. \nMake : L&T/ABB/Schnieder/Siemens | 32 | 15 | Each |
|---|
| 33 | 25 | All as per the description of serial item-22 here-in-above but of 200 Amps. \nMake : L&T/ABB/Schnieder/Siemens | 33 | 10 | Each |
|---|
| 34 | 26 | All as per the description of serial item-22 here-in-above but of 160 Amps. \nMake : L&T/ABB/Schnieder/Siemens | 34 | 10 | Each |
|---|
| 35 | 27 | All as per the description of serial item-22 here-in-above but of 125 Amps. \nMake : L&T/ABB/Schnieder/Siemens | 35 | 10 | Each |
|---|
| 36 | 28 | All as per the description of serial item-22 here-in-above but of 100 Amps. \nMake : L&T/ABB/Schnieder/Siemens | 36 | 15 | Each |
|---|
| 37 | 29 | Change over switch ON LOAD type, 415 volt, 50 Hz, AC 4 pole, in steel metal enclosure, capacity 200 Amps rated current manually operated conforming to IS : 13947 or latest edition with high thermal and dynamic strength to withstand short circuit current level of 80 KA rms, in replacement, (taking down old damaged change over switch) complete all as specified and as directed. | 37 | 4 | Each |
|---|
| 38 | 30 | Taking down old unserviceable ACB any type and Supply, installation testing and commissioning new LT ACB of 800 Amps 415 Volts, 50 Hz, four pole mannual draw out microprocessor based, with LCD display with complete set of LSIG protection with self power release with fault indication and with 20 trip history with time stamping suitable for existing location alongwith replacement of burnt aluminum bus bar with connected nut bolts and lugs with new aluminum bus bar /nut bolts/lugs complete all as specified and directed by Engr-in-charge. \nMake : ABB/Schnieder/L&T/Siemens | 38 | 1 | Each |
|---|
| 39 | 31 | Taking down old unserviceable ACB any type and Supply, installation testing and commissioning new LT ACB of 630 Amps 415 Volts, 50 Hz, four pole mannual draw out microprocessor based, with LCD display with complete set of LSIG protection with self power release with fault indication and with 20 trip history with time stamping suitable for existing location alongwith replacement of burnt aluminum bus bar with connected nut bolts and lugs with new aluminum bus bar /nut bolts/lugs complete all as specified and directed by Engr-in-charge. \nMake : ABB/Schnieder/L&T/Siemens | 39 | 2 | Each |
|---|
| 40 | 32 | M&L for painting of LT out door panel in front, top, rear and both sides above ground level with two coats of synthetic enamel paint as per existing colour after preparation of surface and writing panel number complete all as specified and directed by Engr-in-Charge. | 40 | 80 | Each Job |
|---|
| 41 | 33 | Electric panel doors fabricated out of mild steel sheet of thickness as directed by Engineer-in-Charge, made to shape and size as per existing with proper closing/opening arrangements including necessary welding/ fabrication as required and fitted/fixed in position including taking down old damaged panel doors and removing from site of work, with and including two coats of aluminium paint over a coat of red oxide/zinc chrome primer, complete all as specified and as directed. | 41 | 900 | Kg |
|---|
| 42 | 34 | Aluminium bus bar of different size and capacity as per site requirement and as directed by Engineer-in-Charge including PVC insulating materials and cutting, welding as required, making holes and fixed in position including taking down old bus bar and removing from site of work, all as directed. | 42 | 150 | Kg |
|---|
| 43 | 35 | Copper bus bar of different size and capacity as per site requirement and as directed by Engineer-in-Charge including PVC insulation materials and cutting, welding as required, making holes and fixed in position including taking down old bus bar and removing from site of work, all as directed | 43 | 15 | Kg |
|---|
| 44 | 36 | Removing wild grass vegetation, creeper etc around LT panel/transformer/poles, stay assembly, climbing upwards including cleaning bottom surfaces on ground of area not less than 1.00m x 1.00m including surface dressing n.exc 15cm deep in any type of soil and removing rubbish to outside mob lad complete all as directed. | 44 | 3500 | Sqm |
|---|
| 45 | 37 | Earthing complete with galvanized iron or steel plate electrode 600mm X600mm X 6.0 mm burried directly in ground vertially in a pit of depth not less than 2.25m below normal ground level with top edge of the earth plate at a depth of not less than 1.50m below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to with and including GI/ Steel strip of size 32mmx6mm upto a length of 7.50 metre by means of bolts, nuts, check nuts & washers of galvanized iron /steel, earth strip protected by and including galvanized steel pipe light grade of bore 40 mm (internal dia) & connected to main control board / switch board or any other electrical equipment complete all as shown in electrical plate No : 3 MES SSR including necessary excavation & earth work, disposal of surplus soil not exceeding 50m, in any type of soil. (The rate also includes for cost of charcoal & salt in alternate layers of 15 cm thickness, 20 mm bore internal dia GI/steel pipe light grade) for watering, funnel, wire mesh, PCC chamber in cement concrete (1:3:6) type C-1, 40mm thick RCC(1:2:4) type B-0, reinforced with XPM of weight not less than 4.00 kg/Sqm and mild steel frame of angle 50mmx50xxx6mm and testing on competion including dismantling / taking out existing earthing and removing dismantling / taken out materials outside the defence land complete all as directed. | 45 | 15 | Each Job |
|---|
| 46 | 38 | Supply and fix switch disconnection fuse unit sheet steel enclosure 250 Amps 3 pole with neutral link and multi break arcing contacts per pole, front operated postive isolation switch mechanism with modular construction & compact size , in replacement (taking down old swithc fuse) complete all as specified and directed by Engr-in-Charge. | 46 | 5 | Each |
|---|
| 47 | 39 | Supply, installation testing and commissioning of out door type LT feeder pillar box CPRI approved openable from front & rear double door type, dust and vermin proof, fabricated out of 2.15 mm CRCA sheet of size not less than 0.75x 0.50x.0.50 duly painted with two coats of powder coated of approved shade over a coat of zinc chrome primer and MS Channel frame of ISMC 75 at base of panel only and 04 Nos legs of not less than 50 cm long each below the base of panel made of angle iron 50x50x6mm for grouting purpose and grouted in PCC 1:2:4 type B1 (using 20mm graded stone aggregate) alongwith incoming MCCB four pole, 415volts, 25 KA, 50 Hz, 200 Amps- 01 including 4 Nos heat shrink insulated 200 Amps rated aluminum bus bar suitable for 4 Nos outgoing 25 Sqmm to 35 Sqmm 3.5/4 Core XLPE armoured cable including taking down of existing rusted / unsv LT feeder pillar complete all as specified and directed by Engr-in-Charge \nMake of MCCB : L&T/ABB/Schneider/Siemens | 47 | 5 | Each |
|---|
| 48 | 40 | Note: Quoted Contract Sum shall be arrived at after deducting the amount of Credit Schedule (refer Schedule of Credit Revised in pdf form for quantity, rate and amount etc.) for old unserviceable materials retrieved from site. | 48 | | |
|---|