| 1 | 1 | Based on Electrical BSR 2013 | | 0.0001 | Each |
|---|
| 2 | 2 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) of approved make in surface / recessed ISI marked medium duty PVC conduit & it's accessories, round tiles,Hot Dipped Galvanized Modular Box with earth terminal, 6 A Modular switch,Modular plate with grid plate, screws, making connections, testing etc. as required. Group -A1 | | 0.0001 | Each |
|---|
| 3 | 3 | Short point (up to 3 mtr.) | | 36 | P. point |
|---|
| 4 | 4 | Medium point (up to 6 mtr.) | | 100 | P. point |
|---|
| 5 | 5 | Long point (up to 10 mtr..) | | 60 | P. point |
|---|
| 6 | 6 | Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) of approved make in surface / recessed ISI marked medium duty PVC conduit & it's accessories, round tles, Hot Dipped Galvanized M.S Modular box of 20 SWG with earth terminal,6 A two way Modular switch, Modular plate with grid plate, screws, making connections, testing etc. as required.Group -A1 | | 0.0001 | Each |
|---|
| 7 | 7 | Long point (up to 10 mtr..) | | 12 | P. point |
|---|
| 8 | 8 | Wiring of 3 pin 5 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) of approved make in surface / recessed ISI marked medium duty PVC conduit & it's accessories, Hot Dipped Galvanized M.S Modular box of 20 SWG with earth terminal, 6 A modular switch, 6 A modular socket, Modular plate with grid plate, screws, making connections, testing etc. as required.Group -A1 | | 0.0001 | Each |
|---|
| 9 | 9 | On board | | 50 | P. point |
|---|
| 10 | 10 | Short point (up to 3 mtr.) | | 10 | P. point |
|---|
| 11 | 11 | Medium point (up to 6 mtr.) | | 10 | P. point |
|---|
| 12 | 12 | Long point (up to 10 mtr..) | | 10 | P. point |
|---|
| 13 | 13 | S&F following sizes (dia.) of ISI marked medium duty PVC conduit along with accessories in surface / recessed using saddles, clamps, fastener as required including cutting the wall, covering conduit and making good the same as required.GP 1 | | 0.0001 | Each |
|---|
| 14 | 14 | 20 mm | | 300 | R. mtr. |
|---|
| 15 | 15 | 25 mm | | 900 | R. mtr. |
|---|
| 16 | 16 | 32 mm | | 100 | R. mtr. |
|---|
| 17 | 17 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor ISI marked (IS:694) of 1.1 kV grade and approved make in existing surface or recessed conduit/casing capping including making connections etc. as required. Group -A1 | | 0.0001 | Each |
|---|
| 18 | 18 | 1 x 1.5 sq.mm (for inverter wiring) | | 600 | Mtr. |
|---|
| 19 | 19 | 3x 1.5 sq.mm ( Extra long and comp onboard wiring ) | | 360 | Mtr. |
|---|
| 20 | 20 | 2 x 2.5 sq. mm. + 1x1.5sqmm ( Light and room Power plug circuit ) | | 800 | Mtr. |
|---|
| 21 | 21 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. ( Power for AC And geyser only) | | 540 | Mtr. |
|---|
| 22 | 22 | 4 x 10.0 sq.mm ( Sub main from Meter to DB ) | | 80 | Mtr. |
|---|
| 23 | 23 | 1 x 6.0 sq.mm ( With sub main ) | | 80 | Mtr. |
|---|
| 24 | 24 | 2 x 6.0 sq. mm. + 1 x 2.5 sq. mm. | | 100 | Mtr. |
|---|
| 25 | 25 | Supplying and drawing PVC jacketed with annealed bare copper inner conductor & tinned copper conductor shielding foam PE dielectric coaxial cable of approved make in existing surface or recessed conduit/casing capping including making connections as required. GP1 | | 0.0001 | Each |
|---|
| 26 | 26 | RG - 6 | | 200 | Mtr. |
|---|
| 27 | 27 | Supplying and drawing PVC/ Polythene insulated and PVC sheathed unarmoured/ armoured telephone cable with 0.5 mm dia. Tinned / annealed copper conductor taped &confirming to ITD specification S/WS -113C of approved make in existing surface or recessed conduit/casing capping. GP1 | | 0.0001 | Each |
|---|
| 28 | 28 | Unarmoured Telephone cable in existing surface or recessed conduit/casing capping. | | 0.0001 | Each |
|---|
| 29 | 29 | 5 pair | | 200 | Mtr. |
|---|
| 30 | 30 | P & F Krone module with base frame in the recess / surface made out of 16 SWG sheet steel box, front openable, having locking arrangements duly powder painted.,including dressing, ferruling and punching of telephone cable with krone tool etc. as required. | | 0.0001 | Each |
|---|
| 31 | 31 | 10 Pairs | | 2 | Each |
|---|
| 32 | 32 | Supplying and fixing of power plug point Modular accessories on hot dipped galvanized modular box of 20 SWG on surface or in recessed with suitable size of grid plate with cover plate including cost of modular 16 amp. Switch and socket outlet, making connection, testing, etc. as required. GP1 | | 36 | Each |
|---|
| 33 | 33 | P&F 240/415 V AC MCB with positive isolation of breaking capacity not less than 10 KA (B/ C/ D tripping characteristic) ISI marked IS 8828(1996)]/ conforming to IEC 60898 in existing board/sheets including making connections, testing etc. as required. Group -A1 | | 0.0001 | Each |
|---|
| 34 | 34 | Single pole MCB | | 0.0001 | Each |
|---|
| 35 | 35 | 6 A to 32 A rating | | 72 | Each |
|---|
| 36 | 36 | Four pole MCB | | 0.0001 | Each |
|---|
| 37 | 37 | 40 A 63 A rating | | 2 | Each |
|---|
| 38 | 38 | Double pole MCB | | 0.0001 | Each |
|---|
| 39 | 39 | 40 A 63 A rating | | 4 | Each |
|---|
| 40 | 40 | P&F 240/415 V Residual current circuit breaker conforming to IS:12640:1988/ IEC 61008 on existing board/sheet including making connections, testing etc. as required GPA1 | | 0.0001 | Each |
|---|
| 41 | 41 | Two pole 100/300mA sensitivity | | 0.0001 | Each |
|---|
| 42 | 42 | 40 A rating | | 6 | Each |
|---|
| 43 | 43 | P&F Recessed/ Surface mounting heavy duty horizontal type sheet steel Distribution board phophatised/ powder painted complete with suitable rating insulated copper bus bar, shorting link , neutral link, earth link and din bar,masking sheet, conforming to IS13032 & IS8623 including making internal DB terminations with copper lugs , testing etc. as required.Gr. A1 | | 0.0001 | Each |
|---|
| 44 | 44 | Double door (Three phase) Per phase isolation | | 0.0001 | Each |
|---|
| 45 | 45 | 2+8 Way | | 2 | Each |
|---|
| 46 | 46 | Double door (single phase) | | 0.0001 | Each |
|---|
| 47 | 47 | 6 Way | | 4 | Each |
|---|
| 48 | 48 | P & F following modular accessories made out of unbreakable and fire retardant poly carbonate with silver contacts including making connections testing etc. as required GP1 | | 0.0001 | Each |
|---|
| 49 | 49 | RJ-11 telephone jack single two line | | 12 | Each |
|---|
| 50 | 50 | T.V. coaxial socket | | 10 | Each |
|---|
| 51 | 51 | 5 step fan regulator 2 Module | | 32 | Each |
|---|
| 52 | 52 | Blanking plate | | 60 | Each |
|---|
| 53 | 53 | 32 Amp. 2 Module switch With Indicator | | 12 | Each |
|---|
| 54 | 54 | 25 Amp. 2 Module Socket | | 12 | Each |
|---|
| 55 | 55 | P & F following size hot dip galvanized M.S. box of 20 SWG with earthing terminal in recess/ surface suitable for modular accessories as required. | | 0.0001 | Each |
|---|
| 56 | 56 | 1-2 Module ( for Tel, TV,AC switch and socket) | | 48 | Each |
|---|
| 57 | 57 | P & F following size mounting grid plates with cover plates Gr-1 | | 0.0001 | Each |
|---|
| 58 | 58 | 1/2 Module | | 48 | Each |
|---|
| 59 | 59 | P & F extra down rod of 15 mm dia . ERW (Electrical resistance welded ) of 1.6mm nominal thick medium duty steel pipe including cutting, threading, drilling, fixing quarter pin etc as reqd. | | 8 | Rmtr |
|---|
| 60 | 60 | P/Laying P.V.C. / XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required of size. | | 0.0001 | Each |
|---|
| 61 | 61 | 16.0 Sq.mm | | 0.0001 | Each |
|---|
| 62 | 62 | 4 core | | 100 | Mtr. |
|---|
| 63 | 63 | Making of hole in wall of required size for housing exhaust fan and making good the same, with cement plaster as required of following size: | | 0.0001 | Each |
|---|
| 64 | 64 | Up to 457 mm size | | 20 | Each |
|---|
| 65 | 65 | P & F 18 swg M.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 100 mm length extended on each side . | | 38 | Each |
|---|
| 66 | 66 | P & F ISI marked ding dong/musical chime bell including making connection testing etc. as required. Group-1 | | 6 | Each |
|---|
| 67 | 67 | P&F of Double ball bearing, capacitor start single phase metallic blade fresh air fan, in existing opening including cost of hardware , flexible copper conductor ,making connections, testing etc. as required. Gr-1 | | 0.0001 | Each |
|---|
| 68 | 68 | 300 mm sweep | | 16 | Each |
|---|
| 69 | 69 | P&F of Heavy duty capacitor start, Double ball bearing 900/1400 RPM single phase ISI marked Exhaust fan, IS:2312 marked in existing opening including making connections testing etc. as required. Group-1 | | 0.0001 | Each |
|---|
| 70 | 70 | 300 mm sweep(900/1400 RPM) | | 2 | Each |
|---|
| 71 | 71 | P & F of Gravity Louver shutter of superior quality made out of frame of 18 swg M.S. sheet & Louvers made from 24 swg MS Sheet with enamel paint including cost of nuts, bolts, etc as reqd. | | 0.0001 | Each |
|---|
| 72 | 72 | Up to 380 mm size | | 2 | Each |
|---|
| 73 | 73 | P & F of capacitor start, metal body, metal blade three speed wall mounting fan of following sweep with the help of anchor bolts including making connection testing etc. as required. GP1 | | 0.0001 | Each |
|---|
| 74 | 74 | 400 mm sweep(Oscillating type) | | 2 | Each |
|---|
| 75 | 75 | P & F of IP20 LED Recessed / Surface Mounted, Round / Sqaure Non-Dimmable Downlight with die-cast aluminum housing & Heat Sink for heat dissipation, high purity reflector with external BIS certified 2.5 KV surge protected driver having efficiency > 85% and in compliance to IEC standards. System Lumen efficacy of = 100 lm / watt and life time of minimum 35000 Burning Hours with 70% of intial Lumen maintaned, CCT 3000°K / 4000°K / 6000°K , maximum power consumption should not more than the specified rating and Fixture shall be of CE complianed.Group 1 | | 0.0001 | Each |
|---|
| 76 | 76 | Surface Mounting | | 0.0001 | Each |
|---|
| 77 | 77 | LED Downlight 12 W | | 40 | Each |
|---|
| 78 | 78 | P / L of Double wall corrugated HDPE pipe confirming to IS : 14930 P - 1 & 2 with HDPE Coupler at 1 mtr. Depth below the ground for laying cable including making the trench and back filling , compaction of earth as required of Gemini or IS:14930 marked make. Outer Dia. / Inner dia. | | 0.0001 | Each |
|---|
| 79 | 79 | 90 / 76 mm | | 60 | Mtr. |
|---|
| 80 | 80 | Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 25 mm dia. G.I. 'B' class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. | | 4 | Set |
|---|
| 81 | 81 | S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required. | | 0.0001 | Each |
|---|
| 82 | 82 | 20mm x 3mm G.I. ( Hot Dipped ) Strip | | 60 | Mtr. |
|---|
| 83 | 83 | 8 SWG G.I. ( Hot Dipped ) Wire | | 80 | Mtr. |
|---|
| 84 | 84 | S & Laying following size' B ' class G.I. Pipe confirming to IS : 1239 P - 1 ( 1990 ) with accessories for laying earth conductor/strip / cable in ground/surface/recess as required | | 0.0001 | Each |
|---|
| 85 | 85 | 50 mm dia. | | 12 | Mtr. |
|---|
| 86 | 86 | P & F energy efficient/energy saving 9 watt IP 20 LED Bulb cool white, in existing holder/fixture as required, minimum 900 Lumen output, 25000 burning hours, CCT 5700 K or 6500 K (as per direction of Engineer incharge), ANSI Lamp efficacy minimum 100 lumen /Watt, CRI 80, Driver efficiency > 85%, PF 0.95 at full load/230 volt AC. | | 40 | Each |
|---|
| 87 | 87 | SITC of Interconnecting refrigerant pipe work with closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications including chase cutting, supports etc. as required. | | 0.0001 | Each |
|---|
| 88 | 88 | 6.35 mm | | 50 | Mtr. |
|---|
| 89 | 89 | 15.88 mm | | 50 | Mtr. |
|---|
| 90 | 90 | S & F of Hard rigid PVC (20/25mm) drain piping with 6mm thick nitrile rubber insulation. | | 60 | Rmtr |
|---|
| 91 | 91 | S & F of FR PVC insulated & sheathed 3 core flexible copper conductor ISI marked (IS:694) of 1.1 kV grade of following rating: GP1 | | 0.0001 | Each |
|---|
| 92 | 92 | 4.0 Sq.mm | | 70 | Mtr. |
|---|
| 93 | 93 | P & F of 4 star rated vertical storage water heater with outer casing made of M.S.sheet finished with anti-corrosive powder coating,inner tank made of pure electrolytic copper/stainless steel / SPHP, Tubular copper sheathed and Nickel plated heating element/ twin ceremic cartridge heating element, stem type thermostat and thermal cut out,Dual indicating lamps for power supply and thermostat,PUF insulation, Pressure relase valve,fusible plug etc. as required held in position with 4 no. rack bolts,duly wired with 3 core 2.5/4.0 Sqmm PVC insulated & sheathed copper conductor and 16 A/25A three pin plug top,including making inlet,outlet heavy gauge C.P./ Flexible alloy connection,testing etc. as required. GP1 | | 0.0001 | Each |
|---|
| 94 | 94 | 6 Ltr. | | 2 | Each |
|---|
| 95 | 95 | 15Ltr. | | 6 | Each |
|---|
| 96 | 96 | P&F recessed mounting heavy duty sheet steel End Box for distribution board duly phophatised powder coated complete as required. Group-A1 | | 0.0001 | Each |
|---|
| 97 | 97 | For TPN 8 way DB | | 2 | Each |
|---|
| 98 | 98 | P & F IP-65 protected Wall mounted Bulk Head light fixture suitable for 15/18 watt CFL lamp with integral control gear, housing made from cast aluminium with UV stablized diffuser comprising of copper ballast, copper conductor including making connection testing etc. as required (without lamp) | | 8 | Each |
|---|
| 99 | 99 | NON BSR ITEMS | | 0.0001 | Each |
|---|
| 100 | 100 | P & F of IP20 Box type LED tube light fixture made from extruded aluminium housing suitable for moutning LED tube system non replaceable driver, with a minimum system lumen output of 2400 lumens and a minimum system efficiency of 110 lm/W. Power Consumption of 22W , life time of 25,000 burning hours with 70% initial lumen maintained. CCT 4000°K & 6500°K. Contractor should submit LM79 & LM 80 Report of fixture & LED Lamp for conforming above specification at the time of approval of fixture. (Make PHILIPS, Havells, Crompton , Wipro , Bajaj, Polycab, Jaquar) | | 36 | Each |
|---|
| 101 | 101 | P & F following modular accessories made out of unbreakable and fire retardant poly carbonate with silver contacts including making connections testing etc. as required . Make should be according to accessories used in wiring items and prior approval of Engineer-in- charge | | 0.0001 | Each |
|---|
| 102 | 102 | 20-25 Amp. 1 Module MCB ( For AC switch of window AC if reqd ) | | 12 | Each |
|---|
| 103 | 103 | P & F of 1200 mm sweep double ball bearing capacitor start, aluminium body & blade ceiling fan with down rod from 30 cm to 100 cm as required rated speed 390(+/- 10% ) RPM, Air delivery at 230 V should be 230 m³/min, Temp. rise 75Degree Centigrade Maximum, Insulation Resistance 2 mega ohm Minimum, with Secondary Support safety cable, wiring with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. of Havells/ Usha / Orient / Crompton Make. ( Note : Routine test, acceptance test and air delivery test (type test) shall be carried out on samples at manufacturers works as per test procedures of IS 374, in presence of Departmental Engineers.) | | 30 | Each |
|---|
| 104 | 104 | Supplying, installation, testing & commissioning of 9-10 watt 3000K mirror light all accessories i/c connections with 3 x 1.5 sq.mm PVC insulated FR copper conductor cable etc. as reqd. (Make:- Wipro/ Philips/ bajaj/havells) | | 8 | Each |
|---|