Defence Statutory Bodies & Commissions/Committees Closing in 0 days TDR #28409068

Provision Of Certain Sanction Works At Ins Parundu 8155/E8

Issued by Statutory Bodies & Commissions/Committees · Ramnad, Tamil Nadu
Tender Value
Ref. Documents
Estimated cost
Bid Submission
24 Jul 2021
0 days left
EMD
88000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Ramnad → Tamil Nadu
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Provision Of Certain Sanction Works At Ins Parundu 8155 / E8

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 17-Jul-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 24-Jul-2021

BOQ

Name of Work: PROVISION OF CERTAIN SANCTION WORKS AT INS PARUNDU 8155/E8
Sl.No.Item DescriptionItem Code / MakeQuantityUnits
11SCHEDULE 'A' PART-I [ B/R WORKS]
22Excavation in trenches, n exc 1.5m wide and n exc 1.5m in depth, for foundation/laying cable in Hard/Dense soil and getting out complete all as specified and directed.16.9Cum
33Material and Labour for PCC 1:4:8 type D-2 using 40mm graded stone aggregate as in foundation including form work complete all as specified and as directed.45.8Cum
44Material and Labour for PCC 1:2:4 type B-1 using 20mm graded stone aggregate as in foundation including form work complete all as specified and as directed.8.8Cum
55Supply and fix for rolled sections as in main and cross beam, hip and jack rafter purlins where connected to common rafter and running rails and guides for sliding door,fixed with angle cleats or other connecting plates etc conforming to Fe 410-W (Gde-E-250) complete all as specified and directed.850KG
66Material and labour for roof trusses (framed) trussed, purlins, crane gantries, rails and fastenings and heavy bracket framing (beam, tee, angle, channel or flat sections) including distance pieces, cleats etc conforming to Fe 410-W (Gde-E-250) complete all as specified and directed.1000KG
77Supply and fixing galvalume single skin corrugated profiled/ Plain roofing sheet of 0.50mm thickness (Total coated Metal thickness) having tensile strength of 550 MPa, coated with hot dip metallic zinc aluminium alloy coating zincalume AZ-150 or equivalent (as per AS 1397) @ 150 gms/sqm, total on both sides of ZN (45%) & AL (55%), with super polyester colour bond XRW quality paint coat or equivalent as per AS/NZS-2728 (Category 3-4) of approved colour, total coating thickness of 35 microns of a super polyester XRW quality paint system or equivalent comprising of 20 microns (NOM) exterior coat on top surface and 5 microns (NOM) reverse coat on back surface over 5 microns (NOM) primer coat, on both surface, of approved colour shade fixed with GI self tapping fastening bolt/screw as in roof covering/cladding etc as per manufacturers instructions complete all as specified and as directed.50Sqm
88All as per item No.7 above but 0.5mm thick prepainted plain galvalume sheeting as in ridge and gate covering fixed with GI self tapping screw complete all as specified and as directed.11.8Sqm
99Supply and fix for MS Plates (plain or chequered)channels, square cut or notched (ordinary and counter sunk)forming holes, with riveted, bolted or welded attachment complete all as specified and as directed.140KG
1010Supply and fix for mild steel Bands, straps, supports or stays\nfor rainwater, ventilating pipes, including bolts, if required: hooks (stay), heavy, for large gates; hook and pintle hinges: large hasps and staples; chains; hand made sliding bolts; clamps; hold fasts; wall ties; hooks for hanging fans; plain angle cleats for securing purlins to wood trusses or rafters; knee piece inserts; two way and three way straps, plate washers and similar small articles conforming to Fe-410 or Fe-310 complete all as specified and as directed.15KG
1111Supply and fix Mild steel screw bolts (machine made) with hexagonal or square heads at one end and each screwed end to be fitted with washers and one hexagonal or square not exceeding 30cm long & dia exc 20mm and n exc 25mm complete all as specified and as directed.40KG
1212Removing excavated material / soil to a distance exe 250m & n.exc 500m away and depositing where as directed at a level n.exc 1.5m above the starting point, complete all as specified and as directed.27.6Cum
1313M&L for Preparation of new untreated steel surfaces of any description, over 10 cm width or girth, not otherwise described and applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and as directed.90Sqm
1414Excavation in over areas, n exc 1.5m in depth, in any type of soil and getting out complete all as specified and directed.293Cum
1515Rolling and consolidation of formation surfaces in cutting with capacity 8 to 12 tonnes power roller including filling in hollows and depressions which occur during the process of olling complete all as specified and as directed.45X-Sqm
1616Supply and laying Moorum/red bajri brought from outside MD land, as in filling in pathways/floor, laid in layers not exc 15 cm thick, spread, levelled and rammed including watering rolling with 8 to 12 tonnes power roller complete all as specified and as directed.135Cum
1717Material and labour for hard core with granite broken stone of gauge not exceeding 63 mm, deposited, spread, and levelled in layers not exceeding 15 cm thick watered and rammed to a true surface all as specified and as directed.45Cum
1818Material and labour for Reinforced cement concrete, M30 Design mix using 20mm graded stone aggregate as in as in foundation including raft, footing, base of column, plinth beams , basement slab and the like any thickness including attached pillasters etc all as specified and as directed.68Cum
1919Material and Labour for TMT bar 10mm dia and over, cut to length, bent to shape required, including cranking,bending spirally for hooping ,for columns,hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and as directed.2650KG
2020Formwork to edges of concrete flats, treads, breaks in floors,\nwindow cills, concrete railings, openings in concrete walls, floor and roofs n exc 20 cm wide and sides of RCC/ PCC bands in walls, horizontal or sloping and similar work exc 10cm but n exc 20cm\nwide complete all as specified and as directed.150RM
2121Material and labour for forming 12mm thick expansion joints filled with preformed bituminous filler and top 30mm primed and sealed with sealing compound Grade B for 150mm thick concrete complete all specified and as directed.0.6X-RM
2222Material and labour for Forming Contraction (Dummy) joints 85 mm deep x 10 mm wide, filled with sealing compound, Grade ‘B’ complete all as specified and directed.15X-RM
2323Removing excavated material to a distance n.exc 50m away and depositing where as directed at a level n.exc 1.5m above the starting point, complete all as specified and as directed.296.1Cum
2424Material and labour for Poweder coated aluminum frame for doors, windows, grills, ventilators with one or more rebats including joining cleat for fixing etc complete all as specified and as directed.\n320KG
2525Supply & fix Anodised Poweder coated aluminium door shutters, aluminium section weighing 0.55 kg/ m including necessary joining cleats, glazing clips, ruber neoprene packing, handles 2 Nos in each door, anodised aluminum snap beading, roller screws etc. complete all as specifieds4.2Sqm
2626Supply and fix Sheet glass of 5.5mm thick, ordinary quality and glazing with glazin clips in square in exc 0.5 sq.m in each panel complete all as specified and as directed.33Sqm
2727Supply and fixing 12mm thick Prelaminated particle board, exterior grade, prelaminated both side with decorative choice lamination fixed with screws to frame work complete all as specified as directed.33Sqm
2828Material and labour for Brick work with old size subclass 'B' brick straight or curved on plan exc 6m mean radius and built in CM 1:4 complete all as specified and as directed.4Cum
2929Material and labour for 15mm thick rendering in cement mortar 1:4, on fair faces of brick/concrete surfaces finished even and smooth with out using extra cement all as specified and as directed. \n40Sqm
3030Material and labour for preparation of newly plastered wall surfaces and applying two coats of oil bound distemper over two coat of primer over a coat of wall care putty complete all as specified and as directed.40Sqm
3131Supply & fix anodised aluminium snap grid frame work for false ceiling with 605mm x 605mm size, consisting of main Tee of size 23.50mmx36.50mmx1.50mm, cross Tee of size 23.50mmx23.50mmx1.50mm and wall angle of size 36.00mmx25.00mmx1.50mm of approved make including all necessary cuttings, fixing of aluminium section firmly in position with and including steel hangers 6 mm dia G.I. wire (upto 1200 mm length) adjusting level fixed to roof slabs by means of ceiling cleats made out of G.I. flat 40 x 3 mm size 60 mm long and expansion hold fasteners 40 mm long in soffit of slab/walls complete all as specifed and as directed including provision of 12mm thick perforated gypsum board, 600mmx600mm size, fixed in ceiling, flat or sloping complete all as specified and directed.45Sqm
3232Excavation in post holes (or similar holes) each n exc 0.5 cum and getting out, returning filling in and ramming earth or broken rubble mixed with earth around, in layers n exc 25cm, watering and removing surplus soil to a distance n exc 50m and making good surface in any type soil complete all as specified and directed.118Each
3333Material and Labour for PCC 1:3:6 type C-2 using 40mm graded stone aggregate as in foundation including form work complete all as specified and as directed.11Cum
3434M&L for providing reinforced cement concrete (nominal mix)1:2:4 type B-1(using 20mm graded aggregate) in precast posts, fencing posts, straining or terminal posts, struts etc. for fencing, average sectional area exc 100 sq. cm and n exc 200 sq. cm, with or without chamfered angles and flat, splayed, rounded or mitred tops as directed etc complete all as specified and directed.14Cum
3535Material and labour for Mild steel TMT bars 6 to 8mm dia, cut to length, bent to shape required, including cranking bending spirally for hooping ends and binding with and including mild steel wire annealed not less than 0.9 mm dia or securing with clips all as specified and as directed.723KG
3636Material and labour for Preparation of newly plastered surface of walls and applying three coats white wash incl preparation of surface all as specified and as directed. \n8Sqm
3737Material and labour for Forming letters, figures etc. by cutting 'V\ngrooves in new lime, cement-lime or cement plaster (per cm of height) complete all as specified and directed.1125Each
3838SCHEDULE 'A' PART-II [ E/M WORKS]
3939Material and labour for Sub main wiring with PVC insulated unsheathed 1100 volts FRLS grade single core multi stranded copper conductor cable 2 runs of 4 sqmm drawn through in and including suitable size PVC conduit heavy duty ISI marked(IS 9537 Part III) fixed in walls and all accessories along with 1 run of 4 sqmm PVC insulated unsheathed copper conductor single core multi stranded cable 1100V FRLS grade as earth continuity conductor and connected to common earth dolly complete all as specified and as directed. \nNote: 2 runs of 4 sqmm cable along with 1 run of 4 sqmm cable for earth conductor and one run of PVC conduit shall be measured as one length.60RM
4040Material and labour for Point wiring complete with FRLS PVC insulated unsheathed cable 1100V grade conforming to IS-694, 1.5 Sqmm (nominal area) multistranded with copper conductor drawn through and including non metallic rigid PVC conduit 20mm dia (ISI marked) and accessories, wall / surface (open conduit) on ceiling with sunken type pressed steel / welded terminal boxes made out of 2mm mild steel sheet, 3mm thick laminated sheet cover for mounting of switches, socket outlets, regulators etc., including provision of FRLS PVC insulated unsheathed 1.5 Sqmm FRLS multistranded with copper conductor as earth continuity conductor and connecting to common earth dolly complete all as specified and as directed for One light/fan point controlled by one, one-way switch14Per point
4141Supply and fix Sheet metal enclosures, powder coated double door, MCB DB for SPN 4 way 240 V with neutral bus bar 200 Amps double door type with locking arrangement complete all specified and as directed. \n1Each
4242Supply and Fix of Switch Piano, flush type, Single Pole, 230 Volts, AC, one-way 5 Amps with ISI mark all specified and as directed.14Each
4343Supply and Fix Ceiling rose 2/3 terminals, surface bakelite 65 x 50mm complete all specified and as directed.\n14Each
4444Supply and fix in repair LED energy saving surface mounted decorative bulk head edge light comprising of high brightness 10W, 6000K LEDs complete with all accessories internally pre wired and including connecting up with twin / three core flexible copper conductor cable with suitable size from ceiling rose to fitting etc, complete all as specified and as directed. \nMake : Crompton LBHE-10-CDL or equivalent in Philips / Havells/ Bajaj/C&S6Each
4545Supply and fix 32 mm dia light grade GI tube bracket of length 1.5 metre bend to required shape including MS clamp made out of 30 mm x 6 mm MS flat iron and fix on poles/wall with necessary GI bolts, nuts and washers - 2 sets for each fittings complete set all as specified and directed.\n4Each
4646Supply and fix energy saving LED street light fittings, 30 Watts or nearest higher wattage, with in-built electronic driver, IP 66 class of protection with versatile pressure die-cast aluminium body, toughened glass cover with silicon gaskets and energy efficient LED and connecting up light fitting with copper conductor cable of suitable size from junction box to connector block including all accessories and dismantling of old unserviceable fitting for taking into credit complete all as specified and as directed.\nMake:Crompton LSTS-30-CDL-M (ASTRA NEO) or equivalent in Philips/Bajaj/ Havells4Each
4747Supply and fix MCB SP, AC 240 Volts 5A to 32 Amps 10 KA, rupturing capacity, 'B' curve complete all as specified and as directed.10Each
4848Supply and fix MCB DP, AC 240 Volts 32 Amps 10 KA, rupturing capacity, 'B' curve complete all as specified and as directed.1Each
4949Earthing complete with Galvanized steel earth plate electrode of size 600mmX600mm, 6.00 mm thick buried directly in ground vertically to a depth not less than 2.25 metres below the normal ground level with top edge of the plate not less than 1.5m below normal GL and connected to galvanized earth strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanized iron steel all as shown in Electrical Plate No.3 connecting to earthing test point, including necessary earth work in any type of soil, PCC earth chamber made in PCC 1:3:6 type C1 (using 20mm graded aggregate), common salt, charcoal, CI funnel, earth pit cover in RCC 1:2:4 type B1 (using 20mm graded aggregates), with 8mm CTD bars @ 100mm c/c in both ways, including necessary form work complete including necessry test on completion including taking down of old all as specified and as directed. \nNote :1. The unit rate shall also include for excavation, earth work in hard/dense soil PCC (1:3:6) type C1 pit, RCC cover slab, GI funnel with 20 mm dia watering pipe, wire mesh, 40mm dia medium grade GI protection pipe for earth strip etc., complete.\n2. Earthing strip upto 7.5 metre length shall be deemed to be included in quoted unit rate beyond 7.5 metre, the same shall be measured and paid separately. \n1Each Job
5050Supply and fix non-clogging portable submersible pumpset with KBL IE2 motor, 10 meter electric cable, Control panel & 10 meter chain. Technical Specification : Motor Kw:- 5.50 , Rated RPM - 965, Differential Head - 10 m , Flow, rated : 80.00 m3/h, Minimum Continuous Safe Flow (MCSF) : 26.73 m3/h . Material : S3 MOC-ASTMA351,CF8M(232)/ASTMA351,CF8M(232)/ALUMINIUM\nROTOR+SS316(158).Control Panel shall be suitable for NS65/32i Kirloskar Pumps and provided by M/s Kirloskar Brothers limited must consist of DOL Starter, Three phase with neutral switch, High rupuring capacity fuses, safety features like tripping of motor in case of single phasing and reverse phasing , Moisture sensing circuit for detecting ingress of moisture of water into oil of oil chamber and tripping of motor in case of contamination of oil , tripping of motor by detecting high winding temperature with the help of thermister relay , Thermal overload Relay for overload protection, Automatic operation of pump on liquid level controllers,Analog Ammeter, LED indication for OIl contamination, Low liquid level , High temperature of the motor winding, Low/ High voltage/ Rev. Phasing/ Single Phasing , Overloading of motor, Pump On , Push button for start , stop and reset for moisture contamination, Auto/Off/Manual selector. Control Panel shall be equipped with fully automatic starters designed to operate pump motors of following specification : Voltage :- 415 +/- 10 % , Frequency : 50 Hz +/- 5 % , Phase : 3 Phases + Neutral , Class of duty : Continous , Class of insulation : F , Ingress Protection : IP 54. Make: KIRLOSKAR BROTHERS LIMITED, Pump Model: NS65/32Ni , TYPE - i-NS3Each Job
5151Supply and fix Flexible PVC Heavy duty hose or polymer reinforced thermoplastic hoses of dia 50/63 mm for delivery line with connecting accessories like hose bracket and clamps etc complete all as specified and directed . \nNote : Flexible hose connection must be secured to the discharge pipe nipple or hose to iron pipe adapter and sealed with a stainless steel clamp.90RM
5252Supply and laying LT cable, 1100 volts grade, XLPE insulated and PVC sheathed, armoured, multistranded, heavy duty electric cable with aluminium conductor laid in trenches/ducts/ on poles/ walls/ through pipes etc complete for the sizes of 4 core 16 Sqmm including copper tubular terminal socket (at either end of cable) complete all as specified and directed75RM
5353Material and labour for Point wiring complete with FRLS PVC insulated unsheathed cable 1100V grade conforming to IS-694, 1.5 Sqmm (nominal area) multistranded with copper conductor drawn through and including non metallic rigid PVC conduit 20mm dia (ISI marked) and accessories, wall / surface (open conduit) on ceiling with sunken type pressed steel / welded terminal boxes made out of 2mm mild steel sheet, 3mm thick laminated sheet cover for mounting of switches, socket outlets, regulators etc., including provision of FRLS PVC insulated unsheathed 1.5 Sqmm FRLS multistranded with copper conductor as earth continuity conductor and connecting to common earth dolly complete all as specified and as directed for One 3 pin 5 amps socket on independent board8Per point
5454All as per Item No. 53 above, but using 4 sqmm FRLS single core multi stranded copper conductor cable and 4 Sqmm FRLS copper earth wire cable drawn through 20 mm dia PVC conduit including provision of conduit and conduit accessories connected to all metal boxes and common earth dolly all as specified for for One 3 pin 15 amps socket on independent board1Per point
5555Supply and Fix Switch socket outlet, multipurpose, flush type, 3/5 Pin,AC, 230 Volts, 5 Amps complete all specified and as directed. \n8Each
5656Supply and Fix Switch socket outlet, multipurpose, flush type, 3/5 Pin,AC, 230 Volts, 15 Amps complete all specified and as directed. \n1Each
5757Supply and Fix LED 24W 2'X2' WHITE POWDER COATED CRCA FULL GLOW RECESS MOUNTING LED BACKLIT PANEL ,environmental friendly new generation, asthetically designed, ultra modern recess mounting with high briteness, suitable for armstrong/grid ceilling fitting complete all as specified and as directed. \nMake: Crompton Cat No. LCTLRNE-24-FO-WW or equivalent in Philips/ Havells/Bajaj/C&S4Each
5858Supply and fix wall mounted fan 450mm sweep AC 230 V, 50 Hz 1440 RPM with powder coated guard with aluminium die cast blade minimum three speed control with vertical adjustment complete all as specified and as directed. \nMake : Almonard, Wall Fan 18\" WALL MARK II or equivalent in Crompton Greeves /Bajaj/Usha.4Each
5959Supply and fix sheet metal enclosure SPN with 2 pin and earth plug and socket complete with one single pole MCB 20/32 Amps 240V complete all as specified and as directed.1Each
6060Material and labour Cutting chases, pinning in stone/concrete block walls, making good to facings where required and pointing in cement mortar 1:3 for concealed water tubing, cutting exceeding 10 cm but not exceeding 20 cm including making good and painting to match with adjacent wall colour all as specified and as directed.15RM
6161Supply and fix Sheet metal enclosures, powder coated double door, MCB DB for TPN 4 way 415 V with neutral bus bar 200 Amps double door type with locking arrangement complete all specified and as directed. \n1Each
6262Supply and fix MCB TPN , AC 415 Volts 63 Amps 10 KA, rupturing capacity, 'B' curve complete all as specified and as directed.1Each
6363Supply and fix MCB TP , AC 415 Volts 40 Amps 10 KA, rupturing capacity, 'C' curve complete all as specified and as directed.1Each
6464Supply ,install and testing split Air conditioner of 2 TR capacity inverter 5 Star rating with indoor and outdoor units (copper condenser coil, copper cooling coil and evaporator including required length of copper tubing and cables for connecting indoor and outdoor units ) complete with cordless remote control unit , with inverter rotary compressor with minimum 10 yrs warranty ,complete all as specified and as directed. Make : VOLTAS / BLUESTAR /CARRIER/ O GENERAL/HITACHI.\nNote : Rate quoted is inclusive of the following:- \n(i) Drain pipe UPVC with insulation from indoor unit (at any floor) to ground floor level and is to be fixed with necessary clamps complete. \n(ii) Drilling hole on the brick wall to facilitate routing of Copper pipe, drain pipe and cable from indoor unit to outdoor unit. \n(iii) Sealing the hole from outside ,after installation, with white cement.\n(iv) Pressure testing , cooling performance check and product demonstation. \n(v) 4 core cable of any required length for connecting indoor and outdoor unit.\n(vi) Material and labour for fixing Remote stand in wall.\n(vii) Copper pipe, 1/2\" dia and 1/4 \" dia upto 3.00 Mtr each.1Each Job
6565Supply and fixing of GI powder coated brackets , for fixing of split AC's including grouting with suitable size fastners complete all as specified and directed.1Each Set
6666Supply and fixing Copper pipe 1/2\" dia with foam insulation including connecting complete all as specified and directed.3RM
6767Supply and fixing Copper pipe 1/4 \" dia with foam insulation including connecting complete all as specified and directed.3RM
6868Supply and fix LT under ground cable 1100 volts grade PVC /XLPE sheathed armoured multistranded heavy duty electric cable with aluminium conductor 3.5 core 35 Sqmm, laid in trenches/ duct / walls including cable gland on both termination where necessary including laying, connecting to various switches in panel board, testing and commissioning etc complete all as specified and directed.\nNOTE: Earth work excavation shall be measured and paid separately.40RM
6969Returning, filling in incl spreading leveling, watering and well ramming in layers n.exc.25cm thick complete all as specified and as directed.3.5Cum
7070Supply and spread natural river sand in trenches for cushioning and covering to cable complete all as specified and as directed. \nNOTE: Punned thickness shall be measured and paid.2.4Cum
7171Supply, lay in trenches burnt Bricks, old size, Sub class \"B\" for cable protection all as specified and directed.0.2Per 1000 Nos
7272Supply and laying GI tubing Light grade of size 40 mm dia bore laid in trenches / on floors / walls/ceiling for protection of UG cable complete all as specified and as directed.8RM
7373Cutting the existing bituminous road / cement concrete surface to the required width and depth for laying pipe lines and returning filling in, removal of surplus material complete all as specified.\nNote: PCC for making good the top level to match raod surface shall be measured and paid separately.0.5Cum
7474Material and labour for 150mm thick Plain Cement Concrete 1:3:6 type C2 using 40 mm graded stone aggregate for making good the disturbed road surface after laying of pipe line over returned filled and compacted earth surface to match with existing road level complete all as specified and as directed.0.3Cum
7575Earthing complete with GI earth plate electrode 600 x 600 x 6.0mm buried directly in ground vertically to a depth not less than 2.25 M below GL with top edge of the earth plate not less than 1.5 M below normal GL connected with GI earth wire 4mm dia by means of bolts, nuts check nut and washers of GI and earth wire protected by GI pipe 40mm bore light grade and watering pipe 20mm bore GI pipe medium grade including one test point for testing purpose with funnel and connected to switch/control board upto 7.5m away from earth electrode including earth work, PCC (1:3:6) type C-1 chamber, RCC (1:2:4) type B-1cover slab 50mm thick with 8mm dia TMT bars reinforcement both ways at 140mm C/C, charcoal, salt, water pipe, wire mesh, lugs etc and testing complete all as applicable and as per Plate No. 3 of SSR 2009 and all as specified. \nNote : The unit rate shall also include for excavation, earth work in hard/dense soil PCC (1:3:6) type C1 pit, RCC cover slab, GI funnel with 20 mm dia watering pipe, wire mesh,40mm dia light grade GI protection pipe for earth strip etc., complete.The rate quoted shall be deemed to include for Earth continuity conductor and GI protection pipe upto 7.5m.1Each Job
76Total in Figures

AI Tender Summary

OUR REF NO 28409068
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE Ref. Documents
LAST DATE 24-07-2021
Authority
Authority Name Military Engineer Services
Work Description Provision Of Certain Sanction Works At Ins Parundu 8155 / E8
Basic Detail
Tender No GE/TVL/8155
Bidding Type Tender
Location
City Ramnad
State Tamil Nadu
Key Dates
Publish Date 17 Jul 2021
Submission Date 24 Jul 2021
Open Date 26 Jul 2021
Finance
Tender Value Ref. Documents
Tender Fee 500
EMD 88000
Exemption Not Available
Document List
Tendernotice_1.pdf
8155TenderDocuments.pdf
BOQ_509527.xls
46FC2FA7-33A2-4B07-9AF4-89D5F1F559DE.html

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 17, 2021
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 24, 2021
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Completed
Jul 24, 2021
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Jul 26, 2021

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
pdf

Tendernotice_1.pdf

pdf

8155TenderDocuments.pdf

xls

BOQ_509527.xls

html

46FC2FA7-33A2-4B07-9AF4-89D5F1F559DE.html

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender