| 1 | 1 | Supply of Ex Proof Resistive Capacitive type earthing relay of approved make as per technical specifications mentioned in the tender document in PESO / CCOE approved FLP enclosure for usage in Zone 1 (Hazardous Area Classification as per IS 2148).\nFlameproof cum weather proof smart type Grounding unit (Resistive Capacitive type earthing relay) shall have Red and Green indicating lamps and dual output for safety earthing of tank trucks, suitable for giving safety interlocking signal as per specifications and datasheet. | BI01010001010000000000000515BI0100001111 | 8 | ea |
|---|
| 2 | 2 | Supply of 1.1 KV LT XLPE PVC Sheathed HR copper / aluminum Power Armoured cables of following sizes as per IS:7098 Part-I. 4Cx2.5 sqmm (2XWY) for Power / Signal | BI01010001010000000000000515BI0100001112 | 800 | m |
|---|
| 3 | 3 | Supply of 1.1 KV LT XLPE PVC Sheathed HR copper / aluminum Power Armoured cables of following sizes as per IS:7098 Part-I.1Cx16 (A2XY) (Aluminum) for earthing | BI01010001010000000000000515BI0100001113 | 120 | m |
|---|
| 4 | 4 | Supply of 4 way FLP Enclosure of approved make duly approved by PESO for usage in Hazardous Area - Zone I with PESO Approved FLP Glands of suitable size, complete as required for termination of cable inside enclosure. FLP enclosure should of size for housing 1 SMPS inside the enclosure for supply of DC power to Earthing Relay. 1 Such enclosure shall be required for each bay. Supply of 8 Nos. SMPS of adequate rating for supply of 24 Volt DC output to Earthing Relay for each bay shall be under scope of Contractor. | BI01010001010000000000000515BI0100001114 | 8 | ea |
|---|
| 5 | 5 | Supply of GI Cable trays of size: 100 mm width | BI01010001010000000000000515BI0100001115 | 130 | m |
|---|
| 6 | 6 | Supply of GI Cable trays of size: 200 mm width | BI01010001010000000000000515BI0100001116 | 130 | m |
|---|
| 7 | 7 | Supply of ROV(Ball Valve + Pneumatic Actuator + Solenoid Valve + Required accessories), 2\" 300# RF, A216 WCB, SS316 Ball material, Wetted parts: SS316, Class VI, Fire safe, hand wheel, 1 SOV, 1 AFR as per specifications and data sheets given. | BI01010001010000000000000515BI0100001117 | 16 | ea |
|---|
| 8 | 8 | Supply of Weld Neck Raised face flane WNRF A 105 CS , Class 300, Sch 80 - 50 mm | BI01010001010000000000000515BI0100001118 | 32 | ea |
|---|
| 9 | 9 | Supply of Metal Gasket 50 mm size class 300 | BI01010001010000000000000515BI0100001119 | 75 | ea |
|---|
| 10 | 10 | Supply of Elbow 50 mm seamless class 300. (For extension of LPG pipeline at TLD Bay) | BI01010001010000000000000515BI0100001120 | 16 | ea |
|---|
| 11 | 11 | Supply of GI ERW PIPE HEAVY AS PER IS 1239 PT 1- 15 mm | BI01010001010000000000000515BI0100001121 | 250 | m |
|---|
| 12 | 12 | Supply of GI ERW PIPE HEAVY AS PER IS 1239 PT 1- 25 mm | BI01010001010000000000000515BI0100001122 | 150 | m |
|---|
| 13 | 13 | Supply of GI Tee 25 mm | BI01010001010000000000000515BI0100001123 | 10 | ea |
|---|
| 14 | 14 | Supply of CS seamless pipe size 50 NB (Class 300, sch 80) | BI01010001010000000000000515BI0100001124 | 15 | m |
|---|
| 15 | 15 | Supply of GI Elbow Heavy duty socket 25mm | BI01010001010000000000000515BI0100001125 | 40 | ea |
|---|
| 16 | 16 | Supply of Janatics 5/2 hand lever valve | BI01010001010000000000000515BI0100001126 | 16 | ea |
|---|
| 17 | 17 | Horizontal and vertical laying of XLPE / PVC insulated armoured and PVC sheathed cables 1.1 KV grade of the following sizes in readymade concrete or soil trenches, trays, risers, support hangers, saddles etc., pulling through pipe on walls, floors and columns, steel structures including transportation from stores to site, unpacking, erection, dressing including supply and fixing of aluminum tags for identification of cable at both ends and at every 30 meter interval, providing GI saddles, saddle bars GI / Al clamps for cables laid vertically on walls / column / structures etc., GI bolts, nuts and washers, lugs of appropriate size etc., complete with all labour, material and as per specification enclosed and direction of site in-charge, excluding\nsupply of cables. Item also includes laying and fixing of supplied cable trays wherever required complete as per instructions of LIC.: 4Cx2.5 sqmm (2XWY) | BI01010001010000000000000515BI0100001127 | 800 | m |
|---|
| 18 | 18 | Horizontal and vertical laying of XLPE / PVC insulated armoured and PVC sheathed cables 1.1 KV grade of the following sizes in readymade concrete or soil trenches, trays, risers, support hangers, saddles etc., pulling through pipe on walls, floors and columns, steel structures including transportation from stores to site, unpacking, erection, dressing including supply and fixing of aluminum tags for identification of cable at both ends and at every 30 meter interval, providing GI saddles, saddle bars GI / Al clamps for cables laid vertically on walls / column / structures etc., GI bolts, nuts and washers, lugs of appropriate size etc., complete with all labour, material and as per specification enclosed and direction of site in-charge, excluding\nsupply of cables. Item also includes laying and fixing of supplied cable trays wherever required complete as per instructions of LIC.: 1Cx16 (A2XY) (Aluminum) | BI01010001010000000000000515BI0100001128 | 120 | m |
|---|
| 19 | 19 | Welding of supplied WNRF 300# Sch 80: Job includes welding, cutting, fitting & erection of pipes, fittings, flanges, nut , studs, gaskets etc. Transportation from OWNER/ VENDOR’S stores/storage points to shop/site, installation in position by threading, bolting or welding as per drawings, specifications, standards/ codes, instructions of Owner /Owner's representative and scope of work along with supplying and fixing of Metallic Spiral Wound gaskets (with 100% spare quantity for replacement after hydrotesting) confirm to SS 316 with Graphite fill as per ASME B16.20, nuts & stud bolts confirm to ASTM A194-2H & ASTM A193B-7 respectively. Rates shall also include the cost of supply of stud nuts, washers, gaskets, supervision, labor, overhead /profits, materials in Vendors scope, Hydrostatic testing of spool pieces before installation wherever required and other associated arrangements required to execute all the related activities. Rates shall be inclusive of cost of supervision, labour, overheads/profits, material which are in vendor's scope, consumables, conditions listed in preamble / scope of work and other associated arrangements required for the work to be completed as per the existing site conditions including the shut down jobs in a working / operating LPG Plant. Shifting, positioning, cutting pipe line as necessary, laying the pipelines above ground at all elevations, manifold connections to existing manifolds / pipelines as per the tentative layout and welding, handling laying with flanges, bends, elbows, tees, reducers etc. aligning the pipeline as per good engineering practices and instructions of IOCL. This item also includes supply and erection of studs, washers, nuts and gaskets, bonding jumpers of 30 mm wide 6 mm thk GI strips. Note: Required Electrical power and water shall be arranged at one place and it's successful bidder's responsibility to lay required cables / hoses / pipes etc., as required for the work. | BI01010001010000000000000515BI0100001129 | 64 | SU |
|---|
| 20 | 20 | Erection of supplied ROVs with all electrical, pneumatic and flange connections complete. | BI01010001010000000000000515BI0100001130 | 16 | SU |
|---|
| 21 | 21 | Radiography of all the joints | BI01010001010000000000000515BI0100001131 | 32 | SU |
|---|
| 22 | 22 | Above Ground Laying of GI pipe of size upto 40 mm with fittings, Job includes Fabrication, Welding & testing including surface preparation according to standard SSPC ST2 and painting with 2 coats of Red oxide Zinc phosphate with 2 coats of aluminum finish paint as per IOCL specification | BI01010001010000000000000515BI0100001132 | 250 | m |
|---|
| 23 | 23 | Excavation & back filling for Cable | BI01010001010000000000000515BI0100001133 | 500 | m |
|---|
| 24 | 24 | Supply, cutting, welding, fabrication and erection in place for structural steel stands, brackets etc., for installation of JBs, Cable Trays, etc., as per instructions of EIC complete with fasteners, anchor bolts etc., as required for erection of stands / brackets. | BI01010001010000000000000515BI0100001134 | 500 | kg |
|---|
| 25 | 25 | Testing and commissioning of entire earthing system complete for the TLD Gantry of 8 Bays, along with of cable trays inside and outside TLD Bays up to ROVs, fixing and laying of supplied cable trays complete as per instructions of site engineer.\nThe item also includes fixing FLP Glands, supply and providing PESO approved FLP dummies of required size of unused cable entries in FLP JBs, termination of cables / wires, earthing for the JBs as per instruction of EIC with the nearest earth bus bar. | BI01010001010000000000000515BI0100001135 | 1 | SU |
|---|
| 26 | 26 | Providing & Termination of 1.1 kV grade armoured cable for 2 Core X 4 sqmm including supply of FLP heavy duty double compression cable gland. Baliga/FEPL/CEAG-FCG/Flexpro make, crimping lugs and allied jointing material etc. all complete as per direction of Engineer in charge. Copper lug for copper cable and aluminum lug for aluminum cable | BI01010001010000000000000515BI0100001136 | 100 | SU |
|---|