Military Engineer Services-MES has published Repair Maint Of Lt Panels Mccbs And Pf Panels Earthing Lightening Arrestors Flame Proof Wiring Fittings Incl Lt Cables At Af Stn Chandinagar. Submission Date for this Tender is 23-06-2021. Electrification Work Tenders in AF STATION CHANDINAGAR Uttar Pradesh. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 16-Jun-2021 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 23-06-2021 |
Name of Work: REPAIR/MAINT OF LT PANELS, MCCBS AND PF PANELS, EARTHING LIGHTENING ARRESTORS, FLAME PROOF WIRING & FITTINGS INCL LT CABLES AT AF STN CHANDINAGAR UNDER GE AF FARIDABAD | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Excavation in trenches in soft/loose soil not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr depth for laying of cables/poles or foundation etc and getting out complete all as specified and directed by Engineer-in-Charge. | 302.4 | CUM | |
2 | 2 | Returning, filling, including spreading levelling and well ramming in layers not exceeding 25cm apart complete all as specified and directed by Engineer-in-Charge. | 172.98 | CUM | |
3 | 3 | Removing of surplus excavated soil to a distance not exceeding 50 Mtr from starting point and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and directed by Engineer-in-Charge. | 129.42 | CUM | |
4 | 4 | M&L for sand cushoning with a layer of sand 80mm thick before laying of cable and 150mm thick after laying of cable to trenches complete all as specified and directed by Engineer-in-Charge. | 90.72 | CUM | |
5 | 5 | M&L for sub class `B` bricks for cable protection complete all as specified and directed by Engineer-in-Charge. | 9.74 | PER 1000 Nos | |
6 | 6 | Taking down UNSV LT Under Ground cable of any size complete all as specified and directed by Engineer-in-Charge. | 1600 | RM | |
7 | 7 | Supply & Laying connecting of cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured LT 1100 Volts grade aluminium conductor of cross sectional area 16 Sqmm 4 core incl thimbles as required with suitable size of clamps on wall/under trenches etc complete all as specified and directed by Engineer-in-Charge. | 200 | RM | |
8 | 8 | All as above item No 7 but 50 Sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge. | 150 | RM | |
9 | 9 | All as above item No 7 but 70 Sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge. | 250 | RM | |
10 | 10 | All as above item No 7 but 95 Sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge. | 100 | RM | |
11 | 11 | All as above item No 7 but 25 Sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge. | 300 | RM | |
12 | 12 | All as above item No 7 but 240 Sq mm 3.5 core complete all as specified and directed by Engineer-in-Charge. | 600 | RM | |
13 | 13 | M&L Boring of holes under road, pavement, hard standing by trench less technology using ultra sounding technique and necessary \nmachine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed by Engineer-in-Charge. | 20 | RM | |
14 | 14 | Supply & fixing MCCB TPN 63 Amps 415 Volts 16 kA complete all as specified and directed by Engineer-in-Charg | 5 | Each | |
15 | 15 | Supply & fixing MCCB TPN 100 Amps 415 Volts 16 kA complete all as specified and directed by Engineer-in-Charg | 6 | Each | |
16 | 16 | Supply & fixing MCCB TPN 125 Amps 415 Volts 16 kA complete all as specified and directed by Engineer-in-Charg | 3 | Each | |
17 | 17 | Supply & fixing MCCB TPN 250 Amps 415 Volts 35 kA complete all as specified and directed by Engineer-in-Charg | 2 | Each | |
18 | 18 | Supply & fixing MCCB TPN 400 Amps 415 Volts 36 kA complete all as specified and directed by Engineer-in-Charg | 2 | Each | |
19 | 19 | Supply & fixing MCCB TPN 630 Amps 415 Volts 36 kA complete all as specified and directed by Engineer-in-Charg | 2 | Each | |
20 | 20 | S&F Current Transformer (100/5) set of three incl necessary connection in existing panel complete all as specified and directed by Engineer-in-Charge | 3 | Each | |
21 | 21 | S&F Current Transformer (250/5) set of three incl necessary connection in existing panel complete all as specified and directed by Engineer-in-Charge | 1 | Each | |
22 | 22 | M / L for checking electrical /electronic circuit for finding out fauilty capacitors and replacement with Ultra heavy duty box type capacitor suitable for 440 volt 50 Hz operation of rated capacity 20 kVAr including taking down old unserviceable capacitor and and making all circuit connection and testing for smooth functioning as directed by Engineer in charge. | 1 | Each Job | |
23 | 23 | All as per item No 22 above but 10 kVAr complete all as specified and directed by Engineer-in-Charge. | 1 | Each Job | |
24 | 24 | All as per item No 22 above but 5 kVAr complete all as specified and directed by Engineer-in-Charge. | 1 | Each Job | |
25 | 25 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 25 to 50 sqmm,Indoor/Outdoor type complete all as specified and directed by Engineer-in-Charge. | 2 | Each | |
26 | 26 | All as item No 25 above but for cable of size 70 to 120 sq mm complete all as specified and directed by Engineer-in-Charge. | 2 | Each | |
27 | 27 | S&F on load Change Over Switch 200 Amps 4 pole 415 Volt incl making suitable arraangement to fix in existing LT Panel as required complete all as specified and directed make HPL/Havells/L&T/Legrand all as specified and directed by Engr-In-Charge. | 2 | Each | |
28 | 28 | S&F on load Change Over Switch 100 Amps 4 pole 415 Volt incl making suitable arrangement to fix in existing LT Panel as required complete all as specified and directed make HPL/Havells/L&T/Legrand all as specified and directed by Engr-In-Charge. | 2 | Each | |
29 | 29 | S&F on load Change Over switch 415V in sheet metal enclosures 4 pole of capacity 250 Amps 415 Volt incl making suitable arrangement to fix on wall/panel as required complete all as specified and directed make Havells/L&T/Legrand all as specified and directed by Engr-In-Charge. | 2 | Each | |
30 | 30 | S & F in replacement of hot pressed moulded SMC boxes with hinged door fixing of size 345mm x 225 mmx 140 mm with MS clamp 25 x 3mm made to shape with necessry nuts bolts clamps and washers complete comprising of Aluminium bus bar 63 Amps capacity of suitable size -04 nos mounted over Porcelain insulator with nuts & bolts washers incl MCB SP 6 amps and making incoming and outging connections by taking out loops of cable of any size incl necesary excavations and other civil works Make :- Sintex /Universal/ SMS complete all as specified and directed by Engineer-in-Charge. | 20 | Each | |
31 | 31 | S & F Earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick, buried directly in ground vertically to a depth not less than 2.25 meters deep below ground level with top edge of the plate not less than 1.5 Mtrs below normal ground level connect to galvanized iron earth strip 25 x 4 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel up to 7.5 meter length connected to earth plate including necessary excavation & earthwork, PCC (1:3:6) type C-1 earth chamber, 40 mm thick RCC cover 1:2:4 mix with 6mm dia nominal reinforcement @ 150mm c/c both ways etc complete all as shown in electrical plate No 3, connected to earthing test point complete including testing on completion complete all as specified and directed by Engineer-in-Charge. | 8 | Each | |
32 | 32 | All as item No 31 above but by using Galvanised iron plate 60×60cm × 6 mm as earth plate electrode and and 4 Sq mm GI wire as earthing lead complete all as specified and directed by Engineer-in-Charge. | 4 | Each | |
33 | 33 | Design development supply commissioning and testing EHCC certified ground terminal earthing system hollow tube solid bar CCPRI tested for sensitive signal/Electrical equipments highly anti corrosive long life severe wear conditions in the earth pit and of standard size ISI marked copper tube out side secondary conductor of 50mm dia and main primary conductor inside 25mm dia 3000mm length ready to install with suitable connecting terminal confirming to IS:3043 1987 specification highly conducive packing material to be filled in earth pits for providing uniform low resistivity anti corrosive hygroscopic medium around the earth system for improving the efficency of current dissipation 20 Kg per bag (3 bag per kit) min or sufficeient quantities required as per site complete incl PCC pits of inside dimension 0.5x0.5x0.5m and suitable cover complete all as specified and directed by Engineer in Charge. | 2 | Each job | |
34 | 34 | Supply, installation, testing and commissioning of LT panel indoor type made out of 2.0 mm thick CRCA sheet, suitable angle iron frame for structure and base, copper busbar 600 amps rated with SMC busbar supports - 04 Nos, dust/vermin proof, epoxy powder coated siemens grey painting over a coat of red oxide primer inside/outside of the panel, double shuttered with locking arrangements, cable alley, anodized aluminium with black background with white engraved letter of name plates, schematic diagram for distribution, rubber gaskets, cable glands and internal copper wirings with appropriate lugs complete including necessary civil works and making good disturbed surfaces with following accessories complete all as specified and directed by Engineer-in-Charge. (CPRI Approved) \nIncoming\nMCCB four pole, 36 KA, 400 Amps (adjustable type) - 01 No\nOnload change over switch 400 Amps, four pole - 01 No\nOutgoing\nMCCB four pole, 36 KA, 200 Amps (adjustable type) - 01 No\nMCCB four pole, 25 KA, 125 Amps (adjustable type) - 02 No\nMCCB four pole, 16 KA, 100 Amps (adjustable type) - 02 No\nMCCB four pole, 16 KA, 63 Amps (adjustable type) - 02 No\nMeter\nVoltmeter 0 - 500 V - 01 No\nAmmeter 0 - 600 amps - 01 No\nSelector switch - 02 No\nIndicating lamp (R, Y, B) - 01 Set\n | 1 | Each job | |
35 | 35 | S&F switch flameproof rotary type with termination box in LM6, 16 A, single pole 250 V all as specified and directed by Engineer in Charge | 5 | Each | |
36 | 36 | M&L for point wiring with two runs of 1.5 sqmm Single Core Havells Single Core copper conductor (Flexible) Industrial Cables HFFR compound insulated (Unsheathed),\n1100 Volts Generally confirming to IS: 694 insulated stranded copper conductor cable drawing in stove enammeled steel conduit incl tees, bends, junction boxes surface wiring on wall ceiling with suitable clamps of medium grade ISI marked not less than 20mm dia alongwith 1.0 sqmm PVC insulated stranded copper conductor cable for continuous earth wire connected to main earth dolly with provn of pressed steel terminal box of suitable size as per site requirement with one light point/fan point controlled by one switch complete all as specified and directed by Engineer-in-Charge. | 30 | RM | |
37 | 37 | M&L for rigid stove enamelled conduit welded not less than 25 mm dia incl tees bends etc fixed with suitable clamps with proper screws complete all as specified and directed by Engineer-in-Charge. | 20 | RM | |
38 | 38 | M&L for junction box suitable for 25mm conduit with cover and outlets fixed with suitable clamps with proper screws complete all as specified and directed by Engineer-in-Charge. | 5 | Each | |
39 | 39 | Design development supply commissioning and testing EHCC certified ground terminal earthing system hollow tube solid bar CCPRI tested for sensitive signal/Electrical equipments highly anti corrosive long life severe wear conditions in the earth pit and of standard size ISI marked GI tube out side secondary conductor of 50mm dia and main primary conductor inside 25mm dia 3000mm length ready to install with suitable connecting terminal confirming to IS:3043 1987 specification highly conducive packing material to be filled in earth pits for providing uniform low resistivity anti corrosive hygroscopic medium around the earth system for improving the efficency of current dissipation 20 Kg per bag (3 bag per kit) min or sufficeient quantities required as per site complete incl PCC pits of inside dimension 0.5x0.5x0.5m and suitable cover complete all as specified and directed by Engineer in Charge | 2 | Each job | |
40 | 40 | Supply and labour for Brickwork with sub class ‘B’ bricks, straight or curved on plan exc 6m mean radius built in cement motar 1: 4 complete all as specified and directed by Engineer-in-Charge. | 7 | Cum | |
41 | 41 | M & L for cement plaster work 15 mm thick in 1:4 Rendering on fair faces of brick work or concrete surfaces including 5 mm thick finishing to be carryout one even and smooth surface (without usingextra lime or cement) complete all as specified and directed by Engineer-in-Charge. | 70 | Sqm | |
42 | 42 | Surface dressing in soft/loose soil not exceeding 15 cm deep complete all as specified and as directed by Engineer-in-charge | 80 | Sqm | |
43 | 43 | M&L Broken stone or boulders Hardcore of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15cm thick complete all as specified and as directed by Engineer-in-charge | 12 | Cum | |
44 | 44 | Supply installation,testing commissioning in replacement of horizontal single mounted single phase 220 V/250 V 6000 RPM 50 Hz, AC siren audible range 2 Km 1/4 HP complete incl necessary grounting on wall/roof etc incl connections complete all as specified and directed by Engineer-in-Charge. | 1 | Each | |
45 | 45 | M&L LT Busbar of size 1 x 1 x .3 mtr for accomodating busbars suitable for incoming and outgoing of XLPE cables of size upto 400 Sqmm 3.5 Core, 600 amps rated TPN, bus bar shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators made on non hygroscopic , non combustible , track resistant , high strength FRP/SMC/DMC material at regular interval through out the length of the TPN bus outdoor made out of 3.15 mm thick CRCA sheet, angle iron frame of size 40 x 40 x 6 mm for structure and base, dust/vermin proof, epoxy powder coated siemens grey painting over a coat of red oxide primer inside/outside of the panel, double shuttered with locking arrangements with opening at one side, the bottom of the outer shell containes a detachable plate having provision for entry of armoured cable with glands, angles with legs of 450mm long embedded in PCC (1:2:4) type B2 platform of size 1.5x.5 x.3 mtrs , including necessary excavation & earth work complete all as specified and directed by Engineer-in-Charge. | 1 | Each |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy