Medical Gas Pipeline System And Equipments Supplying, Installation, Testing And Commissioning Of Medical Gas Pipeline System And Equipments For Upgradation From 100 To 150 Bedded Esic Hospital At Asansol, West Bengal., ESIC HOSPITAL AT ASANSOL, WEST BENGAL.-West Bengal

Hindustan Prefab Limited has published Medical Gas Pipeline System And Equipments Supplying, Installation, Testing And Commissioning Of Medical Gas Pipeline System And Equipments For Upgradation From 100 To 150 Bedded Esic Hospital At Asansol, West Bengal.. Submission Date for this Tender is 17-06-2021. Medical Gas System Tenders in ESIC HOSPITAL AT ASANSOL, WEST BENGAL. West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

28054058
Corrigendum : Medical Gas Pipeline System And Equipments Supplying, Installation, Testing And Commissioning Of Medical Gas Pipeline System And Equipments For Upgradation From 100 To 150 Bedded Esic Hospital At Asansol, West Bengal.
Open Tender
Indian
West Bengal
ESIC HOSPITAL AT ASANSOL, WEST BENGAL.
17-06-2021

Tender Details

Medical Gas Pipeline System And Equipments Supplying, Installation, Testing And Commissioning Of Medical Gas Pipeline System And Equipments For Upgradation From 100 To 150 Bedded Esic Hospital At Asansol, West Bengal.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 10-Jun-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 17-06-2021

Key Value

Document Fees
INR 5900 /-
EMD
Refer document
Tender Value
Refer document

BOQ Items

Name of Work: SUPPLYING, INSTALLATION, TESTING AND COMMISSIONING OF MEDICAL GAS PIPELINE SYSTEM AND EQUIPMENTS FOR UPGRADATION FROM 100 TO 150 BEDDED ESIC HOSPITAL AT ASANSOL, WEST BENGAL.
Sl. No. Item Description
1Part - A : Medical Gas System. Supply, Installation, Testing, Commissioning and Handing Over of Medical Air Compressor unit of 4 Nos (in quadraplex system as per HTM/NFPA) non lubricated reciprocating air cooled air compressors ( Ingersoll Rand,Anestiwata, Hitachi, Kirloskar Make) with60CFMrefrigerant typeairdrier with Prefilter, Afterfilter,15HP TEFCcagemotors,drivepackage, suction air filters,starter, mountingbase framecompletewith Air colled aftercooler, Pressure Reducing Station.The operation ofthe compressors shallbe havingautocutoffsystemaccordingto the presetpressures for the lower and upperlimit.The system shall have all the necessary controls like pressureswitches,reliefvalves,etc. including Supply, Installation, testing, commissioningandhandingover of Airreceiver forthe above compressors with a storage volume of 3000 ltrs at NTP conditions.
2Duplex ThreestageBreathingAirFiltrationSystemwithBypass pipeline system & Isolation Valves.
3SITC ofTriplex MEDICAL VACUUM SYSTEM.The package shall consist of Reciprocating Vacuum pumps ( including civil foundation and electrical wiring of suitable capacity from Pump to electrical panel and non return valve complete ) with suitable hp motor. The vacuum pump, motor and associated accessories as required shall be supplied as a package by the manufacturer, and not as discrete items. completee system are as per specification
4Duplex BacterialFilterVacuum withBy pass pipeline system with Isolation valves. As per specification
5Supply, Installation,Testing,Commissioningand Handing over of Oxygen Manifold comprising of 2 x 10 Oxygen cylindersin the mainmanifold and 2 x 4 cylinders in theemergencymanifold with Piston type Heavy duty, High flow Oxygen Regulator.
6S.I.T.C of ImportedCE Marked compliant with HTM or NFPA Oxygen Change-Over Reduction Box (Automatic Control Panel) of Digital fully Automatic type, capable of switching from “Bank in Use” to “Reserve Bank” without fluctuation in delivery line pressure and without the need for external electrical power. The Changeover panel shall be rated for min. 175 QMH at 400 kPA, and shall include the following accessories. Panel shall comply with HTM/NFPA& as per specification.
7Supply, Installation, Testing, Commissioning and Handingoverof NitrousOxideManifold comprising of 2 x 3 N2Ocylinderinthe main manifoldwith a 2 cylindersintheEmergency manifold.
8S.I.T.C of Imported CE marked Nitrous Oxide Change-Over Reduction Box (Automatic Control Panel conforming to HTM/ NFPA ) of Digital fully Automatic type, capable of switching from “Bank in Use” to “Reserve Bank” without fluctuation in delivery line pressure and without the need for external electrical power. Product should be as per specification.
9AGSS System consisiting of Duplex, Skid Mounted AGSS Pumps with RemoteSwitches - AGSS Simplex Start Switch. As per specification
10Plant/Master Gas Alarm:- S.I.T.C. of ImportedCE marked (with CE Number) Master Gas Alarm for 4-gases conforming to HTM/NFPA. This panel shall be able to test Short Circuit Fault, Open Circuit Fault, Source Equipment Fault and include thea) Duall Circuit LED Indicators. b) Test facility to check LEDc) Test facility to check LED Integrity. Panel shall be equipped with Micro-procesor based alarm. product should be as per specification.
11Supply, Installation,Testing,Commissioningand Handingoverof Solid drawncopperpipesmanufactured asperBS2871-EN 13348/ ASTM B819duly certifiedby LLoydsor third party inspection agency withall necessaryfittings, pipesupports, etc complete. as per specification
12a). 12 mm OD x 0.6 mm thk
13b). 15 mm OD x 0.9 mm thk
14c). 22 mm OD x 0.9 mm thk
15d). 28 mm OD x 0.9 mm thk
16e). 42 mm OD x 1.2 mm thk
17f). 54 mm OD x 1.2 mm thk
18SITC of gas lockable Area Valve Service Units with integrated alarm system as per specifications, and as required. Product should be as per specification. Must have Gas Pressure alarm facility LED digital display, audio visual feature. Must have emergency feed facility in case of shutdown for intrepted supply. SS sheet construction, CE certified/UL Listedwith relevant notified no. on it as required, entry/ exist of gases from upward direction as per specification (Imported)
19a). 5 Gas Service
20b). 4 Gas Service
21c). 3 Gas Service
22c). 2 Gas Service
23Supply, Installation, Testing, Commissioning and HandingoverofIsolation Ballvalvesfor thepipelines complete withsupports,etc.These quantities donotincludethe valves inthe equipment room,which shall bequoted as included in the equipment as specified above.
24Supply,Installation,Testing,Commissioningand Handingover of Gas outlets Points as per latest standard & specification (Imported)
25a). Oxygen Outlet
26b). Nitrous Oxide Outlet
27c). Compressed Air Outlet ( 4 Bar )
28d). Compressed Air Outlet ( 7 Bar )
29e). Vacuum Outlet
30f). AGSS Outlet
31Electrical ControlPanelEquippedalongwith Duplex & Cascade system for Air compressor & vacuum Pump System
32MEDICALGAS BSYSTEM:
33Supply,Installation,Testingandcommissioning etcasrequiredfor Medical Call System:
34Part-B:PipelineAccessories. Back pressure Compensated Oxygen flowmeters witha range of 0 - 15 LPM. The body shallbe madeof brass and chromium plated. The flow tube shall be of clear,impactresistant polycarbonate.The humidifiersbottles shall bemadeof breakable polycarbonate andareautoclavableat121 Deg C. The metersand humidifiersshallbe suitable for the outlets offered as per specification.
35WardVacuumUnits withunbreakablecollectionjars and regulators.The unit shall besuppliedwith vacuumguageto indicate the suction supplied to the unit. The unit shall have abracketforwall mounting.The600 ml jars shall be made of unbreakablepolycarbonate and are autoclavable at 121 Deg C as per specification.
36Theatre Vacuum Units on mobile trolleys with twin2000mlunbreakable bottles made of polycarbonate,autoclavable at121 DegC. Theunit shall be supplied with a regulatorwith instant ON/OFF switch and three wayselection to use the left, right or both thebottles. The completeunit shall be mounted on a trolley with castor wheels as per specification.
37Antistatic HP Tubing for connection (5 Mtr.) according to specific color coding and MGPL standard as required.
38a) HP Tubing for oxygen conversion Kit
39b) HP Tubing for Nitrous Oxide conversion Kit
40c) HP Tubing for Medical Air conversion Kit
41d) HP Tubing for Vacuum conversion Kit
42Part -C:BedHeadWallPanels 1 meter length Supply, installation and providing wiring and piping connectionsfor bedheadwall panels. The panel shall be fabricated out of high strengthsextruded alluminium sections with inbuilt single railing and powder coated tocolor aspertheOwnerschoice.Thepanel shallhave facility to accomodate :Max. 5 nos ofGas outlets,5/15 A multipin switchedsocketoutlets- 4 nos,1 no Nursecallswitchpanelwithwired remote, 1 no arm lamp 60Wwithadaptor,1noInfusionpumprail mount polewithadaptor,1noIVtreerailmountwithadaptor andholderfor vacuum collection jarTo be included with OT Equipments
43Providing and fixing Adaptor or Probe of BS Type Oxygen Gas Outlet/Terminal:
44Providing and fixing Adaptor or Probe of BS Type Vacuum Gas Outlet/Terminal:
45Providing and fixing Adaptor or Probe of BS Type AGSS Gas Outlet/Terminal:
46Providing and fixing AGSS Receiving System: Balancer / Receiver Unit along-with connecting hose for Anaethesia Machine to Receiver and from AGSS Outlet to Receiver Unit.
47Low-Pressure Tube For Vacuum / Suction Unit/Accessories.
48Providing and fixing of 5 amp Switch with Modular Plate
49Providing and fixing Blanker Plate
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail