| 1 | 1 | NOTE (Applicable for all items) :- The bidders/contractors are advised to read tender document & all corrigendum / amendments and General conditions of contracts before entrying/quoting the rates.\n\nSCHEDULE 'A' PART-I | BI01010001010000000000000515BI0100001112 | | |
|---|
| 2 | 1.001 | Excavating in trenches,in soft/loose soil n exc 1.5m wide and n exc 1.5m in depth, for foundation etc or shafts,walls,cesspits,manholes,pier holes,etc.n exc 10 sqm on plan and n exc 1.5m in depth and getting out all as specified and as directed. | BI01010001010000000000000515BI0100001113 | 520 | Cum |
|---|
| 3 | 1.002 | Returning,filling in,including spreading,leveling,watering and well ramming in layers not exc 25cm. | BI01010001010000000000000515BI0100001114 | 245 | Cum |
|---|
| 4 | 1.003 | Removing excavated material n exc 50m and depositing where directed at a level n exc 1.5m above the strarting point. | BI01010001010000000000000515BI0100001115 | 221 | Cum |
|---|
| 5 | 1.004 | Materials and labour for sand filling around the cable with approved quality coarse sand for sand cushioning of under ground cable including spreading and punning down to desired thickness complete all as specified and as directed by the Engr-in-Charge. | BI01010001010000000000000515BI0100001116 | 109 | Cum |
|---|
| 6 | 1.005 | M&L for well burnt brick of size (sub class B) locally available as protection of cable in trenches including taking out old bricks complete all as specifed.\nNote : Taking out bricks reused as per ground requirement | BI01010001010000000000000515BI0100001117 | 7 | Per 1000 Nos |
|---|
| 7 | 1.006 | Cutting of existing PCC road / hard standing / floor, etc. exc. 45 cm. and not exc. 90 cm in depth and width 45 cm (min) for laying of cable protection pipe, etc. and making good and finished the disturbed surfaces with existing materials complete all as specified and directed. | BI01010001010000000000000515BI0100001118 | 40 | RM |
|---|
| 8 | 1.007 | Cutting of exsiting Bituminous road exc. 45 cm. and not exc. 90 cm in depth and width 45 cm (min) for laying of cable protection pipe, etc. and making good and finished the disturbed surfaces with existing materials complete all as specified and directed. | BI01010001010000000000000515BI0100001119 | 25 | RM |
|---|
| 9 | 1.008 | M&L GI pipe 40 mm dia light grade for cable protection including all fittings and fixtures and fixed complete to walls and ceilings or laid in trenches.\n | BI01010001010000000000000515BI0100001120 | 20 | RM |
|---|
| 10 | 1.009 | Supply and laying under ground XLPE insulated PVC sheathed (Heavy duty) armoured 1100 volts grade aluminium conductor cable of size 120 Sqmm 3.5 core as per IS 7098 (Part I) including connection cable glands, aluminium lugs etc including taking down/up existing unserviceable cable complete all as specified and as directed by the Engr-in-Charge.\nNote : Earth work, brick protection and sand cushioning will be measured and paid separately under respective item. \n | BI01010001010000000000000515BI0100001121 | 120 | RM |
|---|
| 11 | 1.01 | All as per Sl Item No. 1.009 above but for cable of size 35 Sqmm 4 Core | BI01010001010000000000000515BI0100001122 | 100 | RM |
|---|
| 12 | 1.011 | All as per Sl Item No. 1.009 above but for cable of size 25 Sqmm 4 Core | BI01010001010000000000000515BI0100001123 | 150 | RM |
|---|
| 13 | 1.012 | All as per Sl Item No. 1.009 above but for cable of size 16 Sqmm 4 Core | BI01010001010000000000000515BI0100001124 | 300 | RM |
|---|
| 14 | 1.013 | All as per Sl Item No. 1.009 above but for cable of size 10 Sqmm 3 Core | BI01010001010000000000000515BI0100001125 | 100 | RM |
|---|
| 15 | 1.014 | Repair/maintenance and servicing of oil cooled step down transformer of capacity 150 to 300 KVA, comprising following work services :-\n(a) Disconnection of cable termination of HT & LT ends.\n(b) Opening of top cover by removing nuts, bolts and all mounting accessories and conservator tanks.\n(d) Cleaning all sludges from main oil tank and conservator tank and removal off the site.\n(e) Servicing of tap changing gears by cleaning and polishing tapping contact points.\n(f) Cleaning, polishing of serviceable bush and stud both HT/LT side and refixing the same.\n(g) Replacing unserviceable stud and bush as required as directed by Engr-in-Charge. \n(h) New silica gel requied for replacing \nNote : (i) While replacing and refixing the stud and bush all nuts, washers and gaskets are to be replaced with new one against the coated rate \n(ii) New bushes and studs required for replacement .\n(h) Refixing all cable terminals HV & LV sides and transformer top cover, conservator tank in position. \n\n(l) Connecting HT & LT side with existing incoming and outgoing cables including reconnection of earth strip/lead.Note:\n(i) HT side cable connection shall be made with new HT tape & M Seal Monoplast. \n(ii) M seal monoplast required for replacement shall be deemed in coated rate. \n(iii) The items of work mentioned here-in-after are tentative and may vary as per site requirement as assessed by the representative and the Engn-in-Charge after strip inspection and the contractor shall have no claim on that account. \n(iv) Contractor wiil be very careful and should ensure not to enter any type of moisture in side the transformer during maintenance. | BI01010001010000000000000515BI0100001126 | 6 | Per Job |
|---|
| 16 | 1.015 | Supply and refilling of transformer oil having di-electric strength not less than 50 KV after initial dehydration/filteration conforming to IS 335 and ISI marked to be brought at site in sealed container different capacity of transformers including drain out the old transformer oils all as directed. | BI01010001010000000000000515BI0100001127 | 200 | Liters |
|---|
| 17 | 1.016 | Supply and fixinfy buchholz relay for 250 KVA Buck/Boost transformer as per existing type and model. | BI01010001010000000000000515BI0100001128 | 6 | Each |
|---|
| 18 | 1.017 | Material and labour for painting of transformers any capacity with one coat of synthetic enamel paint after and including cleaning of existing surface of all dirts and greasy materials including marking of SM/MES Nos with letters n exc 15cm height at appropriate places complete all as specified and as directed. \nNote: The superficial area for the purpose of painting shall be considered approx 10 Sqm. | BI01010001010000000000000515BI0100001129 | 6 | Per Job |
|---|
| 19 | 1.018 | Complete servicing to the DG set comprising of the following works for the capacity 20 to 35 KVA complete all as specified and as directed by the Engr-in-Charge :-\n(a) Draining out unserviceable engine oil from engine, refill with new. (Engine oil will be supplied by contactor)\n(b) Cleaning all sludge/deposits in the oil sump and removed off the site\nc) Supply and replacing the primery, secondary and bi-pass fuel filters \n(d) Supply and replacing oil filters with gasket\n( e) Cleaning of air filters\n(f) Supply and replace unserviceable hose pipe as required at site \n(g) Supply and replace PVC fuel indication tube \n(h) Supply and replacing battery terminals (g) Cogged fan belt | BI01010001010000000000000515BI0100001130 | 4 | Each Job |
|---|
| 20 | 1.019 | Dismantling of HT 11 KV GOAB switch /DO fuse assembly / lightening arrestor of any type complete with all accessories complete all as specified. \nMake : Jaipuria/HEI Gurgaon/Atlas/Pactil | BI01010001010000000000000515BI0100001131 | 3 | Each |
|---|
| 21 | 1.02 | M&L Switches Air Break gang operated 11000 V graded tripple pole mechanically operated , mounted on insulator and steel frame with operating mechanism worked from ground level, for current rating up to 200 Amps complete with all accessories complete all as specified. | BI01010001010000000000000515BI0100001132 | 3 | Each |
|---|
| 22 | 1.021 | M&L for lighting arrestors expulsion type complete with all fitting, transmission class, discharge capacity 65 KA suitable for 11 KV complete with necessary connection and testing complete including taking down old U/S complete all as specified. | BI01010001010000000000000515BI0100001133 | 3 | Per set of three |
|---|
| 23 | 1.022 | M&L Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm. | BI01010001010000000000000515BI0100001134 | 2 | Each |
|---|
| 24 | 1.023 | M&L for heat shrinkable type straight through joint kit for 70-150 Sqmm x 3 to 4 core LT UG XLPE Cable with aluminium conductor ( Make : M-seal / Denson / Yamuna cablees Pvt Ltd Cat Part No : XSS04 | BI01010001010000000000000515BI0100001135 | 2 | Each |
|---|
| 25 | 1.024 | S&F for install of LED street light fittings with PDC aluminium housing with toughned glass of IP 66 protection of cap - 45W LED with lens and suitable size of bracket & clamp Including taking down old U/S lights complete all as specified & as directed .Make-C & S cat pt No. INDUS/45W/LS or equivalent of Philips, CG. | BI01010001010000000000000515BI0100001136 | 80 | Each |
|---|
| 26 | 1.025 | Supply and fixing for 20 watt LED post top lanterns fitting made in, cast aluminium spigot, housing with decorative clear acrylic diffuser and IP 65 protection with and including LED lamp and all necessary electric connection with 2.5 Sq mm PVC copper wire from junction box to post top lantern after and including dismantling of existing unserviceable fitting complete all as specified and as directed by the Engr-in-Charge.\nMake : C & S Cat No CETUS-M/20W or equivalent approved make of Philips/Havells/CG. | BI01010001010000000000000515BI0100001137 | 12 | Each Job |
|---|
| 27 | 1.026 | S&F for install of LED Flood light with PDC aluminium housing with toughned glass of IP 66 protection of cap - 30 W LED with lens Including taking down old U/S lights complete all as specified & as directed .Make-C & S cat pt No. GLOFLO/30W or equivalent of Philips, CG. | BI01010001010000000000000515BI0100001138 | 6 | Each Job |
|---|
| 28 | 1.027 | Supply & draw 2.5 Sqmm twine core flat along with one single core flat 1.5 Sqmm flat type weather proof aluminium conductor cable as repair from street light to terminal box drawn through PVC contude pipe complete including taking down all as specified & as directed ( For street light connection) | BI01010001010000000000000515BI0100001139 | 300 | RM |
|---|
| 29 | 1.028 | Supply & Replace lead acid type wet cell battries of Capacity 150Amp/hr 12V for DG sets including taking down. Make : Exide, SF super sonic | BI01010001010000000000000515BI0100001140 | 3 | Each |
|---|
| 30 | 1.029 | Supply and fixing prestressed concrete pole 9 metres long, 102 mm x 152 mm at top and 102 mm x 289 mm at bottom class 10 complete including taking down all as specified & as directed | BI01010001010000000000000515BI0100001141 | 6 | Each |
|---|
| 31 | 1.03 | Material and labour for painting of panel board any size at various locations with two coat of superior quality of synthetic enamel paint after cleaning of existing surface including marking of incoming feeder and outgoing feeder with letters n exc 15cm height complete all as specified and as directed.\nNote : The superficial area for the purpose of painting shall be considered as n exc 15 Sqm. | BI01010001010000000000000515BI0100001142 | 25 | Per Job |
|---|
| 32 | 1.031 | M & L for cleaning of PCC pole 9 mtr long and carrying out following phase of work all sa directed.\n(a) Cleaning and preparation of surface of PCC pole 9.0 Mtr\n(b) Carrying out one coat cement based paint (approximate 7.0 Mtr long)\n(c) Carrying of painting by synthetic enamel paint one coat over the concrete surface of pole using black and yellow paint all as directed area 0.80 Sqmtr (Approx) per pole including painting of brackets & clamp of any size.\n(d) Writing of PCC pole Number over black painted surface (0.02 Sqmtr) using capital letter 10.0 Cm high (5 Nos in an average for each pole) | BI01010001010000000000000515BI0100001143 | 200 | Each |
|---|
| 33 | 1.032 | Supply and Fixing for glow sign boards of size 1200 mm x 900 mm made out of MS tubular steel legs & frame with l40 mm dia pipe with 0.6 mm MS Sheet for receiveing the matter, illuminated glow adhesive sticcker in with base blue colour and lettering in white colour as required at each location, fixing the board with PCC 1:3:6 type C2 using 40mm stone aggregate, excavation in post hole fixing the board with top height of the board 1,8m above ground level complete all as specified and as directed. | BI01010001010000000000000515BI0100001144 | 12 | Each Job |
|---|
| 34 | 1.033 | S&F Pole mounting junction Box of size 240 mm x 130 mm x 110 mm for street light for 3 phase/4 core , made of high grade SMC/FRP dust free and weather proof,IP-55 for cable entry from all sides of boxes including all fixing accessories, Make : Sintex cat no- GSJB-2817 or equivallent. | BI01010001010000000000000515BI0100001145 | 40 | Each |
|---|
| 35 | 1.034 | Supply and fixing as in replacement Voltmeter, single phase, class - 1, digital type including taking down old unserviceable one complete all as specified and as directed by the Engr-in-Charge. \nMake : L&T Cat No. WDS101FEV00 or equivalent approved make of Legrand. | BI01010001010000000000000515BI0100001146 | 8 | Each |
|---|
| 36 | 1.035 | Supply and fix as in repair Digital AC ampere meter, 3 phase, of size 96 x 96 square type , accuracy class 1.0 complete all as specified and as directed by the Engr-in-Charge.\nMake : L&T Cat No : WDS301FCAOO or equivalent approved make. | BI01010001010000000000000515BI0100001147 | 8 | Each Set |
|---|
| 37 | 1.036 | Supply and fixing on load change over switch disconnector 125 Amp, type CO2-125, in sheet steel enclosure, conform to IEC 60947-3 after and including taking down old unserviceable and making good to existing disturbed surface complete all as specified and as directed.\nMake : L&T Cat No.CO21250OSOO or equivalent approved make of Legrand. | BI01010001010000000000000515BI0100001148 | 2 | Each |
|---|
| 38 | 1.037 | Supply and fixing MCCB 4 pole,415 V,adjustable type,160 amps with breaking capcity 36 KA including taking down old one. | BI01010001010000000000000515BI0100001149 | 3 | Each |
|---|
| 39 | 1.038 | Supply and fixing MCCB 4 pole,415 V,adjustable type,250 amps with breaking capcity 36 KA including taking down old one. | BI01010001010000000000000515BI0100001150 | 2 | Each |
|---|
| 40 | 1.039 | Supply and fixing MCCB 4 pole,415 V,adjustable type,400 amps with breaking capcity 36 KA including taking down old one. | BI01010001010000000000000515BI0100001151 | 2 | Each |
|---|
| 41 | 1.04 | Supply and fixing MCCB 4 pole,415 V,adjustable type,500 amps with breaking capcity 36 KA including taking down old one. | BI01010001010000000000000515BI0100001152 | 2 | Each |
|---|
| 42 | 1.041 | M&L for filling of Silica Gel, suitable for any type of transformer for moisture free all as directed | BI01010001010000000000000515BI0100001153 | 8 | Kg |
|---|
| 43 | 1.042 | Materials and labour for earthing as in repair complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with galvanised strip of size 32 x 6mm by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe 40 mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion all as specified and as directed by the Engr-in-Charge. | BI01010001010000000000000515BI0100001154 | 20 | Each |
|---|
| 44 | 1.043 | Material and labour in replacement for Galvanised iron strip 32 x 6 mm burried in ground complete all as specified and directed by the Engineer-in-Charge. | BI01010001010000000000000515BI0100001155 | 50 | RM |
|---|
| 45 | 2 | SCHEDULE 'A' PART-II\nNote : Earth work in excavation, returning filling, romoval, sand filling, cutting of hardstanding/pavement & road, etc. required for the execution of items covered under this part shall be measured and paid under Schedule ‘A’ Part-I | BI01010001010000000000000515BI0100001156 | | |
|---|
| 46 | 2.001 | Disconnecting & taking out old existing unserviceable HT cable of size 3 core 95 Sqmm ,in any position from trench/duct, cleaning the outer surface of cable, examining cable and joints for defects and ascertaining suitability of cable for reuse, cutting out the defective portion of cable/joint, including taking out old serviceble PCC cable covers or GI pipe of any description for remove/re-use all as directed by the Engineer –in-Charge. | BI01010001010000000000000515BI0100001157 | 800 | RM |
|---|
| 47 | 2.002 | Supply and laying connecting and testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric power cable with aluminium conductor 11000 V grade cross sectional area 95 Sq mm 3 core complete all as specified and directed. Make : ICL/Gloster/Havells. | BI01010001010000000000000515BI0100001158 | 220 | RM |
|---|
| 48 | 2.003 | Re- laying connecting and testing XLPE insulated screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric power cable with aluminium conductor 11000V grade cross sectional area 95 Sq mm 3 core complete all as specified and directed. | BI01010001010000000000000515BI0100001159 | 600 | RM |
|---|
| 49 | 2.009 | Supply and laying un-reinforced precast conrete cable cover suitable for 11000 volts grade HT UG cable laid the length of cover prependicular to the direction of cable of class HV type 1 flat size 300 mm x 180 mm x 40 mm all as directed. | BI01010001010000000000000515BI0100001160 | 3000 | Each |
|---|
| 50 | 2.01 | Laying only un-reinforced precast conrete cable cover suitable for 11000 volts grade HT UG cable laid the length of cover prependicular to the direction of cable of class HV type 1 flat size 300 mm x 180 mm x 40 mm all as directed. | BI01010001010000000000000515BI0100001161 | 1400 | Each |
|---|
| 51 | 2.011 | M&L GI pipe light grade 80 mm bore with all fitting laid in trenches and under road/floor/culverts along with pole etc cable protection. | BI01010001010000000000000515BI0100001162 | 35 | RM |
|---|
| 52 | 2.012 | M & L for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable size 95 sqmm Make : Denson/Raychem/M Seal | BI01010001010000000000000515BI0100001163 | 12 | Each |
|---|
| 53 | 2.013 | M & L for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable size 95 sqmm Make : Denson/Raychem/M Seal | BI01010001010000000000000515BI0100001164 | 7 | Each |
|---|
| 54 | 2.014 | M & L for replacement of cable jointing kit for 11 KV (Earthed) grade cable for Straight through Epoxy heat shrink type joint complete with jointing material accessories suitable for 3 core XLPE armoured aluminium conductor cable size 95 Sqmm Make : Denson/Raychem/M Seal\nNote : Earth work shall be paid and measured under respective item | BI01010001010000000000000515BI0100001165 | 10 | Each |
|---|
| 55 | 2.015 | M&L for checking and finding pin point location of fault in HT 11 KV UG cable with the help of fault locating mobile machine complete all as directed.\nNote : (i) Rate for rent of the fault locating mobile machine, charges for operator, engineer, electricians etc are deemed to be included in the quoted rate.\n(ii) Fault should be located and repaired within 12 hours\n(iii) Excavation, earth work and jointing material will be measured and paid separately under relevant items of Schedule. | BI01010001010000000000000515BI0100001166 | 4 | Each Job |
|---|
| 56 | 2.016 | S&F On Load Change Over switch open execution with advance neutral of capacity 400 Amps, 4 pole including fixing in existing LT panel, connecting existing cable by means of suitable lugs/thimbles and taking old US change over switch any type complete all as specified and directed. Cat Part No ICHNF00400 of Havells/L&T/Scheinder | BI01010001010000000000000515BI0100001167 | 2 | Each |
|---|
| 57 | 2.017 | All as per Sl Item No 2.016 here-in-before, but with SS enclouser of capacity 250 Amps 4 pole complete all as specified and directed. Make - Havells Cat Part No ICHNFE0250/L&T/Scheinder | BI01010001010000000000000515BI0100001168 | 2 | Each |
|---|
| 58 | 2.018 | M&L for Bus Bar Panel of capacity 400 Amps, 4 Way copper bus bar fixed on insulator welded with iron angle leg of size 50x50x6 mm thick grouting in floor 0.45 m depth with PCC 1:3:6 type C2 and height of bottom portion of bus bar from ground level shall be 0.60 m including mounting bus bar on angle iron by means of suitable size nuts and bolts complete and connecting incoming and out going cables by means of suitable lugs and taking old unserviceable bus bar of any type and capacity all as directed by Engr-in-charge. Make - Havells, cat part No IHBC040004/Sallabh/Standard | BI01010001010000000000000515BI0100001169 | 2 | Each |
|---|
| 59 | 2.019 | All as per Sl Item No 2.018 here-in-before but of capacity 250 Amps complete all as specified and directed. Make- Havells Cat Part No IHBC025004/Sallabh/Standard | BI01010001010000000000000515BI0100001170 | 2 | Each |
|---|
| 60 | 2.02 | M&L for repairing of LT panels/Feeder pillar boxes after taking proper shut down by replacing burnt aluminium bus bars of existing size, repairing locking arrangement, hinges, sliding bolts, knob, gaskets, necessary welding works etc complete all as specified and directed. | BI01010001010000000000000515BI0100001171 | 15 | Each Job |
|---|
| 61 | 2.021 | M&L for painting of LT Panels of any size and type by applying two coats of synthetic enamel paint super quality(Smoke grey) using spray gun after scraping old paint and writing details of incoming and all outgoing switchgear complete all as specified and directed. | BI01010001010000000000000515BI0100001172 | 25 | Each Job |
|---|
| 62 | 2.022 | S & F in repair MCCB, 4 pole, 630 Amps, 415 Volts , 36 KA adjustable thermal and magnetic setting complete all as directed by Engineer-in-Charge including taking down old and unserviceable one. Make : L&T Cat Part No CM9680700TOOG or equivalent model from C&S/Havells | BI01010001010000000000000515BI0100001173 | 2 | Each |
|---|
| 63 | 2.023 | All as per Sl Item No 2.022 here-in-before but of rating 400 Amps, 36 KA complete all as directed. Make : L&T Cat Part No CM98412OOROOG or equivalent model from C&S/Havells | BI01010001010000000000000515BI0100001174 | 2 | Each |
|---|
| 64 | 2.024 | All as per Sl Item No 2.022 here-in-before but of rating 250 Amps, 36 KA complete all as directed. Make : L&T Cat Part No CM9680300POOG109OOP1OG or equivalent model from C&S/Havells | BI01010001010000000000000515BI0100001175 | 2 | Each |
|---|
| 65 | 2.025 | Supply and fixing of Thermoplastic Circuit Breaker Boxes of size 202 x 238 x 111 mm made of thermoplastic, halogen free, weather proof with metric Knock outs for cable entry from all side of box and cable entry stainless steel glands for incoming and out going and cable connection with protection grade IP-65 and suitable for LT under ground cable of 16-35 sqmm, including fixing material clamps nut and bolts including taking down old box cat Part No-KV-7109 Make : Hensel/Sintex/Universal | BI01010001010000000000000515BI0100001176 | 5 | Each |
|---|
| 66 | 2.026 | All as per Sl Item No 2.025 here-in-before but of size 295 x 333 x 129mm complete all as directed. Make : Hensel Cat part No -KV-9112M C or equivalent model from Sintex/Universal | BI01010001010000000000000515BI0100001177 | 5 | Each |
|---|
| 67 | 2.027 | Supply,installing, testing and commissioning Indoor type LT feeder piller box of suitable size, cubical padestal mounted, CPRI approved factory made totally enclosed, dust and vermin proof, Front and rear openable type made of 3.15 mm thick CRCA sheet of suitable size and framing with 50 x 50 x 6 mm thick MS angle iron duly fabricated and having proper locking arrangement in both front and rear door with duly painted to both internal and External surfaces with powder coating paint in heat process of sheet including internal wiring with copper strip & wire, suitable for 440 volts, 50 Hz, 3 phase 4 wire system and comprising with and including following accessories and mounted on PCC Plat form made out of PCC 1:3:6, 60 Cm height , 0.5 Mtr all round the panel board complete with the following items housed in :-\n(A) BUSBAR :- 600 Amps rated copper bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support (Square/round ) insulators of suitable size and good insulation resistance.\n(B) INCOMING:- (i) 4 pole MCCB of capacity 400 Amps, 415 Volts, 50 Hz, 3 phase breaking capacity 36 KA with microprocessor release, Adjustable overload 40 - 100%, neutral protection 50 - 100% -01 No. Make - L&T/Lwgrand/BCH\n(ii) On Load change over switch 400 Amps 4 Pole -01 No, Make- L&T/Legrand/BCH\n(iii) Analogue type volt meter of range 0- 500 volts -01\n(iv) Volt meter selector switch -01 No.\n(v) Analogue type Ammeter of range 0-400 Amp\n(vi) Ammeter selector switch-01 No .\n(vii) Indicator lamp with integral circuit (230/240 volt) and cluster LED (RED, ORANGE, BLUE) -01 set\n(viii) CT (400/5A) -03 Nos \n(C) OUTGOING:- (i) 4 pole MCCB of capacity 250 Amp, breaking capacity 36 KA with thermal magnetic release adjustable type - 01 Nos. Make- L & T/Legrand/BCH\n(ii) 4 pole MCCB of capacity 160 Amp, breaking capacity 36 KA with thermal magnetic release adjustable type - 01 Nos. Make - L & T\n(iii) 4 pole MCCB of capacity 100 Amp, breaking capacity 25 KA with thermal magnetic release adjustable type - 02 Nos. Make- L & T/Legrand/BCH\n(iv) 4 pole MCCB of capacity 63 Amp, breaking capacity 25 KA with thermal magnetic release adjustable type - 04 Nos. Make - L & T/Legrand/BCH\n(v) 4 pole MCCB of capacity 32 Amp, breaking capacity 16 KA with thermal magnetic release adjustable type - 02 Nos. Make - L & T/Legrand/BCH | BI01010001010000000000000515BI0100001178 | 1 | Each Job |
|---|