}

Electric Sub Station Work For 128 Slice Ct Scan Machine At Jln Hospital , Ajmer, Ajmer-Rajasthan

Public Works Department-PWD has published Electric Sub Station Work For 128 Slice Ct Scan Machine At Jln Hospital , Ajmer. Submission Date for this Tender is 08-06-2021. Electrical Substation Tenders in Ajmer Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

28033936
Electric Sub Station Work For 128 Slice Ct Scan Machine At Jln Hospital , Ajmer
Open Tender
Indian
Rajasthan
Ajmer
08-06-2021

Tender Details

Electric Sub Station Work For 128 Slice Ct Scan Machine At Jln Hospital , Ajmer

Key Value

Document Fees
INR 500 /-
EMD
Refer document
Tender Value
Refer document

BOQ Items

Name of Work: Electric Sub Station Work for 128 Slice CT Scan Machine at JLN Hospital, Ajmer
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply &abfrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001113 450 Kg
2 2 Earth work in excavation / by mechanical means (Hydraulic Excavator) / manual means over areas (exceeding 30 cm in depth, 1.5m in width as well as 10 sum on plan) including disposal of excavated earth, lead upto 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed: BI01010001010000000000000515BI0100001114 30 Cum
3 3 Random Rtounbebles masonry for with hard stone in foundation and plinth in Cement Sand mortar above 30 CM thick wall in: BI01010001010000000000000515BI0100001115
4 3.1 Cement Mortar 1:6 ( 1-Cement : 6-Sand). BI01010001010000000000000515BI0100001116 40 Cum.
5 4 Providing anyidngl in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - All work up to plinth level. BI01010001010000000000000515BI0100001117
6 4.1 M10 grade Nominal Mix\n1: 3: 6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size). BI01010001010000000000000515BI0100001118 5 Cum
7 5 Plaster new surface on wall in cement sand mortar 1:3 including racking of joints etc. complete fine finish : BI01010001010000000000000515BI0100001119
8 5.1 25 mm thick BI01010001010000000000000515BI0100001120 40 Sqm.
9 6 Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS C class pipes conforming to IS 3589 / 1239 part-I for hydrent and sprinkler applications including cutting, screwing, welding etc & malleable iron fittings like elbows, tees, flanges, tapers, reducer, with compressed asbestos gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts as per approved spacing. complete with painting of one coats of Red Oxide and two or more coats of synthetic enamel paint of Post office red shade complete as required.Complete installtion shall be pressure tested at 14kg/sqcm for 24 hr as per practice complete in all respect. Appropriate Test Certificate/ report of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001121
10 6.1 80 mm dia BI01010001010000000000000515BI0100001122 90 Mtr.
11 7 Providing & Fixing of 240/415 V AC MCB with positive isolation of breaking capacity not less than 10 KA (B/ C tripping characteristic as per type of load and site requirement) 4KV impulse withstand voltage, as per PWD specification for electrical Works with ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum, energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm., conductorline load reversibility, label holding facility, IP 20 contact protection and fitted with existing distribution board/sheets, min. operation 20,000 upto 32 A rating and 10,000 upto 63 A, 5000 for 80 A rating including making connections, testing etc. as required. . OEM shall have submit NABL / CPRI / ERDA accrediated lab test reports before execution & All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A"attached with this BSR . BI01010001010000000000000515BI0100001123
12 7.1 Single pole MCB 3 A to 5 A rating BI01010001010000000000000515BI0100001124 6 Each
13 7.2 Triple pole MCB 40 A rating BI01010001010000000000000515BI0100001125 10 Each
14 8 Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar as per PWD specification for electrical Works, by means of SMC / DMC type insulator, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001126
15 8.1 Electrolytic grade Aluminium bus bar 6010 grade BI01010001010000000000000515BI0100001127 120 Kg.
16 9 Providing & Fixing of IP 51 ( upto n50ge0) V rangge Volt meter on existing panel as per PWD specification for electrical Works, making connection by PVC insulated copper conductor with PVC sleeves / channel etc. Meter shall give true RMS measurments, acc. CI 1.0 or better , with field programmable primary & sec. values PT(VT) primary upto 2000 KV. Field-programmable high and low threshold values, meter shall compliance of IS 13875 & IEC 61236. as required. OEM Must have BIS certificate and & shall have submit NABL / CPRI / ERDA lab test reports before execution & All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001128
17 9.1 Digital type BI01010001010000000000000515BI0100001129 2 Each
18 10 Providing & Fixing of CT operated direct reading t-ype IP 51 Ampere meter on existing panel as per PWD specification for electrical Works, making connection by PVC insulated copper conductor with PVC sleeves / channel etc. Ampere meter shall give true RMS measurement, Acc. Cl 1.0 or better , Measuring current range 50 mA to 6 A, with Field- programmable primary and secondary values CT primary up to 15000 A, Field-programmable high and low threshold values as required. compliant to IS 13875, & IEC 61326. OEM Must have BIS certificate and & shall have submit NABL / CPRI / ERDA lab test reports before execution &. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001130
19 10.1 Digital type Confirming to IEC 62053-21 Below 500 A BI01010001010000000000000515BI0100001131 2 Each
20 11 SITC of wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as per PWD specification for electrical Works, made out of CRCA sheet . Other parameters required as per point (a) ,(b), (c),(d) below:- BI01010001010000000000000515BI0100001132
21 11.1 (a)Thickness of sheet shall not be less than m1.6 m up to 600 mm length / width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required . Side walls and cable alley compartments having bolted type doors with / without detachable extension type structure BI01010001010000000000000515BI0100001133
22 11.2 (b)panel shall be duly treated for derusting in n7kta process with dephosphating and with powder coating of minimum 70 microns on both side of panel in desired shade The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware, separate detachable gland plate M.S. base channel (min75mm) , hinged door with locking arrangement for equipment/switchgear BI01010001010000000000000515BI0100001134
23 11.3 [c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 125 amp ) and by solid bus bar (>125 amp ) . All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. BI01010001010000000000000515BI0100001135
24 11.4 (d) only outer area on all sides shall beaesumred & panel to be fabricated only from CPRI approved fabricator. All as per drawing pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001136 30 SQ.Mtr.
25 12 Providing & Fixing of BIS approved Current Transformer as per PWD specification for electrical Works ,ISI marked as per IS 2705-1992/ conforming to IEC 60044-1, with secondary terminal of CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as required Current transformer Resin Cast Wound Primary / Ring Type Tape Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001137
26 12.1 C T Class 1, Ratio upto 150/5, Burden 5 VA BI01010001010000000000000515BI0100001138 3 Each
27 12.2 C T Class 1, Ratio 200/5 to 300/5, Burden 10 VA BI01010001010000000000000515BI0100001139 6 Each
28 13 Providing & Fixing of ISO certified company made iUstLedl, IP 65 110/220 V, unibody LED Indicating lamp IEC 60947 , CSA 22.2 with integral circuit, IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 29 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001140
29 13.1 Red/yellow/Green colour BI01010001010000000000000515BI0100001141 16 Each
30 14 Multifunction LCD meter with V, I, F, PF, KW, Kva, Kvar, Kwh, Kvah, Kvarh, Run hours, On hours, Phase angle, Interrupts, THD, Events, Neutral Current class 1 accuracy with RS485 port. BI01010001010000000000000515BI0100001142 1 Each
31 15 Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 / 2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001143
32 15.1 3.3 KV, 2 mm thick with proof voltage V10 K / 3 min. and Break Down Voltage 30 KV BI01010001010000000000000515BI0100001144 4 SQ.Mtr.
33 16 Providing & Fixing of self healing IP20 MPP thyupnets capacitor (banks) as per PWD specification for electrical Works, ISI marked IS:13340-41 / conforming to IEC :831-1&2 OR IEC : 60831-1& 2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz and total wattage loss less than 0.35 Watt per KVAR. Min over current capacity\n1.8 times rated current & peak inrush current min. 250 times of rated current, including making connections, testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001145
34 16.1 Heavy duty Three phase 480 V, 50 Hz cylindrical capacitor (Bank) BI01010001010000000000000515BI0100001146 70 kVAR
35 17 Providing & Fixing of IP54 on front microprocessor bharesed three phase sensing power factor correction relay , IEC / EN 61000-6-(2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR, VTHD, ITHD, metering facility as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab test reports. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001147
36 17.1 12 to 14 stage BI01010001010000000000000515BI0100001148 1 Each
37 18 Providing & Fixing of ISO certified company made cmera operated rotary (Auto/manual) switches on existing panel with 2 way and off position using high grade engineering material to international standards with cam assembly insulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range -25 degree C to 55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour including making connection etc. as required . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001149
38 18.1 10 AMP BI01010001010000000000000515BI0100001150 4 Each
39 18.2 32 AMP BI01010001010000000000000515BI0100001151 6 Each
40 19 Providing & Fixing of 440 Volt 3 pole cAaCpacitor ( 6 B ) duty contactor with 3 no. early make and post break auxiliary contacts in series with quick discharge damping resistors/ reactors to limit the inrush current as per PWD specification for electrical Works, IS/IEC 60947-4-1 : 2000, insulation voltage 1000V, impulse withstand voltage 8 KV,Din rail mounting type including making connections, testing etc. as required. suitable for following capacity capacitor bank. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001152
41 19.1 up to 6 kVar BI01010001010000000000000515BI0100001153 4 Each
42 19.2 12.5 kVar BI01010001010000000000000515BI0100001154 6 Each
43 20 SITC of Draw out type 3/4 pole IP53, IK 08 door interlock Air Circuit Breaker (ACB) as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 in existing LT panel suitable for LT installation 440 V, 50 Hz and having adjustable over load short-circuit, earth fault and with separate LED indication for each type of fault , Password protected relase (trip mechanisum) shall confirm to EMI/ EMC test , LCD/LED display , Thermal memory , pollution degree 4, trip free mechanisum , suitable for ambient 50 degree and utilization catagary B. In built electrical & mechanical anti pumping fearute , 100% rated neutral . ACB shall have separate indication for service, test, isolation & maintenance position, Breaking capacity Icu = Ics = Icw ( 1 sec ) , U imp - 12 KV, break time not more then 25 ms. Provision for electrical & mechanical interlock between ACBs, Min.electrical operation 10,000 upto 2000 A rating and 5,000 for 2500 A. including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution & All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001155
44 20.1 800 A Rating , 50kA Microprocessor based release Draw out type (Manual spring charged) 4Pole BI01010001010000000000000515BI0100001156 1 Each
45 21 SITC of IP 40 quick make and quick break 4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings as per PWD specification for electrical Works, conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load inerchange ability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 800 V, provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections with lugs & spreaders, etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . With Thermal Magnetic release BI01010001010000000000000515BI0100001157
46 21.1 up to 100 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu BI01010001010000000000000515BI0100001158 4 Each
47 21.2 125 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics =100 % Icu BI01010001010000000000000515BI0100001159 5 Each
48 21.3 160 Amp, 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu BI01010001010000000000000515BI0100001160 3 Each
49 21.4 200 Amp , 35kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu BI01010001010000000000000515BI0100001161 3 Each
50 21.5 250 Amp , 35 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu BI01010001010000000000000515BI0100001162 3 Each
51 21.6 400 Amp ,50 kA, adjustable O/L & adjustable S/C setting, Ics = 100 % Icu BI01010001010000000000000515BI0100001163 2 Each
52 22 Supply and fixing of following accessories for Moulded case circuit breaker (MCCB) compatible to main MCCB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001164
53 22.1 Direct Rotary Handle BI01010001010000000000000515BI0100001165 20 Each
54 23 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-armoured / Armoured aluminium cable of 1.1 KV grade as per PWD specification for electrical Works in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench with filling of excavated earth in trench , on existing cable trays or on surface etc. including making necessary connection, testing etc. as required of size and as per points (a), (b), (c), mentioned below:- BI01010001010000000000000515BI0100001166
55 23.1 (a) Material :- H4- Grade aluminium conductor of purity >99.6 % & as per IS:1554 P-I / IS :7098 P - I BI01010001010000000000000515BI0100001167
56 23.2 (b) conductor shall have electrolytic aluminium confirming to IS 8130, IS 3975-1999 for armouring of cables in armoured cable items , IS 5831 for sheath, IS 10810 (Part 0 to 64 ) for testing procedures . BI01010001010000000000000515BI0100001168
57 23.3 (c) OEM Must have ISO 9001 & 14001 certifications for quality assuarance & its own in house NABL lab setup for all testing facilities for cables . Appropriate type test certificate / OEM test report shall be submitted . All above as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .\nArmoured Cable BI01010001010000000000000515BI0100001169
58 23.4 70.0 Sq. mm X 3.5 core BI01010001010000000000000515BI0100001170 15 Mtr
59 23.5 95.0 Sq. mm X 3.5 core BI01010001010000000000000515BI0100001171 35 Mtr
60 23.6 185.0 Sq. mm X 3.5 core BI01010001010000000000000515BI0100001172 35 Mtr
61 23.7 240.0 Sq. mm X 3.5 core BI01010001010000000000000515BI0100001173 35 Mtr
62 23.8 300.0 Sq. mm X 1 core BI01010001010000000000000515BI0100001174 400 Mtr
63 24 Supplying and making one end termination with heavy duty brass compression gland (as per IS 12943- 1990) SIBG type, heavy duty aluminium lugs (as per IS 8309 - 1993 & IS 8337-1976 ) duly crimped with crimping tool, PVC tape as per PWD specification for electrical Works etc for following size of Armoured PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required of size. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001175
64 24.1 3.5 x 70.0 sq.mm BI01010001010000000000000515BI0100001176 2 Each
65 24.2 3.5 x 95.0 sq.mm BI01010001010000000000000515BI0100001177 2 Each
66 24.3 3.5 x 185.0 sq.mm BI01010001010000000000000515BI0100001178 2 Each
67 24.4 3.5 x 240.0 sq.mm BI01010001010000000000000515BI0100001179 2 Each
68 25 Supplying and making end termination with heavy aluminium lugs Pin / ring type (as per IS 8309 -1993 & IS 8337-1976 ) duly crimped with crimping tool, PVC tape as per PWD specification for electrical Works etc of following size. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001180
69 25.1 300.0 Sq.mm BI01010001010000000000000515BI0100001181 32 Each
70 26 Providing & Laying XLPE insulated as per IS:7098/II/85 H.T.cable as per PWD specification for electrical Works for working voltage 11 K.V.(E) in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench with filling of excavated earth in trench , on existing cable trays or on surface etc. including making necessary connection, testing etc. as required of size as per points (a), (b), (c) mentioned below:- BI01010001010000000000000515BI0100001182
71 26.1 (a) Material :- H4- Grade aluminium conductor of purity>99.6 % & as per IS:1554 P-I / IS :7098 P - I BI01010001010000000000000515BI0100001183
72 26.2 (b) conductor shall have electrolytic aluminium confirming to IS 8130, IS 3975-1999 for armouring of cables , IS 5831 for sheath, IS 10810 (Part 0 to 64 ) for testing procedures BI01010001010000000000000515BI0100001184
73 26.3 (c) OEM Must have ISO 9001 & 14001 certifications for quality assuarance & its own in house NABL lab setup for all testing facilities for cables . All above as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001185
74 26.4 3 core 120.0 Sq.mm BI01010001010000000000000515BI0100001186 48 Mtr
75 27 Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit as per PWD specification for electrical Works suitable for 11 KV / 33 KV cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streight through joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Cross linking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. OEM test lab should be as per ISO 9001:2015 & 14001 : 2015 & reports submitted to engineer in charge including testing etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001187
76 27.1 3 core 120/150/185 Sq.mm\n11 KV End Termination Kit Indoor type BI01010001010000000000000515BI0100001188 4 Each
77 27.2 3 core 120/150/185 Sq.mm\n11 KV End Termination Kit Outdoor type BI01010001010000000000000515BI0100001189 4 Each
78 28 Plate Earthing as per PWD specification for electrical Works as per IS:3043 with copper Earth plate of size 600mm x 600mm x 3.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe, including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly- propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A"\nattached with this BSR . BI01010001010000000000000515BI0100001190 4 Set
79 29 SITC of chemical Gel earthing system of Dual Pipe Technology made of with "B" Class G I Pipe as per IS 1239 ( part-1):2004 of Medium duty of following sizes as per points mentioned (a), (b), [c), (d), (e) below :- BI01010001010000000000000515BI0100001191
80 29.1 (a) filled with anti corrosive conductive compounds with the permanent sealings at both the ends, CPRI/ ERDA tested with RMS capacity of minimum 35- 40 KA for withstanding 1 second. BI01010001010000000000000515BI0100001192
81 29.2 (b) To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated lab for low resistivity ( less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major content as per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts BI01010001010000000000000515BI0100001193
82 29.3 ©Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. BI01010001010000000000000515BI0100001194
83 29.4 (d) Testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book. BI01010001010000000000000515BI0100001195
84 29.5 (e) Self certificate for confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001196
85 29.6 With Pipe in Pipe Technology (Outer pipe dia. / Inner pipe dia. ) Minimum 100 mm dia borewell BI01010001010000000000000515BI0100001197
86 29.7 GI pipe 2000 mm long, 80 / 50 mm, Terminal 50mm x 6 mm GI Strip BI01010001010000000000000515BI0100001198 7 Set
87 30 Supply & Laying following size earth strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001199
88 30.1 25mm x 3mm copper strip BI01010001010000000000000515BI0100001200 10 Mtr.
89 30.2 32mm x6mm G.I. ( Hot Dipped ) Strip BI01010001010000000000000515BI0100001201 30 Mtr.
90 31 Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu thimble etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001202
91 31.1 10 SWG G.I. ( Hot Dipped ) Wire BI01010001010000000000000515BI0100001203 350 Mtr.
92 32 Supply & Laying following size' B ' class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001204
93 32.1 80 mm dia. BI01010001010000000000000515BI0100001205 3 Mtr.
94 33 Supply ,nIstallation, Testing and Comissioning of factory made 11 KV, 630 A, 20kA / 3 sec, Out door Extensible type IP54 for panel & IP67 for main circuits Ring main unit (RMU) IEC 62271-200 in suitable RCC foundation with 2 no. Load break switch & 1 no. VCB / SF6 circuit breaker with over load, Earth fault, short circuit relay, copper bus bar, bus support and insulation marerial epoxy resin,ring core protection & metering CT, Auxiliary relay for WTI, OTI, Bucholz alarm & trip along with annuciator panel, master trip relay, mechanical ON / OFF / Earth indication, Voltage presence indicator, Shunt trip coil, 24 V DC power pack, Digital multi function meter, with Bus PT panel with 3 Nos single phase voltage transformers of the ratio 11kV/v3 / 110 V/v3, 25 VA, Class 1.0 with HT fuses in the primary and MCB on the secondary side, Voltmeter with selector switch, R Y B phase indication, Anti reflex operating handle, right angle boots etc. OEM Must have BIS certificate and & shall have submit NABL / CPRI / ERDA lab tpye test reports before execution as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001206 1 Set
95 34 SITC of star rated Aluminium wound distribution Transformer of following rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11,ONAN Cooled & as per BEE star level- 2 & BIS approved as per IS 2026- 1977 & losses as defined as per IS 1180 part I 2014. including standard accessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cable boxes, temperature rise in winding/oil 35-40 degree C upto 200 KVA & 40-45 degree C for above 200 KVA, ISI marked drain valve, Dial type Temperature gauge, first filling of transformer oil as per IS :335-1953, Epoxy based paint, including carrying of pre-commission Testing & Charging of Transformer complete in all respect .NABL accredeated / CPRI/ ERDA lab testing reports with OEM certificate must submitted to engineer in charge .Transformer must be tested from CTL test lab of discom (if reqd.) before charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, CTL testing charges & Inspection charges shall be reimbursed by the department to the contractor as per actual expenditure. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001207
96 34.1 250 KVA with Off -LTC (+5% to - 10% @ 2.5%) BI01010001010000000000000515BI0100001208 1 Each
97 35 Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001209
98 35.1 300mm x 50mm x 1.6mm BI01010001010000000000000515BI0100001210 30 Mtr
99 36 Providing & Fixing of ISI marked (IS : 4985 - 2000) Hard rigid PVC 25mm drain water piping with fittings like elbow, soket, Tee etc & support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . BI01010001010000000000000515BI0100001211 45 Mtr.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail