Military Engineer Services-MES has published Repair/Maint Of Dg Set , Amf Panel , Lt Panel , Ug Cable And Connecting Work At Afs Darbhanga Under Ge ( Af ) Bihta . . Submission Date for this Tender is 05-08-2021. Diesel Generators Tenders in Darbhanga Bihar. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 29-Jul-2021 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 05-08-2021 |
Name of Work :Repair/maint of DG set, AMF Panel, LT Panel, UG cable and connecting work at AFS Darbhanga under GE (AF) Bihta. | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Overhauling/servicing oil sump of 10 KVA DG Sets, turbochargers, self starter motor, rectfication of oil and leakage from turbocharge refilling new oil as per stander and testing complete, cleaning, removing sediments/foriegn particles from the complete oil circulation system, refixing, including replacing oil sump gasket , all fillter (oil filtter,air filtter) and testing for fuel pipeline PVC connection with new highly transperent PVC flexible pipes of suitable diameter, painting of outer surfaces of fuel tank Check, clean, adjust/tighten, grease and set for proper functioning of valve 'V' belts, pulleys, Fan hub, idler, water pump, filters, engine cylinder head incl decarbonising electrical wirings all bolts, nuts and washers vibration dampers, coupling, alternator terminals, carbons brushes vibration dampers, coupling, alternator terminals, carbons brushes, springs, AVR's, exhause pipes etc of DG Sets after fixing all items required for smooth functioning of DG set and tested on full load to entire satisfaction of Engineer-in-Charge.\nNote:- Spare part if any required shall be paid separately under appropriate items | 2 | Each Job | |
2 | 2 | 1. Fule Pump service | 1 | Each | |
3 | 3 | 2. Fule injector service | 1 | Each | |
4 | 4 | 3. Self starter repair | 1 | Each | |
5 | 5 | Spare Parts \n(a) Engine oil 7.5 Ltrs\n | 7.5 | LTR | |
6 | 6 | (b) Air filter | 1 | Each | |
7 | 7 | ( c) Diesel Filter | 1 | Each | |
8 | 8 | (d) Mobil filter | 1 | Each | |
9 | 9 | (e) painting | 1 | Each | |
10 | 10 | (f) coolent | 4 | LTR | |
11 | 11 | (g) batrry 80 Amps Black | 1 | Each | |
12 | 12 | Overhauling/servicing of oil sump 62.5 Kva DG Sets, turbochargers, self starter motor, rectfication of oil and leakage from turbocharge refilling new oil as per is stander and testing complete, cleaning, removing sediments/foriegn particles from the complete oil circulation system, refixing, incl replacing oil sump gasket , fillter all (oil filtter,air filtter,and testing for fuel pipeline PVC connection with new highly transperent PVC flexible pipes of suitable diameter, painting of outer surfaces of fuel tank Check, clean, adjust/tighten, grease and set for proper functioning of valve 'V' belts, pulleys, Fan hub, idler, water pump, filters, engine cylinder head incl decarbonising electrical wirings all bolts, nuts and washers vibration dampers, coupling, alternator terminals, carbons brushes vibration dampers, coupling, alternator terminals, carbons brushes, springs, AVR's, exhause pipes etc of DG Sets after fixing all items for smooth functioning of DG shall be tested on full load to entire satisfaction of Engineer-in-Charge.\nNote:- Spare part if any required shall be paid separately under appropriate items | 2 | Each Job | |
13 | 13 | 1. Radiater Repair | 1 | Each | |
14 | 14 | 2. Main alterneter service and varnish | 1 | Each | |
15 | 15 | 3. Charging alterneter service | 1 | Each | |
16 | 16 | 4. Turbo charger service | 1 | Each | |
17 | 17 | 5. Fuel pump service | 1 | Each | |
18 | 18 | 6. Fuel injecter service | 1 | Each | |
19 | 19 | 7. self starter repair | 1 | Each | |
20 | 20 | Spare Parts:-\n(a) Engine oil 13.5 Ltrs | 13.5 | Ltr | |
21 | 21 | (b) Air filter | 1 | Each | |
22 | 22 | ( c) Diesel Filter | 2 | Each | |
23 | 23 | (d) Mobil filter | 1 | Each | |
24 | 24 | ( e) Coolant | 3 | Ltr | |
25 | 25 | (f) Battry 130 Amps Black | 1 | Each | |
26 | 26 | (g) door kabza | 1 | Each | |
27 | 27 | (i) door Lock | 1 | Each | |
28 | 28 | (j) V belt | 1 | Each | |
29 | 29 | M&L for removing US absestos rope and providing new absestos rope 12mm dia wound spirally around exhaust pipe of DG sets all as directed. | 10 | Kg | |
30 | 30 | Dismanting existing unserviceable AVR of the alternator and providing new AVR of same capacity/model/type incl connecting up and testing and battriy charger assembly for the following:- \n(a) 62.5 KVA capacity | 1 | Each | |
31 | 31 | (b) 10 KVA capacity | 1 | Each | |
32 | 32 | Repair/Maintenance by complete overhauling of AMF panel upto 62.5 KVA/10 KVA replacement of micro based AMF relay unit (GUC) with all accessories, three phase unit, setting timing, voltage, low oil temp, charging battery etc making the AMF panel tuned with DG set complete by replacement of battery charger, time changer control set on - off and contractor all as directed by Engineer-in-Charge | 1 | Each Job | |
33 | 33 | S&F in repair Power Contactor 4P 125 A, with NO NC contacts for AMF panel upto 62.5 KVA including disconnecting the existing unserviceable contactor and connecting to new unit and, testing complete all as specified and directed by Engineer-in-Charge. Make: HPL or equivalent in specified makes. | 2 | Each | |
34 | 34 | S&F in repair Power Contactor 4P 63A, with NO NC contacts for AMF panel upto 50 KVA including disconnecting the existing unserviceable contactor and connecting to new unit and, testing complete all as specified and directed by Engineer-in-Charge. Make: HPL or equivalent in specified makes. | 2 | Each | |
35 | 35 | Supply and fix in repair MCCB 4 pole, 415 V, adjustable type100 Amp with braking capacity 16KA complete all as specified and as directed. Make : Havells Cat No IHLASF0100 or equivalent and approved model of L&T/MDS/Scheineder | 1 | Each | |
36 | 36 | Supply and fix in repair MCCB 4 pole, 415 V, adjustable type63 Amp with braking capacity 16KA complete all as specified and as directed. Make : Havells Cat No IHLASF0630 or equivalent and approved model of L&T/MDS/Scheineder | 1 | Each | |
37 | 37 | S & F in repair change over switch in steel sheet enclosure with side of handle 100 Amps type(SCHS), 415 V AC 50 HZ, four poles complete all as specified and as directed. Make " Havells cat No : IHBFFE0100 or equivelant model of L&T/Scheineder/MDS. | 1 | Each | |
38 | 38 | S & F in repair change over switch in steel sheet enclosure with side of handle 63 Amps type(SCHS), 415 V AC 50 HZ, four poles complete all as specified and as directed. Make " Havells cat No : IHBFFE063 or equivelant model of L&T /Scheineder/MDS. | 1 | Each | |
39 | 39 | Supply and fixing in repair for contactor 40 amp cn695f 4 Pole with NO/NC relay along with wire for connection complete all as specified and directed .Make L&T/Havells/Scheineder/MDS. | 2 | Each | |
40 | 40 | Material & labour for cleaning and removal of rust particle, cleaning, preparation of surface of panels of any size indoor/outdoor type and painting with two coats of synthetic enamel paint over one coat of red oxide primer including minor repair of LT door, hinges and locking arrangement wherever required by welding complete all as specified and as directed. | 50 | Each Job | |
41 | 41 | Supply ,installation, testing and commissioning of LT control panel out door type, factory made pedastal type fabricated out of 3.15 mm CRCA sheet having inner sheet of MS black and slopy roof , spray painting two coat inside and outside with synthetic enamel paint of approved shade over a coat of red oxide primer complete with locking arrangement, provision of cable gland for all incoming and outgoing cable , grouting of feeder pillor box 30 cm above ground level by providing 45 cm long angle iron of size 40x40x6 mm welded on all the for corner embeded in PCC 1:2:4 (using 20 mm stone agregrate) up to 30 cm deep complete including coprising the following component including taking out the old panel :- Incoming-(a) MCCB 4 Pole 440 Volt 250 Amp, 25 KA – 01 No,outgpoing- (b) MCCB 3 Pole 440 Volt 123 Amp – 04 Nos (d) MCCB 3 Pole 440 Volt 63 Amp – 02 (e) MCB SPN 220 Volt 40 Amp – 02 Nos (e) LED type indecator lamp (green /red)- 01 set Make of MCBs/MCCBs- LEGRAND /L & T/SCHNEIDER/ABB | 1 | Each | |
42 | 42 | Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 metre below normal ground level (with top edge of earth plate not less than 1.5 metre below ground level) connected to galvanized iron earth strip 25x4mm, (main earthing lead) by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt alround earth plate & 15 mm dia GI pipe light grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia light grade for watering pipe with funnel & wire mesh including necessary earth work and PCC (1: 3 : 6) type C-1 for earth pit and 40 mm thick precast RCC cover in 1 : 2 : 4 type B1 with 3 Nos 8 mm dia TMT bars both ways with 12mm dia round bar handle complete all as specified & directed by Engineer-in-Charge. NOTE: Earth lead wire and its protection pipe upto and including 7.5 mtr only from the top of earth electrode are included under this item and additional earth strip/protection pipe etc. if any required at site shall be measured and paid for separately under appropriate item of Schedule `A’ | 2 | Each Set | |
43 | 43 | All as per serial item No 42 here-in-before but GI wire size 4mm dia | 2 | Each Set | |
44 | 44 | Repair/replacement/brazing of earth continuity conductor or main earthing lead 25mm X 3mm, aluminum strip/earth lead, in any position including jointing with existing tinned copper/brass nuts, bolts and washers complete all as specified & directed. \nNote:-\n(i) Each joint shall be considered for measurement purpose.\n(ii) Existing nut bolts & washers shall be reused for jointing of strips.\n(iii) Brazing shall be done with gas welding using brass electrode.\n | 50 | RM | |
45 | 45 | Taking out old unserviceable cable from tenches/pole etc all as directed | 580 | RM | |
46 | 46 | Supply and laying XLPE insulated, armoured heavy duty electric under ground cable with aluminium conductor, 1100 volts grade, cross sectional area 35 sqmm 3.5 core complete all as specified and directed by Engineer-in-Charge. | 100 | RM | |
47 | 47 | All as per serial item No 46 here-in-before, but of cross sectional area 50 Sqmm 3.5 Core. | 100 | RM | |
48 | 48 | All as per serial item No 46 here-in-before but of cross sectional area 95 Sqmm 3.5 Core. | 200 | RM | |
49 | 49 | All as per serial item No 46 here-in-before but of cross sectional area\n120 Sqmm 3.5 Core. | 180 | RM | |
50 | 50 | Excavation In trenches not exceeding 1.5 mtr. In depth and not exceeding 1.5 mtr. In width and getting out in soft/loose soil for laying of cables/pipes, erection of poles, stays, cable fault detection etc complete all as specified and as directed. | 65 | Cum | |
51 | 51 | Returning filling of excavated soil after laying the cable including spreading leveling, watering and well ramming in layers not exceeding 25cm thick in loose/soft soil complete all as specified and as directeddirected. | 40 | Cum | |
52 | 52 | Removing excavated materials/ surplus soil to a distance n.exc 50 m and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specifed and as directed. | 25 | Cum | |
53 | 53 | M&L for sand cushioning to cable by filling fine river sand in trenches 8 cm before laying of cable and 15 cm after laying of cable for protection of cable and punned the sand as specified in SSR - Part-I all as specified and as directed.\nNote:-For payment punned depth shall be measured. | 20 | Cum | |
54 | 54 | M & L for laying well burnt Sub-Class 'B' bricks (old size) for protection of cable laid flat perpendiculor to direction of cable complete all as specified and as directed. | 3.1 | Per 1000 Nos. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy