| 1 | 1 | External Electrification work for Traffic Management and Data base Centre, Ujjain | BI01010001010000000000000515BI0100001112 | | |
|---|
| 2 | 1.01 | Supplying and erection of HT/LT over head line single length supports complete with aligning and keeping it in truly vertical position, including digging pit of required size in all type of soil/rocks filling with 1:3:6 cement concrete of 0.60 mtr. dia. around the pole up to ground level including muffing of 0.45 mtr. dia. from ground level to 0.45 mtr. high as per specifications with 20 cm. thick base foundation in 1:4:8 cement concrete as required refilling the pit with boulder and soil as required, including painting of pole with bitumen paint below GL and two coats of red oxide and two coats of aluminium paint or synthetic enamel paint above GL as directed complete as per specification. The depth of burying of pole shall be 1/6th of the length of pole. | | | |
|---|
| 3 | 1.03 | l)H Beam 11 Mtr Long 152x152 or 150x150 mm 37.1 Kg/Mtr. Weight | H Beam 11 Mtr Long 152x152 or 150x150 mm 37.1 Kg/Mtr. weight | 2 | Each |
|---|
| 4 | 2 | Supplying and fixing of angle / channel / flat iron / RS Joist fittings for over head lines as cross arms / brackets / clamps etc. including nut bolts, required holes, welding, cutting, fabricating with necessary materials including two coats of red oxide and two coats of aluminium or synthetic enamel paint etc. as required. | | 75 | kg |
|---|
| 5 | 3 | Supplying and erection of GI/MS stay set complete with stay rod, anchor plate of size 300x300x5mm, thimble, stay clamp, turn buckle, bow tightener etc. with stay wire, strain insulator, nut bolts as per specifications including excavation in all type of soil/ rocks and foundation in cement concrete 1:3:6 of required size and other necessary materials complete as required as per specifications. | | | |
|---|
| 6 | 3.01 | A. GI Stay Rod 16mm dia 1.8 m long with 7/3.15mm stay wire for LT line | | 4 | Each |
|---|
| 7 | 4 | Supplying and fixing polymer 11KV/33KV HT Disc (strain) insulator of approved make on existing pole or bracket with GI hardware and other necessary materials complete as required. | | | |
|---|
| 8 | 4.01 | 11 KV Strain insulator set (Hardware suitable upto Racoon conductor) | | 3 | Each |
|---|
| 9 | 6 | Supplying and drawing ACSR/AAAC conductor of approved make with stringing making off complete with binding at existing insulator, jointing, jumpering, teeing off connecting etc. as required and clearing of obstacles (if any). | | | |
|---|
| 10 | 6.01 | AAAC 7/3.35mm dia.(0.05) 55 sqmm.(Rabbit) | AAAC 7/3.35mm dia.(0.05) 50 sqmm.(Rabbit) | 0.03 | km |
|---|
| 11 | 7 | Supplying installing, connecting, testing and commissioning of 3 Phase, 50 Hz, 11/0.433 KV or 33/0.433 KV, Delta/Star connected, Aluminium/Copper wound, oil filled, Indoor/outdoor type, Distribution/Station transformer of accepted standard specification, 4 star catagory class, with accessories such as drain & filter valve, earthing terminals, lifting arrangements of suitable size, dehydrating breather with silica gel of suitable size, Conservator tank, air release devise, Rating & diagram plate including CI rollers, Radiators with shut off valve, Cable end boxes on HT & LT side bushings, Explosion vent with diaphragm, Off load tap changing switch, Buchholz relay, thermometer pocket with 6” dial type thermometer & OTI, wherever required complete with first filling of oil with installation on existing DP structure or foundation etc. complete as per specification. The no load and full load losses should not be more than as mentioned below. BIS CERTIFIED, EE LEVEL-II | | | |
|---|
| 12 | 7.01 | 100 KVA 11/.433 KV (Alluminium wound with tap changing arrangement) NLL 0.51 KW & FLL 3.0 KW | 100 KVA 11/.433 KV (Alluminium wound with tap changing arrangement) NLL 0.51 KW & FLL 3.0 KW | 1 | Each |
|---|
| 13 | 8 | Providing and fixing outdoor type pole mounting weather, dust and vermin proof LT distribution box made of 14 gauge MS sheet with clamping arrangements, lockable hinged door duly painted on all sides with red oxide after antirust and corrosion treatment, two coats of synthetic enamel paints of approved make and shade, consisting of following fittings: | | | |
|---|
| 14 | 8.01 | For 100 KVA Transformer | | | |
|---|
| 15 | 8.02 | a) 200 Amps 35 KA breaking capacity TP MCCB with neutral link for incoming - 1No. | | | |
|---|
| 16 | 8.03 | b) 4 strip aluminium bus bar 225Amps supported on epoxy insulators - 1 Set | | | |
|---|
| 17 | 8.04 | c) 160/200 Amps, 415Volts DMC cutout with base for outgoing feeder with 160/200 amp HRC - 9 Nos. | | | |
|---|
| 18 | 8.05 | d) GI earth terminals- 2 Nos. | | | |
|---|
| 19 | 8.06 | e) 6 Lever Godrej Padlock with 3 keys - 1 No. | | | |
|---|
| 20 | 8.07 | f) Light point with switch and lamp holder with lamp - 1 No. | | | |
|---|
| 21 | 8.08 | Distribution box complete as above (a to F) as per MPKVVCL norms & specifications complete. | | 1 | Each |
|---|
| 22 | 9 | Providing and fixing earthing arrangement for HT/LT poles with 8SWG GI lead of 115 turns of 50 mm dia. connection with pole / cross arm / control junction box on pole with 4 mm dia. GI lead through 20 mm dia A class GI protection pipe of 2.5 m length duly bend, packing of charcoal powder and salt as per specification including excavation of pit in all type of soil / rock, refilling of pit by black cotton soil etc. complete. | | 2 | Each |
|---|
| 23 | 10 | Supplying, laying, testing and commissioning of XLPE insulated and PVC sheathed heavy duty power cable confirming to IS 7098/Part-I/88 with latest amendments, 1100 volts grade armoured cable of approved make with aluminium solid / stranded conductor. The cable shall be laid in air/in existing pipe/in existing cable trench/on existing cable tray with clamp as required as per specifications including providing of metal/PVC cable identification tags at both ends and every 10 Mtr. length of cable with inscriptions there on. | | | |
|---|
| 24 | 10.02 | Un armoured cable 1 core 150 Sq.mm | | 40 | RM |
|---|
| 25 | 10.03 | Un armoured cable 1 core 70 Sq.mm | | 80 | RM |
|---|
| 26 | 11 | Supplying and fixing 2 ply 12 gauge barbed wire around the existing HT/LT electric pole for safety measures as per IE rules including all stapples and all other necessary materials complete as required as per specifications. | | 2 | Each |
|---|
| 27 | 12 | Providing and fixing enamelled danger caution plate/board on existing electric poles or wherever required of size 250x200 mm, made of 1.6mm thick mild steel sheet and vitreous enamelled white, with latest, figures and the conventional skull and cross-bones in signal red colour (as per IS-5-1978 with latest amendment) on the front side. The rear side of the plate shall also be enamelled. The corner of the plate shall be rounded off with required material such as screws, wires clamps, nut bolts etc. complete. | | | |
|---|
| 28 | 12.01 | 11 KV | | 2 | Each |
|---|
| 29 | 13 | Supplying Installatin Testing and Commissioning of D.P. structurre over existing support with painting in an approved manner consisting of following:- | | | |
|---|
| 30 | 13.01 | (a) D.C. cross arm with clamp and nuts bolts (100x50mm channel) – 1Set | (a) D.C. cross arm with clamp and nuts bolts (100x50mm channel) – 1Set | | |
|---|
| 31 | 13.02 | (b) 11KV D.O. fuse unit, lighting arrester and A.B. switch mounting channels with nuts and bolts (75x10mm channel) as required –1 set. | (b) 11KV D.O. fuse unit, lighting arrester and A.B. switch mounting channels with nuts and bolts (75x10mm channel) as required –1 set. | | |
|---|
| 32 | 13.03 | (c) Transformer mounting cross arms with clamps nuts and bolts (100x50mm. Channels) – 1 set. | (c) Transformer mounting cross arms with clamps nuts and bolts (100x50mm. Channels) – 1 set. | | |
|---|
| 33 | 13.04 | (d) Transformer clamping set with nuts and bolts etc. complete. 1 set. | (d) Transformer clamping set with nuts and bolts etc. complete. 1 set. | | |
|---|
| 34 | 13.05 | (e) Transformer belting set with nuts and bolts etc. complete. – 1 set. | (e) Transformer belting set with nuts and bolts etc. complete. – 1 set. | | |
|---|
| 35 | 13.06 | (f) Distribution pannel mounting channel and clamp with nuts and bolts etc. (75x40mm channel).-1 set | (f) Distribution pannel mounting channel and clamp with nuts and bolts etc. (75x40mm channel).-1 set | | |
|---|
| 36 | 13.07 | (g) G.I. Pipe/bend as required for cable laying. -1 Job | (g) G.I. Pipe/bend as required for cable laying. -1 Job | | |
|---|
| 37 | 13.08 | (h) S/f DTR metering unit i/c meter box as per MPEB specification complete. | (h) S/f DTR metering unit i/c meter box as per MPEB specification complete. | | |
|---|
| 38 | 13.09 | (i) G.I. pipe earthing complete with G.I. strip 25x3 mm as required complete. | (i) G.I. pipe earthing complete with G.I. strip 25x3 mm as required complete. | | |
|---|
| 39 | 13.1 | (j) A.B. Switch as per M.P.E.B. norms completed. 1 Set | (j) A.B. Switch as per M.P.E.B. norms completed. 1 Set | | |
|---|
| 40 | 13.11 | (k) L.A. as per M.P.E.B. norms specification complete. | (k) L.A. as per M.P.E.B. norms specification complete. | | |
|---|
| 41 | 13.12 | (l) 11 KV 200 Amps DO Fuse (3.nos) 1 Set | (l) 11 KV 200 Amps DO Fuse (3.nos) 1 Set | | |
|---|
| 42 | 13.13 | (m) 11 KV gap less polymer type LA | (m) 11 KV gap less polymer type LA | | |
|---|
| 43 | 13.14 | (n) D.P. structure complete as above. Complete as above (a to m) | (n) D.P. structure complete as above. Complete as above (a to m) | 1 | Each |
|---|
| 44 | 14 | Providing and fixing chain link fencing sourriding existing DTR S/S finical (total 37 running meter maximum) of 6 feet height with chain ling fencing on MS Angle (50X50X6) mm support 7 nos. 7 feet height including digging of pit in all type of soil / rock as required. The depth of burying of angle post shall be 0.5 mtr. and filling with 1:3:6 cement concrete of 30 cm. dia. around the post as required. & Supplying, stacking and spreading of nominal size metal 40 mm with following feature. | | | |
|---|
| 45 | 14.01 | (A) Upper & lower frame of fencing will be of MS angle (25X25X4) mm size. | | | |
|---|
| 46 | 14.02 | (B) MS strip of (25X5) mm flat shall be used fro cross bracing of fencing | | | |
|---|
| 47 | 14.03 | (C) Double Gate (2nos. 2.5’X5’) of MS angle (50X50X6)mm. bracing of 25X5 mm flat with mesh & locking arrangement.Complete as above( A to C) – one job. | | 16 | SQM |
|---|
| 48 | 23 | (1) The contractor is responsible for approval fo transformer/sub station/HT/LT lines/ Testing of LTCT. Meter, form competent authority of Electrical Inspector and energy station/commissioning of sub station HT/LT lines and necessary shut down form MPMKVVCO. No extra payment will be done for this job (2) Quantities/ items may increased/ decrease as per site conditions. (3) Ready to carryout maintenance work if failure of any equipment i.e. transformer, Line in colony within 5 year period from the date handing over. (4) All Material for use in External Electrification work of as per approved List attached. | | | |
|---|