| 1 | 1 | Providing DG set (DG without Panel shall be supplied by KELat site) | BI01010001010000000000000515BI0100001112 | | |
|---|
| 2 | 1.01 | od20795/2021_2022 : Supply Installation, testing & commissioning of 100 kVA Diesel Generator(DG without Panel shall be supplied by KELat site) set with AMF control panel and integral acoustic enclosure as per relevant CPCB norms with standardized accessories as per technical details given below.\n1. Engine : a) Make of Engine - Cummins/ KEL/ KOEL/ Leyland) Type of Engine - Diesel Engine c) No. of Cylinders - As per manufactures standards. d) Method of Cooling - Water cooled with radiator. e) Design - Suitable for generating set operation 2.Standard accessories with Diesel Engine a) Fly wheel to suit flexible coupling b) Close Coupling c) Air cleaner d) Radiator with fan provided with fan guard. e) Fuel Pump f) Fuel filter g) Lubricating oil filter h) Exhaust silencer i) Exhaust Muffler j) Battery Charger/Generator 3. Engine Instrument Panel with the following items a) Starting switch with key or button b) Lubricating oil pressure gauge. c) Water temperature gauge. d) RPM Indicator with hour meter e) Battery charging Ammeter 4. Safety Controls for Engine a) Trip for low lubricating oil pressure b) Trip for high water temperature. 6. Brush less Alternator a) Make - LS/ Crompton/ KEL/ Stanford/ Kirloskar b) Type - Self exited and self regulated. c) Capacity - 100 KVA/80 K W @ 0.8PF d) System of Voltage - 3 phase, 415 V, e) Frequency - 50 Hz f) Insulation - Class F/H The Alternator should confirm to IS 4722. Operation and service manual, spares and tools shall be provided. 7. Fuel Tank Suitable size built in type integrated with the acoustic enclosure Fuel connection shall be done as per standards 8. Battery Suitable size built in type integrated battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. Automatic Battery charger Solid state phase indication lamp for supply ON/OFF with HRC protection. standard control panel as per Statutory authority requirements, with 160A 4 pole 16 KA Thermal magnitc MCCB ,earth fault relay using CT in neutral conductor and accessories such as Multi function meter and separate Energy meter, In built solid state battery charge with over charge protection etc. The AMP panel should consist AMF relay.\nATS / Motorized change over / Contactor with MCCB protection, fabricated in 16 swg MS enclosure prvided as a separate unit out side the DG set | BI01010001010000000000000515BI0100001113 | 1 | set |
|---|
| 3 | 1.02 | od20899/2021_2022 : Supply and providing the following size of C class MS pipe IS:1239 PART-1 (2004) conforming to relevant IS specifications complete with heavy gauge specials such as bends, flanges etc welded and fixed at appropriate locations providing cork sheet in between the flanges at the joints, bolting the flanges together, painting the pipe, flanges etc with 2 coats of heat resistant paint suitable for outdoor applications fixing the pipe firmly with fabricated structure/ mechanical support etc as required 150 mm\ndia. | BI01010001010000000000000515BI0100001114 | 10 | metre |
|---|
| 4 | 1.03 | od20867/2021_2022 : Supply of HSD for testing of the DG set\nincluding loading at the fuelpump,conveyance,unloading at site,filling in the tank etc | BI01010001010000000000000515BI0100001115 | 175 | Litre |
|---|
| 5 | 1.04 | od20869/2021_2022 : Supply and installation of self priming\npump with 1/4 HP motor with suitable MS brackets etc as required including painting the bracket | BI01010001010000000000000515BI0100001116 | 1 | no |
|---|
| 6 | 1.05 | 90.12.5.32 : Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 120 sq mm | BI01010001010000000000000515BI0100001117 | 70 | metre |
|---|
| 7 | 1.06 | 90.12.7.32 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 120 sq mm | BI01010001010000000000000515BI0100001118 | 30 | metre |
|---|
| 8 | 1.07 | od21278/2021_2022 : Supply & laying of one number PVC insulated and PVC sheathed armoured copper power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.6 core 2.50 sq mm | BI01010001010000000000000515BI0100001119 | 70 | metre |
|---|
| 9 | 1.08 | od21280/2021_2022 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60 cms, making good the damages , colour washing etc. as required.6 core 2.50 sq mm with\nfactory made clamp | BI01010001010000000000000515BI0100001120 | 25 | metre |
|---|
| 10 | 1.09 | 90.12.39.1 : Supply & laying of one number PVC insulated and PVC sheathed armoured copper power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/\nDWC pipe as required.2 core 4 sq mm | BI01010001010000000000000515BI0100001121 | 70 | metre |
|---|
| 11 | 1.1 | 90.12.41.1 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 4 sq mm with factory made clamp | BI01010001010000000000000515BI0100001122 | 25 | metre |
|---|
| 12 | 1.11 | 90.12.10.6 : Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation110/94 mm or nearest size | BI01010001010000000000000515BI0100001123 | 70 | metre |
|---|
| 13 | 1.12 | 90.12.10.3 : Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation63/50 mm or nearest size | BI01010001010000000000000515BI0100001124 | 70 | metre |
|---|
| 14 | 1.13 | 9.1.25 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of\n1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm) | BI01010001010000000000000515BI0100001125 | 6 | set |
|---|
| 15 | 1.14 | 9.1.1 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of\n1.1 KV grade as required.2 X 6 sq. mm (19mm) | BI01010001010000000000000515BI0100001126 | 2 | set |
|---|
| 16 | 1.15 | 9.1.34 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of\n1.1 KV grade as required.4 X 25 sq. mm (28mm) | BI01010001010000000000000515BI0100001127 | 2 | set |
|---|
| 17 | 1.16 | od20821/2021_2022 : Providing and fixing 200A ON Load change over switch in sheet steel enclosure making connections, etc. as\nrequired. | BI01010001010000000000000515BI0100001128 | 1 | each |
|---|
| 18 | 1.17 | 90.11.1.15 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43) | BI01010001010000000000000515BI0100001129 | 1 | each |
|---|
| 19 | 1.18 | 2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole | BI01010001010000000000000515BI0100001130 | 6 | each |
|---|
| 20 | 1.19 | 2.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole | BI01010001010000000000000515BI0100001131 | 4 | each |
|---|
| 21 | 1.2 | 90.12.41.20 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 25 sq mm with factory\nmade clamp | BI01010001010000000000000515BI0100001132 | 15 | metre |
|---|
| 22 | 1.21 | 90.14.1.2 : Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame) | BI01010001010000000000000515BI0100001133 | 6 | sqm |
|---|
| 23 | 1.22 | 90.14.2.1 : Supply and providing 2mm SMC sheet as shrouding for\nbus interconnection / terminations etc. including required nut & bolt etc. | BI01010001010000000000000515BI0100001134 | 1 | sqm |
|---|
| 24 | 1.23 | 90.14.3.2 : Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for\n1.60/ 2.00 mm sheet | BI01010001010000000000000515BI0100001135 | 12 | metre |
|---|
| 25 | 1.24 | 90.14.5 : Supply and fabrication conveyance and installation of\nangle iron frame work for wall mounting panel board | BI01010001010000000000000515BI0100001136 | 200 | kg |
|---|
| 26 | 1.25 | 90.14.6 : Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required. | BI01010001010000000000000515BI0100001137 | 1100 | Cum cm |
|---|
| 27 | 1.26 | 90.14.7 : Supply and providing copper earth bus in the panel board | BI01010001010000000000000515BI0100001138 | 300 | Cum cm |
|---|
| 28 | 1.27 | 90.14.10.3 : Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL | BI01010001010000000000000515BI0100001139 | 3 | no |
|---|
| 29 | 1.28 | od21338/2021_2022 : Supply and fixing 125 A, 25 kA\n(Ics=100%Icu), 4 pole, MCCB having thermal setting range of 80 - 100% with extended terminal | BI01010001010000000000000515BI0100001140 | 2 | no |
|---|
| 30 | 1.29 | od21340/2021_2022 : Supply and fixing 160 A, 25 kA (Ics=100%Icu), 4 pole, MCCB having thermal setting range of 80 -\n100% with extended terminal | BI01010001010000000000000515BI0100001141 | 1 | no |
|---|
| 31 | 1.3 | od20859/2021_2022 : Supply and providing Red, Green, Black, Yellow, Orange colours LED indicators, AC/DC 22.5mm cut out dia | BI01010001010000000000000515BI0100001142 | 9 | each |
|---|
| 32 | 1.31 | od20861/2021_2022 : Supply and providing Blue colour LED\nindicator lamp, AC/DC, 22.5 cm cut out dia. | BI01010001010000000000000515BI0100001143 | 3 | each |
|---|
| 33 | 1.32 | od20863/2021_2022 : Supply and installation of Three phase multifunction meters to read V, A and F, accuracy class 0.5 | BI01010001010000000000000515BI0100001144 | 1 | each |
|---|
| 34 | 1.33 | od20865/2021_2022 : Supply and fixing of 100/5 A, 5 VA, accuracy class 1, Resin Cast Metering CT | BI01010001010000000000000515BI0100001145 | 3 | each |
|---|
| 35 | 1.34 | 5.4 : Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, andproviding masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. | BI01010001010000000000000515BI0100001146 | 3 | set |
|---|
| 36 | 1.35 | 90.16.3.9 : Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal\nrun)25 x 3 mm copper strip | BI01010001010000000000000515BI0100001147 | 40 | metre |
|---|
| 37 | 1.36 | 90.2.1.1 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Short point | BI01010001010000000000000515BI0100001148 | 3 | point |
|---|
| 38 | 1.37 | 90.2.1.6 : Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points | BI01010001010000000000000515BI0100001149 | 1 | each |
|---|
| 39 | 1.38 | 90.3.20.3 : Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture | BI01010001010000000000000515BI0100001150 | 3 | each |
|---|
| 40 | 1.39 | 90.6.10.1 : Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as\nrequired20 mm | BI01010001010000000000000515BI0100001151 | 10 | metre |
|---|
| 41 | 1.4 | 1.17.21 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface\n/ recessed steel/ PVC conduit as required.3 x 4 sq. mm | BI01010001010000000000000515BI0100001152 | 10 | metre |
|---|
| 42 | 1.41 | 2.3.2 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door | BI01010001010000000000000515BI0100001153 | 1 | each |
|---|
| 43 | 1.42 | 2.12.1 : Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps | BI01010001010000000000000515BI0100001154 | 1 | each |
|---|
| 44 | 1.43 | 2.14.1 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps | BI01010001010000000000000515BI0100001155 | 1 | each |
|---|
| 45 | 1.44 | 90.16.1.3 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) | BI01010001010000000000000515BI0100001156 | 150 | metre |
|---|
| 46 | 1.45 | 90.16.5.3 : Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as\nrequired.3.15 mm (10 SWG) | BI01010001010000000000000515BI0100001157 | 4 | each |
|---|
| 47 | 1.46 | 14.1 : Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres. | BI01010001010000000000000515BI0100001158 | 5 | cum |
|---|
| 48 | 1.47 | 14.7 : Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as\nrequired. | BI01010001010000000000000515BI0100001159 | 5 | cum |
|---|
| 49 | 1.48 | 14.12.1 : Providing 15mm thick cement plaster of mix 1:4 (1\ncement : 4 fine sand) at all levels. | BI01010001010000000000000515BI0100001160 | 10 | sqm |
|---|
| 50 | 1.49 | od21264/2021_2022 : 5.9.5.Form work for reinforced cement concrete in slabs including wooden planks, joists, bamboo posts and labour for taking down after completion of work (Hire and labour\ncharges only) | BI01010001010000000000000515BI0100001161 | 4 | sqm |
|---|
| 51 | 1.5 | od21266/2021_2022 : 13.62.1.Painting with one or more coat of aluminium paint of approved brand and manufacturer to give an even shade.of aluminium paint of approved brand and\nmanufacturer to give an even shade. | BI01010001010000000000000515BI0100001162 | 15 | sqm |
|---|
| 52 | 1.51 | od21268/2021_2022 : 12.4.2.Providing ridges or hips of width 60 cm overall width plain G.S. sheet fixed with polymer coated J or L hooks, bolts and nuts 8 mm dia G.I. limpet and bitumen washers\ncomplete 0.63mm | BI01010001010000000000000515BI0100001163 | 75 | metre |
|---|
| 53 | 1.52 | od21270/2021_2022 : 12.1.3.Providing corrugated G.S. sheet roofing including vertical / curved surface fixed with polymer coated J or L hooks, bolts and nuts 8 mm diameter with bitumen and G.I. limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete (up to any pitch in horizontal/ vertical or curved surfaces),excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.0.63 mm | BI01010001010000000000000515BI0100001164 | 25 | sqm |
|---|
| 54 | 1.53 | od21272/2021_2022 : 10.16.1. Steel work in built up tubular (round, square or rectangular hollow tubes etc.)trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. | BI01010001010000000000000515BI0100001165 | 175 | kg |
|---|
| 55 | 1.54 | od21274/2021_2022 : 50.10.2. Steel work for Purline/Single Section with GI Pipe (round, square or rectangular hollow tubes etc.)trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.33 mm dia | BI01010001010000000000000515BI0100001166 | 35 | kg |
|---|
| 56 | 1.55 | od21276/2021_2022 : Reinforcement for R.C.C works, bend tied\nand placed in position (plain grill requiring bend cold) using tor steel | BI01010001010000000000000515BI0100001167 | 50 | kg |
|---|
| 57 | 1.56 | od20903/2021_2022 : Supply and providing ISI marked 6 Kg. ABC Fire Extinguisher with hose and clamps including fixing it to wall as\nrequired. | BI01010001010000000000000515BI0100001168 | 6 | each |
|---|
| 58 | 1.57 | od20917/2021_2022 : Supply and providing 9 litre capacity GI Fire bucket painted in post office red with primer coat of red oxide and written with white paint 'FIRE' mounted on MS angle frame work/ wall bracket filled with fine sand painting the bracket/ floor stand including making good the damages, colour washing etc as\nrequired. | BI01010001010000000000000515BI0100001169 | 2 | no |
|---|
| 59 | 1.58 | od20913/2021_2022 : Painting letters or figures of the 2.5 cm, 4 cm or 5 cm height sizes with enamel paint as identification mark to SB,\nDB, Panel board as required. | BI01010001010000000000000515BI0100001170 | 200 | each |
|---|
| 60 | 1.59 | od20915/2021_2022 : Supply and providing 2mm thick\nElastomeric fire retardent insulating mat as per IS 15652/2006 to withstand 3.3 KV dielectric strength. | BI01010001010000000000000515BI0100001171 | 5 | sqm |
|---|
| 61 | 1.6 | od20797/2021_2022 : Charges for preparation of Electrical/fire\nDrawing per A3 sheet first copy | BI01010001010000000000000515BI0100001172 | 3 | each |
|---|
| 62 | 1.61 | od20799/2021_2022 : Copying charges of Electrical/fire Drawing\nper A3 sheet additional copies | BI01010001010000000000000515BI0100001173 | 21 | each |
|---|
| 63 | 1.62 | od21262/2021_2022 : LS provision for KSEB Ltd / Inspectorate / Fire & Rescue Dept fee / Charges { Actual amount will be reimbursed on production of original documents. Tender deviation\nis not applicable for this item } | BI01010001010000000000000515BI0100001174 | 1 | each |
|---|
| 64 | 1.63 | Note :1 All materials, Items, Equipment shall be best branded items with IS and approved by client/KEL | | | |
|---|
| 65 | 1.64 | 2:Rate should be inclusive of Insurance,Transportation, delivery and installation cost for all items | | | |
|---|
| 66 | 1.65 | 3.Rate should be Exclusive of GST. | | | |
|---|
| 67 | 1.66 | 4.Work should be executed as per Electrical Inspectorate / KSEB specification and direction of Engineer at site. | | | |
|---|