Repair Maintenance Of Lt Feeder Pillar Lt Panels Earthings Lt Cable Apfc Panels Alongwith Connected Items At Af Stn Gurgaon Under Age Em Af Gurgaon Of Ge Af Gurgaon, GE (AF) Gurgaon-Haryana

Military Engineer Services-MES has published Repair Maintenance Of Lt Feeder Pillar Lt Panels Earthings Lt Cable Apfc Panels Alongwith Connected Items At Af Stn Gurgaon Under Age Em Af Gurgaon Of Ge Af Gurgaon. Submission Date for this Tender is 17-06-2021. Feeder Pillar Tenders in GE (AF) Gurgaon Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

27946740
Corrigendum : Repair Maintenance Of Lt Feeder Pillar Lt Panels Earthings Lt Cable Apfc Panels Alongwith Connected Items At Af Stn Gurgaon Under Age Em Af Gurgaon Of Ge Af Gurgaon
Open Tender
Indian
Haryana
GE (AF) Gurgaon
17-06-2021

Tender Details

Repair Maintenance Of Lt Feeder Pillar Lt Panels Earthings Lt Cable Apfc Panels Alongwith Connected Items At Af Stn Gurgaon Under Age Em Af Gurgaon Of Ge Af Gurgaon

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 02-Jun-2021 Amendment Other 10-06-2021
2 10-Jun-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 17-06-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 82000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work : REPAIR/MAINTENANCE OF LT FEEDER PILLAR, LT PANELS, EARTHINGS, LT CABLE, APFC PANELS ALONGWITH CONNECTED ITEMS AT AF STN GURGAON UNDER AGE E/M (AF) GURGAON OF GE (AF) GURGAON
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Isolate/de-energize the supply to the LT Panel Board of capacity ranging from 200 Amps to 2000 Amps and voltage 415 Volts/230 Volts, opening the doors/covers of the cubicle enclosure for carrying out the servicing/maintenance/repairs of the Panel Board, switch gear, metering etc and re-fixing the same in place after repairs including testing and commissioning of the paenl board comprising of the following.\n\n(a) Cleaning the inside switch gear chambers for removing dust, carbon and rusted surfaces including cleaning with blower and apply insulating varnish.\n\n(b) Check the condition of the DMC/SMC support insulators including cleaning applying Dr beck red for better IR values and replacement of insulators if required.\n\n(c) Tightening up of all bus bar connections, cable connections, replace bolt, nuts wherever required. \n\nNote Contractor has to inspect the site before quoting. Any modifications/frame work and renewal is deemed to be included in the quoted rates. Spares will be measured and paid under relevant items of schedule\n\n\n\n\n\n\n\n\n\n 7 Each Job
2 2 S&F in repair mild steel hinges suitable for LT panel board shutters incl welding, riveting complete all as specified and as directed. 8 Each
3 3 Disconnecting and taking down existing bus bars 4 wire system from LT panel board cleaning with CTC applying with becktol solution, removing old insulation and providing new heat shrink insulating sleeves, connecting and fixing in the same panel with new nuts, bolts, washers of suitable size complete all as specified and directed. 5 Each Set
4 4 Disconnecting and taking out old existing worn out control wiring connections incl cable lugs of LT panel board of 4 wire system and supply and connect with new cable PVC insulated, stranded copper conductor 2.5 sqmm incl new copper lugs and nuts, bolts, washers complete all as specified and directed. 4 Each Panel
5 5 Disconnecting and taking out old existing worn out cable lugs, nuts, bolts, washers etc from LT panel board of 4 wire system (incomming and outgoing) and supply and connect with new aluminium lugs and nuts, bolts, washers etc complete all as specified and directed. 6 Each Panel
6 6 Taking out old existing worn out neoprene gasket from shutters of LT panel board single door /double doors or openable on both sides and supply and fix new neoprene gasket complete all as specified and directed. 4 Each Panel
7 7 Excavation in trenches n exc 1.5 wide and n exc 1.5 m in depth for foundation etc or for laying cable etc n exc 10 Sqm on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and as directed. 590 Cum
8 8 Returning filling in including spreading, leveling, watering and well ramming in layers not exc 25 cm thick complete all as specified and as directed. 383 Cum
9 9 Removal of excavated material/surplus soil to a distance n exc 50m and depositing where directed at a level n exc 1.5m above the starting point complete all as specified and as directed. 207 Cum
10 10 Supply and filling river sand in trenches including spreading for cushioning of LT UG cable complete all as specified and as dirceted.\nNote : Punned down thickness shall be measured and paid . 178 Cum
11 11 M&L for sub class ‘B’ bricks old size laid flat dry in trenches over cable, across the direction of cable complete all as specified & directed . 15400 Each
12 12 Supply, laying and testing in replacement of cable XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 Volts grade cross sectional area 3.5 core x 300 Sq mm. complete all as directed.\nNote : Provision of suitable double crimpped lugs and glands shall deemed to be included in quoted rates. 80 RM
13 13 Ditto - all as per item No 12 described here in before but 3.5 core 240 sqmm 100 RM
14 14 Ditto all as per item No 12 described here in before but 3.5 core 185 sqmm 200 RM
15 15 Ditto all as per item No 12 described here in before but 3.5 core 120 sqmm 300 RM
16 16 Ditto all as per item No 12 described here in before but 3.5 core 95 sqmm 300 RM
17 17 Ditto all as per item No 12 described here in before but 3.5 core 70 sqmm 400 RM
18 18 Ditto all as per item No 12 described here in before but 3.5 core 50 sqmm 500 RM
19 19 Ditto all as per item No 12 described here in before but 4 core 25 sqmm 500 RM
20 20 Ditto all as per item No 12 described here in before but 4 core 16 sqmm 500 RM
21 21 Material and Labour for disconnection of LT Electric supply by taking proper shut down and removing old UNSV LT Fidder Pillar retrieved from existing location vide Ser item No 59 of DCS complete all as spfd and directed by Engr-in-Charge. 1 Each
22 22 Material and Labour for disconnection of LT Electric supply by taking proper shut down and removing old UNSV LT Fidder Pillar retrieved from existing location vide Ser item No 60, 61 of DCS complete all as spfd and directed by Engr-in-Charge. 2 Each
23 23 S&F ACB (air circuit breaker) draw out type of rating 800 Amps 4 pole, 50 KA, O/L, S/C, micro processor based release and cassette mounted horizontal draw out type fully interlocked cassette door automatic safety shutters, mechanical on and off indicators, service/test/isolated position with position indicators, provision of castell lock, with O/L, S/C with 3 CT's of standard ratings 4 blocks of 6 way sliding type LT disconnectors, error prevention plug, racking handle, safety shutters and painted with finished light grey shade as per IS:631 and as per IS 13947-2-1993 inclusive suitable length of bus bars complete all as directed. 1 Each
24 24 Ditto all as per item No 23 described here in before but 630 Amps 1 Each
25 25 S&F MCCB 400 A ,4 pole ,36 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as directed as per existing model/make. 2 Each
26 26 M & L for Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including using galvanised iron strip 32×6mm as earthing strip by means of bolts, nuts, check nuts and washers of galvanized iron or steel, earth plate surrounded by packed layer of char coal dust and common salt, 15cm thick all around bottom and top and watering pipe 20mm bore of GI light grade with funnel, wire mesh and 40 mm dia GI protection pipe medium grade all as shown in electrical plate No 3 of SSR Part-I and connected to earthing test point, main switch board and testing on completion including excavation, earth work concrete pit with 80mm thick RCC cover in RCC 1:2:4 type B-1 duly reinforced with MS bars 8mm dia @ 150C/C both ways and pit chamber in PCC 1:2:4 type B-1 with 2 Nos suitable lifting handles of 12mm MS bar complete all as specified and directed 8 Each
27 27 Supply and lay in trenches GI strip 25 mm x 4 mm galvanised iron strip for earth continuity earthing all as specified and directed 70 RM
28 28 M&L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as directed. 40 RM
29 29 Supply and lay in trenches /under roads/ crossing or fixed to wall/ pole, GI tubing light grade of size 40mm bore for protection of UG cables complete all as directed. 30 RM
30 30 Ditto all as per item No 29 described here in before but 80 mm 30 RM
31 31 M&L for defect rectification high tension or LT cable laid in trenches by locating fault with the help of electronic fault locating machine comprising of surge generator pulse, ECHO fault locator with high frequency distance calculator etc. including and additional excavation in normal alluvial strata required for exposing the cable fault ; removal of deteriorated portion of cable treating of cable and keeping the same ready for jointing work for cable of size up to 185 Sq mm three core. The fault locating equipments shall be brought to site within the hours of instruction from Engr-in-Charge as directed 20 Each
32 32 S&F in repairs/removing the UG cable for rectification of faults after fault detection excavating the area and Crimping with suitable ferrules/lugs or any other misc items providing suitable insulation tape and relaying complete after rectification of faults complete all as specified and as directed. Note: (i) Excavated area shall be made good to original finish and no extra payment shall be done on this account. The items like Lugs, Ferrules, nuts, bolts if any shall deemed to be included in the rates quoted and no extra payment shall be done on this account.\n(ii) Item No 31 & 32 shall be attended immediately on intimation by phone or SMS failing which an amount of Rs 5000/- per day after 2 days shall be recovered as penality. 20 Each
33 33 Supply and Fix in replacement of security Light for use on top of the watch tower cabin with motorised system: 400 W HPSV high intensity, long range, weather & dust proof motor operated Security Search light with highly polished stainless steel reflector-cum-body, suitable heat sinks, toughened front glass, retaining ring, M.S. Cradle and passivated bolts. The search light would be supplied with 230 V ,400 Watt HPSV Lamps with control gear in cast alumiminum housing, The search light fitting would be suitable for installing on the roof of the watch tower cabin. The search light would be swiveling type & have both vertical & horizontal operational controls with the help of remote control unit with suitable control cables complete all as specified and directed. Make:Kalin/Dragon/Superoptics sale. 2 Each
34 34 Dismantling and taking down existing LED light fittings with safty from pole bracket and refix the same on newly installed pole all as specified and directed at site. 10 Each
35 35 Dismantling concrete poles any size complete and setting aside complete all as directed.\nNote: "Hydra Crane Charges deemed to be included in the quoted rates". 10 Each
36 36 Supply, fixing and erection steel tubular swaged pole type 410SP-31(9 Mtr long) Swan neck complete with CI base plate,taper plug,bolts,nuts,and screws etc duly painted internally and externally with metal oxide anti corrosive paint before errection and painting with two coats aluminium paint after erection complete all as cofirming to IS 2713 (part-1 to 111) and complete all as specified and as directed.\nNote : Necessary earth work and concrete shall be measured and paid separately\n 10 Each
37 37 M&L for Foundation for Tubular swaged pole type including excavation , getting out, pole foundation with PCC (1:4:8) type D 2 (using with 40 mm graded crushed stone aggregate). Coping of pole with PCC (1:3:6) type C1 ( using with 20 mm graded stone agregate) and removing surplus soil to a distance n.exc 50 m and making good surface complete all as specified and as directed 10 Each
38 38 Supply and jointing in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size120 to 185 sqmm 3.5 core complete all as specified and as directed 6 Each
39 39 Supply and jointing in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 70 to 95 Sqmm 3.5 core complete all as specified and as directed 12 Each
40 40 Supply and jointing in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 25 to 50 Sqmm 3.5 core complete all as specified and as directed 15 Each
41 41 Taking down unserviceble CDG relay and Supply, install, testing and commissioning of self powered microprocessor based numerical 3 Phase over current and earth fault relay with high set for both O/C and E/F, fault records and suitable for panel mounting with auxialiary supply voltage range 24 V to 110 V as per site requirement. 1 Each
42 42 Taking down old UNSV fidder pillar and Supply, fixing, testing and commissioning of feeder pillar panel single door floor mounted and wall/pole mounted outdoor type, as per IP-55 grade, made out of MS sheet 3.15 mm thick of size 540x525x200mm with aluminium bus bar 250 Amps, 4 strip (3 phase) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking with 150 Amps 25 KA MCCB four pole for incomer cable, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands etc and providing fixing arrangements including earthing lead fixing arrangement, complete all as directed.\nNote :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel shall included in rates quoted. 4 Each
43 43 S&F vertical type load line distribution board, double door, 4 way AC, 3 phase 415 volts, TPN bus bar 200 Amps rating and earth bus and din rail including 01 No. MCCB 3/4 pole 415 volts, 50 Hz, 100Amps 16 KA breaking capacity as incomer complete . 10 Each
44 44 S&F in replacement of MCCB 4 pole, 415 volts, adjustable type 63 Amps with breaking capacity 16 KA and connecting testing with MCCB complete all as specified and as directed. 4 Each
45 45 S&F in replacement of MCCB 4 pole, 415 volts, adjustable type 100 Amps with breaking capacity 16 KA and connecting testing with MCCB complete all as specified and as directed. 4 Each
46 46 Supply and fix in replacement of MCB SP 6-32 Amps 230 volts 'B' series complete all as specified and as directed. 55 Each
47 47 Supply and fix in replacement of MCB SPN 40-63 Amps 230 volts 'B' series complete all as specified and as directed. 10 Each
48 48 M&L submain wiring with unsheathed multi-stranded FR Grade copper conductor cable 1100 volts grade drawn through in and including PVC rigid conduit medium grade of not less than 25mm dia with conduit accessories and concealed in wall/surface of ceiling for two runs of 6 Sqmm single core HR Grade and one run of 4 Sqmm PVC insulated copper conductor for earth continuity wire between main DB to Sub main DB complete all as specified and as directed.\nNote :- (i) Two run of single core cable with one run of earth continuity conductor and PVC conduit and accessories will be measured as one length including cutting chasing in wall complete.\n (ii): Rates shall deemed to be included for chases of conduit and sunking for boxes cutting and making holes in wall/floor for passing in or through conduit. 550 Each
49 49 M&L for point wiring complete with stranded copper conductor 4 Sqmm size (Nominal area) PVC insulated unsheathed FRLS cable 1100 volts grade confirming to IS: 694 drawn in and including medium grade concealed PVC conduit confirming to ISI marked not less than 25mm dia with concealed sunk-in pressed steel terminal boxes of required size not less than 1.2 mm thick factory made and painted with stove enamelled black paint top cover 2.80 mm thick plastic laminated sheet of required colour fixed with brass screwes and cup washers including single core stranded copper conductor 4 Sqmm PVC insulated unsheathed cable as earth wire to common earth and connected to earth dolly drawn in same concealed conduit complete all as specified for one 6 pin socket outlet two in one 16/6 Amps on an independent board. (for AC point)\nNote : Rates shall deemed to be included for chases of conduit and sunking for boxes cutting and making holes in wall/floor for passing in or through conduit. No Extra payment shall be done on this account\n 30 Each Point
50 50 Supply & fix in replacement of SPN enclosure with two pin and earth plug and socket complete with on SP MCB 20 Amps complete all as specified and as directed Make Legrand or equivalent in Siemens/Hagger/L&T. 20 Each
51 51 Supply & fix in replacement of SPN enclosure with two pin and earth plug and socket complete with one SPN MCB 32 Amps complete all as specified and as directed Make Legrand or equivalent in Siemens/Hagger. 20 Each
52 52 S&F in replacement of Solar panel for Intergrated Solar Street light 30 watt LED all in one luman/watt>125,Solar charge controller MPPT, Solar PV Module (wp) flow, Battery 12.8V 36AH, Back up 02 days with Li-ion battery with kit with hardware, connector & panel for installation of street light with Pole, with suitable dia for street light fitting with all fixing arrangements like nuts, bolts, clamps, PCC foundation etc complete all as directed\nNote: Earth work & PCC foundation is included in quoted rate.\nMake :- (Model No LHSTAKU7CBAF030 of Havells or equivalent in Halonix/Crompton) 3 Each
53 53 M&L for painting of steel tubular pole including cable protection pipe and all iron parts of 9 mtr long pole complete with 2 coats of aluminium paint after cleaning all rust and dust and preparing surface with wire brush and including strips of white and red colour of synthetic enamel paint up to the height of 1.5 mtr from the bottom of the pole complete all as directed.\n 50 Each
54 54 S&F MCCB 250 A ,3 pole ,25 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as specified and as directed\n 2 Each
55 55 S&F MCCB 200 A ,3 pole ,25 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as specified and as directed 2 Each
56 56 Supply and Fix in replacement of old unserviceable pole box with new weather proof street light PVC junction box of size 250 x 140 x 95mm and connecting terminals 4 way including 06 Amps SP/MCB and fixing with street light poles using necessary MS clamps, nuts, bolts washers, lugs for incoming and out going cables, gland for cable etc of suitable size complete all as specified and as directed. Make : Hensel/Sintex/Universal Switch Gear control. 21 Each
57 57 Supply and fixing weather proof street light PVC junction box of size 300 x 200 x 105mm including MCB SP 6 Amps and connecting terminals 4 way and fixing with street light poles using necessary MS clamps, nuts, bolts washers, lugs for incoming and out going cables, gland for cable etc of suitable size complete all as specified and as directed. Make : Hensel/Sintex/Universal Switch Gear control \nNote for item No 56 & 57 : The rates quoted shall inclusive of provision and fixing of suitable lugs and glands for cable connection. 24 Each
58 58 Material and labour for PVC flat twin core 2.5 sq mm aluminium wire 1100 volt grade laid in 20 mm dia medium grade rigid PVC conduit (and fixing brackets on PCC pole) from Loop-in-loop out junction box to light fitting terminal complete all as specified and as directed.\nNote :- PVC conduit shall be clamped properly with suitable clamps and no extra payment shall be done on this account. 200 RM
59 59 Takng down old unservicable LT Panel/Feeder Pillar Box of any type, Supply, installing, testing and commissioning factory made and tested LT Outdoor type, platform mounted LT Panel, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar chamber with insulated electrolytic Aluminium bus bars TPN of capacity 600 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, and made out of 3.15 mm thick CRCA mild steel sheet and mild steel & Angle iron frame work made out of 50 mm x 50 mm X 6 mm ), front opening type with aprons for cable entry, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey RAL- 7035 shade. The scope of work also comprising of the following incl necessary brick work, PCC work and plastering suitable for mounting the LT Panel box all as per specified and directed complete \n 1 Each
60 59.01 BUS BAR CHAMBER :- \n(a) 800 Amp 3 Strips & Neutral Strip 400 Amp, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings.\nINSTRUMENT CHAMBER :- \n(i) Digital Volt Meter, 96X96mm, flush type rated 0-500V, with Volt meter selector switch- 01 Set. \n(ii) Digital Amp Meter, 96X96mm, flush type rated 0-400A, with Amp meter Selector switch- 01 Set. \n(iii) C.T's 400/5 A CL 1.0 Tape Wound- 01 Set. (Set of three)\n(iv) Red,Yellow,Green Phase indicating Lights LED type 220V AC- 1 Set. (Set of three).\n(v) Protection MCB 6 A SP C Series- 1 Set. (Set of three). \nMake of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.\n\nINCOMING SUPPLY :- \n(i) MCCB 315 Amps 35 KA , 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz,=01 No., \nMake of MCCB:-L&T/ Siemens / Legrand\nOUTGOING SUPPLY :- \n(i) MCCB 100 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 08 Nos,\n(ii) Provison of spare space for fixing of MCCB 63 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 No,\nMake of MCCB:- L&T/ Siemens/ Legrand/Indoasian.\n
61 60 Taking down old unservicable LT Panel/Feeder Pillar Box of any type, Supply, installing, testing and commissioning factory made and tested LT Outdoor type, platform mounted LT Panel, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar chamber with insulated electrolytic Aluminium bus bars TPN of capacity 600 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, and made out of 3.15 mm thick CRCA mild steel sheet and mild steel & Angle iron frame work made out of 50 mm x 50 mm X 6 mm ), front opening type with aprons for cable entry, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey RAL- 7035 shade. The scope of work also comprising of the following incl necessary brick work, PCC work and plastering suitable for mounting the LT Panel box all as per specified and directed complete\n 1 Each
62 60.01 BUS BAR CHAMBER :- \n(a) 800 Amp 3 Strips & Neutral Strip 400 Amp, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings.\nINSTRUMENT CHAMBER :- \n(i) Digital Volt Meter, 96X96mm, flush type rated 0-500V, with Volt meter selector switch- 01 Set. \n(ii) Digital Amp Meter, 96X96mm, flush type rated 0-400A, with Amp meter Selector switch- 01 Set. \n(iii) C.T's 400/5 A CL 1.0 Tape Wound- 01 Set. (Set of three)\n(iv) Red,Yellow,Green Phase indicating Lights LED type 220V AC- 1 Set. (Set of three).\n(v) Protection MCB 6 A SP C Series- 1 Set. (Set of three). \nMake of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.\n\nINCOMING SUPPLY :- \n(i) MCCB 315 Amps 35 KA , 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz,=01 No., \nMake of MCCB:-L&T/ Siemens / Legrand\nOUTGOING SUPPLY :- \n(i) MCCB 200 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 02 Nos,\n(ii) MCCB 125 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 Nos,\n(iii) Provison of spare space for fixing of MCCB 63 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 02 No,\nMake of MCCB:- L&T/ Siemens/ Legrand/Indoasian.\n
63 61 Taking down old unservicable LT Panel/Feeder Pillar Box of any type, Supply, installing, testing and commissioning factory made and tested LT Outdoor type, platform mounted LT Panel, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar chamber with insulated electrolytic Aluminium bus bars TPN of capacity 800 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, and made out of 3.15 mm thick CRCA mild steel sheet and mild steel & Angle iron frame work made out of 50 mm x 50 mm X 6 mm ), front opening type with aprons for cable entry, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey RAL- 7035 shade. The scope of work also comprising of the following incl necessary brick work, PCC work and plastering suitable for mounting the LT Panel box all as per specified and directed complete :- Make of Panel: Unilac/ Indoasian / Universal Switch Gear Control/ Tricolite.\n 1 Each
64 61.01 BUS BAR CHAMBER :- \n(a) 800 Amp 3 Strips & Neutral Strip 400 Amp, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings.\nINSTRUMENT CHAMBER :- \n(i) Digital Volt Meter, 96X96mm, flush type rated 0-500V, with Volt meter selector switch- 01 Set. \n(ii) Digital Amp Meter, 96X96mm, flush type rated 0-600A, with Amp meter Selector switch- 01 Set. \n(iii) C.T's 600/5 A CL 1.0 Tape Wound- 01 Set. (Set of three)\n(iv) Red,Yellow,Green Phase indicating Lights LED type 220V AC- 1 Set. (Set of three).\n(v) Protection MCB 6 A SP C Series- 1 Set. (Set of three). \nMake of Metering Accessories :-L&T/ AE/ Trinity/ Schneider/Indoasian.\n\nINCOMING SUPPLY :- \n(i) MCCB 630 Amps 35 KA , 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz,=01 No., \nMake of MCCB:-L&T/ Siemens / Legrand\nOUTGOING SUPPLY :- \n(i) MCCB 250 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 Nos,\n(ii) MCCB 100 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 04 Nos,\n(iii) Provison of spare space for fixing of MCCB 63 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 02 No,\nMake of MCCB:- L&T/ Siemens/ Legrand/Indoasian.
65 62 S&F street light liminaree high power LED of 72 watt rating with unique lens to ensure to uniform distribution complete all as spcd as directed Cat Part No LSTP-72-CDL Make of CG or its equvalent Havells/Hallonix \nNote :- Rent for hydra is included in rates quoted by the contractor. All fixing material inculdied in the unit rate. 15 Each
66 63 Supply only aluminium thimble heavy duty ISI mark suitable for 25 sqmm 3.5 cable all as spfd & directed by Engr-in-Charge 200 Each
67 64 Ditto all as per item No 63 above but 35 x 3.5 sqmm cable 200 Each
68 65 Ditto all as per item No 63 above but 50 x 3.5 sqmm cable 500 Each
69 66 Ditto all as per item No 63 above but 70 x 3.5 sqmm cable 200 Each
70 67 Ditto all as per item No 63 above but 95 x 3.5 sqmm cable 150 Each
71 68 Ditto all as per item No 63 above but 120 x 3.5 sqmm cable 150 Each
72 69 Ditto all as per item No63 above but 150 x 3.5 sqmm cable 100 Each
73 70 Ditto all as per item No 63 above but 185 x 3.5 sqmm cable 100 Each
74 71 Ditto all as per item No 63 above but 240 x 3.5 sqmm cable 50 Each
75 72 Ditto all as per item No 63 above but 300 x 3.5 sqmm cable 40 Each
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail