| Name of Work: SPECIAL REPAIRS/REPLACEMENT OF LT PANELS, LT LINES, RMUs, PERIMETER SECURITY LIGHTS AND TOWER LIGHTS AT AF STN ADAMPUR | |||||
|---|---|---|---|---|---|
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
| 1 | 1 | Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying/taking out of cables and foundation of poles etc. and getting out, complete all as specified and directed. | 808 | Cubic Metre | |
| 2 | 2 | Returning, filling in trenches (soil), including spreading, leveling and well ramming in layers not exceeding 25 cm thick, complete all as specified and directed. | 488 | Cubic Metre | |
| 3 | 3 | Removal of surplus excavated soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5metre above the starting point, complete all as specified and directed. | 320 | Cubic Metre | |
| 4 | 4 | Material and labour for sand cushioning with a layer of dry river sand, 80mm thick before laying of cable and 150mm thick (punned down to 100mm thick) after laying of cables, in trenches/ducts, complete all as specified and directed. \nNote : Punned down thickness (overall 18cm), shall be considered for measurement and payment. | 270 | Cubic Metre | |
| 5 | 5 | Supplying and laying factory made unreinforced precast concrete cable cover HV type-1, flat, of size 300mm x180mm x40mm, laid flat and dry in trenches over the cable for protection, length perpendicular to the direction of cable adjacent to each other, complete all as specified and directed. | 1000 | Each | |
| 6 | 6 | Supply & laying old size sub class 'B' bricks laid flat in trenches over the cable with the length of brick perpendicular to the direction of cable length, adjacent/abutting each other complete all as specified and directed by Engineer-in-charge. | 25.2 | Per 1000 Nos | |
| 7 | 7 | Supply and laying / fixing , GI pipe light grade 50mm bore for cable protection fixed to pole/wall or laid under floor/road/pavement, including taking out old pipe & removal, complete all as specified and directed.\n\n | 24 | Running Metre | |
| 8 | 8 | All as per serial item No 7 here-in-before but of size 80mm dia | 18 | Running Metre | |
| 9 | 9 | All as per serial item No 7 here-in-before but of size 100mm dia | 18 | Running Metre | |
| 10 | 10 | Taking out / down old existing HT 11000 volt grade cables, size 95 Sqmm, aluminium conductor 3core, XLPE, armoured, laid in trenches, including PCC / Brick Covers for protection, and stacking, removal to store for re-use or for credit, complete all as specified and directed. | 200 | Running Metre | |
| 11 | 11 | Supply, laying, jointing, testing and commissioning of High Tension (HT), 11000 Volts (earthed) grade, XLPE insulated, screened, PVC bedded, galvanized steel strip armoured, electric power cable (heavy duty) with stranded aluminum conductor, cross sectional area 95 Sqmm, 3core under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and directed. \nNote : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. | 200 | Running Metre | |
| 12 | 12 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 10 Sqmm 4core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. \nNote : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. \n | 200 | Running Metre | |
| 13 | 13 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 16 Sqmm 4core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. \nNote : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. | 300 | Running Metre | |
| 14 | 14 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 25 Sqmm 4core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. \nNote : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. | 300 | Running Metre | |
| 15 | 15 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 35 Sqmm 3.5core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. \nNote : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. | 400 | Running Metre | |
| 16 | 16 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 50 Sqmm 3.5 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. \nNote : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. | 300 | Running Metre | |
| 17 | 17 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 70 Sqmm 3.5 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. \nNote : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. | 200 | Running Metre | |
| 18 | 18 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 95 Sqmm 3.5 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. \nNote : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. | 200 | Running Metre | |
| 19 | 19 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 120 Sqmm 3.5 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. \nNote : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. | 150 | Running Metre | |
| 20 | 20 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 150 Sqmm 3.5 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. \nNote : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. | 100 | Running Metre | |
| 21 | 21 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 185 Sqmm 3.5 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. \nNote : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. | 200 | Running Metre | |
| 22 | 22 | Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 240 Sqmm 3.5 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. \nNote : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. | 450 | Running Metre | |
| 23 | 23 | Material and Labour for boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure. Note: The quoted rate shall be deemed to include the cost of provn of HDPE pipe. | 15 | Running Metre | |
| 24 | 24 | Taking out / down old existing LT 1100 volt grade cables, size 10 Sqmm to 16 Sqmm, aluminium conductor 4.0 core, XLPE, armoured, laid in trenches, including bricks for protection, and stacking, removal to store for re-use or for credit, complete all as specified and directed. | 500 | Running Metre | |
| 25 | 25 | Taking up or down defective/faulty LT underground cable 1100 volts 25 Sqmm 4.0 to 35 Sqmm 3.5 core from the existing trench/duct/pole etc an Re-laying the same in the trenches/duct/pole etc after rectification of defects, including meggering of cable, provn of cable lugs, glands, thimble, insulation tape and connecting up with existing control gears, panels etc as per site requirement, complete all as specified and as directed. \nNote:- Excavation, returning filling etc shall be measured and paid seperately.\n | 700 | Running Metre | |
| 26 | 26 | Taking out / down old existing LT 1100volt grade cables, size 50 Sqmm to 95 Sqmm, aluminium conductor 3.5core, XLPE, armoured, laid in trenches, including bricks for protection, and stacking, removal to store for re-use or for credit, complete all as specified and directed. | 700 | Running Metre | |
| 27 | 27 | Taking out / down old existing LT 1100 volt grade cables, size 120 Sqmm to 185 Sqmm, aluminium conductor 3.5core, XLPE, armoured, laid in trenches, including bricks for protection, and stacking, removal to store for re-use or for credit, complete all as specified and directed. | 450 | Running Metre | |
| 28 | 28 | Taking out / down old existing LT 1100 volt grade cables, size 240 Sqmm to 300 Sqmm, aluminium conductor 3.5 core, XLPE, armoured, laid in trenches, including bricks for protection, and stacking, removal to store for re-use or for credit, complete all as specified and directed. | 450 | Running Metre | |
| 29 | 29 | Supply and fixing cable jointing kit for 11 KV grade cable for in door termination, heat shrinkable type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 95 sqmm to 185 sqmm complete all as specified and directed. | 2 | Each | |
| 30 | 30 | Supply and fixing cable jointing kit for 11 KV grade cable for outdoor termination , heat shrinkable type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 95 sqmm to 185 sqmm complete all as specified and directed. | 2 | Each | |
| 31 | 31 | Supply and fixing cable jointing kit for 11 KV grade cable for straight through cold shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 50 Sqmm to 95 sqmm, Indoor/Outdoor type complete all as specified and directed. | 2 | Each | |
| 32 | 32 | Supply and fixing cable jointing kit for 11 KV grade cable for straight through cold shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 120 sqmm to 185 sqmm, Indoor/Outdoor type complete all as specified and directed. | 12 | Each | |
| 33 | 33 | Supply and fixing cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrinkable type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Aluminium conductor cable of size 25 to 50 sqmm,Indoor/Outdoor type complete all as specified and directed. | 2 | Each | |
| 34 | 34 | Supply and fixing cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrinkable type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Aluminium conductor cable of size 70 to 95 sqmm,Indoor/Outdoor type complete all as specified and directed. \n\n\n\n\n | 3 | Each | |
| 35 | 35 | Supply and fixing cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrinkable type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Aluminium conductor cable of size 120 to 185 sqmm,Indoor/Outdoor type complete all as specified and directed. \n | 3 | Each | |
| 36 | 36 | Supply and fixing cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrinkable type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Aluminium conductor cable of size 185 to 240 sqmm,Indoor/Outdoor type complete all as specified and directed. \n | 2 | Each | |
| 37 | 37 | Supply and fixing cable route marker for HT cable duly engraved (HT 11 KV cable) on 150mm dia MS round plate, duly painted with brown colour paint, and fixed on MS angle of size 40mmx40mmx5mm with nuts and bolts and embedded in PCC (1:2:4) concrete block of size 230mmx230mmx150mm, complete all as specified and directed.\nNote : The length of MS angle shall not be less than 50 cm above ground level. | 5 | Each | |
| 38 | 38 | Repair, Maintenance & overhauling of HT (11 KV) VCB of capacity 400 Amps to 630 Amps, indoor type complete after taking out trolley, checking of all fixed and moving parts for smooth operations, cleaning with CTC or CRC 226 and rustlick, air blower, replacement of minor parts, checking and repair to locking system, alignment & closing / tripping & charging system including replacement of FRP phase barrier and provideing re-insulation to bus bar with HT tape, repair to heaters and making the complete VCB functional with free and operating mechanism, complete all as specified and directed. | 5 | Each Job | |
| 39 | 39 | Supply and fixing PT unit of HT VCB 11 KV/110V, 50 VA conforming to IS and CPRI/NABL approved as in replacement, including connecting, testing & commissioning, complete all as specified and directed.\n | 2 | Set of Three | |
| 40 | 40 | Supply and fixing CT unit, 200/5 Amps, 15 VA burden, accuracy 8.5 as per IS- 2705 for metering / protection of HT VCB 11KV, as in replacement, including connecting, testing & commissioning, complete all as specified and directed.\n | 2 | Set of Three | |
| 41 | 41 | Supply and fixing Volt meter 0-15 KV with PT, digital type, suitable for HT VCB 11KV/110 V, as in replacement, complete all as specfied and directed. | 4 | Each | |
| 42 | 42 | Supply and fixing Ammeter, digital type, 200/5 Amps & 100/5 Amps, suitable for HT VCB 11KV, as in replacement, complete all as specified and directed. | 4 | Each | |
| 43 | 43 | Supply and fixing Ammeter, digital type, 60/5 Amps & 30/5 Amps, suitable for HT VCB 11KV, as in replacement, complete all as specified and directed. | 4 | Each | |
| 44 | 44 | Supply and fixing frequency metre 50 c/s, confirming to IS -1248 as per the existing, as in replacement, complete all as specified and directed. | 3 | Each | |
| 45 | 45 | Supplying, fixing, testing & commissioning over current & earth fault relay, digital self power relay showing earth fault & over current etc, including taking down old defective, removal and modification to existing panel to fix the new relay etc, complete all as specified and directed.\nMake : Crompton Greaves (Type- CG-I 14 S) or equivalent from makes as per Appendix 'B'. | 4 | Each | |
| 46 | 46 | Supplying, fixing & programming, microprocessor based numerical relay with O/L, E/F and S/C protection suitable to work on 24 volts DC supply in renewal of any type relay including modifications to existing panel so as to accommodate the new relay complete all as specified and directed.\nMake : Schneider (Formely Areva) cat part No. Schneider MICOMP 111L without communication or equivalent from makes as per Appx 'B'. | 3 | Each | |
| 47 | 47 | Supply and fixing trip circuit supervision relay with hand reset contacts, operating voltage 24 to 27 volts DC with 03 NO + 02 NC contacts, including connecting with existing system commissioning and testing complete all as specified and directed. \n | 2 | Each | |
| 48 | 48 | Supply and fixing single element high speed tripping relay with hand reset contacts, operating voltage 24 to 27 Volts DC with 02 NO + 01 NC contacts, including connecting with existing system, commissioning and testing complete all as specified and directed. \n | 2 | Each | |
| 49 | 49 | Material and labour for LT ACB cut OFF/ON relay, repair to ON/OFF system including taking down old and removal, complete all as specified and directed. \n | 2 | Each | |
| 50 | 50 | Disconnecting, taking out and removing of RMU, 11KV, 630 Amps, 50Hz, indoor type, 3 way to 5 way, with CT/PTs, from site to workshop for repair, opening in the presence of Engineer-in-charge, checking of all mechanical parts and repairing of the same, checking of old fixed & moving parts, cleaning with CTC or CRC 226 & rustlick, air blower and removal of unserviceable parts of RMU, replacement of minor parts, adjustment of earth switches, checking & adjustment / repair to locking system, setting of alignment, closing & charging system, trip catch assembly and replacement of bushing of bus bar chamber etc and making functional, testing & commissioning, complete all as specified and directed.\nNote : Supply and fixing of new spare parts shall be measured and paid separately.\nMake of existing RMU: Crompton Greaves, ABB, Schneider | 2 | Each job | |
| 51 | 51 | Disconnecting, taking out and removing of RMU, 11KV, 630 Amps, 50Hz, outdoor type, 3 way to 5 way, with CT/PTs, from site to workshop for repair, opening in the presence of Engineer-in-charge, checking of mechanical parts and repair of the same, checking of old fixed & moving parts, cleaning with CTC or CRC 226 & rustlick, air blower and removal of unserviceable parts of RMU, replacement of minor parts, adjustment of earth switches, checking & adjustment / repair to locking system, setting of alignment, closing & charging system, trip catch assembly etc., lubrication of moving parts checking and repairs operation for load break switch and making functional, testing & commissioning, complete all as specified and directed.\nNote : Supply and fixing of new spare parts shall be measured and paid separately.\nMake of existing RMU: Crompton Greaves, ABB, Schneider | 4 | Each job | |
| 52 | 52 | Supply and fixing Cable Terminal Protector Boots, suitable for RMU 11KV 630/400Amps, approved make, complete all as specified and directed. | 2 | Each | |
| 53 | 53 | Supply and fixing indicator LED type (R/Y/B), suitable for RMU 11KV 630Amps, complete all as specified and directed. \n | 8 | Each | |
| 54 | 54 | Disconnecting, taking out and removing of RMU, 11KV, 630/400Amps, 20KA, 50Hz, indoor type, 3way to 5way, with CT/PTs from site to workshop for repair, opening in the presence of Engineer-in-charge, checking of old fixed & moving parts, cleaning with CTC or CRC 226 & rustlick, air blower and taking out unserviceable / damaged parts of incoming system & replacement of unserviceable parts with new parts, replacement of minor parts, servicing of RMU, replacement of defective parts of earth switches, closing & charging system, trip catch assembly etc., checking & adjustment/repair to locking system, setting of alignment, replacement of old metallic body with new metallic sheet MS CRCA 3.0 mm thick body or as per manufacturers specification, powder coated, assembling of parts, re-fixing in original position, connecting & making functional, testing & commissioning, complete all as specified and directed.\nNote : Supply and fixing of new spare parts shall be measured and paid separately.\nMake of existing RMU: Crompton Greaves, ABB, Schneider | 3 | Each Job | |
| 55 | 55 | Supply and fixing trip coil/close coil 24 Volts DC suitable for 11KV RMU , complete all as specified and directed.\n | 5 | Each | |
| 56 | 56 | Supply and fixing 11KV bus coupling bush suitable for 11 KV ring main unit , complete all as specified and directed. | 3 | Each | |
| 57 | 57 | Material and labour for earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick burried directly in ground vertically (depth of pit not less than 2.25 m below normal ground level), with top edge of earth plate not less than 1.5m below normal ground level, earth plate surrounded from all sides by 15cm thick packed alternate layers of charcoal dust and common salt, electrode connections using galvanized iron wire 4mm dia (upto body of equipment) by means of nuts, bolts, check nuts & GI washers, connected to main switch board or main control board or test point, protected by galvanized iron pipe light grade 40mm dia bore, and watering pipe 20mm dia bore GI medium grade with funnel & wire mesh including all necessary excavation & earth work, PCC chamber in PCC (1:2:4) type B-1 & RCC cover, all as shown in electrical plate No 3 of MES Schedule Part-I (2009), testing on completion, complete including dismantling of existing earthing all as specified and directed.\nNote(s) :-\n(i) RCC pit cover shall be pre-cast of RCC (1:2:4) type B-1, 80mm thick reinforced with XPM not less than 4Kg/Sqm.\n(ii) PCC chamber shall be constructed 500 mm away from the edge of earth pit.\n(iii) Rate shall include GI strip and protection pipe of length 7.5m, excess beyond 7.5m length required at site shall be measured and paid separately.\n(iv) Earth resistance should be less than 3Ohm. In case the test results are not found below 3Ohm, complete earthing will be redone without any extra cost to Govt. | 5 | Each Set | |
| 58 | 58 | Supply and fixing Lightning arresters 11KV expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp, complete all as specified and specifed | 1 | Each | |
| 59 | 59 | Material and labour for Cross arms, bracing, supports, clamps and back plates, fabricated from structural steel section Fe-290 grade E-165 quality including nuts, bolts, washers, and welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed including two coats of alminium paint over a coat of primer and taking down old u/s, complete all as specified and directed. | 1 | Quintel | |
| 60 | 60 | Material and labour for plain cement concrete (1:3:6) type C-2 using 40mm graded crushed stone aggregate, for foundation of poles, etc., complete all as specified and directed. | 1 | Cubic Metre | |
| 61 | 61 | Material and labour for plain cement concrete (1:2:4) type B-1 using 20mm graded crushed stone aggregate, for coping/muff of Existing/New poles, plinth blocks of HT/LT poles, in front of out door panel boards etc., including use & waste necessary form work & finishing the exposed surfaces even and smooth without using extra cement, complete all as specified and directed. | 3 | Cubic Metre | |
| 62 | 62 | Supply only for Aluminium ferrule suitable for LT UG Cable, 1100V for 25 Sqmm cable complete all as specified and directed. | 41 | Each | |
| 63 | 63 | Supply only for Aluminium ferrule suitable for LT UG Cable, 1100V for 35 Sqmm cable complete all as specified and directed. | 50 | Each | |
| 64 | 64 | Supply only for Aluminium ferrule suitable for LT UG Cable, 1100V for 50 Sqmm cable complete all as specified and directed. | 50 | Each | |
| 65 | 65 | Supply only for Aluminium ferrule suitable for LT UG Cable, 1100V for 70 Sqmm cable complete all as specified and directed. | 45 | Each | |
| 66 | 66 | Supply only for Aluminium ferrule suitable for LT UG Cable, 1100V for 95 Sqmm cable complete all as specified and directed. | 50 | Each | |
| 67 | 67 | Supply only for Aluminium ferrule suitable for LT UG Cable, 1100V for 120 Sqmm cable complete all as specified and directed. | 50 | Each | |
| 68 | 68 | Supply only for Aluminium ferrule suitable for LT UG Cable, 1100V for 25 Sqmm cable complete all as specified and directed. (vii) 150 Sqmm | 40 | Each | |
| 69 | 69 | Supply only for Aluminium ferrule suitable for LT UG Cable, 1100V for 240Sqmm cable complete all as specified and directed. | 50 | Each | |
| 70 | 70 | Supply only for Aluminium terminal lugs suitable for LT UG Cable,1100V for 25 Sqmm cable complete all as specified and directed. | 39 | Each | |
| 71 | 71 | Supply only for Aluminium terminal lugs suitable for LT UG Cable,1100V for 35 Sqmm cable complete all as specified and directed. | 50 | Each | |
| 72 | 72 | Supply only for Aluminium terminal lugs suitable for LT UG Cable,1100V for 50 Sqmm cable complete all as specified and directed. | 50 | Each | |
| 73 | 73 | Supply only for Aluminium terminal lugs suitable for LT UG Cable,1100V for 70 Sqmm cable complete all as specified and directed. | 53 | Each | |
| 74 | 74 | Supply only for Aluminium terminal lugs suitable for LT UG Cable,1100V for 95 Sqmm cable complete all as specified and directed. | 48 | Each | |
| 75 | 75 | Supply only for Aluminium terminal lugs suitable for LT UG Cable,1100V for 120 Sqmm cable complete all as specified and directed. | 48 | Each | |
| 76 | 76 | Supply only for Aluminium terminal lugs suitable for LT UG Cable,1100V for 150 Sqmm cable complete all as specified and directed. | 50 | Each | |
| 77 | 77 | Supply only for Aluminium terminal lugs suitable for LT UG Cable,1100V for 240 Sqmm cable complete all as specified and directed. | 50 | Each | |
| 78 | 78 | Supply and installation in repairs, commissioning and testing Polycarbonate CPRI approved OEM made main LT Panel. The panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES including MCCBs and indicator lamps which shall be UV resistance in accordance with IEC 61439-1, clause 10.2.4: The panel shall be anti-acid & anti corrosive. Degree of protection against mechanical load shall be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of CPRI TEST REPORT IN POLYCARBONATE only also share panel assembled by OEM, channel partner or sister concern assembly will not be accepted. DEGREE OF INGRESS PROTECTION IP 65 IN ACCORDANCE WITH IEC 60529. The gasket shall be internally embedded made of polyurethane. The manufacturer of panel SHALL submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily - Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits. The board manufacturer shall submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The panel shall pass glow wire test 960 degrees Centigrade in accordance with 60695-2-11 [flame retardant and self-extinguishing. Make-Hensel/Rittal/Emitter/Schneider INCOMER:\n250 Amp, 4 pole MCCB, 25 KA- 01 No,\nMultifunction meter - 01 No\nSet of LED type indicating lamps - 01 No\nOUTGOINGS:\n63 Amp, 415 V, 4 pole MCCB - 02 Nos.\n160 Amp, 415 V, 4 pole MCCB - 01 No.\n200 Amp, 415 V, 4 pole MCCB - 01 No. | 1 | Each Job | |
| 79 | 79 | All as per item No 78 hereinbefore but INCOMER:\n160 Amp, 4 pole MCCB, 25 KA - 01 No,\nOUTGOINGS:\n63 Amp, 415 V, 4 pole MCB - 06 Nos. | 1 | Each Job | |
| 80 | 80 | All as per item No 78 hereinbefore but INCOMER:\n400 Amp, 4 pole MCCB, 25 KA -01 No,\nMultifunction meter - 01 No\nSet of LED type indicating lamps\nOUTGOINGS:\n63 Amp, 415 V, 4 pole MCCB - 02 Nos.\n160 Amp, 415 V, 4 pole MCCB - 01 Nos.\n200 Amp, 415 V, 4 pole MCCB - 02 Nos. | 1 | Each Job | |
| 81 | 81 | All as per item No 78 hereinbefore but INCOMER:\n200 Amp, 4 pole MCCB, 25 KA - 01 No, Multifunction meter - 01 No\nSet of LED type indicating lamps\nOUTGOINGS:\n63 Amp, 415 V, 4 pole MCCB - 04 Nos.\n160 Amp, 415 V, 4 pole MCCB - 01 Nos. | 1 | Each Job | |
| 82 | 82 | All as per item No 78 hereinbefore but INCOMER:\n100 Amp, 4 pole MCCB, 25 KA -01 No,\nOUTGOINGS:\n63 Amp, 415 V, 4 pole MCCB - 04 Nos. | 2 | Each Job | |
| 83 | 83 | All as per item No 78 hereinbefore but INCOMER:\n400 Amp, 4 pole MCCB, 25 KA - 01 No,\nOUTGOINGS:\n160 Amp, 415 V, 4 pole MCCB - 06 Nos. | 1 | Each Job | |
| 84 | 84 | All as per item No 78 hereinbefore but INCOMER:\n200 Amp, 4 pole MCCB, 25 KA - 01 No,\nMultifunction meter - 01 No\nSet of LED type indicating lamps\nOUTGOINGS:\n160 Amp, 415 V, 4 pole MCCB - 02 Nos.\n120 Amp, 415 V, 4 pole MCCB - 02 Nos. | 1 | Each Job | |
| 85 | 85 | All as per item No 78 hereinbefore but INCOMER:\n200 Amp, 4 pole MCCB, 25 KA - 01 No,\nMultifunction meter - 01 No\nSet of LED type indicating lamps\nOUTGOINGS:\n63 Amp, 415 V, 4 pole MCCB - 02 Nos.\n100 Amp, 415 V, 4 pole MCCB - 02 Nos. | 1 | Each Job | |
| 86 | 86 | All as per item No 78 hereinbefore but INCOMER:\n400 Amp, 4 pole MCCB, 25 KA - 01 No,\nMultifunction meter - 01 No\nSet of LED type indicating lamps\nOUTGOINGS:\n100 Amp, 415 V, 4 pole MCCB - 02 Nos.\n160 Amp, 415 V, 4 pole MCCB - 02 Nos.\n200 Amp, 415 V, 4 pole MCCB - 02 Nos. | 1 | Each Job | |
| 87 | 87 | All as per item No 78 hereinbefore but INCOMER:\n160 Amp, 4 pole MCCB, 25 KA - 01 No,\nMultifunction meter - 01 No\nSet of LED type indicating lamps\nOUTGOINGS:\n63 Amp, 415 V, 2 pole MCB - 04 Nos.\n63 Amp, 415 V, 3 pole MCB - 01 Nos. | 1 | Each Job | |
| 88 | 88 | Supply and Fixing in replacement LED street light 90 Watt with highly optimised and efficient lighting distribution made from Die cast aluminum housing, high power ceramic LEDs with integrated lens and IP66 protection. Efficacy : 110LM/W, Cat Part LSTP-90-CDL-M of Crompton or equivalent from /Philips/C&S/Havells. | 30 | Each Job | |
| 89 | 89 | Supply and Fixing in replacement LED street light 120 Watt made up of pressure die cast aluminium housing with toughened glass and high power LEDs and secondary lenses with IP 66 protection including 10KV SPD.\nEfficacy : 110LM/W, Cat Part No:LSTP-120-CDL-M of Crompton or equivalent from /Philips/C&S/Havells. \n | 30 | Each | |
| 90 | 90 | Supply and Fixing in replacement High efficient LED flood light of 150W Capacity with lens made of pressure dia cast aluminum housing, extruded aluminum heat sink & enclosed with toughened glass, IP 66 protection suitable for high mast light fitting with all necessary accessories complete all as specified. MakeCrompton Cat Part No LFLN-150-CDL/60-M or equivalent from /Philips/C&S/Havells. \n | 26 | Each | |
| 91 | 91 | Supply and Fixing Tubes, 'medium grade', 50mm bore galvanised, with all fitting; laid in trenches/for light fittings complete all as specified by Engineer in charge\n | 75 | Running Metre | |
| 92 | 92 | Supply and fixing in replacement high intensity, long range, UDCA mounted, manual mounted, LED search light, Minimum beam range 600 meters, 1x300W, LED, Efficiency > 140 lm/w, PF > 0.95, CCT 5000K-6500K, CRI >80, Optical grade lens-reflector having efficiency > 95% & narrow beam 5 degrees, Anti-UV oxidation, die cast LM6 body with air fins, fully powder coated, working voltage 150-280V, 50Hz, constant current, Minimum lux 3000 at 10 meter with circle of approx 1 meter, IP-66, meeting the standard of LM79, LM80, IS:10322 & IS:13383. The above search-light shall be installed on “UDCA\" stand (1 meter above from roof) and the operating lever of UDCA shall be in shoulder height to enable to rotate luminary easily from inside of the watch tower 360° in horizontal plane & vertical movement > 30° bulit-in locking knob. All bushes of UDCA shall be made of gun metal, hardware shall be in S.S. and others metal parts shall be Zinc electroplated / powder-coated for outdoor installations and having 3 Nos. foundation holes at bottom. Make: Kalin Cat No RSL-LRFLL-25PC25 or equivalent from /Philips/C&S/Havells. | 22 | Each | |
| 93 | 93 | Note: The Total amount shall subject to adjustment of credit of Rs. 258422.00 for old Materials as per Schedule of Credit. |