| 1 | 1 | Taking down care fully copper/aluminium point wiring from wooden batten or conduits (light, fan, socket or power) complete excluding l fittings such as switches, sockets, ceiling roses, pendents, regulators, light fittings any type etc to be measured seperately) and making good disturbed surfaces of walls, floors etc complete all as specified and directed by Engineer in charge. | | 990 | Per Point |
|---|
| 2 | 2 | M & L for Point wiring complete with 1.5 sqmm single core PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor drawn through Existing PVC conduit, including provision of 1.5 sqmm PVC insulated copper cable FRLS as earth continuty and fabricated branded modular metal flush box / M S Steel terminal boxes, concealed in walls with suitable modular inner and outer plate / 3 mm thick laminated top sheet cover for housing switches , socket out let and fan regulators etc , all as specified and as directed for the followings:- complete all as specified and directed by Engineer in charge. | | | |
|---|
| 3 | 2.01 | One light/fan point controlled by one way switch | | 320 | Per Point |
|---|
| 4 | 2.02 | One bell / buzzer point controlled by one bell push | | 16 | Per Point |
|---|
| 5 | 2.03 | One light point controlled by two Nos two way switches | | 8 | Per Point |
|---|
| 6 | 2.04 | One 3 pin 5 Amps socket outlet point controlled by one way switch on independent board. | | 80 | Per Point |
|---|
| 7 | 2.05 | One 3 pin 5 Amps socket outlet point controlled by one way switch on same board | | 64 | Per Point |
|---|
| 8 | 3 | All as per item No 2 but point wiring with 4 Sqmm single core copper cable and earth continuity wire with 4 Sqmm single core stranded copper cable for one three pin 15 socket outlet point on independent board complete all as specified and directed by Engineer in charge. | | 82 | Per Point |
|---|
| 9 | 4 | M & L for Point wiring complete with 1.5 sqmm single core PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor drawn through and including non-metalic rigid PVC conduit medium grade ISI Marked and all conduit accessories concealed in wall/ceiling/fixed to roof/truss/columns etc and including provision of 1.5 sqmm PVC insulated copper cable FRLS as earth continuty, fabricated branded modular metal flush box / M S steel terminal boxes, concealed in walls with suitable modular inner and outer plate / 3 mm thick laminated top sheet cover for housing switches , socket out let and fan regulators etc , all as specified and as directed for the followings:- complete all as specified and directed by Engineer in charge. | | | |
|---|
| 10 | 4.01 | One light/Exh fan point controlled by one way switch | | 240 | Per Point |
|---|
| 11 | 4.02 | One bell / buzzer point controlled by one bell push | | 12 | Per Point |
|---|
| 12 | 4.03 | One light point controlled by two Nos two way switches | | 12 | Per Point |
|---|
| 13 | 4.04 | One 3 pin 5 Amps socket outlet point controlled by one way switch on independent board. | | 60 | Per Point |
|---|
| 14 | 4.05 | One 3 pin 5 Amps socket outlet point controlled by one way switch on same board | | 36 | Per Point |
|---|
| 15 | 5 | All as per item No 2 but point wiring with 4 Sqmm single core copper cable and earth continuity wire with 4 Sqmm single core stranded copper cable for one three pin 15 socket outlet point on independent board complete all as specified and directed by Engineer in charge | | 60 | Per Point |
|---|
| 16 | 6 | Taking down old unserviceable MS Steel terminal boxes from wall and supply and fixing fabricated branded modular metal flush box 1 module / 2 module concealed in walls with suitable modular inner and outer plate for housing switches , socket out let and fan regulators etc including make good of disturbed surface complete all as specified and directed by Engineer in charge. Note-Switch,socket, regulator will be paid separately | | 90 | Each |
|---|
| 17 | 7 | Taking down old unserviceable MS Steel terminal boxes from wall and supply and fixing fabricated branded modular metal flush box 3 module / 4 module concealed in walls with suitable modular inner and outer plate for housing switches , socket out let and fan regulators etc including make good of disturbed surface complete all as specified and directed by Engineer in charge. Note-Switch,socket, regulator will be paid separately | | 600 | Each |
|---|
| 18 | 8 | Taking down old unserviceable MS Steel terminal boxes from wall and supply and fixing fabricated branded modular metal flush box 6 module concealed in walls with suitable modular inner and outer plate for housing switches , socket out let and fan regulators etc. including make good of disturbed surface complete all as specified and directed by Engineer in charge. Note-Switch,socket, regulator will be paid separately | | 120 | Each |
|---|
| 19 | 9 | Taking down old unserviceable MS Steel terminal boxes from wall and supply and fixing fabricated branded modular metal flush box 8 module concealed in walls with suitable modular inner and outer plate for housing switches , socket out let and fan regulators etc including make good of disturbed surface complete all as specified and directed by Engineer in charge. Note-Switch,socket, regulator will be paid separately | | 150 | Each |
|---|
| 20 | 10 | M&L in replacement switch Modular type 6 Amps 1 Way,1 module, 230V AC complete all as specified and directed by Engineer in charge. \n | | 868 | Each |
|---|
| 21 | 11 | M&L in replacement Modular socket outlet 2/3 pin 6 Amp socket 2 module complete all as specified and directed by Engineer in charge. \n | | 468 | Each |
|---|
| 22 | 12 | M&L in replacement switch modular type 6 amp SP two way, 1 module complete all as specified and directed by Engineer in charge. | | 28 | Each |
|---|
| 23 | 13 | M&L in replacement Modular Bell push button SP with indicator 6 Amps, 1 module 230V AC complete all as specified and directed by Engineer in charge. | | 36 | Each |
|---|
| 24 | 14 | M&L in replacement switch Modular type 16 Amps 1Way, 1 module with modular plate light marking 230V AC complete all as specified and directed by Engineer in charge. | | 234 | Each |
|---|
| 25 | 15 | M&L in replacement Modular socket outlet 2/3 pin 6/16 Amp universal socket 2 module complete all as specified and directed by Engineer in charge. | | 234 | Each |
|---|
| 26 | 16 | M&L in replacement modular stepped type electronic fan regulator 120W, 2 module all as specified and directed by Engineer in charge. \n | | 240 | Each |
|---|
| 27 | 17 | M&L in replacement switch piano flush button type single pole one way 6 Amps complete all as specified and directed by Engineer in charge. | | 360 | Each |
|---|
| 28 | 18 | M&L in replacement switch piano flush button type single pole Two way 6 Amps complete all as specified and directed by Engineer in charge. | | 20 | Each |
|---|
| 29 | 19 | M&L in replacement bell push single pole 6 Amps complete all as specified and directed by Engineer in charge, | | 40 | Each |
|---|
| 30 | 20 | M&L in replacement switch piano flush button type single pole 16 Amps complete all as specified and directed by Engineer in charge . | | 60 | Each |
|---|
| 31 | 21 | M&L in replacement socket outlet, 2 in 1, 3 pin 6 and 16 Amp single pole complete all as specified and directed by Engineer in charge. | | 60 | Each |
|---|
| 32 | 22 | M&L in replacement socket outlet 6 Amp flush button type complete all as specified and directed by Engineer in charge. | | 160 | Each |
|---|
| 33 | 23 | M&L in replacement regulator electronic switch/socket type 5 steps suitable for 1200/1400 mm sweep 230 volts all as specified and directed. \n | | 260 | Each |
|---|
| 34 | 24 | M&L in replacement bell electric (dingdong) 230 volt, SP all complete all as specified and directed by Engineer in charge . | | 40 | Each |
|---|
| 35 | 25 | M/L in replacement insulated body, angle holder (metal ring) with back plate complete all as specified and directed by Engineer in charge. | | 240 | Each |
|---|
| 36 | 26 | S&F ceiling rose surface PVC 65x50 mm type with three terminals complete all as specified and directed by Engineer in charge . | | 500 | Each |
|---|
| 37 | 27 | M&L in replacement sheet metal enclosure, single pole and neutral with a two pin and earth plug and socket 240 Volts grade 10Amps complete with one single pole MCB 'C' series 10/20 A capacity complete all as specified and directed by Engineer in charge. | | 80 | Each |
|---|
| 38 | 28 | Supply and fix LED batten luminaire surface mounted, 4 feet system wattage of 22 Watts, > 2400 systems lumen outputwith lifetime of 50000 burning hours with 70% of its initial lumen maintained. CRI>80, Power Factor > 0.95, THD< 10%, colour temperature - 6500K, surge protection 2.5KV in CM, IP-20 protected, meets LED IS specifications, Class - 1, Short circuit and over circuit protection, voltage range - 150 to 270 Volts AC, temperature range 0 to 50 DegreeC and including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire from ceiling rose to fitting fixed complete all as specified and directed by Engineer in charge. | | 1220 | Each |
|---|
| 39 | 29 | Supply and fix LED batten luminaire surface mounted 2 feet system wattage of 10 watts and not less than 1000 lm with life time of 50000 burning hours with 70% of its initial lumen maintained. CRI > 80, power factor > 0.95, THD < 10%, color temperature > 6500 K , surge protection 2.5 KV in CM IP- 20 protected meets LED IS specifications, voltage range - 150 to 270 volts AC, temperature range 0 to 50 Degree C, system efficiancy at luminarie level =100 Lumens/watt and including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire fixed complete all as specified and directed by Engineer in charge. | | 440 | Each |
|---|
| 40 | 30 | Supply and fix LED 9/10 watts bulkhead fitting with powder coated die cast aluminium housing with glass/ non yellowing polycarbonate cover, IP65 Protection, System level efficacy of the Luminary is > 90 lm/W with a life class of 50,000 burning hours at L70 criteria, Power Factor >0.95, driver with Voltage range 150-270V, Temperature range 0 to 50 Deg, Driver efficiency >85%, THD<10%, CRI>80, Color Temperature-6000K, Surge protection of 2.5 KV, including connecting up with necessary PVC sheathed 3 core 1.5Sqmm copper conductor flexible wire fixed complete all as specified and directed by Engineer in charge. | | 600 | Each |
|---|
| 41 | 31 | S&F in replacement of decorative type wall mounted luminaire (Comet) with unbreakable poly carbonate materials suitable for 1x14 watt LED bulb B22 base complete all as specified and directed by Engineer in charge . | | 400 | Each |
|---|
| 42 | 32 | Supply and fix surface ceiling mounted, LED down light fitting 12 watts with die cast aluminium housing and system wattage of 12W, system efficacy at luminary level = 80 Lumens/watt, 50000 burning hours, 6500K color temperature with CRI >80, Power Factor > 0.90, Driver should meet IEC compliant for safety with multi stage high Isolate CC-CV operated driver with voltage variation range - 150 to 270 Volts AC, and surge protection of 2.5 KV, and including connecting up with PVC sheathed 3 core 1.5Sqmm copper conductor flexible wire fixed complete all as specified and directed. . | | 400 | Each |
|---|
| 43 | 33 | Supply and Fixing LED bulb 9 watts, 900 lumens output, 6500K suitable for B-22 base complete all as specified and directed by Engineer in charge . | | 400 | Each |
|---|
| 44 | 34 | Supply and Fixing LED bulb 14 watts, 900 lumens output, 6500K suitable for B-22 base complete all as specified and directed by Engineer in charge . | | 400 | Each |
|---|
| 45 | 35 | Supply and fix MCB DB SPN 12 way Horizontal, IP - 43 Protection double door 240 V AC 50Hz with for MCB SPN as incomer and DP/SP MCBs as out going with tinned copper bus bar ,neutral link earth link complete all as directed by Engineer -in- Charge.\n | | 40 | Each |
|---|
| 46 | 36 | Supply and fix MCB DB SPN 8 way Horizontal, IP - 43 Protection double door 240 V AC 50Hz with for MCB SPN as incomer and DP/SP MCBs as out going with tinned copper bus bar ,neutral link earth link complete all as directed by Engineer -in- Charge. | | 40 | Each |
|---|
| 47 | 37 | S&F MCB DB SPN 02 way, single door 240 V AC 50Hz , with 10 Amps MCB SPN as incomer / out going complete all as directed by Engineer -in- Charge. | | 10 | Each |
|---|
| 48 | 38 | Supply and fix in repair MCB DP 63 Amps 240 volts 10 KA 50 HZ 'C' curve complete all as specified and directed by Engineer in charge | | 40 | Each |
|---|
| 49 | 39 | Supply and fix in repair MCB DP 40 Amps 240 volts 10 KA 50 HZ 'C' curve complete all as specified and directed by Engineer in charge | | 80 | Each |
|---|
| 50 | 40 | Supply and fix in repair MCB SP 6-32 Amps 240 volts 10 KA 50 HZ 'C' curve complete all as specified and directed by Engineer in charge | | 640 | Each |
|---|
| 51 | 41 | Supply and fixing Ventilating Fan 250 mm sweep, 1250 RPM, non metallic resin body, single phase 240 volts AC 50 Hz and connecting up complete including louvers and provision of copper cable 3 core of size 0.5 sqmm for connection from ceiling rose to fan complete all as specified and directed by Engineer in charge. | | 24 | Each |
|---|
| 52 | 42 | Supply,installation,testing,commissioning of factory made and tested, CPRI approved LT Panel, in door type, wall/floor mounted of size 800x200x1200 mm (LxWxH) suitable for 415 Volts 3 phase and neutral, 4 wire, 50 Hz, AC supply system having bus bar chamber with duly insulated electrolytic copper bus bar of capacity 250 amps rating insulated on DMC insulators with busbar chamber.The Panel shall be dust and vermin proof IP 42 class protection and made out of 2.00 mm thick CRCA sheet, front opening type with approns for cable entry, with proper ferrule and cable gland , internal wiring with PVC insulated multistranded copper conduction FRLS cable of adequate size but not less than 1.5 sqm. All steel metal works including frame shall be with anticorrossive coating with seven tank process and finally epoxy polyster powder coating of siemens grey RAL-7035 Shade complete all as specified and directed. The scope of work also comprising of the following:-\nBUS BAR CHAMBER:- (a) 250 Amp TPN, copper conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combbustible, track resist, high strenth DMC material. interconnection of all incomming & out goings.\nINSTRUMENT CHAMBER:- (i) Volt meter, 96 mm, flush type rated 0-500V, Digital type with volt Meter Selecter switch - 01 set. (ii) Amp meter, 96 mm, flush type rated 0-200A, Digital type with suitable size C Ts, and amp selector switch - 01 Set (iii) RYB Phase indicating light LED type with MCB 6 A SP C series - 01 Set of three. INCOMMING :- (i) MCCB 160 Amps 25 KA, 4 Pole with adjustable thermal magnetic release - 01 No.\nOUTGOING:- (i) MCB 2 Pole 63 Amps, 230 Volts, 50 Hz, 10 KA, 'C' Series - 04 Nos, (ii) MCB 2 Pole 10 Amps, 230 Volts, 50 Hz, 10 KA, 'C' Series - 01 No, (iii) Space for 04 Nos single Phase pre paid KWH energy meters.\n(iv) DMC Connector for outgoing submain - 04 Nos, (v) Panel wiring for control circuit with copper flexible 1.5 Sq mm& power wiring minimum 10 Sq mm flexible.\nNote :- (i) Marking of Flat Nos on outgoing feeders of LT Panel, (ii) Time duration for replacement of LT Panel should notbe more than 4 Hours. (iii) rate quated are deemed to inclusive of all the fixture / fitting cater above \n\n | | 4 | Each |
|---|
| 53 | 43 | Supply and fix in repair MCCB 160 Amps, FP 415 volts 16 KA 50 HZ with thermal magnetic setting complete all as specified and directed by Engineer in charge. | | 4 | Each |
|---|
| 54 | 44 | Supply and fix in repair MCCB 250 Amps, FP 415 volts 25 KA 50 HZ with thermal magnetic setting complete all as specified and directed by Engineer in charge. | | 2 | Each |
|---|
| 55 | 45 | S&F in reapirs sheet metal enclosure one way for independent mounting of 4 Pole MCCB, Including MCCB 4 Pole 250 Amps 25 KA, 415 Volts complete all as specified and as directed by Engr-in-Charge. | | 8 | Each |
|---|
| 56 | 46 | Supply and lay in repairs XLPE insulated PVC bedded galvanised steel strip or wire armoured electric power cables(heavy duty) 1100 volts grade with stranded aluminium conductor of size 95 Sqmm 3.5 core including connection of cable at both ends with suitable size of glands, aluminum lugs complete jointing, testing and commissioning complete all as specified and directed by Engr-in-Charge. | | 40 | RM |
|---|
| 57 | 47 | S&F in repair Sub main wiring with two runs of 4 Sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 4 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through and including 25 mm dia non metallic rigid PVC conduit and conduit accessories on surface of walls complete all as specified and directed. Note: Three runs of cable shall be measured as one leanth | | 400 | RM |
|---|
| 58 | 48 | Supply and fix in repair Sub main wiring complete with two runs of 4 Sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 4 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through existing metallic/ non metallic conduit in walls complete all as specified and directed by Engineer in charge. Note: Three runs of 4 sqmm cable shall be measured as one RM. | | 600 | RM |
|---|
| 59 | 49 | Supply and fix in repair Sub main wiring complete with two runs of 6 Sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 6 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through existing metallic/ non metallic conduit in walls complete all as specified and directed by Engineer in charge. Note: Three runs of 6 sqmm cable shall be measured as one RM. | | 450 | RM |
|---|
| 60 | 50 | Supply and fix in repair Sub main wiring complete with two runs of 10 Sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 10 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through existing metallic/ non metallic conduit in walls complete all as specified and directed by Engineer in charge. Note: Three runs of 10 sqmm cable shall be measured as one RM. | | 400 | RM |
|---|
| 61 | 51 | S&F plug top, 3 pin, 20 amp earth metal clad (ISI marked) complete all as specified and directed by Engineer in charge. | | 60 | Each |
|---|
| 62 | 52 | S&F socket 3 pin 20 amp earth metal clad (ISI marked) complete all as specified and directed by Engineer in charge . | | 50 | Each |
|---|
| 63 | 53 | S & F PVC Gang box surface type heavy duty suitable for single switch 5 Amps complete all as specified and directed by Engineer in charge . | | 20 | Each |
|---|
| 64 | 54 | S & F Gang box surface type heavy duty suitasble for 15 Amps switch and socket complete all as specified and directed by Engineer in charge. | | 20 | Each |
|---|
| 65 | 55 | M & L for in replacement only single core PVC insulated cable 1.5 Sqmm FRLS 1100 Volts with copper multi stranded conductor and drawing in existing concealed conduits, all as specified and directed by Engr-in-Charge. | | 360 | RM |
|---|
| 66 | 56 | M & L in replacement for only single core PVC insulated cable 2.5 Sqmm FRLS 1100 Volts with copper multi stranded conductor and drawing in existing concealed conduits , all as specified and directed by Engr-in-Charge. | | 360 | RM |
|---|
| 67 | 57 | M & L in replacement for only single core PVC insulated cable 4 Sqmm FRLS 1100 Volts with copper multi stranded conductor and drawing in existing concealed conduits , all as specified and directed by Engr-in-Charge. | | 360 | RM |
|---|
| 68 | 58 | M & L in replacement for only single core PVC insulated cable 10 Sqmm FRLS 1100 Volts with copper multi stranded conductor and drawing in existing concealed conduits , all as specified and directed by Engr-in-Charge. | | 180 | RM |
|---|
| 69 | 59 | Supply only SS braided pipe of 12 mm ((internal) suitable for hot/cold water, 60 cm long with brass nuts and rubber washers complete all as specified and directed by Engineer in charge. | | 165 | Each |
|---|
| 70 | 60 | Supply and fixing in replacement heating element of 2 KW any type with nut bolt washer complete all as specified and directed by Engineer in charge. | | 95 | Each |
|---|
| 71 | 61 | Supply only heating element of 1.5 KW any type with nut bolt washer ccomplete all as specified and directed by Engineer in charge. | | 100 | Each |
|---|
| 72 | 62 | Supply only replacement of capacitor 3.15 Mfd, 240 V complete all as specified and directed by Engineer in charge. | | 280 | Each |
|---|
| 73 | 63 | Supply only replacement of capacitor 1.5 Mfd, 240 V complete all as specified and directed by Engineer in charge. | | 100 | Each |
|---|
| 74 | 64 | supply only hole fastner madeup of MS 6\" long with complete nut bolt complete all as specified and directed by Engineer in charge. | | 100 | Each |
|---|
| 75 | 65 | Supply and Fix in repair 35 W High efficient LED Street light fitting with pressure die cast LM6 Aluminum housing and has lenses specially designed for Street Lighting with polycarbonate cover. System level efficacy of the Luminarie is 100lm/W with a life class of 50,000 burning hours at L70. The color temperature is around 6500 K with a color rendering index of 70. The luminaire is IP:66 protected with IK05 impact resistance. It has an electronic driver complaint to IEC safety standards with a power factor>.0.9, voltage variation range 120-270V, THD<20%, High and low protection along with a surge protection of 4 KV including provision of 25 mm dia GI light grade pipe1.5 meter length bend to shape and necessary clamps etc for fixing the light fittings on pole fixed complete all as specified and directed by Engineer in charge. | | 22 | Each |
|---|
| 76 | 66 | Supply and fix LED 2 X 2 ft backlite surface mounted fitting 36/40 Watts not less than 3200lm with Metallic CRCA powder coated body with high efficiency opal/PMMA diffuser with system efficacy > 80 lm/W, CRI>80, color temperature >5700k, IP 20, Power factor<0.95, THD<10%, 50000 burning hours , Ambient temperature 0 to 500 DegC, Driver should meet IEC complaint for safety, with voltage variation range of 150-270 V and surge protection of 2.5 KV including necessary fixing arrangementsfixed complete all as specified and directed by Engineer in charge. | | 20 | Each |
|---|
| 77 | 67 | S & F in replacement exhaust fan 250 mm sweep, metal type including provision of 3 core PVC insulated sheathed 1100 volts grade flexible cable with stranded copper conductor from ceiling rose to fan, length as per requirement at site. complete all as specified and directed by Engineer in charge. | | 11 | Each |
|---|
| 78 | 68 | M&L in replacement for only twin core PVC insulated unarmoured cable 10 sq mm flat 1100 volts with Aluminium multi stranded conductor and drawing in existing concealed conduits, hanging or suspended over GI wire 2 mm dia and binding with real insulator not more than 2 mtr space complete all as specified and directed by Engr-in-charge.\n | | 180 | RM |
|---|
| 79 | 69 | Supply & fix in repair factory made epoxy powder coated Load line Distribution Board TPN-4 ways with metal door (IP-43 protection) fabricated from minimum 1.6mm thick CRCA sheet and fixed flush to wall and suitable for universal mounting and including insulated 200 Amp copper bus bar, Isolated neutral bar, standard DIN rail, Earth bar and cable ties for cable management, top and bottom removeable gland plates with knockouts and suitable for one TPN- MCCB 125/160 Amp as incomer and 32 to 63 Amp SP MCBs outgoing complete all as specified and directed by Engineer in charge. and conforming to IS : 8623. | | 3 | Each |
|---|
| 80 | 70 | Note :- Total amount of Sch of credit is Rs. 68578.00 as per Sch of credit. Net contract sum shall be total quoted amount of bidder (-) amount of Sch of credit. | | | |
|---|