| 1 | Design, supplying,Installation, Testing and commissioning of manufacturer panel board fabricated out of 2 mm thick sheet steelas per spectifications. The panel shall be complete with cable termination arrangement suitable for incomingand outgoing each 1 run x 3c x 240 sqm XL PE 11KV cable and copper bus bar arrangement . The panel shall comprise of the following: |
| 2 | Single Panel Board At Entrance: |
| 3 | 1 No. 11 KV 630 A 25KA drawout type VCB with motorised spring charge machanisum for 240 V AC, closing& tripping coil suitable for 24 V DC |
| 4 | Each incomer comprising with following accessaries |
| 5 | 1 No Mechanical ON/OFF indicator |
| 6 | 1 No. Aux Swich 6 NO+6 NC |
| 7 | Panel Busbar,CT,PT |
| 8 | 1 No. Fully compartmentalisedsheet steelenclosure floor mounting type with automatic safty shutters, independent pressure discharge flaps, PVC sleevedbusbar , etc , with provisionfor terminating PVC/PILC/XLPE cable |
| 9 | 3 Nos. ResinCast CTs100/1-1A with Core 1:7.5 VA CL1Core 2: 7.5 VA CL5P10 |
| 10 | 3 Nos. PT- 11 KV/v3/110/v3V,CL 1.0, 50 VA |
| 11 | BreakerPanel IndicationLamps: |
| 12 | 6 Nos. ON/OFF/TRIP/TRIP Ckt Healthy Spring Charged |
| 13 | Switches and other Accessories |
| 14 | 8 Nos.Fuess |
| 15 | 1 No. Heater |
| 16 | 1 No. Thermostat |
| 17 | 1 No. 6 Window Annunciator |
| 18 | 1 No. Plug & Socket |
| 19 | 1 No. Test Terminal Block |
| 20 | 1 No. T-N-C Switch |
| 21 | 1 no Emergency Push Button |
| 22 | 1 No. Local/Remote Selector Switch |
| 23 | 1 No. Earth Switch |
| 24 | 1 No. Analog Ammeter+ASS |
| 25 | 1 No. Analog Voltmeter + VSS |
| 26 | 1 No. Digital Multifunction Meter |
| 27 | 1 No. (O/C + E/F- IDMT+Inst |
| 28 | 1 No. AVAJH13 Master Trip relay |
| 29 | 1 No. TCS Relay |
| 30 | 24 Volt DC 180 AH supply system comprising of one set of batteries and battery charger with Boost Charger and float charger complete suitable for operating the control devices of HT Pannel |