Special Repair For Replacement Of Lt Panel Provn Of Watch Tower Addition/Alteration And Renovation Of Sncos Bar Room And Other Sanction Works At Af Stn Bamrauli

Tender Notice

28080082
Corrigendum : Special Repair For Replacement Of Lt Panel Provn Of Watch Tower Addition/Alteration And Renovation Of Sncos Bar Room And Other Sanction Works At Af Stn Bamrauli
Indian
Uttar Pradesh
23-06-2021
29-06-2021
30-06-2021

Tender Details

Special Repair For Replacement Of Lt Panel Provn Of Watch Tower Addition/Alteration And Renovation Of Sncos Bar Room And Other Sanction Works At Af Stn Bamrauli

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 21-Jun-2021 Date Corrigendum Date 29-06-2021
2 21-Jun-2021 BOQ Corrigendum BOQ 29-06-2021
3 21-Jun-2021 Financial Corrigendum Financial Bid 29-06-2021
4 23-Jun-2021 Corrigendum_4 Technical Bid 29-06-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 60000.00 /-
Tender Value
INR 30 Lakhs /-

BOQ Items

Name of Work: SPECIAL REPAIR FOR REPLACEMENT OF LT PANEL, PROVN OF WATCH TOWER, ADDITION/ALTERATION AND RENOVATION OF SNCO’S BAR ROOM AND OTHER MISC WORKS AT AF STN BAMRAULI
Sl. No. Item Description Item Code / Make Quantity Units
1 1 S&F MS works as of angles or tees,fixed independently cut to shape drilled incl. bending and welding angles of grade 410-FE including all as specified and directed 1497 Kg
2 2 M&L Framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering. Doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging; also fastening and fixing complete all as specified and directed 400 Kg
3 3 Preparation of new surfaces of steel of any description over 10cm grith or width, not otherwise described with one coat of red oxide followed by two coats of synthetic enamel paint. 60 Sqm
4 4 S&F Pre-painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an any colours( Green Colour) having tensil strength of 550 Mpa as in roof covering to wall fixed with self tapping screws as specified. 52 Sqm
5 5 S&F plate girder or single stanchions, built up of one beam or channel section with flange plates, caps, bases splices angle brackets cleats and other connections 500 Kg
6 6 Excavation in trenches for n.exc 1.5m wide not exceeding 10 Sqm on plan and not exc 1.5m in depth in soft/loose soil and getting out 12 Cum
7 7 M&L PCC (1:4:8) type D2 using 40mm stone agg as in sub base of flooring / fdn of wall etc complete all as specified 4 Cum
8 8 M&L PCC 1:3:6 type C1 (20mm gr agg) as in flooring etc all as specified and directed. 4 Cum
9 9 S& F TMT Steel bars (HYSD) cut to length bent to shape required including straightening,cutting,bending,placing in position and building all complete 10 mm dia and over. 97.11 Kg
10 10 M&L formworks to sides of pillar, strut, piers, columns and stancitions rough similar surface to concrete flat 9.6 Sqm
11 11 M&L of RCC M-25 desighn mix in columns pillars, piers post ,strut. 1.67 Cum
12 12 S&F steel work in tubular including special shaped washer etc. complete using ERW or induction butt welded tubes conforming to I.S 1161-1979 St grade St-240 600 Kg
13 13 Hard core PCC 1:5:10 type E-2 (using 40mm graded stone aggregate) as in fdn filling and mass concrete. 4 Cum
14 14 M&L for chequered 4mm thick galvanished plain sheet with grade of zinc fixed in cable duct as specified by the Engg-in-Charge 10 Sqm
15 15 MS Bolts & Nuts 60mm long & 18mm dia 80 Kg
16 16 Provn & fixing of Rajshri PVC wall panelling of 5mm thick sheet for panel & inner framework. The strips should have in their centre a grove of 6mm & 1MM depth for sinking the head of the screw used to fix the strips to the wall vertically at an equal interval between two PVC strops. The PVC strips shall be fixed to the wall using steel screws through the grovve in the pvc strip by using PVC fasteners panels are joined through solvent content. ( New provision) 120 Sqm
17 17 S&F venation blind vertical type level or ultima 100mm width of strip with necessary pulling threads aluminium channel along with all arrangement tixed to wall completed all as sspecified & directed. ( New provision) 13 Sqm
18 18 Taking down chowkats or fromes exc 1.5sqm but not exc 4 sqm each (without taking off shutters from the fromes) & removing from site complete all as specified and directed 6 Each
19 19 Taking down chowkats or frames not exc 1.5 sqm each (without taking off shutters from the frames) & removing from site complete all as specified and directed 2 Each
20 20 S&F for coloured 12mm toughed glass doors/window including eatching all necessary fiting fixuters & Godrej or link 7 lever lock self , including BIOMERTIC LOCK any size/ type complete all as spd and directed by Engr-in charge 6 Sqm
21 21 Aluminium Door (Powder coated ) single/double leaf with anodized aluminium frame sliding/openable including wheel powder coated of section 62.5x37x2.5 mm thick shutter with bottom & middle rail of section 112.5x37x2.5mm and style & top rail of section 83x37x2.5mm thick with centrally locking arrangement with lock rail of "Godrej or Link 7 lever self closing device with rebate including joints cleat fixing of builders hardware fittings necessary numbers of floor spring and gazing with 5.5mm thick ordinary plain glass including wire mesh shutter necessary fittings fixuters & aluminium snap beads complete. 5 Sqm
22 22 Aluminium window (Powder coated ) double leaf /three leaf with anodized aluminium frame sliding/openable including wheel powder coated of section 62.5x37x2.5 mm thick shutter with bottom & middle rail of section 112.5x37x2.5mm and style & top rail of section 83x37x2.5mm thick with centrally locking arrangement with lock rail of rebate including joints cleat fixing of builders hardware fittings necessary and gazing with 5.5mm thick ordinary plain glass including wire mesh shutter necessary fittings fixuters & aluminium snap beads complete. 9 Sqm
23 23 S&F powder coating aluminium anodized grills powder coated with 6x5mm aluminium section having square gap of 100mm thick with fixing rails of channels 12-15mm complete all as directed 9 Sqm
24 24 M&L for making POP cornices 100mm wide of required design as directed by Engr-in-charge complete all as specified. 18 Per RM
25 25 S&F POP false ceiling over GI snap grid permiter wall channel 25x25m fixed on wall all round, GI main ceiling channel with flange 50x25mm @ 250mm C/C, cross GI channel section 25x12 mm @ 750 C/C alongwith the suspenders of GI angle 25x25 mm @ 1200 mm C/C. The 20 to 25 mm thick POP lath pastering over n. less than 0.56 mm thick wire gauge in complete ceiling incl form work. Ration of POP and wall putty (1:10) and applying two coats of oil bound distemper incl chalk whitening and priming in alkali restant incl preparing the surface complete all as specified 18 Sqm
26 26 M&L for anti static vinyle flooring 2 mm thick fixed with adhesive as per manufacurer instructions over copper strip 0.50 mm thick 75 mm width fixed with adhesive in concrete floor in 1.0 mm meter grid projected to skirting 10 cm height including dismentling of existing tiles complete all as specified and directed 29 Sqm
27 27 Taking down carefully the existing aluminum/copper paint wiring of any size and capacity and type by disconnecting from the either terminals complete including fittings and fixtures such as switches, sockets, ceilling rose, fan regulators, lamp holders, call bell, bell pushes any type etc b unscrewing and taken away from site complete and make good the disturbed surface as existing. Note : Cost of unserviceable materials will be charged from the contractor agaginst schedulr of credit 85 Point
28 28 M & L for point wiring complete with PVC insulated unsheathed stranded copper conductor cable 1.5 sqmm (nominal area) in and incl.concealed PVC conduit not less than 20mm outer dia med grade ISI marked comp.with all the accessories incl metal flush box and white plate covers of suitable Modular fitting including one run of 1.5 Sqmm PVC insulated unsheathed stranded copper conductor cable as continuous earth wire connected to common earth dolly complete all as specified and directed for the following :
29 28.01 (a) For one light point/fan/Exhaust fan point controlled by one switch 51 Point
30 28.02 (b) For one three pin socket out let 5 Amps on independent board complet 20 Point
31 28.03 (c) For one three pin socket outlet on same board 5 Point
32 28.04 (d) Modular Socket out let independent but below the switch board of light points in the same vertical plane. 10 Point
33 29 All as specified in item No.28 herein before but with 4 Sq mm PVC insulated and PVC unsheathed cable for 3 pin 15 Amps power point on independent Board 4 Sq mm copper PVC unsheathed as earth wire all as directed 10 Point
34 30 Supply and fixing Modular Switch single pole one way 6A, 230 Volts. 85 Each
35 31 Supply and fixing Ceiling rose surface type 3 terminals 65x20mm complete all as specified 50 Each
36 32 Supply and fixing Modular Socket outlet 2 in 1, 2/3 pin, 5 Amps 35 Each
37 33 Supply and fixing Modular Socket 6A/16A- 2/3 pin combined 2 module 20 Each
38 34 Supply and fixing Modular Switch single pole one way 16A, 230 Volts. 10 Each
39 35 Supply and fix sheet metal enclosure single pole and neutral 8 way double door 240 volt 200 A rated bus bar Make indo Asian/Legrand/Havells 2 Each
40 36 Supply and fix in repair SPN240 V 32 Amps capacity including taking down old unsv MCB SPN 2 Each
41 37 Supply and fix in repair MCB, SP 06 to 32 Amps including taking down old unsv MCB SPs 20 Each
42 38 S&F MCB Vertical type TPN DB made up with sheet metal, phosphorised, power coated, neutral link, earth bar and din rail, 4 way TPN with 200 Amps rated bus bar, 240 volts complete all as specified and as directed. 1 Each
43 39 S&F MCB FP 100 Amp capacity, 415 volts, 16 KA complete all as specified and directed 1 Each
44 40 M&L of Sub main wiring with single core PVC insluated unsheathed, 1100 Volts grade, (FRLS) copper cable 6 Sqmm stranded conductor and drawing through PVC conduit medium duty (ISI Marked) concealed with conduit accessories such as junction boxes, bends, tees etc. Includingcontinuous earth wirre PVC insulated unsheathed 1100 volts grade, cable 6 Sqmm copper conductor and connected to common earth dolly completed as directed including taking down old submain wiring. Note :- (i) Two run of 6 Sqmm & one run of 4 Sqmm as earth continuity conductor. 50 RM
45 41 M&L of Sub main wiring with single core PVC insluated unsheathed, 1100 Volts grade, (FRLS) copper cable 10 Sqmm stranded conductor and drawing through PVC conduit medium duty (ISI Marked) concealed with conduit accessories such as junction boxes, bends, tees etc. Includingcontinuous earth wirre PVC insulated unsheathed 1100 volts grade, cable 6 Sqmm copper conductor and connected to common earth dolly completed as directed including taking down old submain wiring. Note :- (i) Two run of 6 Sqmm & one run of 4 Sqmm as earth continuity conductor. 50 RM
46 42 Supply and fix round down lighter 8 watt 6500K, 240 volt 50Htz recess mounted 150 lumen/watt inbuilt driver detachable, cut out dia 94mm , Make Philips/Bajaj/Wipro 24 Each
47 43 Supply and fix 200x200mm square LED Panel recess mounting, 240 volt 50Htz 6500 K, system lumen 150 lumen/watt, Make Bajaj/Wipro/Syska 10 Each
48 44 Supply and fix AC starter unit consisting of one 25 Amp capacity starter, one 240 V 25 Amps 10 KA SPN MCB, one 25 Amps socket and one 25 Amp plug top prewired of Make : North West/ Anchor / Legrand complete as specified after taking out old unservicable starter unit all as directed. 4 Each
49 45 Supply and fix star rated wall mounted fan 450 mm sweep, left & rijght rotation, inbuilt regulator, 240 volt 50 Htz. Including fixing arrangement. Make : Bajaj/CG/Havells 8 Each
50 46 Supply and fix spot light 3 watt 240 volt 50 Htz inbuilt driver duly fixed in show case at Bar room 6500k/3000k. 10 Each
51 47 Supply and fix decorative LED fittings with LED lamp opal glass shade esthatic look with premium synthatic and metal combination including 10 watt LED bulb E27 including connection and fixing arrangement Philips Cat Part No-31434 or equivalent in Bajaj/CG. 10 Each
52 48 All as per item No 28 here-in-before but using 2.5 sqmm PVC FRLS insulated copper condutor wire for connecting 15A socket on independent board Make of cable : Finolex/L&T Make of casing Capping : Presto Plast/Modi/Harash 1 Point
53 49 Supply and fix modular socket out 6Amps, 2 module complete 1 Each
54 50 Supply and fix modular socket out 16Amps, 2 module complete 1 Each
55 51 S&F in replacement of Modular Switch Modular switch 1 way 16A, 1 module complete all as specified and directed 1 Each
56 52 S&F in replacement of Modular Switch Modular switch 1 way 6A, 1 module complete all as specified and directed 1 Each
57 53 Supply, testing and fixing LED flood light fitting including luminare 100watt made up to pressure die cast housing with toughned glass and individuals LED's with secondary optics and IP65 protection LED efficacy more then 100Lm/Watt, 6500K, PF not less then 0.95 THD< 10% suitable for mounting on iron chhenal and angle inon, necessary pre cast conector for connecting wire complete Make : Make : Philips/Havells/Cromton/Wipro 3 Each
58 54 S&L of Sub main wiring with four runs of single core 4 Sqmm (nominal area) PVC insluated and unsheathed multi stranded copper conductor cable LT 1100 Volts grade drawn through and including PVC conduit of adequate size and surface with all necessary fitting fixing on steel struchure and accessories and one run of PVC insulated and unsheathed single core cable with copper conductor of size 4 Sqmm as earth wire (green in colour) run through conduit and connected to common earth dolly, including taking out the old one two run of cable one run of casing caping and one run of earth continuity wire for connection to DBs/dolly shall be deemed to be included in this item and shall be measured as one run complete all as specified and diected 20 Each
59 55 S&F vertical Loadline distribution board, double door 8 way SPN fitted with busbar,neutral links, blanking plates (without MCCB) complete all as specified and directed by Engineer-in-Charge. Make Havells/Legrand/L&T 1 Each
60 56 Supply and fix in repair MCB, SP 06 to 32 Amps 240 volt 10 KA "c" series Make Havells/Legrand/L&T 5 Each
61 57 S&F of MCB, single pole and neutral, 230 volts, 32 to 63 Amp rating, 'C' series fixed in DBs catered here-in-before. Make Havells/Legrand/L&T 1 Each
62 58 Earthing complete with galvanised steel earth plate electrode 60 x 60 cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron wire 4mm dia as earth lead wire by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in Electrical plate No. 3, MES SSR Part I- 2009 with 15 mm dia medium grade GI pipe as a protection to earthing lead and 20 mm dia medium grade GI pipe for watering purpose including excavation & earth work in any type of soil, funnel, wire mesh, RCC pit with cover, cast iron frame complete and connected to earthing test point all as specified or indicated including testing on completion. Notes (i) The concrete pit shall be PCC (1:3:6) type C-1, 40mm thick precast cover slab of RCC with suitable Mild steel handle in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I(ii) PCC pit shall be provide at least 500 mm away from the earth pit and not on just on the eath pit and extra cost of additional length of water pipes and fittings junction etc shall be deemed to be included in the rate. (iii) Item includes the cost of 7.5 metre earth lead wire and GI pipe for protection of earth wire. Any varriation in quantity shall be adjusted. Earthing complete with galvanised steel earth plate electrode 60 x 60 cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron wire 4mm dia as earth lead wire by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in Electrical plate No. 3, MES SSR Part I- 2009 with 15 mm dia medium grade GI pipe as a protection to earthing lead and 20 mm dia medium grade GI pipe for watering purpose including excavation & earth work in any type of soil, funnel, wire mesh, RCC pit with cover, cast iron frame complete and connected to earthing test point all as specified or indicated including testing on completion. Notes (i) The concrete pit shall be PCC (1:3:6) type C-1, 40mm thick precast cover slab of RCC with suitable Mild steel handle in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I(ii) PCC pit shall be provide at least 500 mm away from the earth pit and not on just on the eath pit and extra cost of additional length of water pipes and fittings junction etc shall be deemed to be included in the rate. (iii) Item includes the cost of 7.5 metre earth lead wire and GI pipe for protection of earth wire. Any varriation in quantity shall be adjusted. Earthing complete with galvanised steel earth plate electrode 60 x 60 cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron wire 4mm dia as earth lead wire by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in Electrical plate No. 3, MES SSR Part I- 2009 with 15 mm dia medium grade GI pipe as a protection to earthing lead and 20 mm dia medium grade GI pipe for watering purpose including excavation & earth work in any type of soil, funnel, wire mesh, RCC pit with cover, cast iron frame complete and connected to earthing test point all as specified or indicated including testing on completion. Notes (i) The concrete pit shall be PCC (1:3:6) type C-1, 40mm thick precast cover slab of RCC with suitable Mild steel handle in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I\n(ii) PCC pit shall be provide at least 500 mm away from the earth pit and not on just on the eath pit and extra cost of additional length of water pipes and fittings junction etc shall be deemed to be included in the rate. (iii) Item includes the cost of 7.5 metre earth lead wire and GI pipe for protection of earth wire. Any varriation in quantity shall be adjusted. Earthing complete with galvanised steel earth plate electrode 60 x 60 cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron wire 4mm dia as earth lead wire by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in Electrical plate No. 3, MES SSR Part I- 2009 with 15 mm dia medium grade GI pipe as a protection to earthing lead and 20 mm dia medium grade GI pipe for watering purpose including excavation & earth work in any type of soil, funnel, wire mesh, RCC pit with cover, cast iron frame complete and connected to earthing test point all as specified or indicated including testing on completion. Notes (i) The concrete pit shall be PCC (1:3:6) type C-1, 40mm thick precast cover slab of RCC with suitable Mild steel handle in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I\n(ii) PCC pit shall be provide at least 500 mm away from the earth pit and not on just on the eath pit and extra cost of additional length of water pipes and fittings junction etc shall be deemed to be included in the rate. (iii) Item includes the cost of 7.5 metre earth lead wire and GI pipe for protection of earth wire. Any varriation in quantity shall be adjusted. Earthing complete with galvanised steel earth plate electrode 60 x 60 cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron wire 4mm dia as earth lead wire by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in Electrical plate No. 3, MES SSR Part I- 2009 with 15 mm dia medium grade GI pipe as a protection to earthing lead and 20 mm dia medium grade GI pipe for watering purpose including excavation & earth work in any type of soil, funnel, wire mesh, RCC pit with cover, cast iron frame complete and connected to earthing test point all as specified or indicated including testing on completion. Notes (i) The concrete pit shall be PCC (1:3:6) type C-1, 40mm thick precast cover slab of RCC with suitable Mild steel handle in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I\n(ii) PCC pit shall be provide at least 500 mm away from the earth pit and not on just on the eath pit and extra cost of additional length of water pipes and fittings junction etc shall be deemed to be included in the rate. (iii) Item includes the cost of 7.5 metre earth lead wire and GI pipe for protection of earth wire. Any varriation in quantity shall be adjusted. 1 Each
63 59 Supply , laying & testing cable XLPE insulated screened PVC bedded , galvanised steel strip or wire armored, electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts grade,of size 10 Sqmm 2 core . 130 RM
64 60 Excavating in trenches n.exc 1.5 metre wide and n. exc 1.5 metre deep and getting out in soft/loose soil. 23.28 Cum
65 61 Returning, filing in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soil. 13.28 Cum
66 62 Removing excavated surplus soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point. 10 Cum
67 63 Sand filling for cable cushioning including spreading and levelling as directed. \nNote : Thickness for sand shall be measured after punning down. 6.98 Cum
68 64 Supply and lay sub class ‘B’ bricks (old Size) ,common burnt clay building bricks for cable protection laid length wise perpendicular to the axis of cable, abutting each other gap should not more than 10mm.\n 776 Each
69 65 M&L for GI tubing 40 mm dia light grade with all necessary fittings laid in trenches flxed to walls, poles, under road/floor etc for cable protection complete all as specified and directed. 10 RM
70 66 Supply, installation, commissioning and testing LT panel board cubical indoor type floor mounted, factory made 2.15mm MS sheet, conforming to IP-54, with front and back hinges door with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof and painted powder coated including 400 Amp rated copper bus bar 3 phase 4 wire system and wiring with suitable size of copper cable comprising and suitable foundation & following accessories :- INCOMING : (a) ATS 250 Amps 70 Ka 4 P, 415 volt with microprocessor, control wiring, relay, ready to use assembely for DPx 250 with suitable MCCB. Cat Part No 625381 of Legrand make or equivalent Siemens/Hager/Schneider -02 Nos, (b) Digital Voltmeter 0-500V with selector switch -01 No (c) Digital Ammeter0-300A CT ratio type with selector switch and 3 Nos of CTs (d) Phase indicator lamp LED type RYB-01 set OUTGOING :- (a) MCCB 160 Amps, 4 pole, breaking capacity 25 KA at 415 volts , 25 HZ, thermal & megnatic adjustable type.Cat Part No : 420097 of Legrand make or equivalent Siemens/Hager/Schneider - 03 Nos (b) MCCB 100Amp, 25KA, 4 P, 415 V, thermal & megnatic adjustable type. Cat Part No : 420055 of Legrand make or equivalent Siemens/Hager/Schneider - 03 Nos (c) MCCB 63 Amps 16 Ka 4 Pole, 415V, thermal & megnatic adjustable type of capacity 63 Amps, Cat Part No : 420013 of Legrand make or equivalent Siemens/Hager/Schneider - 03 Nos (d) PCC foundation ( 1:2:4)grading=(1.5x1.5x0.5) CUM. Note :- Cable glands should be provided for all incoming /outgoing connections. 1 Each
71 67 Supply, installation, commissioning and testing LT panel board cubical indoor type floor mounted, factory made 2.15mm MS sheet, conforming to IP-54, with front and back hinges door with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof and painted powder coated including 400 Amp rated bus bar 3 phase 4 wire system and wiring with suitable size of copper cable comprising and suitable foundation & following accessories :- INCOMING :- (a) ATS 250 Amps 70 Ka 4 P, 415 volt with microprocessor, control wiring, relay, ready to use assembely for DPx 250 with suitable MCCB. Cat Part No 625381 of Legrand make or equivalent Siemens/Hager/Schneider -02 Nos (b) Digital Voltmeter 0-500V with selector switch -01 No (c) Digital Ammeter0-300A CT ratio type with selector switch and 3 Nos of CTs. (d) Phase indicator lamp LED type RYB-01 Set. OUTGOING :- (a) MCCB 160 Amps, 4 pole, breaking capacity 25 KA at 415 volts , 25 HZ, thermal & megnatic adjustable type.Cat Part No : 420097 of Legrand make or equivalent Siemens/Hager/Schneider - 03 Nos (b) MCCB 100Amp, 25KA, 4 P, 415 V, thermal & megnatic adjustable type. Cat Part No : 420055 of Legrand make or equivalent Siemens/Hager/Schneider - 03 Nos (c) MCCB 63 Amps 16 Ka 4 Pole, 415V, thermal & megnatic adjustable type of capacity 63 Amps, Cat Part No : 420013 of Legrand make or equivalent Siemens/Hager/Schneider - 03 Nos (d) PCC foundation ( 1:2:4)grading=(1.5x1.5x0.5) CUM. OUTGOING :- (a) MCCB 160 Amps, 4 pole, breaking capacity 25 KA at 415 volts , 25 HZ, thermal & megnatic adjustable type.Cat Part No : 420097 of Legrand make or equivalent Siemens/Hager/Schneider - 03 Nos (b) MCCB 100Amp, 25KA, 4 P, 415 V, thermal & megnatic adjustable type. Cat Part No : 420055 of Legrand make or equivalent Siemens/Hager/Schneider - 03 Nos (c) MCCB 63 Amps 16 Ka 4 Pole, 415V, thermal & megnatic adjustable type of capacity 63 Amps, Cat Part No : 420013 of Legrand make or equivalent Siemens/Hager/Schneider - 03 Nos Note :- Cable glands should be provided for all incoming /outgoing connections. 1 Each
72 68 M & L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60cm x 6.0mm thick buried directly in ground vertically to a depth not less than 2.25 mtr below ground level with top edge of the earth plate not less less than 1.5 mtr below normal ground level and connected to earth plate 32mm x 6mm thick by means of bolts, nuts etc surrounded by 15 cm thick packed layers of charcoal dust and common salt and protected by galvanized iron or steel pipe light grade 40mm bore and water pipe 20mm bore GI light grade with funel and connecting to test point including construction of chamber in cement concrete 1:3:6 type C-2 and RCC cover provn of test point and all as shown in electric plate No 3 of MES Sch Part I of 2009. Including dismantling/taking out old earthing with all accessories complete. \nNOTE:- RCC pit cover shall be pre-cast of RCC (1:2:4) type, B-1 80mm thick reinforced with XPM weighting not less than 4 Kgs/Sqm in lieu of CI cover. 4 Each
73 69 Supply installation commissioning and testing in wall split units indoor and outdoor complete with cordless remote control unit and with in built air ioniser and plasma filter for better indoor air quality with minimum 5 star rated EER 3.2 capacity 1.5 ton complete all as specified and directed 9 Each
74 70 Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled outdoor type and designed for input variation between 160 V to 270 V with output voltage stablized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA all as required including necessary connections complete all as specified and directed. Make : V GUARD (Model No. VND500)/ BLUEBIRD (Model No. BA514A) or equivalant 9 Each
75 71 S&F sheet metal enclosure with socket and plug top and MCB single pole and neutral enclosure with two pin and earth plug and socket complete with one single pole MCB, 240 V 20 Amp. 2 Each
76 72 M&L for laying of copper tubing of dia 1/2" including insulation with heavy duty rubber foam and brazing work completed all as specified and as directed by engineer-in-Charge 35 RM
77 73 M&L for laying of copper tubing of dia 1/4" including insulation with heavy duty rubber foam and brazing work completed all as specified and as directed by engineer-in-Charge 35 RM
78 74 S&F 3 core flexible copper cable of size 4 Sqmm complete all as specified and as directed by Engineer-in-Charge 48 RM
79 75 S&F low density polyether pipe (LDPE) of pressure rating 6Kg/cm2 drain pipes of size 20mm from indoor unit to exist point as per design including accessories clamps fastners complete all as specified and as directed by Engineer-in-Charge 50 RM
80 76 M&L of Sub main wiring with 2 single core 4 Sqmm PVC unsheathed and PVC insluated stranded copper conductor cable in and including rigid 20 mm dia PVC conduit and 2.5 sqmm PVC insulated unsheathed contineous earth wire and connected to earth dolly and making good disturbed surfaces with cement mortar and paint to match existing surface complete all as specified and directed. 40 RM
81 77 M&L for laying of copper tubing of dia 5/8" including insulation with heavy duty rubber foam and brazing work completed all as specified and as directed by engineer-in-Charge 8 RM
82 78 M&L for laying of copper tubing of dia 3/8" including insulation with heavy duty rubber foam and brazing work completed all as specified and as directed by engineer-in-Charge 8 RM
83 79 M&L for utdoor unit stand for wall mounting type or floor mounted complete factory made as recommended for make Air conditioner and approved by Engr-in-Charge 2 Each
84 80 M&L of Sub main wiring with 2 single core 4 Sqmm PVC unsheathed and PVC insluated stranded copper conductor cable in and including rigid 20 mm dia PVC conduit and 2.5 sqmm PVC insulated unsheathed contineous earth wire and connected to earth dolly and making good disturbed surfaces with cement mortar and paint to match existing surface complete all as specified and directed. 40 RM
85 81 M&L for Shifting and refixing of split type AC (Indoor and Outdoor units) of any make and any type after servicing and charging of gas (M410a/R134a/R-22/r32) by testing the leakage in system and reparing of leakage if any by gas welding work, cleaning and flushing out the complete system with gas, supply and replacing of drier/filter, making the complete system leak proof, cacuuming the system as existing and testing etc complete all as specified and directed. Note : (a) : Dismantling and refixing of split AC are including in quoted rate. (b) Drier capillary, copper tubing, refrigernt gas, Insulation and LDPE pipe are inclusive in quoted rate. (c) Making hole and filling the hole & Make good the disturbed surface with existing colour matching are inclusive in quoted rate. 7 Each Job
86 82 S&F snap on truking 50x 105, 1 compartment with duct cover on wall for copper tubing of AC including accessories clamps fastners complete all as specified and as directed by Engineer-in-Charge 12 RM
87 83 Note :- Credit shown in credit schedule of tender document shall be considered by the tenderer while quoting the rates of various items of this schedule. The same shall be recovered from various payment to contractor before handing over old material.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2021 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail