Repair Replacement Of Lt Distribution System Including Repairs Apfc Panels At Adm/Domestic Area At Mil Stn Dappar Under Ge ( P ) Dappar, GE (P) Dappar-Punjab

Military Engineer Services-MES has published Repair Replacement Of Lt Distribution System Including Repairs Apfc Panels At Adm/Domestic Area At Mil Stn Dappar Under Ge ( P ) Dappar. Submission Date for this Tender is 05-08-2021. LT Cable Tenders in GE (P) Dappar Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

28472963
Corrigendum : Repair Replacement Of Lt Distribution System Including Repairs Apfc Panels At Adm/Domestic Area At Mil Stn Dappar Under Ge ( P ) Dappar
Open Tender
Indian
Punjab
GE (P) Dappar
05-08-2021

Tender Details

Repair Replacement Of Lt Distribution System Including Repairs Apfc Panels At Adm/Domestic Area At Mil Stn Dappar Under Ge ( P ) Dappar

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 21-Jul-2021 Corrigendum of BOQ and Schedule B items BOQ 29-07-2021
2 29-Jul-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 05-08-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 40000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Repair replacement of LT distribution system including repairs APFC panels at adm/domestic area at Mil Stn Dappar under GE (P) Dappar
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Disconnecting & taking out old unserviceable LT cable of size 120 sq mm 3.5 core. 100 RM
2 2 Disconnecting & Taking out old unserviceable LT cableof size 70 sq mm 3.5 core 200 RM
3 3 Disconnecting & Taking out old unserviceable LT cable of size 50 sq mm 3.5 core 200 RM
4 4 Disconnecting & Taking out old unserviceable LT cable of size 35 sq mm 3.5 core 500 RM
5 5 Disconnecting & Taking out old unserviceable LT cable of size 25 sq mm 4 core 500 RM
6 6 Disconnecting & Taking out old unserviceable LT cable of size 16 sq mm 4 core 500 RM
7 7 Disconnecting & Taking out old unserviceable LT cable of size 10 sq mm 2 core 600 RM
8 8 Disconnecting & Taking out old unserviceable HT cable of size 185 sq mm 3 core 250 RM
9 9 Disconnecting & Taking out old unserviceable HT cable of size 95 sq mm 3 core 130 RM
10 10 Supply, laying, jointing, connecting, testing & commissioning UG cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured electric power cable (heavy duty 1100 volts grade with standard aluminium conductor of cross sectional area 120 sqmm x 3.5 core all as specified and directed by Engr-in-Charge.\nNOTE - (a). The quoted rate is deemed to be inclusive of arranging respective shutdown, disconnection of cables, commissioning of feeder after the completion of job and inclusive of any minor spares and jobs required for the completion of the job. (c). The cost of excavation, returning, filling, removal and PCC cable covers will be measured and paid under relevant items of this schedule. 100 RM
11 11 Description all as per ser item No 10 here-in-before but size of LT under ground cable 70 sqmm 3.5 core. 200 RM
12 12 Description all as per ser item No 10 here-in-before but size of LT under ground cable 50 sqmm 3.5 core. 200 RM
13 13 Description all as per ser item No 10 here-in-before but size of LT under ground cable 35 sqmm 3.5 core. 500 RM
14 14 Description all as per ser item No 10 here-in-before but size of LT under ground cable 25 sqmm 4 core. 500 RM
15 15 Description all as per ser item No 10 here-in-before but size of LT under ground cable 16 sqmm 4 core. 500 RM
16 16 Description all as per ser item No 10 here-in-before but size of LT under ground cable 10 sqmm 2 core. 600 RM
17 17 Laying, jointing, connecting, testing & commissioning UG cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured electric power cable (heavy duty 1100 volts grade with standard aluminium conductor of cross sectional area 185 sqmm x 3 core all as specified and directed by Engr-in-Charge.\nNOTE - (a). The quoted rate is deemed to be inclusive of arranging respective shutdown, disconnection of cables, commissioning of feeder after the completion of job and inclusive of any minor spares and jobs required for the completion of the job. (c). The cost of excavation, returning, filling, removal and PCC cable covers will be measured and paid under relevant items of this schedule.(d) The XPLE Cable is issued under sch B 150 RM
18 18 Laying, jointing, connecting, testing & commissioning UG cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured electric power cable (heavy duty 1100 volts grade with standard aluminium conductor of cross sectional area 95 sqmm x 3 core all as specified and directed by Engr-in-Charge.\nNOTE - (a). The quoted rate is deemed to be inclusive of arranging respective shutdown, disconnection of cables, commissioning of feeder after the completion of job and inclusive of any minor spares and jobs required for the completion of the job. (c). The cost of excavation, returning, filling, removal and PCC cable covers will be measured and paid under relevant items of this schedule.(d) The XPLE Cable is issued under sch B 130 RM
19 19 Excavation in trenches in soft/loose/hard soil n exc 1.5 m wide and not exc 1.5 m in depth and getting out including forming bottom to required level or slope for laying pipes / laying of cable complete all as specified and as directed by Engineer-in-Charge. 778 Cum
20 20 Returning filling in soft / loose soil in trenches including spreading, leveling and well ramming in 25 cm thick layers complete all as specified and as directed by Engineer-in-Charge. 495 Cum
21 21 Removal of surplus soil to a distance n exc in 50 m and deposited where directed at a level n exc 1.5 m above the starting point complete all as specified and as directed by Engineer-in-Charge. 283 Cum
22 22 Material and labour sand cushioning (dry sand) to underground cable for cable protection 23 cm thick in two layers (8 cm thick before laying of cables and 15 cm thick after laying the cable and punning down the sand to 18 cm thickness.). Complete all as specified and as directed by Engineer-in-Charge. (Note:- Only punned thickness 18 cm of sand shall be measured for payment purposes). 207 Cum
23 23 M&L precast concrete cable cover, class LV, type 1 with peak, size 250mm x 150mm x 40mm. 13867 Each
24 24 M&L precast concrete cable cover, class HV, type 1 with peak, size 250mm x 180mm x 40mm. 1244 Each
25 25 Material and labour for galvanized iron tubing size 40 mm bore (Light grade) with all necessary fittings laid in trenches under road crossing or fixed on poles / walls / under floors for cable protectioncomplete all as specfied and as directed. Make:- Jindal. Complete all as specified and as directed by Engineer-in-Charge. 40 RM
26 26 M & L for earthing with galvanised iron earth plate of size 600x600x6mm thick buried directly in ground not less than 2.25m below normal ground level,earth plate packed on all sides with charcoal mixed with salt in alternate layers of 15 cm thickness connected by galvanised iron earth earth strip 32x6mm soldered & riveted toearth plate, galvanised iron earth strip will be provided by using 50mm bore galvanised iron pipe (light grade) earth plate to transformer body and neutral or test point of transformer, including flat iron clamp 25x3mm including bolts, nuts and washers complete including watering galvanised iron pipe 20 mm dia 'Light grade' 2.5mm long the earthing includes PCC pit including necessary earth works and disposal of surplus soil to a distance not less than 50m, chamber of PCC 1:4:8 type D-2 using 40mm graded stone aggregate, coping shall be of PCC 1:3:6 type C-I using 20mm graded stone aggregate, RCC pit cover 50mm thick in1:2:4 type B-I using 20mm graded stone aggregate, rein forced with 8mm dia @ 15cm c/c complete all as shown on sketch No 3 of SSR-I of 2009 and as specified and as directed by Engr-in-Charge. 10 Each
27 27 M & L earth continuity conductor GI of 32x6 mm of GI strip by means of bolts, nuts, check nuts and GI washers complete all as specified. 30 RM
28 28 M & L Synthetic insulating mat (rubber matting), ISI Marked suitable for 1100 Volts electrical grade 2mX1mX2mm thick chequered top, ISI marked to be laid in front of LT panel board complete all as specified and directed. 4 EACH
29 29 M&L for Danger notice boards of 1.6mm thick mild steel sheet, vitreous enamelled white,with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for LT 25x20cm size. 20 EACH
30 30 M&L for application of two coats of aluminium paint on steel tubular/rail pole of 9/11/13/15 M long externally after removal of old paint, rust, dust, oil, grease or any other foreign deposits by paint removers or burning off by blow lamps, cleaning with scrapers and chemicals for removal of rust for any number of coats of any width or girth incl. numbering of poles in blackbase & white letters paint and incld. painting five no. strips upto 30 cm on bottom of pole with black and yellow colour paint alternately all as specified and directed by Engr-in-Charge. 170 Each
31 31 Supply and fix cable jointing kit for 1100 V grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 core XLPE, armoured, Aluminium conductor cable of size upto 25 to 50 sqmm, core outdoor type and taking down fault complete all as specified and directed by Engr-in-Charge. Make : Denson/M Seal/Birla 5 Each
32 32 Supply and fix cable jointing kit for 1100 V grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 core XLPE, armoured, Aluminium conductor cable of size upto 70 to 120 sqmm, core outdoor type and taking down fault complete all as specified and directed by Engr-in-Charge. Make : Denson/M Seal/Birla 4 Each
33 33 Supply and fix cable jointing kit for 1100 V grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 core XLPE, armoured, Aluminium conductor cable of size upto 150 to 185 sqmm, core outdoor type and taking down fault complete all as specified and directed by Engr-in-Charge. Make : Denson/M Seal/Birla 3 Each
34 34 Supply and fix cable jointing kit for 1100 V grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 core XLPE, armoured, Aluminium conductor cable of size upto 240 to 300 sqmm, core outdoor type and taking down fault complete all as specified and directed by Engr-in-Charge. Make : Denson/M Seal/Birla 2 Each
35 35 Disconnecting, dismantling and taking out old burnt unserviceable MCCB from LT distribution panels after arranging necessary electric shutdown, S&F MCCB FP, 36kA, 400 AMPS with Thermal - Magnetic Release Type Ics = 100% Icu, Adjustable Over Load setting: 0.4 -1.0 x In, Adjustable short circuit for each phase from 1.5 - 8 x In, Make - L&T, Cat No. - CM98403OOROOG including spreader terminals (Make-L&T, Cat No.-ST98066OOOO). NOTE - Quoted rate is deemed to be inclusive of minor jobs and minor spares required for fitment of MCCB in the existing panel. 1 Each
36 36 Disconnecting, dismantling and taking out old burnt unserviceable MCCB from LT distribution panels after arranging necessary electric shutdown, S&F MCCB TP, 25kA, 250 AMPS with Thermal - Magnetic Release Type, Ics = 100% Icu, Adjustable Over Load setting: 0.4 -1.0 x In, Adjustable short circuit for each phase from 6 - 10 x In, Make - L&T, Cat No. - CM90642OOPO including spreader terminals (Make-L&T, Cat No.-ST98066OOOO). 1 Each
37 37 Disconnecting, dismantling and taking out old burnt unserviceable MCCB from LT distribution panels after arranging necessary electric shutdown, S&F MCCB TP, 25 kA, 200 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, Adjustable short circuit for each phase from 6 - 10 x In, Make - L&T, Cat No. - CM90642OONO including spreader terminals (Make-L&T, Cat No.-ST98066OOOO). 1 Each
38 38 Disconnecting, dismantling and taking out old burnt unserviceable MCCB from LT distribution panels after arranging necessary electric shutdown, S&F MCCB TP, 25 kA, 160 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, Adjustable short circuit for each phase from 6 - 10 x In, Make - L&T, Cat No. - CM90642OOMO including spreader terminals (Make-L&T, Cat No.-ST98066OOOO). 1 Each
39 39 Disconnecting, dismantling and taking out old burnt unserviceable MCCB from LT distribution panels after arranging necessary electric shutdown, S&F MCCB TP, 25 kA, 125 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, Adjustable short circuit for each phase from 6 - 10 x In, Make - L&T, Cat No. - CM90642OOLO including spreader terminals (Make-L&T, Cat No.-ST98066OOOO). 1 Each
40 40 Disconnecting, dismantling and taking out old burnt unserviceable MCCB from LT distribution panels after arranging necessary electric shutdown, S&F MCCB TP, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, Adjustable short circuit for each phase from 6 - 10 x In, Make - L&T, Cat No. - CM91712OOJOOG including spreader terminals (Make-L&T, Cat No.-ST98066OOOO). 2 Each
41 41 Supply only fuse wire (Tin & Copper) 16/18/20 SWG complete all as specified and as directed by Engr-in-Charge. 4 Kgs
42 42 Taking down unserviceable ACSR conductor and supply and fixing aluminium conductor steel reinforced any type complete all as specified and as directed by Engr-in-Charge. 3 Qtl
43 43 Restringing and Fixing ACSR Conductor reinforced of any size to proper sag incl binding on insulator all as specified and as directed by Engr-in-Charge 3200 RM
44 44 Cutting & trimming of tree branches any girth and size around overhead lines to a clear distance 1.5 mtr both sides of overhead line with in a 25 to 40 mtrs span gap of HT/LT lines including clearing the site all as specified and directed by the Engr-in-Charge. 140 Per Span
45 45 M&L for cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending, cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of two coats of aluminium paint over a coat of red oxide zinc chrome primer including removing old unserviceable rusted ones complete all as directed by Engineer-in-Charge 3 Qtls
46 46 M&L for stay assembly complete with accessories as shown in electric plate No.I including loop type insulator, stay clamps etc complete all as specified & directed with diameter of stay 20 mm of stay rod complete all as specified & directed. Note: - Loop type insulator, PCC foundation, Exc & earth work & GI stay strand will be measured and paid seperately under relevent items of Sch 'A' 3 Per Set
47 47 M&L for inspection of LT FPB all connected accessories/components like MCCB/MCB/ACB ON-OFF/Tripping operations, metering devices, cable lugs joints, bus bar connections, insulators, wiring, CTs, etc., cleaning of LT FPB using dry air pressure, vacuuming out all dust/foreign particles using vaccum cleaner complete, removing flash over/burnt carbon particles from cable lug joints, bus bars, etc. with CRC 226 or WD14 or equivalent cleaner, tightening of nuts/bolts and other electric connections, disconnecting all incoming and outgoing connected cables, cutting off burnt portions, crimping with suitable size aluminium/copper lugs and connecting up inclusive of replacement of cable glands (if any) all as directed at site by Engr-in-charge. Note:- (a). All spares like LED indicating lamps, ACB/MCCB/MCB, fuses with holders, voltmeter, ammeter, CTs, selector switches, copper/aluminium bus bar, control wiring, etc. required for replacement shall be measured and paid separately under relevant items of schedule here-in-after however the quoted rate is deemed to be inclusive of cost of cleaning agents, grease, cable lugs, cable glands, nut/bolt and washer combination all as approved by Engr-in-Charge. (b). The contractor has to arrange for electrical shutdown prior to carry own repairs. 10 EACH
48 48 M&L for sheet metal work for replacement of unsv. panel doors, bus bar cover, metering devices/relay mounting doors in complete alignment with panel's existing doors with 3mm thick CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032 or of shade as specified incld. necessary cutting of MS sheet so as to incorporate old serviceable panel accessories like LED indicating lamps, volt/ammeter, selector switches, MCCB/MCB handles, etc. welding and fixing jobs and dismantling of unsv./rusted doors to the complete satisfaction and as directed and specified by Engr-in-Charge. NOTE - (a). The contractor has to arrange for electrical shutdown prior to carry own repairs. (b). The quoted rate is deemed to be inclusive of cost of hinges, panel locks, accessories required for flush fitting of old serviecable LED indicating lamps, volt/ammeter, selector switches, MCCB/MCB handles, etc. on the new door or any other materials required for fixing and proper opereations of door. 80 Kg
49 49 Supply and relplace existing u/s indicating lamp LED type suitable to operate on 230 volts AC Supply of R/Y/B colour as per site requirement all as specified and directed. 35 Each
50 50 S&F in replacement Single function 3 phase LED ammeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable all as per L&T make, Cat No. - WL131010OOOO and including suitable size CTs (set of 3) - 04 Nos. (Outgoing feeders) 26 Each
51 51 S&F in replacement Single function 3 phase LED ammeter with accuracy Class 1.0, Flush mounting 96 x 96 mm, Input voltage measurement range 50-520 VAC (P-P), CT/PT site programmable all as per L&T make, Cat No. - WL131010OOOO and including suitable size CTs (set of 3) - 04 Nos. (Outgoing feeders) 20 Each
52 52 Supply and replace existing u/s selector switch for voltmeter. 15 Each
53 53 Supply and replace existing u/s selector switch for Ammeter 15 Each
54 54 supply and replace existing unserviceable CT as that of existing ratio and model suitable for 3 phase supply 15 Each
55 55 S&F in replacement Street light control junction box 280x170x130mm upto 16 sq mm 4 core cables made out of FRP sheet moulded and arrangement of incoming 3 phase 4 wire system and out going 3 phase 4 wire system with R.Y.B.& N studs and control for incoming & outgoing cables with MCB SP 2.5 Amps 230 volts with neutral link including flat iron 25x3 mm “D” clamps (2 Nos) suitable to pole of any size including bolts nuts & washers.”NOTE: - The rates includes incoming & outgoing cables glands & lugs of size up to 16 sq mm 4 core. 5 Each
56 56 Painting to electric control panel of E/M installations by cleaning the existing old paint with the help of mechanical tools such as wire brush, scraper and sand paper from the surface of panel and painting the prepared surface with two coat of synthatic enamel paint of approved shade over a coat of red oxide primer complete all as specified abd specified. 25 Sqm
57 57 Repairing/servicing of APFC panel board by replacing the all defective components with new components, re-wiring, cleaning, testing, reconnecting, re-installing and commissioning the APFC panel board complete all as specified and directed by Engr-in-Charge. 5 Each Job
58 58 S&F in replacement APFC relay of 8 stage supply Voltage 415 V AC and current Input - 1A or 5 A with specs as - 3 Phase Current and Voltage measurement, PF display - 3 Digit after decimal, Individual harmonics measurement up to 31st order, Dual PF setting for Mains - DG application, Communication through Inbuilt MODBUS RS-485 Protocol all as per L&T Cat Part No. CS91050OOOO or eqivalent in Epcos/Schenider/Seimens. 8 Each
59 59 Dismantling, supply and install, connect, test and commission of capacitor, 3 phase, Super Heavy Duty cylindrical type, self standing units, self healing property with MPP film with safety device in the form of pressure sensitive (over pressure) mechanical interrupter, 415/440V, 3 phase, 50 Hz, Capacity 5 KVAR, AC conformance to Standards IEC 60831-1 2/96, IS 13340 including testing, commisioning as in repairs complete all as specified and directed. 18 Each
60 60 All as per item no:60 above but 10 KVAR. 16 Each
61 61 All as per item no:60 but 20 KVAR. 16 Each
62 62 S&F in repairs power capacitor duty contactor 3 phase with auxilary switch block 415 volts suitable for 10 kVAR capacitor complete with connected switch gear/ components in various APFC panels of L&T make Type MO C10 Cat Part No. CS96156 or equivalent in Makes as per PS of this CA all as specified and directed by Engr-in-Charge. 14 Each
63 63 S&F in repairs power capacitor duty contactor 3 phase with auxilary switch block 415 volts suitable for 15 kVAR capacitor complete with connected switch gear/ components in various APFC panels of L&T make Type MO C15 Cat Part No. CS90019 or equivalent in Makes as per PS of this CA all as specified and directed by Engr-in-Charge. 15 Each
64 64 S&F in repairs power capacitor duty contactor 3 phase with auxilary switch block 415 volts and Spreader Link Kit suitable for 25 kVAR capacitor complete with connected switch gear/ components in various APFC panels of L&T make Type MO C25 Cat Part No. CS96322 or equivalent in Makes as per PS of this CA all as specified and directed by Engr-in-Charge. 14 Each
65 65 S&F in repairs NO element complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge 14 Each
66 66 S&F in repairs NC element complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge 14 Each
67 67 S&F in repairs Illuminated push button- RED complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge 14 Each
68 68 S&F in repairs Illuminated push button- GREEN complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge 14 Each
69 69 S&F in repairs 1.1 KV current transformer of ratio 150/5 complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge 8 Each
70 70 S&F in repairs 1.5 Sqmm multistranded copper FRLSH wire for control circuit complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge 120 RM
71 71 S&F in repairs 6 sqmm multistranded FRLSH copper flexible cable complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge 120 RM
72 72 S&F in repairs 1.5 sqmm pin type lugs complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge 60 Each Job
73 73 S&F in repairs 6 sqmm pin/fork/round type lugsr complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge 60 Each Job
74 74 S&F in repairs 6-32 A SP MCB, 10 kA 'C' series, 240 V AC, 50 Hzcomplete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge 25 Each
75 75 S&F in repairs 32 A TP MCB, 10 kA 'C' series, 415 V AC, 50 Hz complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge 15 Each
76 76 S&F in repairs 63A TPN MCB, 10 kA 'C' series, 415 V AC, 50 Hz complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge 12 Each
77 77 S&F in repairs 2 way slector adaptor 25 Amps complete switch gear/components in various APFC panels all as specified and directed by Engr-in-Charge 10 Each
78 78 Taking down old unsv fitting and supply and fix LED flood light fitting 90 watts, IP65 class with separate integral driver and with pressure dia-cast aluminium housing all as per Crompton Make, Cat Pat No LFLN-90-CDL or eq in Havells/Bajaj/HPL. NOTE - The quoted rate is deemed to be inclusive of cost of minor spares and misc jobs to be carried at site for fittment of luminarie. 4 Each
79 79 S&F LED LUMINARIE, pressure die cast aluminum housing, 45 watts capacity, 240V, IP 65 class, with suitable in-built electronic driver complete all as directed and specified by Engr-in-charge. MAKE of make Crompton Greaves cat part no - LSTP-45-CDL or Equivalent in Makes as mentioned in PS of thsi tender. NOTE - Cost of all minor spares and jobs required for fixing of light fixture on wall and for electrical connections are deemed to be included in the quoted rate. 8 Each
80 80 Supply only street/security light bracket made out of 40mm dia light grade 1.5mtr bent to shape for fixing on any type of pole/wall with clamps nuts and bolts complete all as directed by engr-in-Charge. Make of GI pipe shall be Jindal/TATA/Swastik. Note:Cost of necessary GI items such as reduce ,coupler ,etc required to be fitted with GI bracket so as toproper fitiment of luminaries with bracket is deemed to be included in the quoted rate. 20 Each
81 81 Dismantling of unserviceable insulator any type and any size. 35 Each
82 82 S&F in replacement Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and\none galvanised iron nut, 100mm height, 65mm dia for 1100 volts grade. 20 Each
83 83 S&F Shackle Type, Porcelain, vitreous, white, brown or green insulator having working pressure 1100 Volts, height 75mm and dia 90mm including galvanised mild steel straps, washers, insulator bolts, washers and nuts. 15 Each