| 1 | 1 | Supply, laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)with stranded aluminum conductor, 11000 volts grade, of size 3 core 95 sq mm, Complete all as specified and directed. \nMake :- Polycab/Havells/ KEI | | 4899 | RM |
|---|
| 2 | 2 | Supply,laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)with stranded aluminum conductor, 11000 volts grade, of size single core 95 sq mm, Complete all as specified and directed by Engr-in-Charge. \nMake :- Polycab/Havells/ KEI | | 272 | RM |
|---|
| 3 | 3 | Supply & Erecting Steel Tubular Swaged Pole Type 410-SP-55 (11.0 Metre long) including Cast Iron Base Plate, Finial Taper Plug, Bolts, nuts and screws, complete all as specified and directed.\n | | 24 | each |
|---|
| 4 | 4 | Supply & Erecting Steel Tubular Swaged Pole Type 410-SP-76 (14.5 Metre long) including Cast Iron Base Plate, Finial Taper Plug, Bolts, nuts and screws, complete all as specified and directed.\n | | 4 | each |
|---|
| 5 | 5 | Supply and fix HT 11 KV Triple pole, mechanically operated,mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 200 amps . Complete all as specified and directed by engr-in-charge. \nMake :- Jaipuriya brothers or equivallent make of Alind/pactil. | | 18 | Each |
|---|
| 6 | 6 | M & L for earthing complete with GI Earth Plate Electrode 600mm x 600mm x6mm, thick buried directly in ground vertically to a depth not less than 2.25 Metre below Ground Level with Top Edge of Earth Plate at depth not less than 1.50 Metre below Normal Ground Level, connected to Galvanised iron earth strip 32X6 mm drawn through and including Galvanised Iron protection Pipe 40 mm bore (dia) Light grade by means of Bolts, Nuts, Check Nuts and Washers etc Earth plate surrounded by a packed thickness of charcoal or coke dust mixed with common salt in alternate layers of not exc 150mm thick PCC Pit in cement concrete 1:3:6 (20 mm graded aggregrate ), Precast RCC 1:2:4 (20mm graded aggregrate ) cover slab 350 x350 x 50mm thick reinforced with and including 8mm dia TMT Bars @ 10 cm Centre to Centre both ways GI Wire Mesh , Funnel, with GI Watering Pipe 20mm bore dia Medium grade necessary excavation in soft loose soil returning filling in and removal of surplus soil upto a distance of 50 METRE and all as shown in Electrical Plate No. 3 of MES schedule Part- I and testing on completion, complete all as specified and as directed. | | 30 | EACH SET |
|---|
| 7 | 7 | Supply and fix cable jointing kit for 11 KV grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 50 to 95 Sq mm complete all as specified and as directed. | | 1 | Each |
|---|
| 8 | 8 | Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 50 to 95 Sq mm complete all as specified and as directed. | | 28 | Each |
|---|
| 9 | 9 | Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 1 core XLPE, armoured, Al conductor cable of size 50 to 95 Sq mm complete all as specified and as directed. | | 8 | Each |
|---|
| 10 | 10 | S&F Unreinforced Pre-cast Concrete Cable Cover, Class HV type 2 flat of size 450x180x40mm with minimum average breaking load 350 Kg, as per IS-5820:1970, complete all as specified and as directed. | | 25361 | EACH |
|---|
| 11 | 11 | M&L Sand Cushioning (dry) in trenches/ducts for protection of UG Cables (below, above and around the UG Cable laid in Trenches) of 23 Cm Spread thickness (8 Cm in depth before laying the Cable and 15 Cm in depth after laying the Cable) and consolidated (punned) upto 180mm thickness, complete all as specified and as directed. \nNOTE : For the purpose of Payment, Punned thickness of Sand Cushioning only shall be measured and paid for. | | 369.77 | CUM |
|---|
| 12 | 12 | S&F Expulsion Fuse, Single Pole, Channel type/drop out type suitable as per Site requirement with Working Pressure 11 KV grade of capacity 50 to 100 Amps complete all as specified and as directed. | | 18 | EACH SET |
|---|
| 13 | 13 | S&F Lightning Arrester Expulsion type complete with all Fittings Transmission Class discharge capacity 65 KA suitable,for working pressure 11000 Volts and connection to earth with GI 32x6mm Strip, complete all as specified and directed. | | 18 | EACH SET |
|---|
| 14 | 14 | M&L for Cross-arms, Bracings, Supports, Clamps and Back Plates fabricated from Structural Steel Sections including Nuts, Bolts, Washer, welding, bending cold or hot, drilling holes for Bolts, in any shape or size as indicated/ directed and inclusive of one coat of Aluminium Primer one Under Coat and One Finishing Coat of Aluminium Paint, complete all as specified and as directed. | | 22.5 | QTL |
|---|
| 15 | 15 | S&F Pre-cast Reinforced Cement Concrete 1:2:4 (20mm graded aggregate) Type B-1 of size (0.5M X 0.05MX1.0M) Cable Route Indicator including embossing 'DANGER/11KV CABLE/MES' on both sides and painted Letters with approved Colour, burried in ground for a depth of 45 Cm including necessary Earth Work, complete all as specified and as directed. | | 137 | EACH |
|---|
| 16 | 16 | Excavation in Trenches not exc 1.50 Metre wide and not exc 1.50 Metre depth for errecting of pole and getting out in Soft/Loose Soil complete all as specified and as directed. | | 1253.5 | CUM |
|---|
| 17 | 17 | Excavating in Trenches, not exc. 1.50 Metre wide and exc. 1.50 Metre but not exc. 3.00 Metre in depth, for Foundation of Poles/ Stays, etc. and getting out in Soft/ Loose Soil, complete all as specified and as directed. | | 1.51 | CUM |
|---|
| 18 | 18 | Returning, Filling in including Spreading, Leveling, Watering and Well Ramming in layers not exc. 25 Cm thick in Soils, complete all as specified and as directed. | | 694.67 | CUM |
|---|
| 19 | 19 | Removing Surplus Soil to a distance not exc 50.00 Metre away and depositing where directed at a level not exc 1.50 Metre above the Starting Point, complete all as specified and as directed. | | 1255.01 | CUM |
|---|
| 20 | 20 | M&L for Cement Concrete 1:3:6 (40mm graded aggregate) type C-2 as in Foundation of Poles, Stays, etc. including Formwork (as/if required) complete all as specified and as directed. | | 19.44 | CUM |
|---|
| 21 | 21 | M&L for Cement Concrete 1:2:4 (20mm graded aggregate) Type B-2 as in Coping of Poles, etc. and finishing the Concrete surfaces Fair and Even including necessary Formwork required at Site(s), complete all as specified and as directed. | | 3.02 | CUM |
|---|
| 22 | 22 | Supply and laying cast iron pipe 300 mm bore for casing pipe of cable carrier pipe below the railway track, complete all as specified and direceted. | | 44 | RM |
|---|
| 23 | 23 | M&L for Machine boring below 3 mtr of ground level for insertion of casing pipe 300 mm dia, boring will be carried out under supervision of engr in charge and railway authorities complete all as specified and as directed. | | 44 | RM |
|---|
| 24 | 24 | Supply and laying GI medum grade pipe of 50 mm dia as a cable carrier pipe passing through casing pipe below the railway track complete all as specified and directed.\nMake :- Jindal/Tata/ National Tubing | | 176 | RM |
|---|
| 25 | 25 | S&F HDPE pipe 110 mm dia for protection of cable, fixing verticle either side of railway track on steel tubular pole complete all as specified and directed. | | 48 | RM |
|---|
| 26 | 26 | M&L for Stay Assembly complete with Accessories as shown in Electrical Plate No. 1 of MES Schedule Part-I, diameter of Stay Rod 20mm, complete all as specified and as directed.\nNOTE: Earthwork, Cement Concrete, Mild Steel Stay Clamps with Bolts, Nuts, etc., Loop Insulator, etc. will be measured and paid under approprite Items.\n\n | | 8 | Each |
|---|
| 27 | 27 | S&F Galvanised Stay Strand 7/3.15mm in size, Stretching to keep the Electric Pole in True Vertical Position, complete all as specified and as directed. | | 0.2 | Qtl |
|---|
| 28 | 28 | S&F Loop Type Insulator Vitreous White, Brown or Green, large size with overall dimensions 90mmx140mm, clearance of hole 25.5mm dia, complete all as specified and as directed. | | 8 | Each |
|---|
| 29 | 29 | M &L for danger notice plate of 25X20 cm,1.6mm thick mild steel sheet, vitereous enamelled white, with letters figures and conventional skull and bones in single red colour and fixed with MS clamps bolts and nuts of approved size for HT,complete all as specified and as directed. | | 28 | Each |
|---|
| 30 | 30 | M&L for anti-climbing devices, comprising 2.24 mm dia galvanised steel 2 strand barbed wire with 2.24 mm dia barbs wrapped spirally round poles to a length of 0.5 to 1.0 mtr clamped and properly secured or as ordered (clamps measured separately),complete all as specified and as directed. | | 1.05 | QTL |
|---|
| 31 | 31 | Boring holes horizontally under Road without damaging the surface of Road (minimum 1.0 METRE below the Road Surface with the help of GI Tubing not exc. 80mm bore (dia) for passing of UG Cable, complete all as specified and as directed.\nNOTE: GI Pipe laid will be measured and paid separately under appropriate Item. | | 30 | RM |
|---|
| 32 | 32 | Supply and laying of GI tubing,light grade of 80mm dia for Protection of UG cable, Complete all as specified and directed by Engr-in-charge.\nMake :- Jindal / National Tubing/ Tata | | 108 | RM |
|---|
| 33 | 33 | Supply and fix Earth continuity conductor or Main Earthing lead fixed to wall or batten or reccess or chasses or buried in ground or drawn in conduit / pipe or fixed to Poles or any other indicated situation for loop copper strip of size 32mmx6mm connected to test point complete all as specified and as directed. | | 110 | RM |
|---|